1. Design ambient temp shall be -50Deg C.

2. Rated Operating voltage shall be 6.6kV.


3. Fault current shall be 26.3kA.
Hole to dimension shall be
indicated.
Shall be corrected
TO Inverter Transformer
TO Client HT Panel
Breaker handling trolley shall be considered.
SCADA feedback from Transformer Fault
relays shall be considered.
TO Inverter Transformer
TO Client HT Panel
Power Pack shall be indicated.
From Power pack
For remote trip and close potential free contacts shall be
considered by 24Vdc operated aux relay.
TB details shall be updated
as per transformer MB TB
details provided.