Update on ASHRAE 15 “Safety 

Standard for Refrigeration Systems”
Karim Amrane
Air‐Conditioning, Heating & Refrigeration Institute 
(AHRI)

Technical Forum on Research Projects for Alternative Refrigerants in High Ambient Countries
31 October 2015 Dubai UAE
31 October 2015, Dubai, UAE
ASHRAE 15
¾ Purpose: Specifies safe design, construction, installation, and 
operation of refrigeration systems
¾ Scope:
S E bli h
Establishes safeguards for life, limb, health, and 
f d f lif li b h l h d
property and prescribes safety requirements
¾ Applies to
– The design, construction, test, installation, operation,
and inspection of mechanical and absorption refrigeration
systems, including heat pump systems used in stationary
applications;
– Modifications including replacement of parts or components if 
they are not identical in function and capacity;
and
– Substitutions of refrigerant having a different designation
Risks of Flammable Refrigerants
What are 2L Refrigerants:
Wh t 2L R f i t
‐Exhibit flame propagation when tested at 60°C
‐LFL > 0.10 kg/m³
‐HOC < 19000 kJ/kg
/ g
‐SU ≤ 0.1 m/s
mability Limit

Heat of Combustion
Subclass 
2L Class 2

(kJ/kkg)
m³)
(kg/m
Lower Flamm

19000
0.1

Class 3
Class 3
Increasing 
probability of a  0.1
Maximum Burning Velocity Increasing 
combustion event
combustion event ( /)
(m/s)
severity of a 
combustion event
Slide Source: P. Johnson, ASHRAE 2012 Annual Meeting Seminar 11
ASHRAE Standard 15 Overview – Basis of Standard
¾ Refrigerant Safety Classification
• Class 1  Nonflammable • Class A  Lower Toxicity
• Class 2  Lower Flammability • Class B  Higher Toxicity
• Class 3  Higher Flammability
¾ Occupancy Classification
• Institutional • Large mercantile
• Public assembly • Industrial
• Residential • Mixed
• Commercial
¾ Refrigerating System Classification
• Direct • High probability
• Indirect  (open or closed) • Low Probability

¾ Restrictions on Refrigerant Use
Restrictions on Refrigerant Use
¾ Installation Restrictions must address each 
possible combination 
¾ Design and Construction of Equipment & Systems of classifications

¾ Operation and Testing
Slide Source: P. Johnson, ASHRAE 2012 Annual Meeting Seminar 11
Class 2 & 3 Restrictions

¾ In general, it is very restrictive.
¾ A2 or A2L refrigerants allowed in self‐contained systems 
g y
with less than 3kg (residential) or 10kg (commercial), 
depending on location in the building. 
– The
The current Standard 15 does not differentiate class 2 and 2L 
current Standard 15 does not differentiate class 2 and 2L
refrigerants because 2L is the sub‐class of class 2.
¾ A3 cannot be used except if allowed by AHJ
– Exceptions: 
Exceptions:
• Laboratories with more than 100 ft2 (9.3 m2) area per person
• Industrial occupancies
• Portable unit systems containing less than 0.331 lb
P t bl it t t i i l th 0 331 lb (150 g) of 
(150 ) f
refrigerant charge

Slide Source: P. Johnson, ASHRAE 2012 Annual Meeting Seminar 11
Change Cycles

¾ Standard 15‐2013 is on “Continuous Maintenance”
¾ Anyone can submit change proposals at any time, 
Anyone can submit change proposals at any time
SSPC15 committee reviews and can modify, accept, 
or reject
j
¾ Consensus based with a public review process
¾ Addenda published on continuous basis
¾ Every 3 years publish an updated edition, including 
bl h l
all addenda approved since the prior edition
…2007,2010, 2013…2016, 2019, 2022
2007 2010 2013 2016 2019 2022

Slide Source: P. Johnson, ASHRAE 2012 Annual Meeting Seminar 11
ASHRAE Standard 15 Recent Activities 

¾ 2L Working Group (WG) was tasked to propose requirements 
on equipment using 2L refrigerants. The WG recent activities 
include:
– use of A2L refrigerants for human comfort with certain 
restrictions
– requirements for refrigerant leak detectors (definition, 
reliability, response time, etc.)
– ventilation requirements for the use of A2L refrigerants in 
machine room (current focus) and occupied space (later stage). 
¾ 15.2
15.2 Subcommittee was created to address residential 
Subcommittee was created to address residential
applications.
ASHRAE Standard 15.2 Subcommittee 

¾ Proposed equipment coverage: 
– split system AC&HPs and single package AC&HPs 
p y g p g
– whole house dehumidifiers, whole house 
dehumidifiers/ventilators, and 
– permanently connected heat pump water heaters
tl t dh t t h t
¾ Proposed scope:
– one‐
one and
and two‐family dwellings
two family dwellings
– multi‐family structures with individual dwelling units, where 
each dwelling unit has its own dedicated heating and air‐
conditioning system
conditioning system
– detached outbuildings (and garages , guest houses, pool houses, 
etc.) located on the same private property defined above
ASHRAE Standard 15.2 Subcommittee 

¾ Proposed timeline:
SC 15.2
15 2 draft
d ft for
f Advisory
Ad i P bli Review
Public R i (APR) 12 / 2016
12 / 2016
ready for SSPC 15 review
SSPC 15 approval for APR 1 / 2017
SC 15.2
15 2 draft
d f forf Publication
P bli i P bli Review
Public R i 6 / 201
6 / 2017
(PPR) ready for SSPC 15 review
SSPC 15 approval for PPR 7 / 2017
SC 15.2 second draft for PPR ready for SSPC 9 / 2017
15 review
SSPC 15 approval for second PPR 10 / 2017
Standard ready for submission to ICC for 2021 1 / 2018
code cycle
Additional Issues

¾ changing Standard 15  model building codes       state and 
local codes adoption of model codes and/or Standard 15
¾ Model building codes are published once every three years, 
following a fixed process during each code change cycle
¾ Safety requirements for class 2L refrigerants were not added 
Safety requirements for class 2L refrigerants were not added
to the 2015 building codes, unlikely to be added in the 2018 
edition, more likely for 2021 
¾ Adoption & effective date by individual states or localities 
will be at different times

Slide Source: P. Johnson, ASHRAE 2012 Annual Meeting Seminar 11
Thank you for your attention!