Heat Transfer by Air Cooled Heat Exchangers
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
large proportion of the process cooling in re neries and chemical plants takes place in Air Cooled Heat
Exchangers (AC-HEs).
AC-HEs for process plants are normally just called Aircoolers, but should not be confused with devices for
cooling air (best described as Air Chillers).
The design of an AC-HE is more complex than for a Shell and Tube Heat Exchanger, as there are many more
components and variables.
The structure of an AC-HE is painted or galvanized, depending on customer speci cation. However, the costs are
roughly the same if a multiple coat paint system is speci ed. Often the painted units are more expensive. There
seems to be a trend toward more galvanized structures because they require virtually no maintenance. Painted
structures require touch-up after installation and they often rust anyway.
Air-cooled heat exchangers are used extensively throughout the oil and gas industry, from upstream production
to re neries and petrochemical plants, under high pressure and high temperature conditions, as well as
corrosive uids and environments.
The fans are usually driven be electric motors through some type of speed reducer. The speed reducers are
usually either V-belts, HTD drives, or right angle gears. The fan drive assembly is supported by a steel mechanical
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
drive support system. They usually include a vibration switch on each fan to automatically shut down a fan which
has become imbalanced for some reason.
This API spec is very good since it includes all the necessary information to properly specify a cooler and
provides for a high level of minimum quality in the design and fabrication of the cooler. In the back it has a very
good checklist where a customer can decide exactly what type construction is needed and what options are
important. These include such items as galvanizing vs. painting, types of headers, maintenance walkways and
platforms, controls, and external loads on the cooler. The following details refer mostly to the API speci cations.
The ns are almost always of aluminum material. The most common type of n is the helically wrapped, L-footed
type. These are used where the process temperatures are below about 350 °. F. The API speci cation calls for
cast zinc bands at the ends of the tubes to prevent the ns from unwrapping. Some of the better manufacturers
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
also use cast zinc bands at the tube supports. For higher process temperatures, most customers prefer either
embedded or extruded ns. The embedded ns have the highest temperature capabilities. They are made by a
process
EXPLORE the WORLDwhichof
cuts a helical groove in the OD of the tube, wraps the n into the groove, then rolls the upset
PIPING
metal from the tube back against the n to lock it into place. The tube wall must be thicker with embedded ns
because of the groove.
In some applications customers often prefer extruded ns. Extruded ns are made by putting an aluminum
sleeve (sometimes called a mu ) over the tube, then passing the tube through a machine which has rollers
which squish the aluminum out to form ns. The process is similar to a thread-rolling machine. The end result is
a n which has extremely good contact with the tube, and no crevices to allow corrosion to start on the tube OD.
Extruded ns are often used in coastal locations or on o shore platforms for this reason.
Some manufacturers make some rather startling claims for their "special" nned tubes. These modi cations
usually involve some kind of wrinkles or cuts in the ns to enhance air turbulence. We believe this is a lot of
baloney. The cost of this extra turbulence is increased static pressure for the fan(s) to overcome. These claims
are sometimes just too fantastic to be considered seriously.
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
What are headers and how are headers constructed?
Headers are the boxes at the ends of the tubes which distribute the uid from the piping to the tubes.
EXPLORE the WORLD of PIPING
Almost all headers on air-cooled exchangers are welded rectangular boxes. A vast majority of the headers are of
the plug type. This means that there is a shoulder plug opposite each tube which allows access for inspection
and cleaning of individual tubes. They can also be used to plug a leaking tube. The plug holes are used in the
manufacturing process for access to roller expand the tubes into the headers.
The other common type of header is the cover plate or bonnet type. These are usually used in low pressure
applications (say below 150 PSIG) where complete tube access is desired. This usually means applications where
fouling is a potential problem and the tube bundle may require occasional internal cleaning.
As the name implies, these have a removable plate on the back side of the header opposite the tubes. The cover
plate is attached to the header by a set of studs or through-bolts to a ange around the perimeter of the header.
A bonnet header is similar, but opposite in construction. The whole header or bonnet bolts to the tubesheet and
comes o . Bonnet headers are sometimes used where the corrosion potential of the process uid is very high
and the tubesheet material is some kind of expensive exotic alloy, such as titanium.
Headers are usually constructed of carbon steel or stainless steel, but sometimes more exotic alloys are used for
corrosion resistance. The selection of materials is usually made by the customer.
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
EXPLORE the WORLD of PIPING
1. Tube bundle 2. Header 3. Plenum 4. Fan 5. Belt drive 6. Motor 7. Fan ring
However, induced draft units have some advantages, too. A common problem with forced draft coolers is
accidental warm air recirculation. This happens when the hot exhaust air is pulled back in to the fans. Since a
forced draft cooler has a low air velocity at the exhaust from the bundle and a high velocity through the fan, a
low pressure area is created around the fan, causing the hot air to be pulled over the side or end of the bay.
For this same reason, there should never be a small space between the bays of a bank of forced-draft cooler.
Induced draft cooler have a high exhaust air velocity through the top-mounted fan, and a lower velocity into the
face of the tube bundle below. This tends to minimize the probability of accidental air recirculation. Also an
induced draft plenum does not have to support the tube bundle so some weight can often be saved in this area.
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
The API speci cation includes a number of paragraphs about fan coverage and dispersion angle. This is for a
very good reason. The actual air coming from a fan does not distribute itself evenly at rst. The most air ow is
seenWORLD
EXPLORE the around the fan tip area. If you measure the air ow across the face of a tube bundle, it is often very
of PIPING
di erent around the fan blade tip as opposed to the center of the fan or the corner of the bundle. However, as
the plenum becomes deeper, this localized e ect is diminished as the air becomes more evenly distributed. All
of the heat transfer programs assume that the air is distributed perfectly evenly.
The fan coverage is the ratio of the fan area to the bundle face area. The higher this ratio, the better the fan
coverage. The API minimum is 40% with a 45 degree maximum dispersion angle from the fan ring to the middle
of the tube bundle at the middle of the sides or the middle of the ends of each fan chamber. More fan coverage
or a lower dispersion angle can improve the air distribution. (See Figure 6 on Page 14 of API 661for a sketch of
this.)
A few manufacturers actually improve on this idea one step more, by using rounded and eased fan rings.
Rounded and eased rings o er two advantages compared to the conventional fan rings. First, they enhance the
distribution of the air. Secondly, they reduce the air pressure drop through the fan ring, slightly reducing the fan
brake horsepower. When designing their coolers, some cooler manufacturers base their fan designs on the use
of rounded and eased rings, even though they don't build them this way.
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
EXPLORE the WORLD of PIPING
References
API Standard 661 Air-Cooled Heat Exchangers for General Re nery Service, 3rd ed., Washington D.C:
American Petroleum Institute.
Air-Cooled Heat Exchangers, Jim Stone, Stone Process Equipment Co.
Briggs.D. E. and Young, E. H. Convection heat transfer and pressure drop of air owing across triangular
pitch banks of nned tubes, Chem. Engng. Progr., Symp. Ser., 59 (41): 1-10.
ESDU High- n staggered tube banks: Heat transfer and pressure drop for turbulent single phase gas ow,
Item No. 86022, London: Engineering Sciences Data Unit.
ESDU Selection and costing of heat exchangers, Item No. 92013, London: Engineering Sciences Data Unit.
PFR Engineering Systems Inc. Heat transfer and pressure drop characteristics of dry tower extended
surfaces, Part II: Data analysis and correlation, Report BNWL-PFR-7-102, Marina del Rey, California.
SUBMENU EQUIPMENT
Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Robinson, K. K. and Briggs, D. E. Pressure drop of air owing across triangular pitch banks of nned tubes,
Chem. Engng. Progr., Symp. Ser., 62 (64): 177-184.
The industrial revolution allowed us, for the rst time, to start replacing human labour with machines. VITALIK BUTERIN