Introduction
Market requirements today are focused on solutions that
deliver optimal performance in terms of:
• Time to market
• Cost efficiency
• Reliability and high quality
1.3 Parameter properties windows will open automatically. Enter Step 2. Assign UNICORN OPC items to the Parameters utilizing
the Parameter name = “FLOW”. Parameter Type =”Floating OPC mirror
point”, Parameter Category = “I/O” and In this step UNICORN OPC items are mapped to the
Properties value = “0”. parameter created in step 1. The next time that any
1.4 Repeat step 1.2 and 1.3 for the UV input parameters. application calls out the parameters, it will automatically
1.5 Save the defined object with defined input tags. Click connect to UNICORN OPC items for data. OPC Mirror is
“File → Save” and enter file name “UNICORN_OPC_Tags”
in the Object Name field, and click “Save” button. Note that
any name can be assigned on the module. The object type
“Modules” are selected.
1.6 The saved object name and parameters for Flow and UV
will appear in Control Studio as shown (Fig 4).
1.7 Download the newly created module
“UNICORN_OPC_Tags”, File → Download. Click “Yes” at
“assign” dialog box (Fig 5).
Define the OPC client Step 3. Displaying UNICORN Run-Time data in the DeltaV
2.3.5 On the right side (Fig 8): enter Host name (computer Operator Interface
name) of the computer where UNICORN OPC Server In this step the UNICORN Data will be displayed in an
resides (“Local Machine” in this application note). object within the DeltaV operator interface. For this example
2.3.6 Assign the OPC client. On the right side of the Pipe switch the values of Flow and UV will be displayed.
click Server/Browse, select “OPC.DeltaV.1” and click “OK”. 3.1 Launch Operator Interface: click start, DeltaV, Operator,
2.3.7 Ensure the “Enable at startup” check box is checked. DeltaV Operate (Fig 9).
2.3.8 Click “Create” button. 3.2 The screen will be in “RUN” mode. Right click any area on
Workspace area and select “Quick Edit” (Fig 9).
TreeView
Workspace
Fig 8. Definition of the OPC client.
2.4 OPC Server items will now appear in the Mirror main
window (Fig 7).
Fig 9. DeltaV Operator Interface.
2.5 Expand EVENT (left pane), ANALOG (Fig 7).
2.6 Expand Modules (right pane), AREA_A, 3.3 Create a new data object by click the “Datalink Stamper”
UNICORN_OPC_TAGS, Flow (Fig 7). icon. This will open the “Datalink” screen (Fig 10).
2.7 Connect the UNICORN OPC server flow object with the 3.4 Click the Down Arrow button and select the data source
corresponding DeltaV OPC client object. Click and hold (Fig 10) “DVSYS.UNICORN_OPC_TAGS/FLOW.F_CV”.
Flow (left pane), drag and drop onto CV (right pane).
3.5 Adjust the desire proper decimal digits and click “OK”
2.8 Connect the UV by expanding UV (right pane) and repeat (Fig 10).
step 2.7 for UV.
2.9 The mapping for both (Flow and UV) will appear on the
lower pane (Fig 7).
2.10 Save the file (Pipe, Save Pipe) and click “OK”.
2.11 Exit OPC mirror configuration.
2.12 Click “Yes” to accept configuration changes.
3.6 Place the item on the workspace by clicking anywhere on 4.7 Click “OK” to exit “Color”By” dialog box.
the Workspace area.
4.8 Click “OK” again to exit “Pump Dynamo” dialog box.
3.7 Enter a text label by clicking the text icon (Fig 9) and place 4.9 Switch to RUN mode (Workspace, Switch to Run).
it anywhere in the workspace.
4.10 When the flow value is > 0.001 the pump will turn from Red
3.8 Type in “Flow” in the text item.
to Green color.
3.9 You can format the items (change color, fonts, etc) by
Step 5. Setup and Store Data in DeltaV PI Database
right click any of the item.
In this step a PI database is configured to receive and store
3.10 Repeat steps 3.3 to 3.8 for the UV data object. data from the UNICORN OPC server.
3.11 Save the file (use “UNICORN_Analog_Data” as file name).
5.1 Open DeltaV Explorer.
3.12 Switch to Run Mode (click RUN Mode icon, Fig 9) to view
5.2 Expand “Control Strategies”, right click “AREA_A”, and
the Run-Time data in the workspace.
select “History Collection…” (Fig 12).
Step 4. Animate an Object
In this step an animated pump-object will show that the flow
is > 0.01 ml/min. The pump will change color from Red to
Green.
4.1 Select a predefined item from the Tree View. Select
“Dynamo Sets” (Fig 9).
4.2 Double click “PumpsAnim”.
4.3 Select the animation pump from the list of pumps. Drag
and drop it onto the workspace area.
4.4 A Pump Dynamo dialog box is opened, Check the
“Animate Pump Color” checkbox and press “OK”.
4.5 Fill in the information as shown in Fig 11 below.
5.5 Ensure the enable box is checked and set the sampling Step 6. View Stored Data
period as needed (5 sec) and click “OK” (Fig 13). In this step the stored data will be presented in a chart
utilizing Process History View.
6.1 Launch “Process History View”: click start, DeltaV,
Operator, Process History View (Fig 15).
6.4 Click “Browse” in the Parameter Reference Entry 6.7 Click “OK”. Process History View Screen with Flow and UV
dialogue. Browse “UNICORN_OPC_TAGS”, and select appear at the bottom of the screen (Fig 18).
“FLOW”, click “OK” (Fig 17).
6.8 Right click “UNICORN_OPC_Tags/Flow”. Select “set Y
scale” and select “Auto Scale” (Fig 18).
www.chromatography.amershambiosciences.com
Asia Pacific Tel: +852 2811 8693 Fax: +852 2811 5251 Australia Tel: +61 2 9899 0999 Fax: +61 2 9899 7511 Austria Tel: 01 57 606 16 19 Fax 01 57 606 16 27 Belgium Tel: 0800 73 888 Fax: 03 272 1637
Canada Tel: 1 800 463 5800 Fax: 1 800 567 1008 Central, East, South East Europe Tel: +43 1 982 3826 Fax: +43 1 985 8327 Denmark Tel: 45 16 2400 Fax: 45 16 2424 Finland & Baltics Tel: +358 (0)9 512 3940
Fax: +358-(0)9-512 39439 France Tel: 0169 35 67 00 Fax: 0169 41 9677 Germany Tel: 0761 4903 490 Fax: 0761 4903 405 Italy Tel: 02 27322 1 Fax: 02 27302 212 Japan Tel: 81 3 5331 9336 Fax: 81 3 5331 9370
Latin America Tel: +55 11 3933 7300 Fax: +55 11 3933 7304 Middle East Tel: +30 2 10 96 00 687 Fax: +30 2 10 96 00 693 Netherlands Tel: 0165 580 410 Fax: 0165 580 401 Norway Tel: 8156 5777
Fax: 2318 6800 Portugal Tel: 21 417 7035 Fax: 21 417 3184 Russia & other C.I.S. & N.I.S. Tel: +7 (095) 232 0250 Fax: +7 (095) 230 6377 South East Asia Tel: 60 3 8024 2080 Fax: 60 3 8024 2090
Printed matter. Licence 341 051
Spain Tel: 93 594 49 50 Fax: 93 594 49 55 Sweden Tel: 018 612 19 00 Fax: 018 612 19 10 Switzerland Tel: 0848 8028 12 Fax 0848 8028 13 UK Tel: 0800 616 928 Fax: 0800 616 927 USA Tel: +1 800 526 3593
Fax: +1 877 295 8102
Licensing information
A license for the commercial use of GST gene fusion vectors must be obtained from Chemicon International Incorporated, 28820 Single Oak Drive, Temecula, CA 92590, USA.
UNICORN, ÄKTA and BioProcess are trademarks of Amersham Biosciences Limited. Amersham and Amersham Biosciences are trademarks of Amersham plc. All goods and services are sold subject to the terms
and conditions of sale of the company within the Amersham Biosciences group that supplies them. A copy of these terms and conditions is available on request. Amersham Biosciences UK Limited, Amersham Place,
Little Chalfont, Buckinghamshire HP7 9NA, England. Amersham Biosciences AB, Björkgatan 30, SE-751 84 Uppsala, Sweden. Amarsham Biosciences Corp., 800 Centennial Avenue, PO Box 1327, Piscataway NJ 08855,
USA. Amersham Biosciences Europe GmbH, Munzinger Strasse 9, D-79111 Freiburg, Germany. Amersham Biosciences KK, Sanken Bldg. 3-25-1, Hyakunincho Amersham Shinjuku-ku, Tokyo 169-0073, Japan.
© Amersham Biosciences AB 2004 – All rights reserved.