Professional Documents
Culture Documents
7.harmonic WOLED PDF
7.harmonic WOLED PDF
discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/258219806
CITATIONS READS
0 177
3 authors, including:
Hari Maghfiroh
Gadjah Mada University
9 PUBLICATIONS 2 CITATIONS
SEE PROFILE
All content following this page was uploaded by Hari Maghfiroh on 20 May 2014.
Abstract² Fluorescent and WOLED are widely used because it II. HARMONICS
consumes less energy. However, both lamps cause a harmonics
because it has semiconductors components. Harmonic is a distorted A. Harmonics in Power Systems
sinusoidal electric wave and cause excess heat. This study compares Harmonic is a phenomenon arising from the operation of
the amount of harmonics generated by both lamps and also measures non-linear loads which is caused by a sinusoidal wave with a
HDFK ODPS¶V Power Factor (PF) from both kinds of lights. The test frequency of integer multiples of the frequency of the source
shows that both lamps have THDv(Total Harmonics Distortion of [2]. For example if the source frequency is 50 Hz harmonics
Voltage) almost the same with average - 2.5% while the average of
frequency is 100 Hz, 150 Hz, 200Hz, and so on.
WOLED¶V THDi(Total Harmonics Distortion of Current) is lower
than fluorescent has. 7KH DYHUDJH :2/('¶V 7+'L LV 29.10 % and
Fourier theory mentions that any repetitive waveform can
fluorescent µV7+'LLV be defined in terms of summing sinusoidal waveforms which
are integer multiples (or harmonics) of the fundamental
Keywords² fluorescent, harmonic, power factor, WOLED frequency. For the purpose of a steady state waveform with
equal positive and negative half-cycles, the Fourier series can
I. INTRODUCTION be expressed as follows[5]:
Nowadays, more research effort is put on energy efficiency ݂ሺݐሻ ൌ σஶ
୬ୀଵ Ǥ ሺςȀሻ (1)
issues. Researcher has been doing research to find more
energy-efficient lamps. Australia and Europe tried to eliminate where
the use of incandescent lamps in 2009, while China targets f(t) is the time domain function
complete replacement in 2016. The underlying reason is n is the harmonic number (only odd values of n are
because incandescent bulbs waste a lot of electrical energy required)
into heat. Based on a research data incandescent lamp has An is the amplitude of the n-th harmonic component
efficacy 14 lm / w, halogen lamp has 20 lm / w, fluorescent T is the length of one cycle in seconds
has 60 lm / w, and WOLED has 100 lm / w [1].
Based on the data above, it is clear that fluorescent and Superposition of harmonic frequency and the source
WOLED are more efficient than data incandescent bulb. frequency causing defects (distorted) on the sine wave in
Although fluorescent and WOLED has higher efficacy, both power system. Sample images of sinusoidal wave and
of them cause harmonic distortion due to the use of non-linear distorted wave due to harmonic signals can be seen in Figure
component. Fluorescent has non-linear component in the 1.
inverter [2], while WOLED using electronic drive to get the
corresponding voltage obtained from the power [1]. Previous
research has shown that the average fluorescent lamp has
THDv rate of 4%, and THDi of 70% [3]. WOLED type
resistor has a THD 39, 5% [4].
The aim of this study is to compare the resulting harmonic
distortion caused by fluorescents and WOLED to find out
which lamp is more energy efficient. Harmonic is an indicator
of the performance lamp to electrical energy consumption
(power factor). The test is performed using the three-phase
star arrangement.
62
World Academy of Science, Engineering and Technology 72 2012
The rectifier can be thought as a harmonic current source 2) Total Harmonic Distortion (THD)
and produces roughly the same amount of harmonic current THD is the percentage of total harmonic voltage distortion
over a wide range of power system impedances. The calculated or measured at PCC(Point of Common Coupling ).
characteristic of the current harmonics that are produced by a Some book mention it as THDv(Total Harmonic Distortion of
rectifier are determined by the pulse number. The following Voltage) and here we use THDv.
equation allows determination of the characteristic harmonics
for a given pulse number [7]: ටσ̱ మ
సమ
ܶ ܦܪൌ ܶ ݒܦܪൌ (5)
h = kq + 1 (2) ଵ
where
h is the harmonic number 3) Total Demand Distortion (TDD)
k is any positive number TDD is the percentage of total harmonic current distortion
q is the pulse number of the converter calculated or measured at PCC. Some book mention it as
THDi(Total Harmonic Distortion of Current) and here we use
This means that a 6-pulse(or 3-phase) rectifier will exhibit THDi.
harmonic at the 5th, 7th, 11th, 13th, 17th, 19th, 23rd, 25th, etc.
multiples of the fundamental. ටσ̱
సమ ூ
మ
ܶ ܦܦൌ ܶ ݅ܦܪൌ ூଵ
(6)
C. Effect of Harmonic
Harmonics can lead to power system inefficiency. Some of
the negative ways that harmonics may affect equipment are E. Standard Harmonics IEEE 519
listed below[7]: IEEE 519-1992 titled ³IEEE Recommended Practices and
x Conductor Overheat: a function of the square rms Requirements for Harmonic Control in Electrical Power
current per unit volume of the conductor. Harmonic System´ establish recommended guidelines for harmonic
currents on undersized conductors or cables can voltages on the utility distribution system as well as harmonic
FDXVHD³VNLQHIIHFW´ZKLFKLQFUHDVHVZLWKIUHTXHQF\ currents within the industrial distribution system. This
and is similar to a centrifugal force. standard give limits for voltage and current harmonic, see
x Fuses and Circuit Breakers: harmonics can cause Table 1 for voltage harmonics limits and Table 2 for current
false or spurious operations and trips, damaging or harmonics limits.
blowing components for no apparent reason.
x Transformers: have increased iron and copper Table 1. Voltage Distortion Limits [8]
losses or eddy currents due to stray flux losses. This
causes excessive overheating in the transformer
windings. Typically, the use of appropriate ³.
IDFWRU´ UDWHG XQLWV DUH UHFRPPHQGHG IRU QRQ-linear
loads.
x Utility Meters: may record measurements
incorrectly, resulting in higher billings to consumers.
x Drives/Power Supplies: can be affected by [1]
High voltage systems can have up to 2.0% THD where the cause is an
misoperation due to multiple zero crossings. HVDC terminal that will attenuate by the time it is tapped for a user.
Harmonics can cause failure of the commutation
circuits, found in DC drives and AC drives with Table 2. Current Distortion Limits for General Distribution
silicon control WOLED rectifiers (SCRs). Systems (120 V through 69 kV) [8]
݊ܦܪܫൌ ͲͲͳݔΨ (4)
ଵ
63
World Academy of Science, Engineering and Technology 72 2012
III. RESEARCH METHOD harmonic voltage spectrum can be seen in Figure 4. As seen
In this study, the circuit used for testing is a star connected on the graph (a) and (b), the percentage of the first value is
three-phase source as seen in Figure 2. 100%, is the fundamental frequency. Then the second and so
on are the harmonics frequency that became smaller. Power
Analyzer measurement results show that the percentage of
average THDv at each phase of testing with fluorescent lamps
is 2.7%, 2.5%, 2.6% with the average THDv is 2.6% . On the
other hand, the average percentage THDv at each phase of
testing with this WOLED lamp is 2.4%, 2.5%, 2.7% with the
average THDv is 2.53%. It can be inferred that the value of
THDv between fluorescents and WOLED is almost equal with
the difference 0.07%. The calculation of THDv is use 49
sample that is from 2nd harmonic to 50th harmonic. From Table
1 we know that THDv standard from IEEE 519-1992 is 5 %,
(a) so THDv of both lamps are within the limits.
The small value of THDv in both lamps means that
sinusoidal voltage wave form is minorly distorted. The voltage
waveform image can be seen in Figure 5.
(b)
Figure 2. (a)Star composition, (b) Test-bench
(b)
64
World Academy of Science, Engineering and Technology 72 2012
(b)
Figure 6. Spectrum of current harmonic: (a) fluorescent, (b) WOLED
(a)
(a)
(b)
Figure 5. Harmonic Voltage Waveform : (a) fluorescent, (b)
WOLED
ACKNOWLEDGMENT
(a) Thanks to the Department of Electrical Engineering and
65
World Academy of Science, Engineering and Technology 72 2012
REFERENCES
[1] Weir, Bernie. (2012, March). Driving 21st Century's Lights. ieee
Spectrum 3.12 , pp. 42-47.
[2] Rasjid, Harun. (2006). Kajian Pnggunaan Filter Pasif Sebagai Pereduksi
Efek Harmonisa. ELTEK , 46-53.
[3] http://karyailmiah.tarumanagara.ac.id/index.php/S1TE/article/view/2221
/0 (11-04- 2012 ± 22.40).
[4] http://www.onceinnovations.com/downloads/perf_diff.pdf . (26-05-2012
± 12. 05).
[5] Ellis, Robert G.Power System Harmonic:A References Guide to Causes
Effects and Corrective Measures.(Ellis 2001)
[6] Wijaya, F.Danang, Avrin Nur Widiastuti, and Zuhdan Febri Wibowo.
"Pengaruh Beban Harmonik Terhadap Putaran Piringan KWh Meter
Induksi." CITEE. Indonesia: Department Of Electrical Engineering and
Information Tech.,UGM, 2011. 124.
[7] Ellis, Robert G. Power System HArmonic, A Reference Guide to
Causes, Effects and Corrective Measures. Canada: Rockwell
International Corporation, 2001.
[8] IEEE Recommended Practices and Requirements for Harmonic Control
in Electrical Power Systems, ANSI/IEEE Std. 519-1992.
66