You are on page 1of 2

07/03/2013 09:46:54 AM 1/2

PE-MACO-00010-Z001-d021

ABB
Data schedule: SF6 Circuit Breaker

Tender: 11Q1262398 , Item: 110

General data
Type LTB 170D1/B
Type of operation 1 Pole Operation
Number of poles 3
Min temperature °C −25
Max temperature °C 40
Max altitude m 1665

Ratings and guaranteed performance in accordance with IEC 62271−100

Rated voltage kV 145

Rated insulation levels


Rated lightning impulse withstand voltage
to earth kVpeak 650
across the open circuit breaker kVpeak 650
Rated switching impulse withstand voltage
to earth kVpeak −
across the open circuit breaker kVpeak −
Rated power frequency withstand voltage
to earth kV 275
across the open circuit breaker kV 275

Rated frequency Hz 60
Rated normal current A 1600
Rated short−circuit breaking current kA 31.5
DC component % 45
First pole−to−clear factor 1.5
Rated transient recovery voltage for terminal faults kVpeak 249

Rated characteristics for short line fault


Peak factor 1.6
RRRV factor kV/µs/kA 0.24
Surge impedance Ohm 450

Rated peak making current kApeak 81.9


Rated duration of short−circuit current s 1

Rated out of phase characteristics


Out of phase making and breaking current kA 7.9
Voltage factor 2.5

Rated line charging breaking current A 50


Rated cable charging breaking current A 160

Rated operating sequence CO−15s−CO

Operating times
Opening time ms 28−35
Break time ms 50
Closing time ms <70

Constructional features
Number of breaks per pole 1
Gas mixture 0.7 MPa SF6
Total mass of gas kg 11
Volume of gas liter 3 x 74
Max. working pressure MPa (gauge) 0.80
Filling pressure at +20°C MPa (abs) 0.70
Alarm pressure MPa (abs) 0.62
Blocking pressure MPa (abs) 0.60

Bursting disc No
IEC(40) 9−hole +
HV terminal
NEMA(44.5) 4−hole
Heater in packing boxes Yes
07/03/2013 09:46:54 AM 2/2

O−I Green−Red (O−I


Breaker position indication (O−I)
prefered by IEC)
Dimension print 1HSB425450M484
Seismic/Reinforced 0.5g IEEE 693

Insulators
Type of insulators and colour Brown porcelain
Min nominal creepage distance phase−to−earth mm 5045
Min nominal creepage distance across open breaker mm 4887

Operating mechanism
Number of drives 3
Motor charged spring operating mechanism FSA1
Whether fixed trip or trip−free (IEC Publ.60050(441)) Trip−free
Operating voltage VDC 125
Heater voltage VAC 220
Motor voltage VDC 125

Power required at rated supply voltage by


Closing coil W 500
Opening coil W 500
Motor kW 0.74
Heating element, continuously W 70
Heating elements, connected by thermostat W 140

Number of auxiliary contacts making and breaking 7NO+7NC


Manual trip Yes, internal
Entrelec M6/8 STA
Type of terminals supply
(disconnectable)
Type of terminals signals Entrelec M4/6
TCS resistor YES without resistor
Circuit diagram 1HSB543200−EAJ
TCS resistor 'ICC' 22 kohm
Circuit diagram 'ICC' 1HSB543200−DAH

© ABB AB 2007. All rights to this document and its information are reserved. Any form of reproduction,
use, or disclosure to third parties or unauthorised persons without our prior written consent is strictly forbidden.