You are on page 1of 131

CHAPTER 4

ACTIVE FIRE
PRECAUTION
01 OBJECTIVE OF ACTIVE SYSTEM
02 DETECTION AND WARNING
SYSTEM
TABLE OF 03 EMERGENCY LIGHTING
CONTENT 04 PORTABLE FIRE
EXTINGUISHERS
05 EXTERNAL HYDRANT SYSTEM
06 WET RISER AND DRY RISER
SYSTEM
TABLE OF 07 DOWN-COMER SYSTEM
CONTENT 08 HOSE-REEL SYSTEM
09 AUTOMATIC INERT GAS
EXTINGUISHING SYSTEM
SECTION 1
OBJECTIVE OF ACTIVE
SYSTEM
OBJECTIVE OF THE ACTIVE SYSTEM
Active fire protection is an integral part of any fire safety
strategy, characterised by items and/or systems
requiring a certain degree of motion and response in
order to work.
An active fire protection system works to detect,
control, suppress, and extinguish fire. It requires an
action to trigger it’s involvement, either manual,
electrical or mechanical.
The benefits of using active fire protection system are
permitting design freedoms and encourage innovative,
inclusive and sustainable architecture
MEC654 // Study Materials by AAR 5
OBJECTIVE OF THE ACTIVE SYSTEM
The overall aim of active systems is to extinguish the
fire by:
⊳Detecting the fire early and evacuating the building
⊳Alerting emergency services at an early stage of the fire
⊳Control the movement of smoke and fire
⊳Suppress and/or starve the fire of oxygen and fuel
Fire can be controlled or extinguished either
automatically or manually.
⊳Automatically is with the used of water sprinkler system
⊳Manually is by using fire extinguisher.

MEC654 // Study Materials by AAR 6


OBJECTIVE OF THE ACTIVE SYSTEM
Installation of active
system inside the building
can be divided into three
groups
⊳Fire Alarm
⊳Portable
⊳Fixed

MEC654 // Study Materials by AAR 7


OBJECTIVE OF THE ACTIVE SYSTEM
Fire Alarm System
⊳Smoke detector
⊳Heat detector
⊳Bell

MEC654 // Study Materials by AAR 8


OBJECTIVE OF THE ACTIVE SYSTEM
Portable System
⊳Dry powder
⊳CO2
⊳Foam

MEC654 // Study Materials by AAR 9


OBJECTIVE OF THE ACTIVE SYSTEM
Fixed System
⊳Hose reel
⊳Hydrant
⊳Sprinkler
⊳Dry riser
⊳Wet riser
⊳Down comer
⊳CO2 & Clean Agent Fire
Suppression System
⊳Smoke Spill

MEC654 // Study Materials by AAR 10


UBBL
SECTION IN UBBL RELEVANT TO ACTIVE FIRE
PROTECTION SYSTEM
⊳PART VIII – Fire alarms, fire detection, fire extinguishment and
fire fighting access (bylaw clauses 225 to 253).
Examples :-
BYLAW 227 – PORTABLE EXTINGUISHERS
BYLAW 230 – DRY RISING SYSTEMS
BYLAW 231 – WET RISING SYSTEMS
BYLAW 237 – FIRE ALARM SYSTEMS
BYLAW 243 – FIRE LIFT SYSTEMS
⊳Third Schedule – Ventilation System (BY-LAW 41)
⊳Tenth Schedule – Table Of Requirements For Fire
Extinguishment, Alarm Systems, And Emergency Lighting
MEC654 // Study Materials by AAR 11
UBBL 10th SCHEDULE
Schedule 10 was UBBL
Specifically referred to
requirement for fire
extinguishment system
REF. CLAUSE

BUILDING TYPE

TYPE OF SYSTEM

What it mean by
this Code?
MEC654 // Study Materials by AAR 12
UBBL 10th SCHEDULE

MEC654 // Study Materials by AAR 13


UBBL 10th SCHEDULE

MEC654 // Study Materials by AAR 14


UBBL 10th SCHEDULE

MEC654 // Study Materials by AAR 15


SECTION 2
DETECTION AND WARNING
SYSTEM
IONIZATION SMOKE DETECTORS

No Smoke
MEC654 // Study Materials by AAR 17
IONIZATION SMOKE DETECTORS

With Smoke
MEC654 // Study Materials by AAR 18
OPTICAL SMOKE DETECTORS
Optical Obscuration
Light Sensitive Light Emitting
Diode Diode

Curved
Mirror

No Smoke With Smoke

MEC654 // Study Materials by AAR 19


OPTICAL SMOKE DETECTORS
Optical Scatter
Light Sensitive Light Emitting
Diode Diode

No Smoke With Smoke

MEC654 // Study Materials by AAR 20


OPTICAL SMOKE DETECTORS
Light Emitting Diode
120 Light Sensitive
Diode

60
Backward Scatter Forward Scatter

Light Sensitive Diode

MEC654 // Study Materials by AAR 21


OPTICAL Vs. IONIZATION DETECTORS
OPTICAL DETECTORS IONIZATION DETECTORS
 Detects large particles  Detects small particles
 Reacts to slower burning fires  Reacts to fast free burning fires
best best
 Detects smoldering fires  Detects early combustion
 Provides detection to modern products
materials burning  Older cold smoke is not
 More difficult to manufacture detected easily
 No special disposal required  Easier to manufacture
 Environmentally unfriendly
MEC654 // Study Materials by AAR 22
BEAM DETECTORS
Obscuration Ceiling

Transmitter

Receiver
Signals to Fire Alarm

Control Unit Power


Supply

MEC654 // Study Materials by AAR 23


HEAT DETECTORS

Thermistor Thermistor

Fixed Temperature Rate of Rise

MEC654 // Study Materials by AAR 24


FLAME DETECTORS

Infra-red & ultraviolet emissions


modulated at typically 1-7Hz

Sapphire
lens

MEC654 // Study Materials by AAR 25


LINEAR HEAT DETECTORS

Control Unit

End line
Signal to
Fire Alarm
Power
Supply
MEC654 // Study Materials by AAR 26
ASPIRATING DETECTORS

Sampling holes

Exhaust

Detection Unit

MEC654 // Study Materials by AAR 27


CONVENTIONAL FIRE ALARM SYSTEMS
Detection Circuits Sounder Circuits

FIRE FIRE

FIRE

FIRE

Panel

MEC654 // Study Materials by AAR 28


CONVENTIONAL FIRE ALARM SYSTEMS
Zone Circuits With Short Circuit Monitoring
I
End of
V line
At the control panel
Upper Voltage
Reference > 7.8V
Condition
Output Zone Input Z+
Outputs
Lower Voltage
Reference < 3.9V
MEC654 // Study Materials by AAR 29
ADDRESSABLE FIRE ALARM SYSTEMS
Detection Circuits Sounder Circuits

FIRE FIRE

FIRE

FIRE

Panel

MEC654 // Study Materials by AAR 30


ADDRESSABLE FIRE ALARM SYSTEMS
WHAT IS ADDRESSABILITY? Ali Hallo Bossku
Nothing much
S

Hallo Ali
What’s happening?

Abu Hallo Bossku


Hallo Abu Nothing much
What’s happening? S

Hallo Bakar
What’s happening?
Bakar Bossku It’s getting
HOT in here!
H

MEC654 // Study Materials by AAR 31


HARD ADDRESSING
Hard addressing uses a hardware device to set an
address for each individual item of equipment.
A variety of methods have been used including dip
switches, plug in modules and wafers.
DIP Switch
1 0

1 0 1 0 1 0 0 1
MEC654 // Study Materials by AAR 32
SOFT ADDRESSING
Soft addressing is a technique where by addresses are
set automatically by the control equipment.
This method uses more sophisticated address
technology and requires additional components in each
device. Isolator

Address
Memory
Communication
interface
Loop
MEC654 // Study Materials by AAR 33
HARD ADDRESSING Vs. SOFT ADDRESSING
HARD ADDRESSING SOFT ADDRESSING
 Low tech inexpensive  High tech requires additional
 Danger of address duplication components
 Easy to add addresses  No duplication of addresses
 No additional benefit  Addition of addresses may result in
 Time required to set addresses address changes unless non volatile
 Possible commissioning problems memory used
from duplication of addresses  Possible additional benefit of individual
device isolation
 Time saving addressing method
 Possible commissioning problems from
address component failure
MEC654 // Study Materials by AAR 34
ANALOGUE FIRE ALARM SYSTEMS
Detection Circuits Sounder Circuits  Analogue detection utilizes
sensors not detectors
FIRE FIRE
 Fire recognition is done at the
control panel
 Fire decisions are based upon
pre-determined thresholds and
fire pattern algorithms
FIRE

FIRE  More rapid and accurate fire


detection is possible
 Compensation for contamination
Panel can be applied
 False alarms can be reduced
MEC654 // Study Materials by AAR 35
ALARM DEVICES
Bells
Electronic Sounders
Voice Message Systems
Visual Alarm Devices
Specialist Alarms

MEC654 // Study Materials by AAR 36


VISUAL ALARM DEVICES (VADs)
EN 54-23 fully implemented Dec 2013
Specifies the requirements, test methods and performance
criteria for VADs.
VADs now classified into three categories based on their
intended application:
⊳ ceiling mounted,
⊳ wall mounted and
⊳ open class
Area of coverage determined by testing is based on the
distance at which 0.4 lumens/m2 on a surface perpendicular
to the direction of the light emitted from the VAD.
MEC654 // Study Materials by AAR 37
VISUAL ALARM DEVICES (VADs)

MEC654 // Study Materials by AAR 38


ALARM CIRCUITS
Most systems currently available utilize conventional
type sounder circuits.
However, sounders which are connected to the same
loop wiring as detectors are becoming more
common.

MEC654 // Study Materials by AAR 39


BELL CIRCUITS

End of
V
line

Circuit Monitoring

MEC654 // Study Materials by AAR 40


IMPLICATIONS OF SOUNDERS ON
DETECTION CIRCUITS
Less installation required since reduced cabling.
Sounders may be addressable allowing greater
flexibility of alarm configuration.
Reduction in monitoring circuitry since the cables are
monitored as part of the detection system.
Sounders require more complex electronics and are
therefore more expensive.

MEC654 // Study Materials by AAR 41


IMPLICATIONS OF SOUNDERS ON
DETECTION CIRCUITS
Sounders require more complex electronics and are
therefore more expensive.
Greater loop circuit integrity is required to ensure that a
single cable fault does not prevent alarm.
Robust design required to ensure detection and alarm
functions operate independently.

MEC654 // Study Materials by AAR 42


SECTION 3
EMERGENCY LIGHTING
EMERGENCY LIGHTING
To indicate clearly and unambiguously the escape
routes
To provide illumination along such routes to allow safe
movements towards and through the exits provided
To ensure that fire alarm call points and fire fighting
equipment provided along escape routes can be readily
located and used
To permit operations concerned with safety measures

MEC654 // Study Materials by AAR 44


EMERGENCY LIGHTING
To indicate clearly and unambiguously the escape
routes
To provide illumination along such routes to allow safe
movements towards and through the exits provided
To ensure that fire alarm call points and fire fighting
equipment provided along escape routes can be readily
located and used
To permit operations concerned with safety measures

MEC654 // Study Materials by AAR 45


DEFINITIONS
Duration
⊳The time that a luminaire can continuously provide the
minimum illuminance required.
Emergency Exit
⊳An exit intended to be used only during an emergency.
Emergency Lighting
⊳Lighting provided for use when the normal lighting supply fails.
Emergency Lighting System
⊳The complete emergency lighting installation.

MEC654 // Study Materials by AAR 46


DEFINITIONS
Escape Lighting
⊳That part of the emergency lighting installation that is
intended to ensure that the escape route is illuminated at all
material times.
Escape Route
⊳The route which forms part of the means of escape from any
point in the building, to a final exit.

MEC654 // Study Materials by AAR 47


DEFINITIONS
Luminaire
⊳Apparatus which distributes, filters and transforms the light
given by a lamp or lamps, and which includes all the items
necessary for fixing and protecting these lamps and for
connecting them to the supply circuit.
Maintained Emergency Lighting
⊳A lighting system in which all emergency lighting luminaires are
in operation at all material times.
Non-maintained Emergency Lighting
⊳A lighting system in which all emergency lighting luminaires are
in operation only when the supply to the normal lighting fails.
MEC654 // Study Materials by AAR 48
DEFINITIONS
Self-contained Emergency Luminaire
⊳A luminaire providing maintained or non-maintained
emergency lighting, in which all the elements such as the
battery, lamp, control unit and the test and monitoring
facilities - where provided - are contained within the luminaire,
or adjacent to it (i.e. within lm).
Slave Luminaire
⊳A luminaire supplied from a central power source and not
having its own internal secondary supply

MEC654 // Study Materials by AAR 49


DEFINITIONS
Uniformity
⊳The ratio of minimum illuminance to the average illuminance
applied to the values of the working plane.
Sustained (Combined) Emergency Luminaire
⊳An emergency lighting luminaire containing at least two lamps,
one of which is energised from the normal lighting supply and
the other from an emergency lighting supply. Such a luminaire
is intended to sustain illumination at all material times.

MEC654 // Study Materials by AAR 50


EXIT SIGN
Signs complying with the Signs Directive are required at
all emergency Exits and along Escape routes
Where direct sight of a sign is not possible a directional
sign or series of signs must be used
There should be no ambiguity as to which direction the
escape route follows

MEC654 // Study Materials by AAR 51


EXIT SIGN

1975
To be replaced by 24 December 1998

1990
Deemed to comply with Signs Directive
for existing installations

1996
European Signs Directive Format
MEC654 // Study Materials by AAR 52
THE SAFETY SIGNS REGULATIONS
Signs complying with BS 5499 will meet the
requirements provided they continue to fulfil their
purpose effectively
Signs may be supplemented by directional arrows
Directional arrows on their own are not acceptable
⊳Small differences from the pictograms or symbols shown are
acceptable providing they do not affect or confuse the
message

MEC654 // Study Materials by AAR 53


THE SAFETY SIGNS LIGHTING
REQUIREMENTS
The Luminance of any area of Colour shall be at least 2
cd/meter squared
The sign shall be white symbol out of green (ISO 3864)
The ratio of max. to min. luminance shall be less than
10:1
The ratio of luminance from white to green shall be
between 5:1 and 15:1

MEC654 // Study Materials by AAR 54


EMERGENCY SIGNS VIEWING DISTANCE

Internally illuminated Max D less than 200 x H


Externally illuminated Max D less than 100 x H

MEC654 // Study Materials by AAR 55


SITING OF LUMINAIRES
Near stairs Near changes of level

MEC654 // Study Materials by AAR 56


SITING OF LUMINAIRES
Exit doors Safety signs

MEC654 // Study Materials by AAR 57


SITING OF LUMINAIRES
Near each change of direction

MEC654 // Study Materials by AAR 58


SITING OF LUMINAIRES
Near each intersection of corridors

MEC654 // Study Materials by AAR 59


SITING OF LUMINAIRES
Near each piece of fire fighting equipment

MEC654 // Study Materials by AAR 60


SITING OF LUMINAIRES
Outside and near to each final exit

MEC654 // Study Materials by AAR 61


SITING OF LUMINAIRES
Near each First Aid point

MEC654 // Study Materials by AAR 62


SITING OF LUMINAIRES
Near each First Aid point

MEC654 // Study Materials by AAR 63


MINIMUM LIGHTING LEVELS
Escape Routes (Previously called “defined escape routes”)

U.K. A. Deviation - 0.2 Lux Recommended normal level - 1 Lux


Permanently unobstructed routes only All Risks
MEC654 // Study Materials by AAR 64
SECTION 4
PORTABLE FIRE EXTINGUISHERS
PORTABLE FIRE EXTINGUISHER
Portable fire extinguisher used to comply with this
standard shall be listed and labelled and meet or exceed
all the requirements of one on the fire test standards
and one of the appropriate performance standard as
below:
⊳Fire test standards:
ANS/UL 711, CAN 4-S508-M83, MS1539 PART 3, BS 5306
⊳Performance standards:
Carbon Dioxide Types: ANSI/UL 154, CAN 4-S503-M83
Dry Chemical Types: ANSI/UL 299, ULC-S504
Water Types: ANSI/UL 626, CAN 4-S507-M83
Film Forming Foam Types: ANSI/UL 8

MEC654 // Study Materials by AAR 66


PORTABLE FIRE EXTINGUISHER
A portable fire extinguisher must contain the type of fire
extinguishing agent suitable for the fire it is required to
extinguish.
It must also be clearly identifiable by colour coding for
its intended purpose.
Fires can be grouped:
⊳Solid fuels, e.g. wood, paper, cloth, etc.
⊳Flammable liquids, e.g.. petrol, oil, paints, fats, etc.
⊳Flammable gases, e.g. methane, propane, acetylene, etc.
⊳Flammable metals, e.g. zinc, aluminium, uranium, etc.
⊳Electrical.

MEC654 // Study Materials by AAR 67


PORTABLE FIRE EXTINGUISHER
The portable fire extinguishers shall be provided as per
NFPA 10, standards for portable fire extinguishers.
Type of Fire Extinguisher Proposed Location
5 kg multipurpose ABC dry chemical type fire Staircase landing and office
extinguishers area
4.5 kg or higher capacity CO2 fire extinguisher Electrical Rooms
9 lt. Aqueous film forming foam (AFFF) stored Generator room and fuel
pressure type fire extinguisher pump room
5 kg or higher capacity Clean Agent Fire Control room / Server
Extinguishers and Data storage area

MEC654 // Study Materials by AAR 68


CLASSIFICATION OF FIRE
Class A Fires : Fires in ordinary
combustible materials such as wood,
cloth, paper, rubber and many
plastics.
Class B Fires : Fires in flammable
liquids, oils, greases, tars, oil-base
paints, lacquers and flammable
gases.

MEC654 // Study Materials by AAR 69


CLASSIFICATION OF FIRE
Class C Fires : Fires that involve
energized electrical non- conductivity
of the extinguishing media is of
importance. (when electrical
equipment is de-energized, fire
extinguishers for Class A and B fires
may be used safely)

MEC654 // Study Materials by AAR 70


CLASSIFICATION OF FIRE
Class D Fires : Fires in combustible
metals, such as magnesium,
titanium, zirconium, sodium, lithium
and potassium.

MEC654 // Study Materials by AAR 71


SECTION 5
EXTERNAL HYDRANT SYSTEM
EXTERNAL FIRE HYDRANT
Installation consist of a system of pipework connected
directly to the water supply mains to provide water to
each hydrant outlet. Intended to provide water to
fireman to fight a fire.
The water is discharged into the fire engine from which
it is then pumped and spray over the fire. If pressure is
too low, use hydrant pumps.

MEC654 // Study Materials by AAR 73


EXTERNAL FIRE HYDRANT
Hydrants are proposed at every
45m of periphery of the Building
to protect the building from
outside with all accessories.
Relevant standards as follows:
⊳B.S. 5306: Part 1 or the equivalent
Malaysian Standard;
⊳M.S. 1395: specification for pillar
hydrant

MEC654 // Study Materials by AAR 74


HYDRANT OUTLETS
Not less than 6 m from building & not more than 30 m
from entrance to the building
Space not more than 90 m apart along the minimum 6 m
in width road
Capable of withstanding a load of 26 tons of Fire brigade
vehicles.
2 or 3 outlets pillar type with underground sluice valve
Underground hydrants are not encouraged due to
difficulty of access
MEC654 // Study Materials by AAR 75
HYDRANT OUTLETS
In owner’s boundary: should be provided with 30m of
65mm rubber-lined hose (complete with nozzles) in steel
cabinet beside each hydrant.
Capable to handle 1000 l/min & running pressure of 4
bars but max to 7 bars only
The hydrant mains are usually laid underground with
cement lined steel pipe.
ABS (Acrylonitrile Butadiene Styrene) material used for
an area where corrosion is a major concern
MEC654 // Study Materials by AAR 76
HYDRANT PUMP
Two sets of pumps
⊳one duty
⊳one standby
Capable to supply 3000 l/min & running pressure of 4-7
bars to 3 hydrants at the same time
Should be supplied with backup diesel/power generator
in case of black out for at least 2 hours
Batteries for diesel engine must be maintenance free
type

MEC654 // Study Materials by AAR 77


HYDRANT PUMP
Normally Jockey pumps driven by electrical motor at
120 l/min required to maintain system pressure
The pumps should be protected from the weather and
away from flood area.
Pumps’ room should be ventilated plus signage

MEC654 // Study Materials by AAR 78


HYDRANT TANK
Minimum capacity 180,000 litres ( 1 hr water supply for 3
hydrants)
Should be refilled automatically by supply pipe at 20l/s
Hydrant tanks are usually separate from other water
storage tanks but may be combined with other fire
fighting system water tanks. So, tank’s capacity is the
sum total of all tanks.

MEC654 // Study Materials by AAR 79


HYDRANT TANK
Tank material: pressed steel, fibreglass reinforced
polyester (FRP) or concrete.
The tank should be compartmented and water level
indicator must be provided
External tank should be painted red OR at least red band
of minimum 200 mm should be painted.

MEC654 // Study Materials by AAR 80


SECTION 6
WET RISER AND DRY RISER
SYSTEM
DRY RISER
Internal Hydrant For Fireman to use
Top most floor is higher than 19.3 m (63 ft) and less than
30.5 m (100 ft)
Normally dry pipe and depend on the fire engine to
pump water
Comprises a riser pipe with landing valves at each floor
which canvas hose with nozzle can be connected.
Breeching inlets into which fireman pump water
provided at ground level. .
MEC654 // Study Materials by AAR 82
DRY RISER SYSTEM
– BY LAW AND STANDARD
UBBL Design Standard
UBBL 230 BS5306 :PART 1
UBBL 232 MS 1210 : PART 2
MS 1210 : PART 3
MS 1210 : PART 4
GUIDE TO FIRE
PROTACTION IN
MALAYSIA (BOMBA)
MEC654 // Study Materials by AAR 83
DRY RISER SYSTEM
Detail of relevant standard
⊳BS 5306 : Part 1 – Dry Riser System of installation.
⊳MS 1210 : Part 2 – Lading Valve for Dry Riser
⊳MS 1210 : Part 3 – Inlet Breeching for Riser
⊳MS 1210 : Part 4 – Boxes for Landing Valves

MEC654 // Study Materials by AAR 84


DRY RISER SYSTEM
Component/Equipment
⊳4 Way Breeching Inlet
⊳Landing Valve
⊳Hose Cradle
⊳Air Release valve

MEC654 // Study Materials by AAR 85


DRY RISER SYSTEM

MEC654 // Study Materials by AAR 86


DRY RISER – LANDING VALVE
Landing Valve provided on each floor
Usually located within fire access lobbies, protected
staircases or protected lobbies.
Installed not more than 0.75m (2.5 feet) above floor
level.
Boxes may be provided to protect landing valves
Fire Hose Canvas Type (38mm) complete with 65 mm
diameter quick coupling.

MEC654 // Study Materials by AAR 87


DRY RISER – LANDING VALVE

MEC654 // Study Materials by AAR 88


DRY RISER – BREECHING INLET
Installed at the bottom of the riser
A two-way breeching inlet should be provided for a 100
mm diameter
A for-way breeching inlet for a 150 mm diameter.
Breeching inlets located not more than 18m (59 ft) from
the fire appliance access road
Breeching inlets located not more than 30m (100 ft) from
the nearest external hydrant outlet.

MEC654 // Study Materials by AAR 89


DRY RISER – BREECHING INLET
2-Way Inlet Breeching Valves 4-Way Inlet Breeching Valves

MEC654 // Study Materials by AAR 90


DRY RISER – PIPE
Galvanized Iron (Heavy Gauge) or Class C tested to 21
Bars
If the highest outlet is more than 22.875m (75 ft) the riser
pipe diameter should be 150 mm.
Normally the riser pipe diameter is 100 mm.
Air release valve installed at the top of the riser to
release air trapped.
Horizontal runs pipework should be sloped for proper
draining after used.
MEC654 // Study Materials by AAR 91
WET RISER SYSTEM
Internal hydrant for fireman to use
Always charged with water
Topmost floor is higher than 30.5m (100ft)
Comprises Duty, Standby and Jockey pumps.
Comprises 150 mm diameter riser pipe with Landing
Valves at each floor.
For high rise building each stage of wet riser should not
exceed 70.15m (230 ft).

MEC654 // Study Materials by AAR 92


WET RISER SYSTEM
– BY LAW AND STANDARD
UBBL Design Standard
UBBL 231 BS5306 :PART 1
UBBL 232 MS 1210 : PART 1
UBBL 248 MS 1210 : PART 3
MS 1210 : PART 4
GUIDE TO FIRE
PROTACTION IN
MALAYSIA (BOMBA)
MEC654 // Study Materials by AAR 93
WET RISER SYSTEM
– TYPICAL ARRANGEMENT  Component/Equipment
1. Water tank
22 21
2. 4-ways breeching inlet
20 3. Vent pipe c/w mosquito net
4. Access opening
5. Level indicator
6. External Cat Ladder
7. Overflow pipe
8. Warning pipe
19 3
4 9. Standby pump
6 2 10. Eccentric reducer
5
7 11. Expansion joint
1
8 12. Y-strainer
16
13 13. Gate valve
15 14. Duty pump
14
15. Concentric Reducer
11
17
9 16. Check valve
10 12
18 17. Jockey pump
18. Pump Start test pipe
19. Pump Starter panel
20. Landing Valve
21. Hose cradle
22. Air release valve c/w Ball valve

MEC654 // Study Materials by AAR 94


WET RISER – LANDING VALVE
Landing valves provided on each floor.
Usually located within fire access lobbies protected
staircases or protected lobbies.
Installed not more than 0.75m (2.5ft) above floor level.
Boxes may be provided to protect Landing valves.
Fire Hose Canvas Type (38mm) complete with 65 mm
diameter quick coupling.
The pressure at Landing Valves not Less 4 bars but not
more than 7 Bars.
MEC654 // Study Materials by AAR 95
WET RISER – BREECHING INLET
Installed at the bottom of the riser.
The fireman can pump water into the wet riser storage
tank to make up for water used.
A four-way breeching inlet for a 150 mm diameter.
Breeching inlet located not more than 18m (59ft) from
the fire appliance access road
Breeching inlet located not more than 30m (100ft) from
the nearest external hydrant outlet.

MEC654 // Study Materials by AAR 96


WET RISER – BREECHING INLET
Galvanized iron (Heavy Gauge) or Class C.
The riser diameter should be 150 mm.
Should cover no more than 900m2 floor area.
When more the one riser required, the distance apart
between not exceed 60m.
The distance between lowest and topmost Landing
Valves not exceed 70.15m.
Air release valves installed at the top of release air
trapped.
MEC654 // Study Materials by AAR 97
WET RISER – PUMP
Duty, Standby and Jockey
The pump flow rate must 1500 litre/min at running
pressure not less than 4 bar but not more than 7 bars
when any 3 Landing Valves are in use at the same time.
Standby pump from Generator or Diesel (fuel supply
storage for 2 hrs).

MEC654 // Study Materials by AAR 98


WET RISER – PUMP
Wet Riser Pumps need to be automatically started upon
actuation of the pressure switches but should only be
stopped manually. Usually three pressure switches are
provided with the following suggested pressure
settings:
⊳starting the duty pump – set : 80% of the system pressure
⊳starting the standby pump – set: 60% of the system pressure
⊳starting and stopping the jockey pump – set at 90% and 110%
of the system pressure perceptively.

MEC654 // Study Materials by AAR 99


WET RISER – TANK
Minimum capacity of 45 500 litre with automatic refill
rate of 455 litre/min
The intermediate break tank for upper stages of the wet
riser is 11 375 litre with automatic make-up flow up of
1365 litre/min.
Tank material from presses steel, fibre reinforce
polyester (FRP) or concrete. The water tank should be
compartmented.

MEC654 // Study Materials by AAR 100


WET RISER – TANK
Located on the ground floor, first or second basement.
Usually separated from other water storage tank but it
may be combined with hose reel tank.

MEC654 // Study Materials by AAR 101


WET RISER – Pump starter panel and control
Power supply cables to panel should be of mineral
Insulated Copper Core (MICC)
Wet riser pumps provided with 3 pressure switches.
⊳Starting and stopping the jockey pump set.
⊳Starting and stopping the duty pump set.
⊳Starting and stopping the standby pump set.

MEC654 // Study Materials by AAR 102


SECTION 7
DOWN-COMER SYSTEM
DOWN-COMER SYSTEM
Internal hydrant for fireman to use and always charge
with water from water tank located on the top of the
building WITHOUT any pump.
Only permitted to residential buildings with open
balcony & the topmost floor is not more than 60m above
the fire appliance access level
150mm riser pipe with landing valve on each floor and to
which rubber-lined hose with nozzles
Should be adopted for low cost flats only
MEC654 // Study Materials by AAR 104
DOWN-COMER SYSTEM
– BY LAW AND STANDARD
UBBL Design Standard
10th Schedule BS5306 :PART 1
MS 1210 : PART 1
MS 1210 : PART 3
MS 1210 : PART 4
GUIDE TO FIRE
PROTACTION IN
MALAYSIA (BOMBA)
MEC654 // Study Materials by AAR 105
DOWN-COMER SYSTEM – LANDING VALVE
Provided on each floor and comply with hydrant system,
hose reels and foam inlets (M.S. 1210 : part 1)
Located within fire fighting access lobbies, protected
staircases or protected lobbies installed not more 0.75m
from floor.
Protected by Boxes comply with M.S. 1210: Part 4
Pressure landing valve depends on static pressure on
valve from roof tank.

MEC654 // Study Materials by AAR 106


DOWN-COMER SYSTEM – LANDING VALVE
Semi-rigid 40mm diameter hose and nozzles should
provided at every landing valve on floor.
Two sets fire hose of canvas type not less than 38mm
diameter, 30m length complete with 65mm diameter
quick coupling and jet spray nozzle should provided at
caretakers unit or management office.

MEC654 // Study Materials by AAR 107


DOWN-COMER SYSTEM
– BREECHING INLETS
Fire brigade breeching inlets into firemen pumps water
provided at bottom of riser at ground floor.
It should 4-way type comply with inlet breeching for
riser inlets.
Where it is enclosed within box and label ‘Downcomer
Inlet’
Drain should be provided at bottom of riser to drain
system.

MEC654 // Study Materials by AAR 108


DOWN-COMER SYSTEM
– BREECHING INLETS
Breeching inlets should located not more 18m from fire
appliance access road and not more 30m from nearest
external hydrant.
Check valve installed between topmost landing valve
and tank to prevent back flow.

MEC654 // Study Materials by AAR 109


DOWN-COMER SYSTEM – PIPES
Located within some free lobby or protected areas
within 45m coverage from landing valve.
More than one riser are required for each floor, distance
not more 60m.
Riser pipe diameter should 150mm galvanised iron to
heavy gauge.
Released valve should installed at top of riser to relief
air trapped.

MEC654 // Study Materials by AAR 110


DOWN-COMER SYSTEM – PIPES
Down-comer pipes should be coated with primer and
finished with red gloss paint.
Pipe can be colour coded with red bands 100mm width
and elbows and tees painted red.
Riser pipe should electrically earthed.

MEC654 // Study Materials by AAR 111


DOWN-COMER SYSTEM – WATER TANK
Fire water storage tank should be sized minimum 45
500l, automatic refill rate of 455l/min.
Tanks maybe pressed steel, FRP or concrete.
It should hot dipped galvanized and coated internally
with bituminous for corrosion protection.
Water tanks should compartmented unless they are
reinforced concrete and ball float valves, overflow pipes,
drain pipes and water level indicators should provided.

MEC654 // Study Materials by AAR 112


DOWN-COMER SYSTEM – WATER TANK
External surface of tank should painted red white or red
band 200mm should be painted to indicate it was a tank.
Usually located on the roof to provide maximum static
pressure and separated from other tank.
It may be combine with hose reel tank when tank
capacity equal to total water storage for down-comer for
hose reel system.
Hose reel tap off level should be above down-comer tap
off level to reserved for down-comer.
MEC654 // Study Materials by AAR 113
SECTION 8
HOSE-REEL SYSTEM
HOSE-REEL SYSTEM
Hose reel system is intended for the occupant to use
during early stages of a fire and comprises hose reel
pumps, water storage tanks, hose reels, pipe work and
valves.

MEC654 // Study Materials by AAR 115


HOSE REEL SYSTEM
– BY LAW AND STANDARD
UBBL Design Standard
10th Schedule BS5306 Part 1
MS 1447
GUIDE TO FIRE
PROTACTION IN
MALAYSIA (BOMBA)

MEC654 // Study Materials by AAR 116


HOSE-REEL SYSTEM
When we need hose reel
system?
It is 5 storey building need
hose reel?

MEC654 // Study Materials by AAR 117


HOSE-REEL SYSTEM
Three factor for
compulsory installation of
Hose Reel.
⊳Type of Building
⊳Building size
⊳Building operation

MEC654 // Study Materials by AAR 118


HOSE-REEL SYSTEM
Three factor for
compulsory installation of
Hose Reel.
⊳Type of Building
⊳Building size
⊳Building operation

MEC654 // Study Materials by AAR 119


HOSE-REEL SYSTEM
Three factor for
compulsory installation of
Hose Reel.
⊳Type of Building
⊳Building size
⊳Building operation

MEC654 // Study Materials by AAR 120


HOSE REEL SYSTEM
Three factor for
compulsory installation of
Hose Reel.
⊳Type of Building
⊳Building size
⊳Building operation

MEC654 // Study Materials by AAR 121


HOSE REEL SYSTEM – STORAGE TANK
Normally minimum effective storage of 9100 Litres
(based on minimum 6 hose reel drums in system)
Minimum incoming flow rate of 20 l/min
Material either pressed steel, FRP
Located either on ground / basement level or on roof
level.

MEC654 // Study Materials by AAR 122


HOSE REEL SYSTEM – PUMP
Two pumps (one duty, and one standby)
Minimum flowrate 120 l/min (for four hose reels
operating at one time); running pressure minimum 2
bars
Standby pump shall be from generator set supply or
else pump shall be diesel type with fuel to run minimum
2 hours.

MEC654 // Study Materials by AAR 123


HOSE REEL SYSTEM – PIPING
Material used Galvanised Iron Class ‘C’ (Heavy Duty)
Pipe size 50mm Ø within building and 65mm Ø if
external building depending on distance.

MEC654 // Study Materials by AAR 124


HOSE REEL SYSTEM – DRUM
Located as such that all areas are generally covered by
the 30m hose radius or approximately every 800m2 area.
Generally can assume every hose reel is able to produce
30 l/min and 6m jet spray.
Normally located at each floor along escape routes..

MEC654 // Study Materials by AAR 125


SECTION 9
AUTOMATIC INERT GAS
EXTINGUISHING SYSTEM
AUTOMATIC INERT GAS EXTINGUISHING
SYSTEM
Gaseous fire suppression is a term to describe the use
of inert gases and chemical agents to extinguish a fire;
also called Clean Agent Fire Suppression.
These Agents are governed by the NFPA Standard for
Clean Agent Fire Extinguishing Systems - NFPA 2001, as
well as NFPA Standard for Carbon Dioxide Fire
Extinguishing Systems - NFPA 12.

MEC654 // Study Materials by AAR 127


AUTOMATIC INERT GAS EXTINGUISHING
SYSTEM
The systems typically consist of the agent, agent
storage containers, agent release valves, fire detectors,
fire detection system (wiring control panel, actuation
signalling), agent delivery piping, and agent dispersion
nozzles.
These systems shall be designed, installed and
maintained by certified professionals. Proper records
shall be kept for all works in relation to these systems.

MEC654 // Study Materials by AAR 128


AUTOMATIC INERT GAS EXTINGUISHING
SYSTEM
Application

MEC654 // Study Materials by AAR 129


AUTOMATIC INERT GAS EXTINGUISHING
SYSTEM
CO2 Vs clean Agent

MEC654 // Study Materials by AAR 130


Ts. DR. AZLI ABD RAZAK
Senior Lecturer

Address
Faculty of Mechanical Engineering
Universiti Teknologi MARA
40450 Shah Alam, Selangor

THANK YOU! Phone & Email


H/P: 0194419556
Office: 03-55442212
azlirazak@uitm.edu.my

You might also like