You are on page 1of 22

LV Circuit Components Bussmann ®

A wide range of circuit components catering for the busy end-user installer are
available to - BS, IEC, UL and CSA standards. Bussmann offer a global package
to meet most circuit protection solutions. The range of circuit components
includes fuse holders, fuse banks, fuse bases/blocks and switch disconnectors
(skeleton).
CAMASTER: The innovative BS fuse holder incorporating a ‘cam’ action built into
the fuse carrier for ease of removal from the base.
OPM 1038 Series: offers unbeatable protection against short circuit damage, in
eight combinations, for a broader coverage of today’s process control panel
applications.
Modular Fuse Holders: A global solution in a 10 x 38mm package. The CH and
CH--E will accommodate fuse links manufactured to European and USA standards,
ensuring circuit protection up to 32 amps.

1
CAMASTER HRC Fuse Holders Bussmann ®

A patented range of fully shrouded HRC Fuse Holders designed


to accommodate offset bolted tag HRC fuse links to BS88: Parts
1 & 2; IEC 269-1 & 2.
The compact dimensioned 32A Fuse Holder, type CM32FC
accepts the A1 size fuse link NITD 2 to 32 Amps. The standard 32A
fuse holder, type CM32F accepts the A2 size fuse link AAO - 2 to
32Amp. The 63A unit, type CM63F, accepts the A3 size fuse link
BAO - 40 to 63 Amp and the 100A unit, type CM100F, accepts
fuse link type OSD - 80 to 100 Amps, which has compact A3
fixing centres.
The Fuse Holders are supplied as front connecting as standard
but can be readily converted to front/back stud or double back
stud connection types at the point of installation, using the
appropriate size back stud accessories.
CAMASTER Fuse Holders are offered with the
following features
• Advanced patented design incorporating a high level of innovation,
with enhanced performance characteristics.
• CAMASTER Fuse Holders fully comply with the requirements of
BS88 section 2.2 (IEC269-2-1, section 2) and the 16th edition of the
IEE Wiring Regulations (BS7671).
• The fuse carriers are fitted with a ‘cam’ action for ease of removal
from the fuse base. The design ensures high contact pressure
between the fuse carrier contacts and the base contacts, with a
corresponding enhanced electrical performance level.
• CAMASTER Fuse Holders have a unique channel and guide
arrangement which prevents any tilting of the fuse carrier when it
is being inserted or removed, eliminating any likelihood of inad-
vertent contact with live metal.
• Fixing screws to the fuse carrier are held in captive hinges,
providing ease of fixing and preventing loss during installation.
The hinges also act as pressure plates thereby reducing the
contact resistance between the fuse link tags and the carrier
contact.
• Cable terminations fully meet the requirements of Sub-clause 7.1.7 -
terminals of IEC947: Part 1 Low Voltage Switchgear and
Controlgear.

• CAMASTER Fuse Holders, as standard, provide both bolted panel and DIN rail mounting features. When DIN rail
mounted all ratings of fuse holder give equal height and depth above and below the DIN rail.
• Non removable full shrouding of live parts within the fuse base provided by the use on hinged shields which cannot
be omitted during installation and are designed so that insertion of the fuse carrier can only be made with them
correctly positioned.
• Neon clip-in indicator accessories are available, the neon being lit when the fuse link has operated. (Minimum system
operation 90V).
• The fuse carrier has a marking label for ease of circuit identification.
• Ganging can be readily achieved by the use of standard accessories, providing improved safety related to isolation
and protection of 2 and 3 pole electrical circuits.

2
CAMASTER HRC Fuse Holders Bussmann ®

Ratings, Catalogue Numbers and Dimensions

Standard front connected unit. Suitable for either Front/Back Stud and Double Back Stud
bolted panel or DIN rail mounting. connected units. These allow easy customer
conversion (illustrated below left) to either Front/
Back or Double Back configuration, by use of
Back Stud Assembly Packs, using only a screw-
driver.

Max. Rec. D imen sion s (mm)


Ratin g
Cat. No. Cable F u se
(A) A B C D E F G H J K
mm2 Lin k
32 CM32FC 16 NITD 25.4 93.7 60 3.2 17.5 66.0 58.0 28.6 11.9 M6
32 CM32F 16 AAO 31.8 117.5 60 3.2 17.5 66.0 74.0 28.6 11.9 M6
63 CM63F 70 BAO 35.6 125 60 4.75 16.4 86.5 79.8 28.6 11.9 M8
100 CM100F 70 OSD 35.6 125 60 4.75 16.4 86.5 79.8 28.6 11.9 M8

Notes.
1 Type CM32FC is also available rated at 20A, catalogue number CM20F
2 For colours other than Black (standard) add the appropriate letter code:
W = White; G = Green and GY = Grey.

Conversion Sequence

Rating Catalogue Carton


Accessory
(A) No. Qty.
32 32BSC 10
Back Stud 32 32BS 10
63/100 63/100BS 5
Ganging Links GLP 1 set
B Neon 90-660-
NI 3
Indicator V ac
1. Remove carrier using the 2. Insert Back Stud 3. Raise contact 4. Repeat steps Lockable 32LSCC 3
Cam Lever. Insert accessory shield by inserting 1, 2 & 3 at Safety 32LSC 3
screwdriver at position screwdriver at opposite end Carriers 63/100LSC 3
‘A’ gently lever and push position ‘B’. to give Double
ferrule upwards to Tighten terminal Back Stud Security Clip CMSC 20
remove. screw. connection.

3
SAFELOC HRC Fuse Holders Bussmann ®

The patented SAFELOC fuse holders provide a simple, safe


range, designed to accommodate the compact rage of offset
blade tag fuse links to BS88 part 6. The combination offers
significant savings in volume and cost as well as a reduction
in fitting time and power loss. They provide a safe and easy
method of protecting a wide range of electrical equipment
such as lighting, heating, motor and control equipment
circuits.
The NNS fuse holder accommodates the NSD range of
compact HRC fuse links whilst the slightly larger ENS fuse
holder accommodates the ESD range of compact HRC fuse
links. Both holders are available in front connection or back
stud arrangements or combinations of these.

SAFELOC Fuse Holders are offered with the following features


• Compact fuse link and fuse holder dimensions.
• Fuse holders employ a unique slide/snap carrier action for positive and secure insertion
and removal of the fuse link. This provides positive, stress free fitting of fuse links
and locks the fuse link in position ensuring safe insertion and withdrawal from the base.
• The direct contact between fuse link blades and the plated base contacts provides
lower watts loss and increased reliability.
• The compact range of fuse links (i.e. NSD & ESD) fitted into the SAFE LOC fuse holders,
have an excellent ability to protect induction motor circuits.
• Complete internal personnel protection against direct contact electric shock is obtained
by fully insulated and shrouded fuse holder base contacts.
• Fuse base consists of glass filled, high impact resistant, thermoplastic polyester and
incorporates a 35mm DIN rail mounting facility as well as a single screw fixing.

Fuse Link Rating


Motor Fuse Link Notes on Motor Circuits
Ratings
Safeloc type NNS ENS Safeloc type NNS ENS
All of the compact range of fuse links have an excel-
lent ability to protect induction motor circuits. The
Fuse Link type NSD ESD Fuse Link type NSD ESD
unique design of the SAFELOC fuse holders has enabled
2 2 20M25 63M80 the design of dual rated fuse links which offer protec-
4 4 20M32 63M100 tion for motor circuits up to 40 hp. Fuse links in this
6 6 20M36 extended range have ratings, as defined in BS88 plus
10 10 32M36 a higher rating, which relates to their ability to with-
550V ac stand motor starting surges. For example, an ESD63M
16 16 32M40
NSD 415V ac 100 has a continuous current carrying capability of
20 20 32M50
ESD 415V ac 63A, coupled with the time current characteristic, and
25 25 32M63 thus the withstand capabilities, of a 100A fuse link.
32 32
The application of these fuse links in motor circuits
40 can achieve significant economies in the size and cost
415V ac 50 of installations. The associated dual rated fuse links
63 are shown left.

4
SAFELOC HRC Fuse Holders Bussmann ®

Ratings, Catalogue Numbers and Dimensions


Catalogue Reference
Available Variants
NNS ENS
Front Connected/Front
32NNSF 63ENSF
Connected
Back Stud/Back Stud 32NNSBS 63ENSBS
Front Connected/Back
32NNSFBS 63ENSFBS
Stud

Suitable for either Bolted Panel or DIN rail


mounting

For colours other than Black Max. Rec. Dimen s ion s (mm)
Ratin g
(standard), add the appropriate (A)
Cat. No. Cable Fu s e
mm 2
Lin k A B C D E F G H J K
letter code: W = White; G = Green;
GY = Grey, at the end of the Cata- 32 NNS 16 NSD 25.4 76.2 46.5 2.3 16.0 39.2 57.7 17.0 9.7 M6
logue Reference. 63 ENS 35 ESD 29.1 90.0 55.0 3.3 17.7 75.0 67.9 39.2 11.0 M8

Security seal (ref. 32551) available for 32A SAFELOC.

Both CAMASTER and SAFELOC fuse holders can be used in Distribution Fuse Boards, CAMASTER is shown below on
the left and SAFELOC on the right. Details of both these products can be found in our Fusegear Catalogue avail-
able on request.

5
HRC Distribution Fuse Banks Bussmann ®

Two ranges of Fuse Banks are available, utilising the CAMASTER


and SAFELOC HRC Fuse Holders. The fuse banks consist of single
phase assemblies of busbar connected fuse holders mounted on
a back strap, for incorporation in distribution fuse boards to
facilitate compliance with BS5486: Part 1; (EN60439-1) and
BS5486: Part 2.
Compatible ranges of neutral bars and earth terminal busbars are
also available, together with enclosure door circuit identification
labels.
The fuse banks are thermally rated and designed for mounting
either horizontally or vertically. This flexibility is complemented by
a fully insulated incoming cable termination shroud which may be
rotationally positioned to accept cable entry from any direction.
CAMASTER Fuse Bank Complete personnel protection against direct contact electric
shock is provided by fully shrouded busbars and shielded fuse
holder base contacts.
Insulation of the busbar assembly and cable termination is by
means of a PVC plastisol material, which has been shown, by
thermal cycling tests, to be satisfactory for use at ambient
temperatures from minus 20 degrees to plus 50 degrees
centigrade.

SAFELOC Fuse Bank

Characteristics
Gen eral O u tgoin g Circu it In comin g Circu it D iversity F actor
Rec. Max.
CAMAS T ER Rated Normal Normal
Rated Max. Cu rren t (A) Max.
F u se Ban k F u se Rec. Cu rren t
Rated Nomin al Cable Cable Termin al 4 6 8 12
P art Nu mbers Holder F u se Ratin g of
Voltage Cu rren t S ize size Bolt S ize W ay W ay W ay W ay
Ty pe Lin k 4 6 8 12 In comin g
(A) ( m m 2) ( m m 2)
W ay W ay W ay W ay F u se Lin k
(A)
32F B--CMC CM32FC 660 32 16 NITD 115 153 205 250 120 M10 250 0.9 0.8 0.8 0.66

32F B--CM CM32F 660 32 16 AAO 115 153 205 250 120 M10 250 0.9 0.8 0.8 0.66

63F B--CM CM63F 660 63 70 BAO 226 302 403 499 300 M12 500 0.9 0.8 0.8 0.66

100F B--CM CM100F 660 100 70 OSD 360 430 528 N/A 400 M12 560 0.9 0.8 0.66 N/A
S A F ELO C
Fuse Bank
P art Nu mbers
32F B--NNS NNS 550 32 16 NSD 115 153 205 250 120 M10 250 0.9 0.8 0.8 0.66

63F B--ENS ENS 550 63 35 ESD 226 302 403 499 300 M12 500 0.9 0.8 0.8 0.66

6
HRC Distribution Fuse Banks Bussmann ®

Dimensions (see table below)

Dimensions (mm)
CAMAS T ER D imen sion s (mm)
No. of Ratin g
Catalogu e
W ay s (A) A B C D E F G H J K L M N
N u m b er
32F B4CMC 4 32 110.9 265 74.6
32F B6CMC 6 32 167.9 265 46.1
46.8 64.5 124.2 93.7 25.4 62.3 77 143.5 80 34
32F B8CMC 8 32 224.9 365 67.6
32F B12CMC 12 32 338.9 515 85.6
32F B4CM 4 32 131.7 265 70.5
32F B6CM 6 32 198.3 265 37.2
58.8 64.5 124.2 117.5 25.4 64.7 77 143.5 80 34
32F B8CM 8 32 264.9 365 53.9
32F B12CM 12 32 398.0 515 62.3
63F B4CM 4 63 149.6 265 55.2
63F B6CM 6 63 225.6 265 17.2
63 64.5 149.4 126 25.4 89.4 106 217 120 44
63F B8CM 8 63 301.6 365 29.7
63F B12CM 12 63 453.6 515 27.7
100F B4CM 4 100 149.6 265 55.2
100F B6CM 6 100 225.6 365 63 64.5 149.4 126 25.4 89.4 106 217 120 44 55.2
100F B8CM 8 100 301.6 515 103.7
S AF ELO C
Catalogu e
Nu mbers
32F B4NNS 4 32 110.9 265 74.6
32F B6NNS 6 32 167.9 265 46.1
38 50 109 76 25.4 62.3 77 143.5 80 34
32F B8NNS 8 32 224.9 365 67.6
32F B12NNS 12 32 338.9 515 85.6
63F B4ENS 4 63 120.6 265 69.5
63F B6ENS 6 63 181.6 265 39.2
45 58 148.2 90 25.4 89.4 106 21.7 120 44
63F B8ENS 8 63 242.6 365 58.7
63F B12ENS 12 63 364.6 515 72.7

7
Modular Fuse Holders CH Series Bussmann ®

The CH range of Modular Fuse Holders is available in three


sizes: 10 x 38, 14 x 51 and 22 x 58 millimetres. Designed to
accommodate Cylindrical type fuse links with ferrule end caps
up to a maximum rating of 125 Amps. The CH101 series, to
IEC269-2-1, accepts 0.5 to 32 Amp C10G and C10M style of
10 x 38mm European fuse links. The CHM accepts the North
American ‘midget’ style of fuse link and the CHCC accepts the
North American Low Peak class CC fuse links. Both the CHM
and CHCC are UL recognised, guide IZLT2, file E14853 and
certified CSA Standard C22.2 No. 39.

North American Design


The flexibility of assembling multi-poles, ease of fuse link
replacement, together with touch safe protection, ensures that
The North American design of CH range
the improved operating characteristics of the fuse link can now
of fuse holders showing the interlocking be achieved in a package comparable to that of alternative
system for the assembly of multiple poles. circuit protection devices.

• Unique dovetail feature built into the CH 10 x 38


Ordering Codes design allows single pole units to be snapped
10 x 38m m 32A 660V 30A 600V 30A 600V together quickly and safely in the assembly of
North North American North American multi-poles.
D escription American * Midget F u se Class CC F u se
F u se Holder Holder Holder • Space saving design incorporates IP20 touch
S in gle P ole CH101* C HM 1 C HC C 1 safe protection and lockout facility for increased
safety.
S in gle P ole with
CH101I* CHM1I CHCC1I
In dicator • Optional open fuse indication available on
D ou ble P ole CH102* C HM 2 C HC C 2 North American 10 x 38 designs.
D ou ble P ole with
In dicator
CH102I* CHM2I CHCC2I • Fuse holders snap easily onto 35mm DIN rail.
Triple P ole CH103* C HM 3 C HC C 3 • Circuit marking system available.
Triple P ole with
CH103I* CHM3I CHCC3I
In dicator
Assembly P in s -
CH102AP CH102AP CH102AP
2 P oles
Assembly P in s -
CH103AP CH103AP CH103AP
3 P oles
Circu it
CH10CM CH10CM CH10CM
Markers
Circu it Marker
CH10CL CH10CL CH10CL
Labels
S pare F u se
5TPH 5TPH 5TPH
Holders
* Although of North American design, all fuse holders
marked with an asterisk are to IEC specification.

Size 10 x 38 Fuse Holder


Dimension (mm) Dimension (mm)
A 57.5 G 52.5
B 44.0 H 19.0
C 45.2 I 17.5
D 49.9 J 35.0
E 82.2 K 80.7
F 6.0 L 7.6

For further detailed specifications on the ‘CH’ range, please ask for Data Sheet number 1151

8
Modular Fuse Holders CH Series Bussmann ®

The CH...E range of Modular Fuse Holders


A range of cost-effective 10 x 38mm fuse holders, moulded
from materials which are resistant to high temperatures.
Silver plated contacts, 35mm DIN rail fixing with a degree
of protection to IP20. Blown fuse indicator versions avail-
able.
Standards: IEC947-1, NFC61 201, UNE21 103.
North American UL approval.

The ‘CH.......E’ European design range.

F u se h older
F u se h older size
catalogu e D escription F u se lin k ty pe
(mm)
n u m b er
CH101E 1 Pole C10G & C10M
CH101EN 1 Pole + Neutral C10G & C10M

CH102E 2 Pole C10G & C10M


CH103E 3 Pole C10G & C10M
CH103EN 3 Pole + Neutral C10G & C10M
10 x 38 CH101EI 1 Pole + Indicator C10G & C10M
1 Pole + Neutral
CH101ENI C10G & C10M
+ Indicator
CH102EI 2 Pole + Indicator C10G & C10M
CH103EI 3 Pole + Indicator C10G & C10M
3 Pole + Neutral
CH103ENI C10G & C10M
+ Indicator

Fuse links for use in Modular Fuse Holders


Fuse Holder Fuse Holder
Fuse Link
Size (mm) Reference
10 x 38 CH--E C 10G C 10M

10 x 38 CH C 10G C 10M
FNQ KTK AGU BAF
10 x 38 CHM
BAN FNM FWA FWC
10 x 38 CHCC LP-CC FNQ-R KTK-R

14 x 51 CH--G C14G C14M NON

22 x 58 CH--G C 22G C 22M

Cylindrical fuse links - C10G, C14G and C22G

9
Modular Fuse Holders CH Series Bussmann ®

A range of larger dimensioned modular fuse


holders rated up to 50A and 125A respectively.
14 x 51 22 x 58
D escription Catalogu e Catalogu e
Referen ce Referen ce
S in gle P ole CH141G CH221G
S in gle P ole with
CH141MSG CH221MSG
Microswitch
D ou ble P ole CH142G CH222G
Triple P ole CH143G CH223G
Triple P ole with
CH143MSG CH223MSG
Microswitch

Dimensions (mm) for CH range sizes


14 x 51 (50A) and 22 x 58 (125A).

Size 14 x 51 Fuse Holder


Dimension (mm) Dimension (mm)
A 26.0 I 89.0
B 52.0 J 5.0
C 78.0 K 32.5
E 81.0 L 98.0
F 53.5 M 106.0
G 44.5 N 21.0
H 52.6 O 43.8

Triple Pole Unit

Size 22 x 58 Fuse Holder


Dimension (mm) Dimension (mm)
A 35.0 I 103.0
B 70.0 J 4.5
C 105.0 K 45.0
E 88.0 L 112.0
F 53.0 M 140.0
G 45.0 N 26.5
H 58.0 O 63.0

Triple Pole Unit

10
Safety J Fuse Holders Bussmann ®

The Safety J is a Class J Touch Safe Fuse Holder for use with
Bussmann Class J fuse links such as the LPJ and JKS. It is made from
thermoplastic with UL flammability 94VO and is available in 30 amp
and 60 amp versions at 600V, with or without indication.
Agency Approvals: UL listed UL 512 30-60A (guide IZLT, file 14853).
CSA Certified 30-60A (class 6225-01, file 47235).
• Compact design saves valuable panel space.
• Touch safe design from direct or indirect contact with live parts
(meets IP20).
• Dual port wire management system simplifies installation of
multiple loads connected to a single branch circuit (30A only).
• Integral 35mm DIN rail adapter built in, providing convenient
mounting.
• The gangable system means reduced inventory, limiting the need
to stock multiple poles.
• Removable fuse carrier provides added safety while replacing
the fuse link.
• Probe holes incorporated in the carrier provide easy access to
fuse for testing purposes.
• Internal DIN rail release latch makes it easily removable from the
DIN rail with just a screwdriver.
• Reinforced fuse clips are standard giving low resistance
performance.
• Built-in labelling system to enable circuit marking.
• Terminals ready to accept cables, saving valuable installation time.
• Open fuse indication available to enable fast response in
identifying open fuse links.

Catalogue numbers for 30A - JT600030; JTN60030 with indication.

Catalogue numbers for 60A - JT600060; JTN60060 with indication.

11
Class J Fuse Blocks Bussmann ®

J600 Series Fuse Blocks


For use with Class J Fuse Links such as Bussmann LPJ and JKS.
Made of black thermoplastic with a 94VO UL flammability rating.
Ratings: 0.5 to 600 Amps at 600 Volts ac.
Agency Approvals: UL Listed UL512, guide IZLT, file E14853
CSA Certified, class 6225-01, file 47235
For more detailed information on dimensions, please ask for Data
sheet number 1114.

Ordering Codes
Catalogue Number
Amps Poles Box Lug with Max. Cable Size
Screw* Pressure Plate* Box Lug
retaining clip
1 J60030-1S* J60030-1P* J60030-1C J60030-1CR†
0.5 to 30 2 J60030-2S* J60030-2P* J60030-2C J60030-2CR† 5.3mm2
3 J60030-3S* J60030-3P* J60030-3C J60030-3CR†
1 - - J60060-1C J60060-1CR†
31-60 2 - - J60060-2C J60060-2CR† 33mm2
3 - - J60060-3C J60060-3CR†
61-100 3 - - - J60100-3CR† 53mm2
1 - - - J60200-1CR
101-200 127mm2
3 - - - J60200-3CR
1 - - - J60400-1CR
201-400 253mm2
3 - - - J60400-3CR
1 - - - J60600-1CR
401-600 (2)253mm2
3 - - - J60600-3CR
* Clip reinforcing springs are standard on fuse blocks rated 100A and above. Available on the 30A and 60A
blocks, to order add the letter ‘R’ to the end of the part number.
† Copper only connections available by changing ‘CR’ suffix to ‘COR’

LPJ-SP is an example of one type of fuse link that can be accommodated in the J600 series
of Fuse Blocks.

12
Class J Fuse Blocks Bussmann ®

JP Series Fuse Blocks


For use with Class J Fuse Links such as Bussmann LPJ and J S.
Made of black thermoplastic with a 94VO UL flammability rating.
Rating: 30 amps, 600 volts.
Agency Approvals: UL listed (UL512, guide IZLT, file E14853)
CSA Certified (class 4225-04, file 47235).

Catalogue Number

Mounting Box Clamp


Screws with
Pressure Plate
Aluminium Copper Only

JP60030-3CR
JP60030-3PR (8.4 to 33.6mm JP60030-3COR
Panel (2.1 to 5.3mm aluminium wire) (2.1 to 33.6mm
wire) (2.1 to 33.6mm wire)
copper wire)
JP60030-3CRA
JP60030-3PRA (8.4 to 33.6mm JP60030-3CORA
With DIN rail
(2.1 to 5.3mm aluminium wire) (2.1 to 33.6mm
adaptor*
wire) (2.1 to 33.6mm wire)
copper wire)
* To order the DIN rail adaptor only use catalogue ref. JPA-3

13
Class H and R Fuse Blocks Bussmann ®

H250 series for use with Class H fuse links such as Bussmann NON
H600 series for use with Class H fuse links such as Bussmann NOS.

R250 series for use with Class R fuse links such as Bussmann LPN-RK,
FRN-R and KTS-R.
R600 series for use with Class R fuse links such as Bussmann LPS-RK,
FRS-R, DLS-R and KTS-R.
H250 and R250 rated at 250V ac - 0.1A to 600A
H600 and R600 rated at 600V ac - 0.1A to 600A
Agency Approvals:UL Listed (UL512. guide IZLT, file E14852).
CSA Certified (class 6225-01, file 47235).

Dimension details (mm) for 250V class H & R single pole fuse blocks.
0.1 to 30A - 250V 31 to 60A - 250V 61 to 100A - 250V

101 to 600A - 250V Dimensions for 101A to 600A Blocks


Rating
A B G H
(A)

101-200 181.0 78.5 76.2 19.05

201-400 230.0 101.6 76.2 25.4

401-600 279.4 126.2 101.6 25.4

These dimensions refer to single pole fuse blocks only. Double and
triple pole configurations are available with slight variations in size
of individual fuse blocks. Please ask for Data sheet numbers 1110
for R250 series and 1112 for the H250 series for further details.

Various terminal types are available including Screw and Box Lug.
Please telephone our application help line for further details or refer
to the Data sheets listed above.

14
Class H and R Fuse Blocks Bussmann ®

Dimensional Details (mm) for 600V Class H & R Fuse Blocks single pole.

0.1 to 30A 31A to 60A 61A to 100A

Dimensions for 101 to 600A


Rating
A B G H
(A)

101-200 244.6 78.5 76.2 19.05

201-400 304.8 101.6 76.2 25.4

401-600 355.6 126.2 101.6 25.4

All dimensions refer to Single Pole only.

For further detailed information please ask for Data sheet number
1111 for R600 series and 1113 for H600 series

Illustration of fuse link types that


can be used in Class H & R fuse
blocks.

15
Modular Fuse Blocks Bussmann ®

A versatile design of fuse block able to accept a wide range of fuse


link types and sizes. Two identical half blocks are included with each
part number.
Catalogue Reference: 1BS101, 1BS102, 1BS103 and 1BS104
Agency Approvals: UL Recognised, guide No. 1ZLT2, file No. E14853

Dimensions (mm)
1BS101 - 0 to 600V, 100Amps
1BS 101 fuse blocks The 1BS101 features a dovetail interlock and anti pivot pin. The
dovetail interlock permitting ganging of single pole units into multi-
pole configurations.
Mounting dimensions for various
fuse link types (mm).
Catalogue
A B C
References
FWA 70A-100A 49.3 16.0 95.4
FWH 35-60B 58.9 25.6 104.9
FWH 70-100B 72.4 39.1 118.3
FWX 35A-60A 59.4 26.1 105.4
FWX 70A-100A 59.7 26.4 105.6
KAC 1-30 63.5 30.2 109.4
KAC 35-60 88.9 55.6 134.8
KAC 70-100 105.7 72.3 151.6
KBC 35-60 88.9 55.6 134.8
KBC 70-100 93.0 59.6 138.9
LPJ 70SP-100SP 95.5 62.2 141.4
JJS 70-100 59.9 26.6 105.9
JKS 70-100 96.3 62.9 142.2
80-100L14C 89.9 56.6 135.8
80-100L09C 112.0 78.7 157.9

Mounting dimensions for various 1BS102 - 0 to 600V, 400Amps


fuse link types (mm).
Catalogue
A B C
References
FWA 70-100A 50.3 8.9 167.9
FWH 125-200B 70.4 29.0 188.0
FWX 125A-200A 61.2 19.8 178.8
KBC 110-200 94.0 52.6 211.6
JJS 110-200 63.5 22.1 181.1
70A-100 CJ 92.2 50.8 209.8
125-400M09C 111.3 69.9 228.9
250-400P09C* 111.3 69.9 228.9

* When used in multiple pole con-


figurations, 19.05 mm should be
maintained between adjacent
mouldings when mounting the
fuses indicated.

16
Modular Fuse Blocks Bussmann ®

Dimensions (mm) Mounting dimensions for various


fuse link types (mm)
1BS103 - 0 to 600V, 400 Amps
Catalogue
A B C
References
FWH 225A-400A 83.8 42.4 201.4
FWX 225A-400A 67.6 26.2 185.2
KAC 110-200 109.2 67.8 226.8
KBC 225-400 103.1 61.7 220.7
160-400LMT 58.9 17.5 176.5
250-400P11C* 184.2 142.7 301.8
JJN 225-400 46.7 5.3 164.3
JJS 225-400 69.1 27.7 186.7
CGL 225-400* 184.2 142.7 301.8

* When used in multiple configura-


tions 25.4mm should be maintained
between adjacent mouldings when
mounting the fuse indicated.

Mounting dimensions for various


fuse link types (mm)
1BS104 - 0 to 600V, 600 Amps Catalogue
A B C
References
FWA 500A-600A 62.0 19.1 222.3
FWH 450A-600A 74.7 31.8 235.0
FWX 450A-600A 62.5 19.6 222.8
KAC 225-400 123.7 80.8 284.0
KAC 450-600 122.9 80.0 283.2
KBC 450-600 95.0 52.1 255.3
JJN 450-600 51.6 8.6 211.8
JJS 450-600 74.9 32.0 235.2
450-600R11C* 184.2 141.2 344.4
CGL 450-600* 184.2 141.2 344.4

* When used in multiple configura-


tions 12.7mm should be maintained
between adjacent mouldings
when mounting the fuse indicated.

17
HRC Fuse Bases for NH Style Fuse Links Bussmann ®

Fuse bases to accommodate NH fuse links in


sizes 00 to 3 single pole and 00 to 2 triple pole.
Specifications: VDE 0636 and DIN43 620/3
HRC Fuse Bases are designed in accordance to DIN 43 620/1 and are
available in sizes 00, 0, 1, 2 and 3. Both the single and triple pole
versions are rated at 660V ac. Due to the excessive pull forces required
to extract the fuse link from associated equipment, it is normal prac-
tice for size 4a/4 fuse links to be fitted into a switch fuse disconnect.
NH Fuse Bases are designed from heat resistant lightweight moulded
materials, with connection to the fuse link by means of silver plated
contacts. Bolted cable terminals are available, with the option of a ‘V’
clamp terminal connection on size 00, which accepts incoming cable
sizes up to 70mm2 (add suffix ‘V’ to the part number i.e. SB00V).
Partition barriers can be mounted between poles on the bases (except
size 00 with ‘V’ clamp terminals). These are sold as separate items,
catalogue reference PB followed by the fuse size.

• Profiled shaped contact springs for secure mounting of


the fuse link.
• Heat resistant lightweight moulded material.
• Silver plating of the contacts ensuring durable fuse link
contact.
• High resistance to short circuit.
• Ease of fuse link extraction with universal fuse link puller
- ref. 630. Can be supplied with leather cuff to special
order - ref. 630LC
• Single pole bases packed in threes, triple pole packed
in singles.

Single pole size 2 (reference SB2)

Dimensions of Single and Triple Pole size 00 and 0 NH Fuse Base (mm)
Catalogue reference SB (single pole) TB (triple pole).

Cat. Rated
Ref. & Current A B C D E F G H J
Size (A)
SB00 160 120 100 75 17 20 32 80 - -
SB0 160 170 150 75 17 20 32 104 - -
TB00 160 120 100 75 17 20 32 80 100 32
TB0 160 170 150 75 17 20 32 104 100 32

Size ‘0’ fuse links fit into size 1 bases

18
HRC Fuse Bases for NH Style Fuse Links Bussmann ®

Partition Barriers
Partition barriers are used when additional security demands have
to be met. To ensure additional safety, cover capes can be mounted
on the contact springs. These cover capes are available for single
pole and triple pole bases size 00 with bolt connections only. Cover
capes are to special order only.
To order Partition Barriers - reference PB followed by the size (00, 1,
2 or 3). Partition Barriers manufactured from a durable fabric.

Triple Pole Base showing universal fuse


Dimensions of Single and Triple Pole NH Fuse Base puller to aid fuse extraction. Cat. Ref. 630
(mm) sizes 1, 2 and 3
Catalogue reference SB (single pole) TB (triple pole).

Triple pole base with Partition


Barriers (reference PB-) fitted.

C at . Rated
Ref. & Current A B C D E F G H J K L
Size (A)
SB1 250 200 175 89 27 25 60 152 - - 2 M10
SB2 400 230 200 98 27.5 35 60 152 - - 2.5 M12
SB3 630 240 210 110 28 45 80 152 - - 3 M12
TB1 250 200 175 89 27 25 60 152 184 60 2 M10
TB2 400 230 200 98 27.5 35 60 152 184 60 2.5 M12
TB3 630 240 210 110 28 45 80 152 244 80 3 M12
Size ‘0’ fuse links fit into size 1 bases.

19
Vertical Fuse Bases for NH Style Fuse Links Bussmann ®

A one-piece vertical arrangement of fuse base, moulded from a


glass fibre strengthened self extinguishing synthetic material, incor-
porating a central corrosion resistant bar and stainless steel contact
springs for secure fuse link positioning. Designed for 185mm busbar
fixing (100mm for the size 00). Horizontal phase separation plates
are included, vertical separation covers are available and can be
fitted as required. (See table below).
Dimensions according to DIN 43. 623
For fuse links according to DIN 43. 620
Sizes available 00, 1, 2, and 3 all at 660V ac.

Rated
Catalogu e Rated
S ize Voltage (V) D escription
Referen ce Cu rren t (A)
ac
VF B100/00 00 160 660 100mm bus bar fixing
VF B185/00 00 160 660 185mm bus bar fixing
100mm bus bar fixing -
For a full list of accessories and detail of VF B100/00T S 00 160 660
touch safe
touch safe requirement for size 1, 2 and 3, VF B185/00T S 00 160 660
185mm bus bar fixing -
contact Bussmann Application engineers on touch safe
+44 (0)1509 882760 and 882766. VF B185/1 1 250 660 185mm bus bar fixing
185mm bus bar fixing -
Vertical fuse bases are available to special VF B185/1T S 1 250 660
touch safe
order only. VF B185/2 2 400 660 185mm bus bar fixing
185mm bus bar fixing -
VF B185/2T S 2 400 660
touch safe
VF B185/3 3 630 660 185mm bus bar fixing
185mm bus bar fixing -
VF B185/3T S 3 630 660
touch safe

TS at the end of the catalogue reference means that vertical


separation covers are fitted for touch safe application.

Size A B C D E F G H J K L M
00 355 200 47 28 - - - 100 15 33 3 72
1, 2 & 3 634 370 - 54 84 97 650 185 24 41 3 124

20
Optima™ Overcurrent Protection Module Bussmann ®

Optima OPM-1038 Series


The OPM-1038 series offers a high specification of protection against
short circuit damage in eight feature combinations, for a broader
coverage of today’s process control panel applications. The unit is
available as a three pole fuse module or, switch fuse disconnect;
employing the unique cam action fuse carrier withdrawal and offering
combinations accepting 10 x 38mm fuse links to European IEC 269
standard or alternatively North American 10 x 38mm LP-CC and
midget types to UL approval and CSA standards. This overcurrent
protection module can be adapted to suit a wide variety of applications,
including communication to a remote PC or PLC.
Types available: C = communication (remote indication)
R = rejection (class CC)

• Small size matches 45mm IEC starter width.


• Smallest 30 amp fusible disconnect available.
• Fits 0.8mm2 to 8.4mm2 cable, both stranded and
solid. Recommended fuse link types
• Open fuse indicator lights.
• Cam action handle for easy removal.
Midget (non-
Class CC European
• Finger safe terminals. rejection)

• Removable module for convenient fuse link loading. LP-CC KTK C10M
• 35mm DIN rail or screw panel mounting.
KTK-R FNM C10G
• Dead-front construction
FNQ-R FNQ
• Can be padlocked for additional security.
• Option for remote ‘open fuse’ status indication feature
available enabling less downtime.
• Offered with Class CC rejection clips or European
10 x 38mm clips to meet global needs.

Types available Non-switch series


Current limiting fuse links can operate Catalogu e Voltage Amp SC
Remote
in as little as 2 milliseconds, breaking Approvals Clips Open Fu s e
Nu mber ( ac ) Ratin g Ratin g
I n d ic at io n
the circuit before let-through energy
OPM-1038 IEC269-2-1 660 32 * Non-rejection No
destroys components inside the panel.
With the OPM and correctly sized fuse OPM-1038R UL Listed 600 30 200kA Rejection No
links, there is no welded contacts or OPM-1038C IEC269-2-1 660 32 * Non-rejection Yes
burned open overload relays, thereby OPM-1038RC UL Listed 600 30 200kA Rejection Yes
eliminating costly repairs to equipment * Rating varies depending on fuse link used in module
and keeping down time to a minimum.

21
Optima™ Overcurrent Protection Module Bussmann ®

Types available Load Break Disconnect Switch


Remote
Catalogu e Voltage Amp SC
Approvals Clips O p en F u s e
N u m b er (ac ) Ratin g Ratin g
In dication
O P M-1038S W IEC947-3 660 32 * Non-rejection No
O P M-1038RS W UL Listed 600 30 200kA Rejection No
O P M-1038S WC IEC947-3 660 32 * Non-rejection Yes Dimensions (mm) for
O P M-1038RS WC UL Listed 600 30 200kA Rejection Yes non-switch series
* Rating varies depending on fuse link used in module

Non-switched