3. Fault current shall be 26.3kA. Hole to dimension shall be indicated. Shall be corrected TO Inverter Transformer TO Client HT Panel Breaker handling trolley shall be considered. SCADA feedback from Transformer Fault relays shall be considered. TO Inverter Transformer TO Client HT Panel Power Pack shall be indicated. From Power pack For remote trip and close potential free contacts shall be considered by 24Vdc operated aux relay. TB details shall be updated as per transformer MB TB details provided.