TABLA C-II

HOJA DE CALCULO DE CAIDA DE TENSION


VOLT (kV) 10 COSENO 0.8 COEF
Conductividad del Aluminio: 37.8 ACOS 0.6435 TEMP. 1
Raiz cuadrada de 3: 1.7321 SENO 0.6000 TEMP. 2
DIST. Entre mensulas 1 1.414 1.414 1.414 1.414
DIST. Entre mensulas 2 1.414 1.414 1.414 1.414
DIST. Entre mensulas 3 2.00 2.00 2.00 2.00

PROYECTO : LINEA EN MEDIA TENSION 10 Kv, PARA PERALES HUANCARUNA SAC


TENSION : 10 kV
SISTEMA : RADIAL

LONG POTENCIA
PUNTOS Ʃ POTENCIA
(Km) (KVA)
0 0.003 0 2100
1 0.024 0 2100
2 0.001 0 2100
3 0.063 0 2100
4 0.063 0 2100
5 0.063 0 2100
6 0.063 0 2100
7 0.04 0 2100
8 0.04 2100 2100
N
0.0036
20
50
1.414
1.414
2.00
Sección
UANCARUNA SAC
120 LINEA PRIMARIA
RED PRIMARIA

CORRIENTE SECCION R (T2) r Equiv DMG REACT (X) CAIDA (V)


121.2436 120 0.31611 0.006180 1.5872 0.437172 0.325
121.2436 120 0.31611 0.006180 1.5872 0.437172 2.597
121.2436 120 0.31611 0.006180 1.5872 0.437172 0.108
121.2436 120 0.31611 0.006180 1.5872 0.437172 6.816
121.2436 120 0.31611 0.006180 1.5872 0.437172 6.816
121.2436 120 0.31611 0.006180 1.5872 0.437172 6.816
121.2436 120 0.31611 0.006180 1.5872 0.437172 6.816
121.2436 120 0.31611 0.006180 1.5872 0.437172 4.328
121.2436 120 0.31611 0.006180 1.5872 0.437172 4.328
SUM. CAIDA % CAIDA
(V) TENSION
0.325 0.0325
2.921 0.0292
3.029 0.0303
9.845 0.0985
16.661 0.1666
23.477 0.2348
30.293 0.3029
34.621 0.3462
38.949 0.3895

AV en PD 4.3

AV 4.6895
SECCION
RESISTENCIA 20°C
CAPACIDAD CORRIENTE(Al)
25 50 70 95 120 150 185
1.31 0.6714 0.484 0.507 0.2663 0.2274 0.1842
125 217 249 310 388 500 628