XCEL TU eliminator

Marley developed the first cellular Drift rates of today's XCEL within the eliminator pack to ensure
drift eliminator in the 1970s when eliminator are half that of the trapped drift is returned to the wet
designs were primarily ineffective original XCEL design with equivalent side of the cooling tower.
blade type configurations. The XCEL pressure drop.
Low drift rates are the primary goal
generation of eliminators evolved in
The eliminator discharge angle of eliminator designs with XCEL
the early 80s. At that time no other
is important enough to warrant two yielding typical drift rates of .0005%
eliminator could come close to XCEL
separate eliminator designs—one for of the total gpm. Lower drift rates
eliminator’s low drift rate and low
crossflow and one for counterflow may be achievable depending upon
pressure drop. Now, virtually every
cooling towers. Tests show the air tower configuration.
eliminator is a nesting cellular PVC
direction leaving the eliminator is
type design. Considering low drift rates and
extremely important—imperfect
low pressure drop, XCEL is one of
The current XCEL TU eliminator designs create additional work for
the most effective cooling tower
is an advanced design that meets the fan. This means either increased
drift eliminator available for cooling
or exceeds today’s demanding fan horsepower—or reduced cooling
towers today.
specifications for drift emissions tower performance. The crossflow
without sacrificing fan horsepower. version features drainage slots
XCEL TU eliminator

SUGGESTED SPECIFICATION
Drift eliminators shall be of cellular type, Marley XCEL TU or The mass drift quantity, determined by the CTI Drift Test Code
approved equal. The eliminators shall be thermoformed from 17 ATC-140 shall not exceed _______% of the total gpm and shall
mil (.017″) PVC (polyvinyl chloride) material into a configuration be guaranteed for all operating conditions.
providing at least three changes of air direction and solvent
welded into multiple sheet packs. Flame spread rating of the The eliminator packs shall be able to span 66" unsupported for
material must not exceed 25 per ASTM E-84. counterflow configurations and 72" for crossflow, with minimal
deflection at design conditions. Eliminators shall be FM approved.
Eliminators used in crossflow towers must provide a discharge
angle (as defined by the angle of the last section of the eliminator Eliminator packs shall measure up to 24" wide, 5.75" in depth
itself) of at least 42° from the horizontal when installed. and up to 12'-0" long.

SPX COOLING TECHNOLOGIES, INC.


7401 WEST 129 STREET XCEL-17 | ISSUED 10/2017
OVERLAND PARK, KS 66213 USA COPYRIGHT © 2017 SPX CORPORATION
913 664 7400 | spxcooling@spx.com In the interest of technological progress, all products are subject to design

spxcooling.com and/or material change without notice.