‫اﻟﻤﺤﺎﺿﺮة اﻟﺘﺎﺳﻌﺔ‬

‫ﻣﻜﻮﻧﺎت اﻟﻤﺤﺎﺿﺮة‪-:‬‬

‫‪ -1‬اﺑﺮاج اﻟﺘﺒﺮﯾﺪ )‪( COOLING TOWER‬‬

‫‪Expansion Tank -2‬‬

‫‪Water softener-3‬‬

‫‪Air control system -4‬‬

‫اﺑﺮاج اﻟﺘﺒﺮﯾﺪ )‪( COOLING TOWER‬‬

‫اﻟﮭﺪف ﻣﻨﮭﺎ‪-:‬‬

‫‪ -‬ﺗﺒﺮﯾﺪ اﻟﻤﻜﺜﻒ ﺑﺎﻟﻤﯿﺎه ﻟﺰﯾﺎدة ﻛﻔﺎءة ال ‪CHILLER‬‬

‫ﻣﻜﻮﻧﺎت اﻟﺪاﺋﺮة ‪-:‬‬

‫‪ .1‬ﺑﺮج اﻟﺘﺒﺮﯾﺪ‬
‫‪ .2‬اﻟﻤﻮاﺳﯿﺮ‬
‫‪ .3‬ﻣﻀﺨﺎت اﻟﺘﺪوﯾﺮ‬

‫‪ .1‬أﻧﻮاع ﺑﺮج اﻟﺘﺒﺮﯾﺪ‪-:‬‬

‫‪Evaporator cooling tower -‬‬


‫‪Closed type ‬‬

‫ﯾﺘﻢ دﺧﻮل اﻟﻤﯿﺎه داﺧﻞ ﺑﺮج اﻟﺘﺒﺮﯾﺪ ﺧﻼل اﻟﻤﻮاﺳﯿﺮ وﺗﻮﺿﻊ ﻣﺮوﺣﺔ ﻛﺒﯿﺮة ﻋﻠﯿﮭﺎ ﻣﻦ أﻋﻠﻰ ﻟﯿﺘﻢ اﻟﺘﺒﺮﯾﺪ‬

‫‪Open cooling tower ‬‬

‫ﯾﺘﻢ ﻋﻤﻞ ‪ spray‬ﻟﻠﻤﯿﺎه وﺗﻘﻮم ﻣﺮاوح ﺟﺎﻧﺒﯿﺔ ﺑﻀﺦ اﻟﮭﻮاء وﯾﺘﻢ ﺗﺠﻤﯿﻊ اﻟﻤﯿﺎه داﺧﻞ ﺣﻮض ﺣﺘﻰ ﺗﺮﺟﻊ‬
‫ﻟﻠﺪاﺋﺮة ﻣﺮة اﺧﺮى‬

‫‪ .2‬اﻟﻤﻮاﺳﯿﺮ‪ -:‬ﯾﺘﻢ ﺗﺼﻤﯿﻢ اﻟﻤﻮاﺳﯿﺮ طﺒﻘﺎ ﻟﻠﺠﺪول ‪ closed type‬اﻟﻤﻮﺿﺢ ﺑﺎﻟﺼﻔﺤﺔ اﻟﻘﺎدﻣﺔ‬

‫‪Page 1‬‬
Page 2
‫‪ .3‬ﻣﻀﺨﺎت اﻟﺘﺪوﯾﺮ‪-:‬‬

‫ﻟﺘﻌﺮﯾﻒ ﻣﻀﺨﺎت اﻟﺘﺪوﯾﺮ ﯾﻠﺰم ﻣﻌﺮﻓﺔ اﻻﺗﻰ‬

‫‪Flow rate (gpm) -‬‬


‫‪Head (FT) -‬‬
‫‪Power (HP) -‬‬

‫ﻟﺤﺴﺎب ‪gpm:-‬‬

‫ﻓﻰ اﻟﺒﺪاﯾﮫ ﯾﺠﺐ ان ﻧﻌﻠﻢ ان ﺑﺮج اﻟﺘﺒﺮﯾﺪ ﯾﻘﻮم ﺑﺘﺒﺮﯾﺪ اﻟﻤﻜﺜﻒ واﻟﻀﺎﻏﻂ ﻟﺬا اﻟﻤﻄﻠﻮب ﻣﻨﮫ ﺗﺒﺮﯾﺪ اﻟﻤﯿﺎه‬
‫ﻟﮭﻤﺎ ﻣﻌﺎ‬

‫)‪Total load of evaporator = load (BTU/HR)………………….. (1‬‬

‫)‪Total load of compressor = load (TON) x 0.7X3400…….. (2‬‬

‫)‪Total BTU/HR for cooling tower = (1) + (2) ………………… (3‬‬

‫‪Total KW for cooling tower = (3) / 3400 KW‬‬

‫‪Total gpm for cooling tower = (3) / 5000‬‬

‫ﻟﻌﻤﻞ ‪selction‬ﻟﺒﺮج اﻟﺘﺒﺮﯾﺪ ﻣﻦ اﻟﻜﺘﺎﻟﻮﺟﺎت ﯾﺘﻢ اﻟﺪﺧﻮل ﺑﺎل ‪kw‬‬

‫ﻓﻰ اﻟﻐﺎﻟﺐ ﻻﯾﻮﺿﻊ ﺑﺮج ﺗﺒﺮﯾﺪ واﺣﺪ ﻓﻘﻂ ﺑﻞ ﯾﻮﺿﻊ أﺛﻨﺎن ﺣﻤﻞ ﻛﻞ ﻣﻨﮭﻢ )‪ (%70‬ﻣﻦ اﻟﺤﻤﻠﻰ اﻟﻜﻠﻰ‬

‫وﯾﺘﻢ وﺿﻊ ﻣﻀﺨﺘﯿﻦ أو أﻛﺜﺮ واﺣﺪة ﻟﻠﻌﻤﻞ واﻵﺧﺮى ﻟﻠﻄﻮارئ‬

‫‪ -‬ﻟﺤﺴﺎب ال ‪ head‬ﯾﺠﺐ اﻟﺘﻔﺮﻗﺔ ﺑﯿﻦ‬


‫‪Evaporator cooling tower ‬‬

‫)‪H= 2(LX1.3X3.281 X4 /100‬‬

‫)‪H→ Total head (ft‬‬

‫)‪L→ Length (m‬‬

‫‪Open cooling tower ‬‬


‫‪H= LX1.3X3.281X4/100+Hst x3.281‬‬
‫‪Hst → height for cooling tower‬‬

‫ﻧﻼﺣظ اﺿﺎﻓﮫ ارﺗﻔﺎع اﺳﺗﺎﺗﯾﻛﻰ ﻟﻠﻧوع اﻟﻣﻔﺗوح‬

‫‪Page 3‬‬
Page 4
Expansion TANK
‫ اﻟﮭدف ﻣﻧﮫ ﺗﻌوﯾض اﻟﻔﻘد ﻓﻰ اﻟﻣﯾﺎه ﻧﺗﯾﺟﺔ اﻟﺑﺧر وﺗﻣدد و أﻧﻛﻣﺎش اﻟﻣواﺳﯾر و ﯾوﺿﻊ ﻋﻠﻰ‬-
‫( ﻟﺿﻣﺎن‬Air Separator) ‫ﺧط ﺳﺣب اﻟﻣﺿﺧﮫ ﻟﯾﻣﻧﻊ دﺧول اﻟﮭواء اﻟﯾﮭﺎ وﯾوﺿﻊ ﻣﻌﮫ‬
‫ﻋدم دﺧول ھواء اﻟﻰ اﻟﻣﺿﺧﮫ‬
‫ طرﯾق ﺣﺳﺎﺑﮫ‬- -

Expansion Tank Sizing (Diaphragm Tanks)


1- Chilled water expansion tank sizing and for system water temp. less than
160o F
(1987, HVAC systems & applications Ashrae Hand Book Chapter 13 )
pf
Vt = e Vs / [ 1- ] Gallons , where ;
Po
Vt = minimum volume of expansion tank (Gallons )

Vs = System volume (Gallons )

Pf = Intial fill or min. tank pr. (FT) 45 FT .

Po = Maximum operating tank PR. (FT)

e = Net expansion factor for water see table attached .

Page 5
‫‪Volume of water in standard pipe and tube‬‬
‫ــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــ‬
‫ـــــ‬
‫‪Standard steel pipe‬‬ ‫‪Type L Copper Tube‬‬
‫‪Nominal pipe size‬‬ ‫‪Inside Diameter‬‬ ‫‪Volume‬‬ ‫‪Inside Diameter‬‬ ‫‪Volume‬‬

‫‪In.‬‬ ‫‪Schedule No.‬‬ ‫‪In.‬‬ ‫‪Gal / ft‬‬ ‫‪In.‬‬ ‫‪Gal / ft‬‬


‫‪3/8‬‬ ‫‪-‬‬ ‫‪-‬‬ ‫‪-‬‬ ‫‪0.430‬‬ ‫‪0.0075‬‬
‫‪1/2‬‬ ‫‪40‬‬ ‫‪0.622‬‬ ‫‪0.0157‬‬ ‫‪0.545‬‬ ‫‪0.0121‬‬
‫‪5/8‬‬ ‫‪-‬‬ ‫‪-‬‬ ‫‪-‬‬ ‫‪0.666‬‬ ‫‪0.0181‬‬
‫‪3/4‬‬ ‫‪40‬‬ ‫‪0.824‬‬ ‫‪0.0277‬‬ ‫‪0.785‬‬ ‫‪0.0251‬‬
‫‪1‬‬ ‫‪40‬‬ ‫‪1.049‬‬ ‫‪0.0449‬‬ ‫‪1.025‬‬ ‫‪0.0429‬‬
‫‪1 1/4‬‬ ‫‪40‬‬ ‫‪1.380‬‬ ‫‪0.0779‬‬ ‫‪1.265‬‬ ‫‪0.0633‬‬
‫‪1 1/2‬‬ ‫‪40‬‬ ‫‪1.610‬‬ ‫‪0.106‬‬ ‫‪1.505‬‬ ‫‪0.0924‬‬
‫‪2‬‬ ‫‪40‬‬ ‫‪2.067‬‬ ‫‪0.174‬‬ ‫‪1.985‬‬ ‫‪0.161‬‬
‫‪2 1/2‬‬ ‫‪40‬‬ ‫‪2.469‬‬ ‫‪0.249‬‬ ‫‪2.465‬‬ ‫‪0.248‬‬
‫‪3‬‬ ‫‪40‬‬ ‫‪3.068‬‬ ‫‪0.384‬‬ ‫‪2.945‬‬ ‫‪0.354‬‬
‫‪3 1/2‬‬ ‫‪40‬‬ ‫‪3.548‬‬ ‫‪0.514‬‬ ‫‪3.425‬‬ ‫‪0.479‬‬
‫‪4‬‬ ‫‪40‬‬ ‫‪4.026‬‬ ‫‪0.661‬‬ ‫‪3.905‬‬ ‫‪0.622‬‬
‫‪5‬‬ ‫‪40‬‬ ‫‪5.047‬‬ ‫‪1.04‬‬ ‫‪4.875‬‬ ‫‪0.970‬‬
‫‪6‬‬ ‫‪40‬‬ ‫‪6.065‬‬ ‫‪1.50‬‬ ‫‪5.845‬‬ ‫‪1.39‬‬
‫‪8‬‬ ‫‪30‬‬ ‫‪8.071‬‬ ‫‪2.66‬‬ ‫‪7.725‬‬ ‫‪2.43‬‬
‫‪10‬‬ ‫‪30‬‬ ‫‪10.136‬‬ ‫‪4.19‬‬ ‫‪9.625‬‬ ‫‪3.78‬‬
‫‪12‬‬ ‫‪30‬‬ ‫‪12.090‬‬ ‫‪5.96‬‬ ‫‪11.565‬‬ ‫‪5.46‬‬

‫‪Net Expansion of water in chilled and dual temperature systems with‬‬


‫)‪lowest temperature of 40 o F (4o C‬‬
‫ــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــ‬
‫‪Highest‬‬ ‫‪Factor‬‬
‫‪o‬‬
‫‪Temperature, F‬‬ ‫‪e‬‬
‫ـــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــــ‬
‫‪90‬‬ ‫‪0.0041‬‬
‫‪100‬‬ ‫‪0.0058‬‬
‫‪110‬‬ ‫‪0.0077‬‬
‫‪120‬‬ ‫‪0.0100‬‬
‫‪130‬‬ ‫‪0.0124‬‬
‫‪140‬‬ ‫‪0.0150‬‬
‫‪150‬‬ ‫‪0.0179‬‬
‫‪160‬‬ ‫‪0.0209‬‬

‫‪Page 6‬‬
‫‪Water softener‬‬

‫‪ -‬اﻟﮭدف ﻣﻧﮫ ﺗﻧﻘﯾﺔ اﻟﻣﯾﺎه ﻟﺗﺧﻠﯾﺻﮭﺎ ﻣن اﻷﻣﻼح اﻟذاﺋﺑﺔ ﺣﺗﻰ ﻻ ﺗﺗرﺳب ﻓﻰ اﻟﻣواﺳﯾر ﺣﯾث أن‬
‫زﯾﺎدة ﺗرﺳب اﻻﻣﻼح ﺑﺳﺑب ﺗﺂﻛل اﻟﻣواﺳﯾر‬
‫‪ -‬ﯾﺗم ﺣﺳﺎﺑﮫ ﻋن طرﯾق ﻣﻌرﻓﺔ اﻟﻔﺎﻗد ﻓﻰ اﻟﻣﯾﺎه اﻟﻣطﻠوب ﺗﻌوﯾﺿﮫ ﻣن ﺟﮭﺎز اﻟﺗﻛﯾﯾف وﺗﻘدر‬
‫ﺑﻘﯾﻣﺔ )‪( 4gpH / Ton‬‬

‫‪Air control system‬‬

‫‪ -‬ﻋﻧد ﺗﺻﻣﯾم اﻟدﻛت ﯾﺗم ﺗوزﯾﻊ ﻟﻛل ﻏرﻓﺔ ﻣدﺧل ھواء ﻣن ال ‪ Duct‬اﻻﺳﺎﺳﻰ‬
‫‪ -‬وﻟﻛن واﺟﮭﺗﻧﺎ ﻣﺷﻛﻠﺔ وھﻰ أﻓﺗراض ﻋدم أﺳﺗﻐﻼل اﻟﻐرﻓﺔ ﺣﺎﻟﯾﺎ ﻓﻛﯾف ﯾﺗم إﯾﻘﺎف ﺿﺦ اﻟﮭواء‬
‫إﻟﯾﮭﺎ‬
‫‪ -‬ھﻧﺎك ﻧوﻋﯾن ﻣن ال ‪control‬‬

‫‪Page 7‬‬
‫‪1- Constant air volume‬‬
‫ﯾﺗم اﻟﺗﺣﻛم ﻓﻰ اﻟﮭواء ﻋن طرﯾق ﻓﺗﺢ ال ‪ by pass‬ﻟﻠﮭواء إﻟﻰ اﻟﺳﻘف اﻟﺳﺎﻗط وﺑذﻟك ﻻ‬
‫ﯾدﺧل اﻟﻐرﻓﺔ ھواء ﻣﺑرد وﯾﺗم ﺳﺣﺑﮫ ﻋن طرﯾق ﻣروﺣﺔ ال ‪ return‬إﻟﻰ اﻟﻣﺎﻛﯾﻧﺔ ﻣرة‬
‫اﺧرى‬
‫‪ -‬اﻟﻣﻣﯾزات ‪-:‬‬
‫‪ ‬رﺧﯾﺻﺔ اﻟﺛﻣن‬
‫‪ ‬اﻟﻌﯾوب‪ -:‬ﻏﯾر ﻣوﻓر ﻓﻰ أﺳﺗﮭﻼك اﻟﻛﮭرﺑﺎء ﺣﯾث أن أﺳﺗﮭﻼك اﻟﻣروﺣﺔ ﺛﺎﺑت ﻻﻧﮭﺎ‬
‫ذات ﺳرﻋﺔ ﺛﺎﺑﺗﺔ ﻻ ﺗﺗﻐﯾر‬
‫‪2- Variable air volume‬‬
‫‪ -‬ﯾﺗم وﺿﻌﮫ ﻋﻠﻰ ال ‪ Duct‬وﻋﻧد ﻋدم اﻟﺣﺎﺟﺔ إﻟﻰ ھواء ﻣﻛﯾف داﺧل اﻟﻐرﻓﺔ ﯾﺗم إرﺳﺎل إﺷﺎرة‬
‫إﻟﻰ اﻟﻣروﺣﺔ ﺑﺗﻘﻠﯾل ال ‪ CFM‬اﻟﺧﺎرج ﻣﻧﮭﺎ ﺑﻣﻘدار ال ‪ CFM‬اﻟداﺧل ﻟﻠﻐرﻓﺔ‬
‫)اﻷﺷﺎرة ﺗﻛون ﻋن طرﯾق زﯾﺎدة اﻟﺿﻐط ﻻن ال ‪ VAV‬ﯾﻘوم ﺑﻐﻠق ﻣﺳﺎر اﻟﮭواء اﻟداﺧل إﻟﻰ‬
‫اﻟﻐرﻓﺔ(‬
‫‪ ‬ﻣﻣﯾزاﺗﮫ‪ -:‬ﻣوﻓر ﻓﻰ أﺳﺗﮭﻼك اﻟﻛﮭرﺑﺎء ﻋﻠﻰ اﻟﻣدى اﻟﺑﻌﯾد ﻻ ال ‪ CFM‬اﻟﺧﺎرج ﻣن‬
‫اﻟﻣروﺣﺔ ھو اﻟذى أﺣﺗﺎﺟﮫ داﺧل اﻟﻣﻛﺎن‬
‫‪ ‬ﻋﯾوﺑﮫ‪ -:‬اﻟﺗﻛﻠﻔﺔ اﻟﻌﺎﻟﯾﺔ ﻓﻰ اﻟﺑداﯾﺔ )‪ ( Initial cost‬ﻻﻧﮫ ﯾﺗطﻠب ﻣروﺣﺔ ذات ﺳرﻋﺔ‬
‫ﻣﺗﻐﯾرة‪.‬‬

‫‪Page 8‬‬