* Load combinations for design

* Project : LRT PROJECT

0 1 2
Category of use: F: Light vehicle traffic areas 0.7 0.7 0.6
Wind 0.6 0.2 0
Temperature 0.6 0.5 0
G: Dead load
Q: Live load
W: Wind load
T: Temperature load
Ad : Accidental load
AEd : Seismic load

Ultimate Limit State (ULS):


Table A1.2(B) - Design values of actions (STR/GEO) (Set B) , Persistent and transient
Eq. (6.10):
W u = 1.35 G + 1.5 Q + 0 W + 0 T
1.35 G + 1.5 Q + 0.9 W + 0.9 T
1 G + 0 Q + 0 W + 0 T
1 G + 0 Q + 0.9 W + 0.9 T
Eq. (6.10a):
W u = 1.35 G + 1.05 Q + 0 W + 0 T
1.35 G + 1.05 Q + 0.9 W + 0.9 T
Eq. (6.10b):
W u = 1.15 G + 1.5 Q + 0 W + 0 T
1.15 G + 1.5 Q + 0.9 W + 0.9 T

Table A1.3 - Design values of actions for use in accidental and seismic
Accidental, Eq. (6.11):
Wu = 1 G + 0.7 Q + 0 W + 0 T + 1 Ad
1 G + 0.6 Q + 0 W + 0 T + 1 Ad
Seismic, Eq. (6.12):
Wu = 1 G + 0.6 Q + 0 W + 0 T + 1 AEd

Serviceability Limit State (SLS):


Table A1.4 - Design values of actions for use in the combination of actions
Characteristic W= G + 1 Q + 0 W + 0 T
G + 1 Q + 0.6 W + 0.6 T
G + 0 Q + 0 W + 0 T
G + 0 Q + 0.6 W + 0.6 T

Frequent W= G + 0.7 Q + 0 W + 0 T

Quasi-permanent W= G + 0.6 Q + 0 W + 0 T