Project 0 18/07/2019

Site 1 / Building 1 / Storey 1 / Room 1 / Room summary

Room 1

Clearance height: 2.100 m, Reflection factors: Ceiling 70.0%, Walls 45.8%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average (Target) Min Max Mean/Min Max/Min

1 Workplane (Room 1) Perpendicular illuminance (adaptive) [lx] 544 (≥ 300) 307 738 1.77 2.40
Height: 0.850 m, Wall zone: 0.300 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

4 SYLVANIA - LED HERMETICA 40W 3790 40.6 93.4

Total via all luminaires 15160 162.4 93.3

Lighting power density: 9.73 W/m² (Floor area of room 16.69 m²),
Lighting power density: 13.55 W/m² = 2.49 W/m²/100 lx (Area of working plane 11.98 m²)

Consumption: 280 - 450 kWh/a of maximum 600 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.