Professional Documents
Culture Documents
Maragondon Branch
Maragondon, Cavite
Submitted by:
Serrano, Justine O.
Tolentino, Renefer Jr. R.
BSME – IV
Submitted to:
Engr. Jhay Ahr C. Flores
March 2019
TABLE OF CONTENTS
Page
ii
3.3 For Doors ......................................................................................................... 14
iii
4.3.4 Total Heat Gain due to Infiltration/Ventilation .......................................... 30
References ................................................................................................................... 37
Appendices .................................................................................................................. 38
iv
LIST OF TABLES
v
LIST OF FIGURES
vi
Definition of Terms
Cooling Load - is the rate at which sensible and latent heat must be removed from the
Wall Gain Load - sometimes called the wall leakage load, is a measure of the heat which
leaks through the walls of the air-conditioned space from the outside to the inside. Since
there is no perfect insulation there is always a certain amount of heat passing from the
outside to the inside whenever the inside temperature is below of that on the outside.
Air Change Load – is a part of cooling load where in air replaces the denser cold air which
miscellaneous sources of heat, including lights and other electrical equipment operating
inside the space and all the people working in or otherwise occupying the air-conditioned
space.
Cooling Load Temperature Difference (CLTD) - This factor is used to represent the
temperature difference between indoor and outdoor air with the inclusion of the heating
Sensible Heat Gain - is the energy added to the space by conduction, convection and/or
radiation.
Latent Heat Gain - is the energy added to the space when moisture is added to the space
difference by which an object or material resists a heat flow. Thermal resistance is the
reciprocal of thermal conductance. (Absolute) thermal resistance R in K/W is a property
of a component.
Infiltration - is described as outside air that leaks into a building structure. These leaks
Fenestration - affects building energy use through four basic mechanisms: thermal heat
the table below represents the peak temperature for the span of 10 years:
Maximum Maximum
Year Temperature Relative
Humidity
o
C o
F (%)
2009 29 84.2 90
2010 31 87.8 89
2011 32 89.6 84
2012 33 89.6 85
2013 34 93.2 85
2014 34 93.2 84
2015 34 93.2 79
2016 34 93.2 82
2017 34 93.2 78
2018 34 93.2 80
Table 1.Maximum Temperature, Rosario, Cavite (2009-2018)
World Weather Online. “Max, Min, and Average Temperature (°C)”. Rosario,
Cavite Weather History. Accessed March 11, 2019.
https://www.worldweatheronline.com/maragondon-weather-averages/cavite/ph.aspx
Considering the peak temperature 34oC for the surrounding temperature where
the room is exposed to. And the desired temperature from the range of 18oC – 27oC from
the solar radiation. A cooling factor or allowance for solar radiation (ASR) is added to the
difference of the outdoor maximum temperature (OMT) and indoor desired temperature
1.2 Materials
Materials
Walls (North, East, West, and South) 112 mm concrete block, sand aggregate, 15 mm
cement plaster on both inside and outside of the
concrete
Floor 127 mm concrete lightweight aggregate with 6.35
mm Acoustical tile
Windows 4.445 mm triple glaze clear glass with operable
Insulated Fiberglass frame
Door 44.45 mm oak wood
12.7 mm Flat wood frame ceiling (insulated with R-
Ceiling 5.3 fiberglass) beneath vented attic with medium
asphalt shingle roof
Table 3. Materials
2.0 Surface Area
𝑆𝑜𝑢𝑡ℎ 𝑊𝑎𝑙𝑙 = (𝐿 × ℎ)
𝑾𝒊𝒏𝒅𝒐𝒘𝒔 = 𝟏. 𝟏𝟒𝒎𝟐
𝐷𝑜𝑜𝑟 = (𝑊𝑑 × ℎ𝑑 )
𝑫𝒐𝒐𝒓 = 𝟏. 𝟑𝟗𝒎𝟐
2.4 Flooring Surface Area
𝐹𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = (𝐿 × 𝑊)
𝐹𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 17.49𝑚2
𝐶𝑒𝑖𝑙𝑖𝑛𝑔 = (𝐿 × 𝑊)
𝑊𝑤 = 𝑤𝑖𝑑𝑡ℎ 𝑜𝑓 𝑤𝑖𝑛𝑑𝑜𝑤
𝑊𝑑 = 𝑤𝑖𝑑𝑡ℎ 𝑜𝑓 𝑑𝑜𝑜𝑟
ℎ𝑑 = ℎ𝑒𝑖𝑔ℎ𝑡 𝑜𝑓 𝑑𝑜𝑜𝑟
Windows 1.14
Door 1.39
Flooring 17.49
Ceiling 17.49
1
𝑈=
𝑅𝑇
1
𝑈=
1 𝑥1 𝑥2 1
+ + +
ℎ𝑖 𝑘1 𝑘2 ℎ𝑜
𝑊
𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 = .72
𝑚−𝐾
𝑊
𝑘𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 = 1.4 𝑡𝑜 2.9
𝑚−𝐾
𝑊
𝑊𝑒 𝑐𝑜𝑛𝑠𝑖𝑑𝑒𝑟, 𝑘𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 = 2.15
𝑚−𝐾
Table 6. Surface Conductance for Walls (ASHRAE Handbook-Fundamentals, 2007)
𝑊
ℎ𝑖 = 8.29
𝑚2 − 𝐾
𝑊
ℎ𝑜 = 22.7
𝑚2
−𝐾
For 112 mm concrete block, sand aggregate, 15 mm cement plaster on both inside and
outside of the concrete substitute the values we get from above tables, to solve for
the 𝑈𝑤𝑎𝑙𝑙 .
1
𝑈𝑤𝑎𝑙𝑙 = 𝑥
1 𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 𝑥 1
+ + 𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 +
ℎ𝑖 𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 𝑘𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 ℎ𝑜
1
𝑈𝑤𝑎𝑙𝑙 =
1 . 015𝑚 . 112𝑚 1
𝑊 + 𝑊 + 𝑊 + 𝑊
8.29 2 . 72 2 2.15 2 22.7 2
𝑚 −𝐾 𝑚 −𝐾 𝑚 −𝐾 𝑚 −𝐾
𝑊
𝑼𝒘𝒂𝒍𝒍 = 𝟒. 𝟐𝟏
𝑚2 − 𝐾
3.2 For Flooring
𝑚2 − 𝐾
𝑅𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 = .26
𝑊
𝑚2 − 𝐾
𝑅𝐶𝑜𝑟𝑘 𝑡𝑖𝑙𝑒 = 0.09
𝑊
See Table 5. Thermal Conductivity for Walls for the conductivity value of sand aggregate.
𝑊
𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 = .72
𝑚−𝐾
See Table 6. Surface Conductance for flooring for the value of surface conductance ℎ𝑖
2017).
𝑊
ℎ𝑖 = 9.26
𝑚2−𝐾
𝑊
ℎ𝑜 = 22.7
𝑚2−𝐾
For 127 mm concrete lightweight aggregate with 6.35 mm Cork tile substitute the
1
𝑈𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 𝑥𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 1
1
+𝑅𝐶𝑜𝑛𝑟𝑒𝑡𝑒 + 𝑅𝐶𝑜𝑟𝑘 𝑡𝑖𝑙𝑒 + +
ℎ𝑖 𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 ℎ𝑜
1
𝑈𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 =
1 𝑚2 −𝐾 𝑚2 − 𝐾 . 127𝑚 1
𝑊 + .26 𝑊 + 0.09 𝑊 + 𝑊 + 𝑊
9.26 2 . 72 22.7 2
𝑚 −𝐾 𝑚−𝐾 𝑚 −𝐾
𝑊
𝑼𝒇𝒍𝒐𝒐𝒓𝒊𝒏𝒈 = 𝟏. 𝟒𝟕
𝑚2 −𝐾
For values of ℎ𝑖 and ℎ𝑜 see Table 6. Surface Conductance for Walls (ASHRAE
Handbook-Fundamentals, 2017).
𝑊
ℎ𝑖 = 8.29
𝑚2−𝐾
𝑊
ℎ𝑜 = 22.7
𝑚2−𝐾
Table 8. Thermal Conductivity for Door (ASHRAE Handbook-Fundamentals, 2017)
𝑊
𝑘𝑑𝑜𝑜𝑟 = .17
𝑚−𝐾
For 44.45 mm oak wood substitutes the values from above to solve for 𝑈𝑑𝑜𝑜𝑟 .
1
𝑈𝑑𝑜𝑜𝑟 =
1 𝑥𝑜𝑎𝑘 𝑑𝑜𝑜𝑟 1
+ +
ℎ𝑖 𝑘𝑜𝑎𝑘 𝑑𝑜𝑜𝑟 ℎ𝑜
1
𝑈𝑑𝑜𝑜𝑟 =
1 . 04445𝑚 1
𝑊 + 𝑊 + 𝑊
8.29 2 . 17 𝑚 − 𝐾 22.7 2
𝑚 −𝐾 𝑚 −𝐾
𝑊
𝑼𝒅𝒐𝒐𝒓 = 𝟐. 𝟑𝟓
𝑚2 − 𝐾
3.4 For Ceiling/Roof
For values of ℎ𝑖 and ℎ𝑜 see Table 6. Surface Conductance for Walls – Horizontal
𝑊
ℎ𝑖 = 6.13
𝑚2−𝐾
𝑊
ℎ𝑜 = 22.7
𝑚2 − 𝐾
For 12.7mm cement board substitutes the values from above to solve for 𝑈𝐶𝑒𝑖𝑙𝑖𝑛𝑔
1
𝑈𝐶𝑒𝑖𝑙𝑖𝑛𝑔 =
1 𝑥𝑜𝑎𝑘 𝑑𝑜𝑜𝑟 1
+ +
ℎ𝑖 𝑘𝑜𝑎𝑘 𝑑𝑜𝑜𝑟 ℎ𝑜
1
𝑈𝐶𝑒𝑖𝑙𝑖𝑛𝑔 =
1 . 0127𝑚 1
𝑊 + 𝑊 + 𝑊
6.13 2 . 25 𝑚 − 𝐾 22.7 2
𝑚 −𝐾 𝑚 −𝐾
𝑊
𝑼𝑪𝒆𝒊𝒍𝒊𝒏𝒈 = 𝟑. 𝟖𝟕𝟔
𝑚2 −𝐾
𝑊
Surface Conductance (𝑚2 −𝐾)
Walls 4.21
Flooring 1.90
Door 2.35
Ceiling 3.876
Table 10. Lists of U Factor
This is a sensible heat transfer process. The heat transfer rate through opaque
𝑄𝑜𝑝𝑎𝑞𝑢𝑒 = 𝑈. 𝐴. 𝐶𝐿𝑇𝐷
Where
𝐴 = ℎ𝑒𝑎𝑡 𝑡𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑡ℎ𝑒 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑛𝑑𝑖𝑡𝑖𝑜𝑛𝑒𝑑 𝑠𝑝𝑎𝑐𝑒 (see Table 4)
𝑊
𝑄𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = (4.21 ) . (15.21𝑚2 ). (14 𝐾)
𝑚2−𝐾
𝑊
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = (4.21 ). (6.95𝑚2 ). (15 𝐾)
𝑚2 − 𝐾
𝑊
𝑄𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = (4.21 ) . (17.49𝑚2 ). (14𝐾)
𝑚2 −𝐾
𝑊
𝑄𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = (4.21 ) . (6.70𝑚2 ). (15 𝐾)
𝑚2−𝐾
𝑊
𝑄𝑑𝑜𝑜𝑟 = (2.35 ) . (1.39𝑚2 ). (15 𝐾)
𝑚2 −𝐾
𝑄𝑑𝑜𝑜𝑟 = 49 𝑊
4.1.6 For Flooring
𝑊
𝑄𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = (1.90 ) . (17.49𝑚2 ). (13 𝐾)
𝑚2 −𝐾
𝑄𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 432 𝑊
𝑊
𝑄𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = (3.876 ) . (17.49𝑚2 ). (18 𝐾)
𝑚2 −𝐾
𝑄𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 1220.24 𝑊
Opaque Surfaces
Heat Gain (W)
North wall 896.48
West wall 438.89
South wall 1030.36
East wall 423.10
Door 49
Flooring 432
Ceiling 1220.24
Total Heat Gain: 4490.57
Heat transfer through transparent surface such as window, includes heat transfer
by conduction due to temperature difference across the window and heat transfer due to
𝑄𝑡𝑟𝑎𝑛𝑠 = 𝐴𝑢𝑛𝑠ℎ𝑎𝑑𝑒𝑑 . 𝐶𝐹
Where:
𝑊
𝐶𝐹 = 𝑆𝑢𝑟𝑓𝑎𝑐𝑒 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐹𝑎𝑐𝑡𝑜𝑟,
𝑚2
𝑊
𝑈 = 𝐹𝑒𝑛𝑒𝑠𝑡𝑟𝑎𝑡𝑖𝑜𝑛 𝑁𝐹𝑅𝐶 ℎ𝑒𝑎𝑡𝑖𝑛𝑔 𝑈 − 𝐹𝑎𝑐𝑡𝑜𝑟, 𝑚2 −𝐾 (see table 12)
𝐷𝑅 = 𝑑𝑎𝑖𝑙𝑦 𝑟𝑎𝑛𝑔𝑒 𝑜𝑢𝑡𝑑𝑜𝑜𝑟 𝑑𝑟𝑦 𝑏𝑢𝑙𝑏 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 = 9.3 𝐾 (𝐴𝑆𝐻𝑅𝐸𝐴 𝑆𝑇𝐴𝑁𝐷𝐴𝑅𝐷 2017)
𝑊
𝑃𝑋𝐼 = 𝑃𝑒𝑎𝑘 𝑒𝑥𝑡𝑒𝑟𝑖𝑜𝑟 𝑖𝑟𝑟𝑎𝑑𝑖𝑎𝑛𝑐𝑒, (see Table 12)
𝑚2
𝑆𝐻𝐺𝐶 = 𝐹𝑒𝑛𝑒𝑠𝑡𝑟𝑎𝑡𝑖𝑜𝑛 𝑟𝑎𝑡𝑒𝑑 𝑜𝑟 𝑆𝑜𝑙𝑎𝑟 𝐻𝑒𝑎𝑡 𝑔𝑎𝑖𝑛 𝑐𝑜𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑡 (see Table 12)
𝑾
Peak Irradiance for North Windows = 135.33
𝒎𝟐
𝑾
Peak Irradiance for West Windows = 468
𝒎𝟐 −𝑲
𝟒. 𝟐. 𝟑 𝐈𝐧𝐭𝐞𝐫𝐢𝐨𝐫 𝐬𝐡𝐚𝐝𝐢𝐧𝐠 𝐚𝐭𝐭𝐞𝐧𝐮𝐚𝐭𝐢𝐨𝐧 𝐜𝐨𝐞𝐟𝐟𝐢𝐜𝐢𝐞𝐧𝐭 (IAC)
In some cases, it is reasonable to assume that a shade is partially open. For
example, drapes are often partially open to admit daylight. IAC values are computed as
follows:
Where:
𝑰𝑨𝑪 = . 𝟖𝟐
𝟒. 𝟐. 𝟒 𝐅𝐞𝐧𝐞𝐬𝐭𝐫𝐚𝐭𝐢𝐨𝐧 𝐬𝐨𝐥𝐚𝐫 𝐥𝐨𝐚𝐝 𝐅𝐚𝐜𝐭𝐨𝐫 (FFs)
𝑊 𝑊
𝐶𝐹 = 1.91 ((14 − .46(9))𝐾 + 135.33 2 (.51)(.82)(.44)
𝑚2
−𝐾 𝑚
𝑊
𝐶𝐹 = 43.73
𝑚2
𝑊
𝑄𝑡𝑟𝑎𝑛𝑠 = 1.14 𝑚2 . 43.73 .2
𝑚2
𝑄𝑡𝑟𝑎𝑛𝑠 = 99.71 𝑊
4.2.4.1 For West Window
𝑄𝑡𝑟𝑎𝑛𝑠 = 𝐴𝑢𝑛𝑠ℎ𝑎𝑑𝑒𝑑 . 𝐶𝐹
𝑊 𝑊
𝐶𝐹 = 1.91 ((15 − .46(9))𝐾 + 468 2 (.51)(.82)(.56)
𝑚2−𝐾 𝑚
𝑊
𝐶𝐹 = 130.34
𝑚2
𝑊
𝑄𝑡𝑟𝑎𝑛𝑠 = 1.14 𝑚2 . 130.34
𝑚2
𝑄𝑡𝑟𝑎𝑛𝑠 = 148.59𝑊
Transparent Surfaces
Cooling Load (𝑊)
North Windows 99.71
West Window 148.59
Total Heat Gain: 248.3
components.
4.3.1 Sensible Heat Transfer Rate Due to Infiltration/Ventilation
Where:
𝐿
𝑄𝑣,𝑐 = 𝐶𝑜𝑚𝑏𝑖𝑛𝑒𝑑 𝑖𝑛𝑓𝑖𝑙𝑡𝑟𝑎𝑡𝑖𝑜𝑛 𝑎𝑛𝑑 𝑉𝑒𝑛𝑡𝑖𝑙𝑎𝑡𝑖𝑜𝑛 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒, 𝑠
𝑊
𝐶𝑠 = 𝐴𝑖𝑟 𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐹𝑎𝑐𝑡𝑜𝑟 , (9.1 𝐿−𝑠−𝐾
ASHREA standard 2017)
𝑊
1.23= air sensible heat factor at standard air conditions,
𝑚3 −𝑠
Where
𝑐𝑚2
𝐴𝐸𝑆 = 𝐸𝑥𝑝𝑜𝑠𝑒𝑑 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑎𝑟𝑒𝑎, = 𝑉𝑜𝑙𝑢𝑚𝑒 𝑠𝑝𝑎𝑐𝑒
𝑚2
Table 17. Typical IDF Values (ASHRAE Handbook-Fundamentals, 2017)
𝑳
IDF Value = .0494 𝒔−𝒄𝒎𝟐
𝑉 = 49.75𝑚3
𝑐𝑚2 𝐿
𝑄𝑖 = 49.75𝑚2 . 2.8 2
. (0.0494 )
𝑚 𝑠 − 𝑐𝑚2
𝐿
𝑄𝑖 = 6.88
𝑠
Substitute the values of ACH and volume to get the infiltration rate:
3.6𝑄𝑖
𝐴𝐶𝐻 =
𝑉
𝐿
3.6(6.88 𝑠 )
𝐴𝐶𝐻 =
49.75𝑚3
𝐴𝐶𝐻 = .498
4.3.2.1 Ventilation outdoor air requirement
Natural leakage rates are often insufficient to maintain acceptable indoor air
quality. ASHRAE Standard 62.2 specifies the required minimum whole-building ventilation
rate as
𝑄𝑣 = 0.15𝐴𝐶𝑒𝑖𝑙𝑖𝑛𝑔 + 3.5(𝑁𝑏𝑟 + 1)
Where:
𝐿
𝑄𝑣 = 𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝑣𝑒𝑛𝑡𝑖𝑙𝑎𝑡𝑖𝑜𝑛 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒, 𝑠
Substitute the values of 𝐴𝐶𝑒𝑖𝑙𝑖𝑛𝑔 and𝑁𝑏𝑟 to get the ventilation flow rate:
𝑄𝑣 = 0.15𝐴𝐶𝑒𝑖𝑙𝑖𝑛𝑔 + 3.5(𝑁𝑏𝑟 + 1)
𝑄𝑣 = 0.15(17.49𝑚2 + 3.5(1 + 1)
𝐿
𝑄𝑣 = 9.62
𝑠
Find the combined infiltration/ventilation flow rates by summing the balanced ventilation
𝑄𝑣,𝐶 = 𝑄𝑣 + max(0, 𝑄𝑖 + .5 𝑥0 )
𝐿 𝐿
𝑄𝑣,𝐶 = 9.62 𝑠 + max(0,6.88 𝑠 + .5 𝑥0 )
𝐿
𝑄𝑣,𝐶 =16.5
𝑠
Now we can get the sensible heat gain through infiltration and ventilation,
𝑊 𝐿
𝑄𝑣𝑖,𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 = (1.23). (9.1 )(16.5 )(16)
𝐿−𝑠−𝐾 𝑠
𝑄𝑣𝑖,𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 = 2954.95 𝑊
4.3.3 Latent Heat Transfer Rate Due to Infiltration
Where
𝑊
𝐶𝑙 = 𝐴𝑖𝑟 𝑙𝑎𝑡𝑒𝑛𝑡 𝑐𝑜𝑜𝑙𝑖𝑛𝑔 𝑓𝑎𝑐𝑡𝑜𝑟 , (1190.91 𝐿−𝑠 ASHREA standard 2017)
𝐿
𝑄𝑣,𝐶 = 𝑜𝑚𝑏𝑖𝑛𝑒𝑑 𝑖𝑛𝑓𝑖𝑙𝑡𝑟𝑎𝑡𝑖𝑜𝑛 𝑎𝑛𝑑 𝑉𝑒𝑛𝑡𝑖𝑙𝑎𝑡𝑖𝑜𝑛 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒,
𝑠
Through interpolation we can get the outdoor and indoor humidity ratio from Table 19.
𝑊𝑜 = 0.0328
𝑊𝑖 = 0.0173
Now we can get the latent heat gain through infiltration,
𝑊 𝐿
𝑄𝑣𝑖,𝑙𝑎𝑡𝑒𝑛𝑡 = 1190.91 (16.5 )(0.0328 − 0.0173)
𝐿−𝑠 𝑠
𝑄𝑣𝑖,𝑙𝑎𝑡𝑒𝑛𝑡 = 304.57𝑊
𝑄𝑖𝑛𝑓𝑖𝑙𝑡𝑟𝑎𝑡𝑖𝑜𝑛 = 2706.97 𝑊
The internal cooling load due to occupants consists of both sensible and latent
heat components. The full design capacity of the room is 4 persons. 2 are assumed seated
with very light work and the other 2 are moderately active in office work.
and the time elapsed since first entering. CLF is equal to 1 if the space temperature is not
The full design capacity of the Room is 4 persons. 2 are assumed seated with very
light work and the other 2 are moderately active in office work. The average sensible heat
we used is 72.5𝑊
𝑄𝑠,𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = (4)(72.5𝑊)(1)
𝑄𝑠,𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 290 𝑊
Since the latent heat gain from the occupants is instantaneous the CLF for latent
𝑄𝑙,𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = (4)(50)
𝑄𝑙,𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 200𝑊
𝑄 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 490𝑊
Lighting adds sensible heat to the conditioned space. Since the heat transferred
Where:
𝑆𝐹 = 𝑠𝑝𝑎𝑐𝑒 𝑓𝑟𝑎𝑐𝑡𝑖𝑜𝑛
5.2.1 Lighting Usage Factor
The lighting usage factor is the ratio of wattage in use, for conditions under which
the load estimate is being made, to total installed wattage. For commercial applications
such as stores, the use factor is generally 1.0 (ASHRAE Handbook-Fundamentals, 2017).
The special allowance factor considers the heat from ballasts. This factor is
typically 1.2 for fluorescent lights and 1.0 for incandescent lights due to the lack of ballasts
The Room has two recessed fluorescent luminaire and has 40𝑊 wattage. Now we
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = (40𝑊)(1)(1.2)(0.69)(2)
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 66.24𝑊
5.3 Power Loads
Instantaneous sensible heat gain from equipment operated by electric motors such
𝑃
𝑄𝑒𝑚 = ( ) . (𝐹𝑈 ). (𝐹𝐿 )
𝐸𝑀
Where
75𝑊
𝑄𝑒𝑚 =. ( ) . (1). (1)
0.50
𝑄𝑒𝑚 = 150𝑊
For appliances and equipment such as televisions, computers, printers etc., the
load is in the form of sensible heat transfer and is estimated based on the rated power
consumption.
Load Rated Power Consumption (W)
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 214W
The total building load consists of heat transferred through the envelope (walls,
roof, floor, windows, doors etc.) and heat generated by occupants, equipment, and lights.
The total heat load is needed to be cooled by the air-conditioner. It is needed to be able
The selection of air-conditioner for the apartment varies from the required cooling
load. The total heat load needs to convert to horsepower to select appropriate size of air
𝐽 8 ℎ𝑜𝑢𝑟𝑠
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 8366.08 𝑠 × (24 ℎ𝑜𝑢𝑟𝑠)
1𝑇𝑅
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 2788.69𝑊 ×
3516𝑊
A 1 𝑇𝑅 Air conditioner can remove the heat per hour from the Tolentino’s apartment
because the capacity of the air conditioner must be greater than the required cooling load.
REFERENCES
[2] World Weather Online. (11 March 2019). Maximum Temperature, Rosario Cavite
https://www.worldweatheronline.com/maragondon-weather-averages/cavite/ph
APPENDICES
Table
Maximum Maximum
Year Temperature Relative
Humidity
o
C o
F (%)
2009 29 84.2 90
2010 31 87.8 89
2011 32 89.6 84
2012 33 89.6 85
2013 34 93.2 85
2014 34 93.2 84
2015 34 93.2 79
2016 34 93.2 82
2017 34 93.2 78
2018 34 93.2 80
Table 25.Maximum Temperature, Rosario, Cavite (2009-2018)
Materials
Walls (North, East, West, and South) 112 mm concrete block, sand aggregate, 15 mm
cement plaster on both inside and outside of the
concrete
Floor 127 mm concrete lightweight aggregate with 6.35
mm Acoustical tile
Windows 4.445 mm triple glaze clear glass with operable
Insulated Fiberglass frame
Door 44.45 mm oak wood
12.7 mm Flat wood frame ceiling (insulated with R-
Ceiling 5.3 fiberglass) beneath vented attic with medium
asphalt shingle roof
Table 27. Materials
Windows 1.14
Door 1.39
Flooring 17.49
Ceiling 17.49
Walls 4.21
Flooring 1.90
Door 2.35
Ceiling 3.876
Table 29. Lists of U Factor
Opaque Surfaces
Heat Gain (W)
North wall 896.48
West wall 438.89
South wall 1030.36
East wall 423.10
Door 49
Flooring 432
Ceiling 1220.24
Total Heat Gain: 4490.57