Metal Deck - Shear Connectors PDF
Metal Deck - Shear Connectors PDF
Deck
manufacturers
may specify
placement
“Button-punching” deck
http://www.vercodeck.com/index.php?option=com_content&view=article&id=267&Itemid=875
Shear Connectors
Height ~ 2” – 8”
Placing shear studs
Welded wire fabric (WWF)
diameter of
Welded wire fabric wire, 10 gage,
d ~ 1/8”
W1.4 x 1.4
6x6
Spacing (inches)
May add reinforcement across girders
AISC C-I3.2 – “where … longitudinal cracking detrimental
to serviceability is likely to occur, slab should be
reinforced transverse to the supporting steel section ...”
Ar 0.002 Ac
Shear Studs and Metal Deck
Hs hr
Hs ≥ hr + 1-1/2”
Hs ≥ 4ds
≥2” ≥ ½” ≥1-1/2”
≤3” Hs
≥4 ds
≥6 ds (in general)
≤ 8 ts
≥4 ds and ≤36”
(for ribs perpendicular to beam)
(in any direction)
5½” minimum flange width for 2 rows of studs (for ¾” stud)
8½” minimum flange width for 3 rows of studs (for ¾” stud)
AISC I8.1
Limits, cont’d.
ds 2.5tf
Unless stud placed over web
Limits, cont’d.
≥1/2” req’d, ~1” typ.
AISC I8.2d
Lateral cover of 1”
for shear
connectors,
except in ribs of
formed steel decks
Calculation of fMn
AISC I3.2c
Concrete below top of
deck (in ribs) shall be
neglected for section
properties and
calculation of Ac
(strength, etc.)
Ribs perpendicular to
axis of beam
Calculation of fMn
AISC I3.2c
Concrete below top of
deck (in ribs) is
permitted be included
for section properties
(Ix)
and SHALL be
Ribs parallel to axis of beam included in calculation
of Ac (strength)
Lateral bracing during construction
(concrete placement)
With puddle welds / studs / combination at
no more than 18” o.c.
Beams are fully laterally braced
Girders are perhaps not braced by the
deck
Depends on girder – filler beam detail
Recommend using filler beam spacing as
unbraced length at construction stage
Composite Floor System Design Techniques, 2013 NASCC
Will Jacobs, Sam Easterling
media.aisc.org/NASCC2013/N14a.mp4