SIEX-HC SYSTEM
HFC-227ea
HFC-125
HFC-23

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 1/112


1.1.- Most common Installation types
1.1.1.- Single cylinder system (modular cylinder)
1.1.2.- Single cylinder system with continuous weighing
1.1.3.- Cylinder bank system
1.1.4.- SMS System (small spaces)
1.2.- Distribution piping and fittings
1.2.1.- Piping
1.2.2.- Pipe joints (fittings)
1.2.3.- Reducers
1.2.4.- Cleaning
1.2.5.- Threads
1.2.6.- Installation
1.2.7.- Approximate diameters
1.2.8.- Electrical clearances
1.3.- Installing discharge nozzles, with or without a calibrated orifice
1.3.1.- Installation instructions
1.3.2.- Positioning the installed nozzle
1.4.- Installing the container, cylinder or bottle
1.4.1.- Identification labels
1.4.2.- Cylinder inscriptions
1.5.- Installing cylinder fixing brackets
1.5.1.- Brackets for a single (modular) cylinder
1.5.2.- Brackets for a single (modular) cylinder horizontally on the floor
1.5.3.- Brackets for a single row cylinder bank
1.5.4.- Brackets for a double row cylinder bank
1.5.5.- Brackets for a single cylinder with continuous weighing (modular, single and
double row)
1.6.- Installing the manifold and manifold brackets
1.7.- Installing check valves in the discharge manifold
1.8.- Installing the pressure switch
1.8.1.- Installing the pressure switch on the discharge manifold (cylinder bank)
1.8.2.- Installing the pressure switch on modular cylinder systems
1.9.- Installing the manifold pressure relief valve (burst disc)
1.10.- Installing discharge hoses
1.10.1.- Single cylinder system (modular cylinder)
1.10.2.- Cylinder bank
1.11.- Installing 227CN pneumatic discharge head
1.12.- Installing flexible discharge hoses
1.13.- Installing the cylinder valve pilot port
1.14.- Installing the resettable 227SOL and 227SOL-E electrical discharge head
1.15.- Installing 227DN manual discharge head
1.16.- Installing the 227DEE electric squib release head
1.17.- Installing the pilot bottle (for banks of more than 5 cylinders)
1.18.- Installing the pilot bottle with an indirect pneumatic delay
1.19.- Installing the remote release pneumatic line
1.20.- Installing remote release manual pull station and pulley elbows
1.21.- Installing 227CMC cable-operated manual release head
1.22.- Fitting the abort or isolation valve to the manifold
1.22.1.- Installation instructions
1.22.2.- Positioning the installed abort valve
1.23.- Fitting the isolation valve to the release line
1.24.- Installing or replacing pressure switches
1.25.- Installing or replacing pressure gauges
1.26.- Installing the cylinder valve burst disc
1.27.- Installing the warning signs

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 2/112


1.28.- Final installation check

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 3/112


INSTALLATION MANUAL
This manual contains installation instructions for components described in the System Component
Manual for SIEX-HC fixed extinguishing systems using halogenated gases (HFC-227ea, HFC-125 and
HFC-23). Before installation, the list of material in the System Design Manual should be consulted to
ensure all the necessary components are available. This manual does not cover the detection and
control elements associated with the extinguishing system.

NOTE: SIEX-HC fixed extinguishing systems manufactured by SIEX, containing HFC-


227ea, HFC-125 and HFC-23 extinguishing agents, are custom designed for a
specific application. If the components described here are assembled with
another manufacturer’s components, or are used for another application not
described in this manual, the component operation will not be correct. In this
case, SIEX does not guarantee nor will be responsible for improper
use or application of the product.

Any non-approved use or application and/or any non-approved modification of


the product or its operation may result in serious accidents and/or personal
injury. SIEX is not responsible for any non-approved use or
application.

The equipment must not be subjected to adverse mechanical or chemical atmospheric conditions or
other damage which might affect the operational capability of the equipment. The equipment must be
installed in accordance with NFPA-2001 (current edition), ISO-14520 or UNE-23570 standards, and
approved by the authority having jurisdiction.

CAUTION

YOU ARE HANDLING PRESSURISED EQUIPMENT

SIEX-HC CYLINDERS AND


CYLINDER VALVE ASSEMBLIES
MUST BE INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE CONTENTS
OF THIS MANUAL.

FAILURE TO FOLLOW THESE INSTRUCTIONS


MAY CAUSE
THE CYLINDERS DISCHARGING VIOLENTLY,
WHICH COULD CAUSE SERIOUS INJURY TO
THE PERSONS HANDLING THEM AND
DAMAGE TO THE SURROUNDING AREA.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 4/112


1.1 MOST COMMON INSTALLATION TYPES

1.1.1 Single cylinder system (modular cylinder)

The most usual type of single cylinder system (modular cylinder) is shown in Figure 1, fitted with a
manual and electrical release.

0,3 MAX

ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.

227SOL-A
24V (DC)
0,60 A
Nº xx

P
ESTO ES UN CONTE

0062
NO Q UIT AR LOS ACCES
QUE ESTE BIEN SUJET

THIS IS HIGH PRESSUR E


ACC ESORIES UNTIL IT IS PRO

30
20 EN 837- 1 40

10 50
bar
0 60

KL. 1.6
112

UN:
947 281

MASA M AX. AUTORIZADA


.- (34)

MAX. AUTHORIZEDCHARGE
(SPAIN) Nº6

CHARGE M AX. AUTORISÉE KG.


8 Fax
Tel.- B urgos M ontija
ejar
onqu

28110

GAS/GAZ:
09001 rindad de
Villal

AL MACENAR EN L UGAR VENTIL AD O / NO RESPIRAREL GAS


) 947

PARA MAN IP UL ACIÓN Y PRECAUCION ES VERETIQUETA CIL INDRO


. Ind.

2
(34
Me

TO BE STO RED IN A W EL L VENTIL ATED AREA / DO NOT INHALE


Pol

FOR HANDL ING INSTRUCTIONS SEE CYLINDER'S LABEL


C/

STO CKER DANS UN ENDROIT VENTIL É / NE PAS N I HALER LE GAZ POUR


MANIPUL ATIO N ET PRECAUTIONS, VOIR L 'E TIQUETTE SUR LE RESERVOIR

T PED
1999/36/CE
Or ga n ismo Not ific ad o/ Not ifie d bod y/O rga nisme N otifié
(0 062) BUREAU VERITAS
Cil indro+Válvula+ Di sco de rotura+Elementos de protección
Cyl ind er+V alve+Bu rst ing di sc+Protecti ons devi ce
Cyl ind re +V alv e+D isqu e d e ru pt ure+Elémen ts de protectio n
Nº de Serie
Serial N umber
Nº de Série

PO SICION DEL CILINDRO / CILIN DE R POSIT ION IN G / POSITION D E LA BOUTEILLE

- 0786
PARED/ WA LL / MUR

Manomet ro hacia arr iba


U pwa rd s p ressu re ga ug e
J aug e de la hau sse

Manomet ro hacia abajo


Do wn wa rd s pr essu re g au ge
Ja uge à

SUELO / F LO OR / S OL
F ALSO SUELO / SU B-F LOOR / FA U X SOL AMBIE NT E / HAZ A RD / E NV IR ONN E ME NT F ALSO T ECHO / SU B -CE IL ING / FA UX P LA FON D

Nota : Marque con una X e l que proce da / N ote: T ick w hit a X the c orr ec t one / Note :M ettre el ca s é chéa ntX

- 0062 C OMPR ESSED GAS


NO INFLAMMABL E

AGENTE EX TINTOR
EXTING UISH AG ENT / A GEN T EX TIN CTEU R

N º. DE CILIN DRO
C YLIN DER No . / Nº D E CY LINDER

PR ESION DE CARGA A 20ºC


FI L L P RE S S UR E AT 20 ºC Bar
PR E S SI ON D E CH A RGE A 2 0º C

PR ESION ROTURA D ISCO SEGURIDAD


BURS TIN G PRES SURE OF THE SAF ET Y DIS C Bar
PRES SION D E RUPT URE DU DI SQUE DE SÉCURIT É

C ARGA / FILL / CH AR GE Kgs.

PR ESU RIZADO CON


PR ESSU RIZED WH IT / PR ESSU RISÉ A U

TARA / TAR E / TAR E Kgs.

PESO TOTAL
Kgs.
TOTA L W EIGH T / PO ID S TO TAL

FECHA DE C AR GA
FILL D ATE / D AT E DE CHA RG E

TEMPERATURA DE FUN CIONAMIENTO DE -20º C A 50ºC


W ORK ING TEMPERA TU RE FRO M -2 0º C TO 50 ºC
TEM PÉ RATU RE DE FO NC TIO NN EMEN T D E -20 ºC A 5 0ºC

POL. IND . VILL ALON QUEJAR


C/ MER IND AD D E MONTIJA Nº 6
090 01 (BU RGOS) - SPAIN
Te l.: (34) 94 7 2811 08 Fax: (34 ) 947 2811 12

S
I
E
X
POLIG ON O IN DUST RIAL
VI LLA LON QUEJAR
C /MERIN DAD DE MO NTIJA N º6
09001 BUR GO S

TEL.: 947 28 11 08
FAX .: 947 28 11 12

Figure 1. Single cylinder system (modular cylinder)

The components that make up the system are shown in the following table:

Nº Denomination Types
6.7 / 13.4 / 25 / 26.8 / 40.2 / 61 / 67.5 /
1 Cylinder
80 / 84 / 100 / 108.4 / 120 / 127 / 150 / 180
2 Modular cylinder bracket anchored to floor
3 Instructions cylinder sticker
4 CE marking cylinder sticker
5 Cylinder positioning sticker
6 PI marking cylinder sticker
7 Cylinder sticker toxic gas
8 Bridle
RGS-MAM-20 / RGS-MAM-40-25 /
9 Container valve
RGS-MAM-40 / RGS-MAM-50
10 Re-assembled electrical actuator 227SOL
11 Manual actuator 227DM
FH-20HC 3/4" BSP / FH-25HC 1" BSP /
12 Discharge hose
FH-40HC 1 1/2" BSP / FH-50HC 2" BSP
13 Discharge pipe 3/8” / 1/2" / 3/4" / 1" / 1 1/4" / 1 1/2" / 2"
FEDR10 / FEDR15 / FEDR20 / FEDR25 /
14 Nozzle
FEDR32 / FEDR40 / FEDR50 (180º-360º)

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 5/112


The dimensions are shown in the following table:

Cylinder volume ØA B C D E G
(Litres) (mm) (mm) (mm) (mm) (mm) F(mm) (mm)
6.7 140 400 580 598 672
13.4 204 400 550 568 642
25 300 300 497 515 589
26.8 229 600 840 858 932
40.2 229 400 1000 1210 1228 1302
61 300 300 800 1039 1075 1174.75 1454.75
67.5 267 500 1300 1470 1506 1605.75 1885.75
80 267 500 1300 1710 1746 1845.75 2125.75
84 300 500 1000 1346 1393 1497
100 360 500 1000 1240 1276 1375.75 1655.75
108.4 374 300 800 1148 1200 1322
120 356 450 1250 1504 1540 1639.75 1919.75
127 374 400 1100 1339 1380 1502 1807
150 403 1535 1576 1698 2003
180 406 1594 1635 1757 2062
NOTE: The cylinder dimensions, diameter and length may vary depending on the manufacturer.

The technical characteristics are shown in the following tables:

CYLINDER VOLUME
CYLINDER TYPE GAS
(litres)
2.7 HFC-227ea
4.7 HFC-125
6.7
13.4
High pressure cylinder 26.8 HFC-227ea
(seamless) 40.2 HFC-125
67.5 HFC-23
(1)
80
100
120
25
61
84 HFC-227ea
Low pressure cylinders
HFC-125
(welded) 108.4 (2)
127
180

NOTE 1: The high and medium pressure (seamless) cylinders filled with HFC-227ea and
HFC-125 are pressurised with dry nitrogen at 24 or 42 bar (at 20ºC).

NOTE 2: The low pressure (welded) cylinders filled with HFC-227ea and HFC-125 are
pressurised with dry nitrogen at 24 (at 20ºC), never at 42 bar.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 6/112


CYLINDER
CYLINDER DISCHARGE NOZZLE
VOLUME
VALVE HOSE ØG
(litres)
RGS-MAM-11/-4 2.7 FH-15CO 21.7-1/2”
1/2” BSP
or 12/-4 4.7 BSP
6.7
13.4
FH-6PO 3/4"BSP 3/4” BSP
RGS-MAM-20 25
26.8
40.2 (1)
61
FH-25HC 1” BSP 1” BSP
RGS-MAM-40-25 67.5
84
61
67.5
80
RGS-MAM-40 FH-40HC 1 1/2” BSP 1 1/2” BSP
84
100
120
84
108.4
RGS-MAM-50 FH-50HC 2” BSP 2” BSP
127
180
NOTE 1: In the case of the 40.2 litre cylinder, an adapter, incorporated in the hose, must
be fitted on the valve to hose connection.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 7/112


1.1.2 Single cylinder system with continuous weighing

This is similar to the previous case except that it includes a continuous weighing system, as well as an
electrical and manual discharge head.

0,3 MAX 0,3 MAX

PEL IGRO:

0062 EST O ES UN CO NTENEDOR DE AL TA PRESI ÓN


N OQUI T AR L OS ACCESORI OS, NI
M ANI PUL ARLO HAST A QUE EST E BI EN SUJET O
MEDIA NT E SUS HERRAJES.

PELI
- 0062 DANG

- 0000
VdS
G 307000

UN: UN:

T PED TPED
1999/36/CE 1999/36/CE
Organismo Notificado/Notified body/Organisme Notifié Organismo Not if icado/ No tif ied body/Organisme Not ifié
(0062) BUREAU VERIT AS (0062) BUREAU VERITAS
Cilindro+Válvula+Disco de r otura+Elementos de protección Cilindr o+Válvula+Disco de rotura+Elementos de protección
Cylinder+Valve+Bursting disc+ Protections device Cylinder+ Valve+ Bursting disc+Protections device
Cylindre+ Valve+Disque de rupture+Eléments de protection Cylindre+Valve+ Disque de rupture+Eléments de protection
Nº de Serie Nº de Serie
Serial Number Serial Number
Nº de S érie N º de Série

P OSICION DE L CILINDRO / CIL INDER PO SITI ONING / POSITION DE LA BOUTEILLE POSICION DEL CILINDRO / CIL INDER POSIT IONING / POSITION DE LA BOUTEILLE

- 0786 - 0786
PARED / WALL / MUR

PARED / WALL / MUR

Manometr o hacia arr iba Manom etro h acia ar riba


Upwa rds pr ess ur e g aug e U pwa r ds pr ess ure g a ug e
Ja ug e d e la h au sse J au ge d e la h au ss e

M anomet ro hac ia abajo Manom etro hacia abajo


Do wnwa rds pre ssur e g aug e Do wnwa r ds pr ess ur e g a ug e
Jau g e à Ja ug e à
S UELO / F LOOR / S OL SUEL O / FLOOR / SOL

FALSO SUELO / SUB-F LOOR / F AUX SOL A MBIENTE / HAZ ARD / E NVIRONNE MENT FALSO TECHO / S UB -CEIL ING / FAUX P LAFOND FALSO S UELO / SUB -F L OOR / F AUX S OL AMBI ENTE/ H AZ ARD / E NVIRONNE ME NT FALSO TECHO / SUB-CE ILING/ F AUX P L AF OND

Nota: Marque con una X el que proceda / Not e: T ick whit a X the correct one / Not e: M et tre le cas échéant X Nota: Mar que con una X el que proceda / N o te : T ic k w hi t a X the co r re ct one / N o te: M e ttre le ca s é c h é an t X

- 0062 COMP RES SED GAS


NO I NF LAMMABLE
- 0062 CO MPRES SED GAS
NO IN FLAMMABLE

AGENTE EXTINTOR AGENTE EXTINTOR


EXTING UISH AG EN T / A GENT EXTINCTEUR EX TIN GUIS H AGE NT / AGE NT E XTINC T EUR

Nº. DE CILINDRO N º. DE CILINDRO


CY LIN DER No. / Nº DE CY LINDER C YL INDE R N o. / N º DE C YLINDE R

PRESION DE CARGA A 20ºC PRESION D E CARGA A 20ºC


F ILL P RES SURE AT 20ºC Bar FILL PRESSU RE AT 20ºC Bar
P RESSI ON DE CH ARGE A 20ºC PRESS ION DE CHARGE A 20ºC

PRESION ROTU RA DISC O SEGURIDAD PRESION R OTURA DISC O SEGURIDAD


BURSTING PRESSURE OF THE SAFETY DISC Bar BURSTING PR ESSUR E OF THE SAFE TY DISC Bar
PRESSION DE RUPTURE DU DISQUE DE SÉCURITÉ PRESSION DE R UPTURE DU DISQUE DE SÉC UR ITÉ

C ARGA / FILL / CHARGE Kgs. C AR GA / FIL L / C HAR GE Kg s.

PRESURIZADO CON PRESURIZADO CON


P RES SURIZED W HIT / PRESSU RISÉ AU PR E SSU R IZ E D W HIT / P R ES SUR ISÉ AU

TAR A / TARE / TARE Kgs. TARA / T AR E / TAR E Kg s.

PESO TOTAL PESO TOTAL


TOTAL W EIGHT / PO IDS TOTAL
Kgs. TOT AL WE IGH T / P OIDS T OTAL
Kg s.

FECHA DE CARGA FEC HA D E CARGA


F ILL DATE / DATE DE CHARGE FIL L DA TE / DA TE DE C HAR GE

TEMPERATURA DE FUNC IONAMIENTO DE -20ºC A 50ºC TEMPERATURA DE FUN CIONAMIENTO DE -20ºC A 50ºC
WO RKING TEM PERATURE F ROM -20ºC TO 50ºC W OR KIN G T E MPE R AT UR E FR OM -20ºC T O 50ºC
TEM PÉRATURE D E FO NCTIONNEMENT DE -20ºC A 50ºC T EM PÉ R AT UR E D E FO NC T IONN EM ENT DE -20ºC A 50ºC

POL. IND. VILLALONQUEJAR POL . IN D. VILLALONQUEJAR


C/ MERINDAD DE MONTIJA Nº6 C/ MERINDAD D E MONTIJA Nº6
0 9001 (BU RGOS) - SPAIN 09001 (BURGOS) - SPAIN
Tel.: (34) 947 28110 8 Fax: (34) 947 281112 Te l.: (34) 947 281108 Fax: (34) 947 281112

S S
I I
E E
X
POLIGON O INDU ST RIAL
X
POLI GONO INDUST RIAL
VILLALONQUEJAR VILLALONQUEJAR
C/M ERINDAD DE MONTI JA Nº 6 C /MERIN DAD DE MONT IJA Nº 6
0900 1 BURGOS 09 001 BURGOS

TEL.: 947 28 11 08 TEL.: 94 7 2 8 11 08


FAX.: 947 28 11 1 2 FAX.: 94 7 28 11 12

Figure 2. Single cylinder system with continuous weighing

Nº Denomination Types
A: 6.7 / 13.4 / 25 / 26.8 / 40.2 / 61 / 67
1 Cylinder
B: 61 / 67,5 / 80 / 84 / 100 / 108,4 / 120 / 127 / 180
2 Bracket type cage
3 Instructions cylinder sticker
4 CE marking cylinder sticker
5 Cylinder positioning sticker
6 PI marking cylinder sticker
7 Cylinder sticker toxic gas
8 Bridle
A: RGS-MAM-20 / RGS-MAM-40-25
9 Container valve
B: RGS-MAM-40 / RGS-MAM-50
10 Re-assembled electrical actuator 227SOL
11 Manual actuator 227DM / 227DMS
A: FH-20HC 3/4” BSP / FH-25HC 1" BSP
12 Discharge hose
B: FH-40HC 1 1/2" BSP / FH-50HC 2" BSP
13 Check valve VALAN-40-23 / VALAN-50-125
14 Discharge pipe 3/8” / 1/2" / 3/4" / 1" / 1 1/4" / 1 1/2" / 2"
FEDR10 / FEDR15 / FEDR20 / FEDR25 /
15 Nozzle
FEDR32 / FEDR40 / FEDR50 (180º-360º)
16 Weighing device SIEX-WD

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 8/112


1.1.3 Cylinder bank system

In this case, there are two options: single row cylinder bank or double row cylinder bank. Each of
these may be fitted with or without a pilot bottle, depending on the number of cylinders in the bank.
Banks of 2 to 5 cylinders do not need a pilot bottle, and from 6 cylinders upwards the bank will always
be fitted with a pilot bottle. See figures 3, 4, 5 and 6.
a)
c)

10 11 17 18 b)
d)

13 15 14
ON
OFF

12 227DM
Nº LOTE
LOT No.
xxxxx

16
227SOL-A
24V (DC)
0,60 A
Nº xx
- 0786

- 0786

- 0786
G 306011

G 306011

G 306011
VdS

VdS

VdS
WP137 BAR

WP137 BAR

WP137 BAR
FH-40HC

FH-40HC

FH-40HC
N - XX XXX X

N - XX XXX X

N - XX XXX X
RGS-MAM-40 RG S-MAM-40 RGS-MAM-40
EN 12094-4 EN 1 2094-4 EN 12094-4

9 10

0
20
30

bar

K L. 1.6
40

50

60
10

0
20
30

bar

KL. 1.6
40

60
50 10

0
20
30

bar

K L.1 .6
40

60
50

8
281112

281112

281112
UN: UN: UN:
947

947

947
MA SA MAX . AUTO RIZAD A MASA MA X. AU TOR IZADA MASA MAX. AU TOR IZADA
( 34)

( 34)

( 34)
MAX . AUTH OR IZED CH ARG E MAX. AU THO RIZED CH AR GE MAX. AU TH OR IZED C HA RG E
Nº6

Nº6

Nº6
KG . K G. KG .
8 Fax.-

8 Fax.-

8 Fax.-
CH AR G E MAX. AU TOR ISÉE C HA RG E MA X. AUTO RISÉE CH AR GE MA X. AUTO R S
I ÉE
de Montija

B urgos Montija

B urgos Montija
C/ Me . Villalonquejar

Villalonquejar

Villalonquejar
IN)

IN)

IN)
( SPA

( SPA

( SPA
28110

GAS/GAZ:
28110

GAS/GAZ:

28110
GAS/G AZ:
de

de
Tel.- B urgos

ALMAC ENA R E N LU GA R V ENT ILA DO / NO R ESPIR AR EL GA S ALMAC EN AR EN LUG AR VEN TILAD O / NO RES PIRAR E L G AS A LMA CE NAR EN LUG AR VE NTILAD O /N O R ESPIRAR EL GAS
rindad

9 47

Me rindad

9 47

Me rindad

9 47
PAR A MAN IPU LAC IÓN Y PR EC AU CIO NE S VER ETIQ UETA C ILIN DR O PA RA MA NIP ULAC IÓ N Y P RE CAU C ION ES VER E TIQ UE TA CILINDR O P ARA MAN IP ULA CIÓ N Y PR ECA UC ION ES VER ETIQU ETA CILIND RO
Ind .

Ind .
Ind

2 2 2
(34)

(34)

(34)
0 9001

TO BE S TO RED IN A WELL VE NTILA TED A REA / DO NO T N I HALE


0 9001

TO BE STO RE D IN A WE LL V EN TILATED AREA / D O NO T INH ALE

0 9001
TO B E ST OR ED IN A W ELL VEN TILATE D AR EA /D O N OT INH ALE
Pol.

Pol.

Pol.
FO R H AN DLIN G IN ST RU CTIO N S SEE CY LIN DER 'S LABE L FO R HA ND LING INS TR UC TIO NS SEE C YLINDE R' S LA BEL FOR H AND LING IN STR UC TIO NS SE E CYLIND ER' S LABEL
Tel.-

Tel.-
C/

C/
S TO CK ER D AN S U N E ND RO IT VE NTILÉ /N E PAS INH ALER LE G AZ POU R STO C KER DA NS UN EN DR OIT VEN TILÉ / NE PA S N I HALER LE G AZ PO UR ST OC KE R D AN S UN EN DR O IT VEN TILÉ / N E PAS INH ALER LE GAZ P OU R
MAN IPU LATIO N E T PR EC AUT ION S, VO IR L' ETIQ UETTE SU R LE RE SERVO IR MA NIP ULAT IO N ET PR EC AU TIO NS , VO IR L'E TIQ UE TTE SUR LE R ESER VO IR MAN IP ULA TION ET P RE CA UTIO N S, VO IR L' ETIQU ETTE SU R LE RESE RVO IR

7
TPED T PED TPED
1 99 9/36/CE 199 9/36 /CE 1 999/3 6/CE
Orga nismo Notificad o/Notified body/Or ganisme Not fi ié Or ganismo No tificado/Not fi e
i d bod y/Organ ism e Notifié O rganism o Notificado /Notified b ody/Org anisme Notifié
(0062) BUREAU VERITAS (0062) BUREAU VERITAS (0062) B URE AU VERITA S
Cilindro+Vál vula+Di sco de rotura+Elementos de protección Cil indro+Válvula+Disco de rotura+Elem entos de protección Cilindro+Válvula+Disco de rotura+Elementos de protección
Cyli nder+ Valve+ Bu rsting disc+ Prot ections device Cy linder +Valv e+Bur st ing disc+Pr otections device Cylind er+V al ve+Bur sting d isc+P rotections devi ce
Cyli ndre+ Valve+ Disque de r uptur e+El ém ents de protection Cy lindr e+Valv e+ Disque d e rupt ure+Eléments de pr otection Cylind re+V al ve+Di squ e de rup tur e+ Eléments de p rotection
Nº de Serie Nº de Serie Nº de S erie
Ser ial Number S er ial Num ber Serial Number
Nº de Série Nº de S ér ie Nº d e Série

6
PO SICION DEL CILINDRO / CILINDER P OSI TIO NING / POSITION DE LA BOUT EILL E POSICIO N DEL CILINDRO / CILINDER POS ITIONING / POSIT ION DE LA BOUTEIL LE POSICION DEL CILINDRO / CILINDER PO SITIONING / POSITION DE L A BOUTE IL LE

- 0786 - 0786 - 0786


P ARED / WAL L / MUR

P ARED / WAL L / MUR

P ARED / WAL L / MUR


Ma nom etr o h acia arr iba M ano met ro haci a ar rib a Man ome tro ha cia ar r iba
U pwards pr es sure gauge Upw ar ds pre ssur e gauge Upw ar ds pre ss ur e gauge
J auge de la hauss e Jauge de al ha usse Ja uge de la hausse

M ano met ro hacia aba jo Mano met ro hac ia ab ajo Man om etr o h acia abajo
Downw ar ds pre ss ur e gauge Dow nw ards pr ess ure gauge D ow nwar ds pr es sure gauge
J auge à Ja uge à Ja uge à
SUE LO / F LOOR / SOL SU ELO / F L OOR / S OL S UELO / FL OOR / SOL

FALSO SU ELO / S UB-FLOOR / F AUX SOL AMBIE NTE / HAZARD / ENVIRONNEMENT FA LSO TECH O / S UB-CEILING / F AUX PLAF OND FALSOSUELO / SUB-F LOOR/ F AUX S OL AMBIENTE / H AZARD / ENVIRONNEM ENT FALSO TECHO/ S UB-CEILING / FAUX P LAF OND FALSO SUELO / S UB-F LOOR / F AUXS OL AMBIENTE / HAZARD/ ENVIRONNEM ENT FALSOTECHO/ SUB-CEILING/ F AUXP LAFOND

Nota: M arqu e con un a X el q ue proceda / Note: Tick w hit a X t he correct one / Note: Mett re le cas échéant X Nota: Marq ue co n una X el que p roced a / Not e: Tick whi t a X the correct on e / Not e: Met tre l e cas échéant X Nota: M arque con una X el qu e proceda / No te: Tick wh it a X t he correct one / No te: Mettr e le cas échéant X

5
- 0062 COMPR ESSED GAS
NO INFL AMMABLE
- 0062 C OMPRESSED GAS
NO INFLAMMAB LE
- 0062 COMPRESSED GA S
N O INFLA MMA BLE

AGENTE EXTINTOR AGENTE EXTINT OR AGENTE EXTINTOR


EXTING UIS H AGENT / AGENT EXTINC TEUR EXTIN GUIS H AG EN T / AGENT EXTI NCTEU R EX TI NGUI SH AGENT / AGENT EXTINCTEUR

Nº. DE CILINDRO Nº. DE CILINDRO Nº. DE CILINDRO


CYLIN DER No. / Nº DE CYLINDER CYLI NDER No . / Nº DE CYLI NDER C YLINDER No . / Nº D E CY LI NDER

PRESION DE CARGA A 20ºC PRESION DE CARG A A 20ºC PRESION DE CARGA A 20ºC


FI LL PRESS URE AT 20º C Bar F ILL PRES SURE AT 20 ºC Bar FI LL P RESS URE AT 20º C Bar
PRES SI ON DE C HARGE A 2 0ºC P RESS ION DE CHARGE A 20ºC PRESS IO N DE CHA RGE A 20º C

PRESION ROTURA DISCO SEGURIDAD PRESION ROTURA DISCO SEGURIDAD PRESION RO TURA DISCO SEGURIDAD
BUR STING PR ESSURE OF T HE SAFET Y DISC Bar B UR STI NG PR ESSUR E OF THE SAFE TY DI SC Bar BURS TING PRE SSUR E OF T HE SAF ETY DISC Bar
PR ESSION DE R UPT UR E DU DISQUE DE SÉC UR ITÉ PR ESSI ON DE R UP TURE DU DISQUE DE SÉ CURIT É PRE SSION DE RUPTUR E DU DI SQUE DE SÉCUR ITÉ

CARGA / F ILL / CHA RGE Kgs. CARG A / F ILL / CHARGE Kgs. CARGA / FI LL / CHARGE Kgs.

PRESURIZADO CON PRESURIZADO CON PRESURIZADO CON


PRES SU RIZED WHI T / P RESS URIS É AU P RESS URIZED W HIT / PRESS URIS É AU PRESS URI ZED WHI T / PR ES SURI SÉ AU

TARA / TARE / TARE Kgs. TARA / TARE / TA RE Kgs. T ARA / TARE / TARE Kgs.

PESO TOTAL PESO TO TAL PESO TOTAL

4
Kgs. Kgs. Kgs.
TOTAL WEIGH T / P OIDS TOTAL TOTAL WEI GHT / P OI DS TOTAL TOTAL W EI GHT / POI DS TO TA L

F ECHA DE CARGA FECHA DE CARG A FECHA DE CARGA


FI LL DATE / DA TE DE CH ARGE F ILL DATE / D ATE DE CHARGE FI LL DA TE / DATE DE CHARGE

T EM PERATURA DE FUNCIO NAMIENT O DE -20ºC A 50ºC TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC
WOR KING TEMP ERATURE FRO M -2 0ºC TO 50 ºC W ORKIN G TEMPERATURE F ROM -2 0ºC TO 5 0ºC WORKI NG TEMPERA TU RE FROM -20º C TO 50º C
TEMPÉRA TURE D E FONC TI ONNEMENT DE - 20ºC A 50º C TEMP ÉRA TU RE DE FO NCTIONN EMENT D E -20º C A 50º C TEMP ÉRATURE DE F ONCTION NEMENT DE -20 ºC A 50 ºC

POL. IND. VILLALONQUEJAR POL. IND. VILLALO NQ UEJAR POL. IND. VILLALONQUEJAR
C/ MERINDAD DE MONTIJA Nº6 C/ M ERINDAD DE M ONTIJA Nº6 C/ MERINDAD DE M ONTIJA Nº6
09001 (BURGOS) - SPAIN 09001 (BURG OS) - SPAIN 09001 (BURGOS) - SPAIN
Tel .: (34) 947 281108 Fax: (34) 947 281112 Tel.: (34) 947 281108 F ax: (34) 947 281112 Tel.: (34) 947 281108 Fax: (34) 947 281112

S S S

3 I
E
X
PO LIGO NO INDUSTRIAL
VIL LAL ONQ UEJAR
C/MERIND AD DEM ONTIJ ANº6
0 9 00 1 BU RGOS
I
E
X
P OLIG ONO INDUSTRIAL
VILL AL ONQUEJAR
C/M ERINDAD DE MONTIJA Nº6
0 90 01 BURGOS
I
E
X
POL IGON O IND USTRIAL
VILL AL ONQUEJ AR
C /M ERINDAD DE MO NTIJ ANº6
0 90 0 1 BURGO S

T EL.: 947 28 11 08 TEL.: 94 7 2 8 11 08 T EL .: 9 47 2 8 1 1 08


F AX.: 947 28 11 12 F AX. : 94 7 2 8 11 12 FAX.: 9 47 28 11 1 2

Figure 3. Single row cylinder bank with no pilot bottle.


Nº Denomination Types
Figure 4. Single row cylinder bank with pilot bottle
1 Manifold system 61 / 67,5 / 80 / 84 / 100 / 108,4 / 120 / 127 / 180
2 System cylinder bracket
3 Figure 5. Double row cylinder bank with pilot bottle
Instructions cylinder sticker
4 CE marking cylinder sticker
5 Cylinder positioning sticker
6 Figure sticker
PI marking cylinder 6. Single row cylinder bank with pilot bottle and directional valves.
7 Cylinder sticker toxic gas
8 Bridle
9 Container valve RGS-MAM-40 / RGS-MAM-50
10 Discharge hose FH-40HC 1 1/2" BSP / FH-50HC 2" BSP
11 Check valve VALAN-40-23 / VALAN-50-125
12 Re-assembled electrical actuator 227SOL
13 Manual actuator 227DM
14 Actuator hose FH-6PO 1/4”G (500 mm)
15 "T" or elbow 1/4" BSP
16 Pneumatic actuator 227CN
Discharge manifold (2) Ø Pipe (2” – 5”)

a) Raccord union (Threaded) HFC-23 (2”)

Raccord union (Welded) HFC-23 (2 1/2" – 4”)


17
b) Bridle (Welded) HFC-227ea, HFC-125 (2” - 5”)

c) Colector cap (Threaded) HFC-23 (2”)

d) Colector cap (Welded) HFC-227ea, HFC-125 (2” - 5”)


HFC-23 (2 1/2" – 4”)
18 Pressure switch POINPRE

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 9/112


c)
10 11 24 25 22 a)
18 d)
17 b)
20 21
ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.

16 227SOL-A
24 V (DC)
0, 60 A
Nº xx

E N 837-1
23
15
bar

KL . 1. 6

- 0786

- 0786

- 0786
G 30 6011

G 30 6011

G 30 6011
VdS

VdS

VdS
19

WP137 BAR

WP137 BAR

WP137 BAR
FH-40HC

FH-40HC

FH-40HC
N - XXXXXX

N - XXXXXX

N - XXXXXX
14
- 0062 C OMPR ESSED G A S
NO IN FLAM MA BLE

RGS-MAM-40 R GS-MAM-40 RGS-MAM-40


EN 120 94-4 EN 12 094-4 EN 1 2094 -4

S SI ON D E CHA RGE A 2 0º C

SIO N RO TUR A D ISCO SEGU RIDAD


S TI NG PRESS URE OF THE SAFE TY DISC
S ION DE RUP TURE DU DISQ UE DE S ÉCURI TÉ

R GA / F IL L / CHA RG E

9
SUR IZADO CO N
S URI Z E D WH IT / P RE SS UR IS É AU

A / T AR E / T A RE

O TO TAL 30 30 30
AL W E I GHT / P OI DS T O TA L
20 40 20 40 20 40
H A D E CARG A
10 50 10 50 10 50
D AT E / DA T E DE CHAR GE

TEMPER ATUR A D E FUNC IO NAMIENTO DE -20ºC A 50ºC bar bar bar


0 60 0 60 0 60
WO RKI NG T E MP E RAT U RE F ROM - 20º C T O 50 ºC
T E MP É RAT U RE D E FO NCT I ON NE ME N T D E -2 0º C A 50 ºC

13
KL. 1.6 KL . 1.6 KL. 1.6

PO L. IN D. VILLALO NQUEJAR
C / MERINDAD D E MONTIJA Nº6
090 01 (BURG O S) - SPAIN
Tel.: (3 4) 947 28 110 8 Fax: (34) 947 281112

947 2 81112

81112

81112
UN: UN: UN:

947 2

947 2
- ( 34)
MA SA MA X . AUTORIZADA

ax. - ( 34)
M AS A MAX . A UT OR IZA DA

- ( 34)
MAS A MA X. AU TORIZ AD A
MAX . A UTHORIZED CHA RGE MA X. AU TH OR IZE D C H AR GE MA X . A UT HO RIZ ED CH AR GE

Nº 6

Nº 6
Te l.- Bu rgo s M ontija Nº
CHARGE MA X. AUTORIS ÉE KG. CH A RG E M AX . AU TOR ISÉE K G. C HA R GE MAX . A UTOR ISÉ E KG.

08 F ax.

08 F ax.
ontija

M ontija
090 01 ind ad d e quejar

090 01 ind ad d e Mquejar

090 01 ind ad d e quejar


( 34) 94 ( SPAIN)

Te l.- ( Bu rgo s ( SPAIN)

08 F

Te l.- Bu rgo s ( SPAIN)


GAS/GAZ: GAS/GAZ: GAS/GAZ:

7 2 811

7 2 811

7 2 811
C/ Mer . Villalon

Ind . Villalon

C/ Mer . Villalon
A LMACENA R E N LUGA R VE NT ILADO / NO RES PIRA R E L GAS A LMA CE N AR EN LU GAR VE N TILA DO / NO R E SP IRA R EL GA S ALMA C EN AR E N LU GA R V EN TIL AD O / N O RE SP IR AR EL GAS

34) 94

( 34) 94
PA RA M ANIP UL ACIÓN Y PRE CAUCIONE S V ER ETIQUETA CIL INDRO PA R A MAN IP U LAC IÓN Y P RE C AU C ION ES VER ET IQU ET A C ILIND R O P AR A MA NIP U LA CI ÓN Y P R EC A UC ION ES VE R E TIQUE TA C ILIN DR O

Pol. Ind

Pol. Ind
2 2 2

C/ Mer
TO BE STORE D IN A WE LL V ENTILA TE D A REA / DO NOT INHAL E T O BE ST ORE D IN A W ELL V EN TIL ATE D AR EA / D O N OT IN HA LE TO B E S TOR ED IN A W EL L VE NT ILAT ED A RE A / DO N OT I NH ALE

12

Pol.
FOR HANDLING INS TRUCT IONS S EE CYLI NDER'S LAB EL FOR H A ND LIN G I NS TR U C TION S S EE CY LIND ER 'S LAB EL F OR HA N DL IN G IN ST R UC TI ONS SE E C YLIN DE R'S LA BE L

S TOCKE R DANS UN E NDROIT V ENTI LÉ / NE P AS INHALE R LE GAZ P OUR S TOC K ER D AN S U N EN D RO IT V EN T ILÉ / NE PAS IN HAL ER LE GAZ POU R ST OCK E R D A N S U N E ND R OIT VE N TILÉ / N E PA S IN HA LER LE GA Z POU R
M ANIPULA TION ET PRECA UT IONS , VO IR L 'E TIQUET TE SUR L E RES ERV OIR MAN IP UL ATIO N E T P RE CA U TION S, V OIR L'ETI QUE TTE SU R LE RE SE RV OIR MA NIP U LAT ION ET P RE C AU TION S, VOIR L'ET IQU ETT E S UR LE RE SE R VOIR

TPE D TPE D TP ED
1999/36/CE 1999/36/CE 1999/36/CE
O rg an ismo No tifica do /Not ified bo dy/ Or ganism e Notifié Or ga nism o N otif icad o/No tifie d b od y/Or ga nisme No tifié Or ga nism o Not ificad o/N otifi ed bod y/O rg anisme Notifié
(0062) BUREAU VERITAS (0062) BUREAU VERITAS (0062) BUREAU VERITAS

7
Ci lin dro+Válvula +Disco de rotura+Elementos de protección Cil indro+Vál vu la+Di sco de rotu ra+Elementos de protecci ón Cil indro+Vál vula+D isco de rotura+ Elementos de protección
C yli nde r+ Val ve+ Bu rsti ng disc+ Pr otectio ns device C yli nd er+ Va lve+ Bu rst ing di sc+ P rotecti ons device Cyl in der+V alv e+B urst in g d isc+Prot ect ions devi ce
Cyl ind re+ V alve+ D isqu e de rup tu re+ E lém en ts de pro tection Cyl in dre +V alv e+D isqu e de ru ptu re+ E lém ents de pr otection Cy li ndre+Val ve+Di sq ue de rup ture+Elément s d ep rotecti on
Nº de Serie Nº de Serie Nº de Serie
S eri al N um ber S er ial Num ber Serial Nu mber
N º de S érie Nº de S éri e Nº de Série

6
POSICION DEL C ILINDR O / CIL IND ER POSI TIONIN G / P OS ITIO N D E LA BO UTEILLE POSICION DEL CILIND RO / CI LIN DER POSI TIONIN G / POS ITIO N DE LA BOUTEILLE POSIC ION D EL CILIN DRO / C ILIN DER POS ITIONI NG / P OSITION DE LA BO UTEILLE

- 0786 - 0786 - 0786

P AR ED / WALL / MUR

P AR ED / WALL / MUR

P AR ED / WALL / MUR
Ma nomet ro ha cia arriba M anome tro haci a arriba M anomet ro hac ia a rriba
Upwards p ress ure gauge Upwards pres sure ga uge Upwards pressu re gauge
Jauge d e la haus se J auge de la hausse J auge de la hauss e

M anometro hac ia a bajo M anomet ro ha cia aba jo Ma nome tro ha cia abajo
Downwards pres sure gauge Downwards pres sure gauge Downwards press ure gauge
J auge à Jauge à Jauge à
SU ELO / F LO OR/ SO L SU E LO / F LOOR / S OL S UE LO / FLOOR / SOL

FA LS O S U ELO / S UB-FLO OR / FAUX S OL A MB IEN TE / H AZARD / ENVI RONNEMENT FA LS O TEC HO / S UB-CEILING / FAUX PLAFOND F ALS O SU ELO / S UB-FLO OR / FAUX S OL A MB IE NTE / HAZARD / ENVIRON NEMENT F ALS O TE CH O / S UB-CEILING / FAUX PLAFO ND FAL SO SU E LO / S UB-FLOOR / FA UX SOL A MBIE NT E / HAZA RD / ENVIRO NNEMENT F AL SO TE CH O /S UB-CEILI NG / FAUX PLAFOND

Nota: Marque con una X el que proce da / No te: Ti ck w hit a X th e correct o ne / Not e: Mett re le cas éch éan t X Nota: Ma rque c on una X el que proc eda / N ote: Tick whi t a X th e correct on e/ No te: Met tre le cas échéant X Nota : Marque con una X el que proceda / Not e: Tick wh it a X t he co rr ect on e / Note: Mettr e le cas échéant X

- 0062 - 0062 - 0062

5
CO MPR ESSED G AS C OMPR ESSED G A S C OM PRESSED GA S
N O INFLA MMA B LE NO IN FLAM MAB LE N O IN FLA MMA BLE

AGENTE EXTINTOR AGENTE EXTINTOR AGENTE EXTINTO R


E XT I NG UI SH AG E NT / AG E NT E XT IN CT E UR E XT I NG UI S H A GE N T / A GE N T E XT I NCT E UR EX TIN GU ISH AG ENT / AG ENT EX TIN CTEU R

Nº. DE CILINDRO N º. DE CILINDRO Nº. DE CILINDRO


CYL I ND E R N o. / Nº D E CYL I ND E R CYL I N DE R N o. / N º D E CY LI N DE R CY LIN DER No. / N º DE CY LIN DER

PRESION D E CARGA A 20ºC PRESION DE CARG A A 20ºC PRESION DE CARGA A 20ºC


FI L L P RE SS U RE AT 20º C Bar F IL L P RE S S URE A T 20 ºC Bar F I LL PR ES S URE AT 2 0ºC Bar
PRE S S IO N D E CH AR GE A 20 ºC P RE SS I ON DE CHA RGE A 2 0ºC P RE S SI ON D E CHA RG E A 2 0º C

PRESION R OTUR A DISC O SEG URIDAD PRESION ROTURA DISCO SEGURIDAD PRESION RO TURA DISCO SEGURIDAD
BURS TING PRESS URE OF THE SAFET Y DISC Bar BURST ING PRES SURE OF TH E SAFE TY DISC Bar BURST ING PRE SSURE OF T HE SAF ETY DIS C Bar
PRES SION DE RUPTU RE DU DIS QUE DE SÉCURITÉ PRE SSI ON DE RUPT URE DU DI SQUE DE SÉ CURIT É P RE SS ION DE RUP TURE DU DISQUE DE SÉ CURIT É

C ARG A / F IL L / CHA RGE Kgs. CARG A / F IL L / CH ARG E Kgs. CARGA / FILL / C HA RGE Kgs.

PRESURIZADO CON PRESURIZADO CO N PRESU RIZADO CON


PRE S S URI Z E D WH IT / P RE SS UR IS É AU P RE SS UR IZ E D W HIT / P RE S SU RIS É A U PRESSU RIZE D WHIT / PRESSU RISÉ AU

TARA / T ARE / T ARE Kgs. TARA / T ARE / T ARE Kgs. TARA / TAR E / TA RE Kgs.

PESO TOTAL PESO TO TAL PESO TOTAL


Kgs. Kgs. Kgs.
T OT AL WE I GH T / P OI DS T O T AL T OT A L WE I GH T / P O ID S T O T AL TO TAL WEIG HT / POIDS TOTA L

FECHA DE CARG A FECHA D E CARGA FECHA DE CARGA


FI L L D AT E / DAT E DE CH ARG E F IL L D AT E / DA T E DE CHA RGE FILL DA TE / D ATE D E CHA RGE

TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC TEMPERATURA DE FUNCIONAMIEN TO DE -20ºC A 50ºC
WO RKI NG T E MP E RAT U RE F RO M - 20 ºC T O 50 ºC WO RK ING T E MP E RA T URE F RO M - 20 ºC TO 5 0ºC WORK IN G TE MPERA TURE FR OM -20 ºC TO 5 0º C
T E MP É RAT U RE D E FO NCT I ON NE ME N T D E -2 0º C A 50 ºC T E MP É RA T URE D E F ON CT IO NN E ME NT DE - 20 ºC A 5 0ºC TEMPÉRA TURE DE FON CTIONN EMENT DE -20 ºC A 5 0º C

4
PO L. IND. VIL LALONQ UEJAR POL. IND. VILLALO NQUEJAR POL . IND. VILLALO NQUEJAR
C/ MERINDAD DE MO NTIJA Nº6 C/ MERINDAD DE MONTIJA Nº6 C/ MERINDAD DE MO NTIJA Nº6
09001 (BURGO S) - SPAIN 09 001 (BURG OS) - SPAIN 0 9001 (BU RGOS) - SPAIN
Tel.: (34) 947 2811 08 Fax: (34) 947 28 1112 Tel .: (34 ) 947 28 1108 Fax: (3 4) 947 281112 Tel .: (34) 94 7 2 81108 Fax: (34) 947 281112

S S S
I I I
E E E

3 X
PO LIGO NO IN DUSTR IAL
VILLALON QUEJAR
C /ME RIN DAD DE MONTIJAN º6
09001 BURGO S

TEL.: 947 28 11 08
FAX.: 947 28 11 12
X
P OLIGO NO INDU STRIAL
VILLALO NQUE JAR
C/MERIN DA D DE MON TIJ A Nº6
09001 BURG OS

TEL.: 947 28 11 08
FAX.: 947 28 11 12
X
POLIG ONO INDU STRIAL
V ILLA LO NQ UEJAR
C/MER IND AD D E MO NTIJA Nº6
09001 BUR GOS

TEL. : 947 28 11 08
FAX .: 947 28 11 12

Figure 4. Single row cylinder bank with pilot bottle.

Nº Denomination Types
61 / 67,4 / 80 / 84 / 100 / 108,4 /
1 Manifold system
120 / 127 / 180
2 System cylinder bracket
3 Instructions cylinder sticker
4 CE marking cylinder sticker
5 Cylinder positioning sticker
6 PI marking cylinder sticker
7 Cylinder sticker toxic gas
8 Bridle
9 Container valve RGS-MAM-40 / RGS-MAM-50
10 Discharge hose FH-40HC 1 1/2" G / FH-50HC 2" G
11 Check valve VALAN-40-23 / VALAN-50-125
12 Pilot cylinder (1) 2 litres
13 Pilot cylinder bracket
14 Bridle
15 Pressure gauge 5140-P315 1/8” NPT
16 Pilot cylinder valve RGS-MAM-11/4
17 Re-assembled electrical actuator 227SOL
18 Manual actuator 227DM
19 Adaptor W21.8x1/14” H – 1/4" G M
20 Actuator hose FH-6PO
21 "T" or elbow 1/4" G
22 Flexible actuator hose FH-6PO 1/4”G (500 mm)
23 Pneumatic actuator 227CN
Discharge manifold (2) Ø Pipe (2” – 5”)
a) Raccord union (Threaded) HFC-23 (2”)
Raccord union (Welded) HFC-23 (2 1/2" – 4”)
24 b) Bridle (Welded) HFC-227ea, HFC-125 (2” - 5”)
c) Colector cap (Threaded) HFC-23 (2”)
d) Colector cap (Welded) HFC-227ea, HFC-125 (2” - 5”)
HFC-23 (2 1/2" – 4”)
25 Pressure switch POINPRE

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 10/112


a)

c)
20 9 10 21 23 24 22 b)

d)
17
ON
OFF

16 227DM
Nº LOTE
LOT No.
xxxxx
18 19
15 227SOL-A
24 V (DC)
0,6 0 A
Nº xx

F H-4 0HC F H-4 0HC F H-4 0HC


WP 1 37 WP 1 37 WP 137
EN 837-1 N º Lote xx x x N º Lote x x xx Nº Lote xx x x

14
bar

KL . 1 .6

RG S-MAM-40 RGS-MAM-40 R GS-MAM-40


EN 12094-4 EN 12094-4 EN 12094-4

8
13
- 0062 C O MPR ESSED G AS
N O IN FLA MMAB LE

30 30 30
20 40 20 40 20 40

10 50 10 50 10 50
bar bar bar
0 60 0 60 0 60

K L. 1.6 K L. 1.6 K L. 1.6


SSIO N D E CHA RG E A 2 0ºC

SION ROTU RA DISC O SEGU RID AD


ST ING P RES SURE OF T HE SAFETY DISC
SI ON DE RUP TURE DU DIS QUE DE SÉCURI TÉ

RGA / F IL L / CH AR GE

SUR IZAD O C ON
S U RI Z E D WH IT / P RE SS URI SÉ AU

7
A / T A RE / T ARE

O TOTAL
A L W EI G HT / P OI DS TO T AL

HA D E CARGA
DA TE / D AT E DE CHA RGE

TEMPERATUR A DE FUNCIONAMIENTO DE -20ºC A 50º C


W OR KI NG T EM PE RA T URE FRO M -20 ºC T O 50 ºC
T EM PÉ RA T URE D E F ON CT IO NN E ME NT D E -2 0º C A 50º C

12
POL. IND. VILLALONQUEJAR
C/ MERIND AD D E MONTIJA Nº6
0900 1 (BU RGOS) - SPAIN
Te l.: (34) 947 2811 08 Fax: (34) 947 281112

TPED TPE D TPE D


1999/36/CE 1999/36/CE 1999/36/CE
O rga nismo No tificad o/Notifie d bo dy/O rgan isme Not fiié O rga nis mo No tificado /Notified bo dy/Or gan isme Not fiié O rga nismo No tificad o/Notifie d b ody/O rga nisme No tif é
i
(0062) BUREAU VERIT AS (0062) BUREAU VERIT AS (0062) BUREAU VERIT AS

6
Cil indro+Vál vula+Disco de rot ura+Element os de protección Cil indro+Vál vul a+Disco de rot ura+Element os de protección Cil indro+Válvula+Disco de rotura+Element os de prot ección
Cylind er+Val ve+Bur sti ng disc+Prot ection s device Cylinde r+Valv e+Bursti ng disc+ Prot ections device Cylin der+Valve+Bur st ing di sc+Pr otection s device
Cy lindr e+Valv e+Disque de r uptur e+Elémen ts d e prot ect ion Cyl indr e+Valv e+ Disque de r uptur e+Elément s d e prot ect ion Cylindr e+Valv e+Disque d er upt ure+Elémen ts d e prot ection
Nº de Serie Nº de Serie Nº de Serie
Seri al Numb er Ser ial Numb er Seri al Numb er
Nº de Sér ie Nº de Séri e Nº de Sér ie

11
5 AGENTE EXTI NT OR
- 0062
EXTING UIS H A GENT / A GENT EXTINC TEUR

Nº. DE CILI NDRO


CYLIN DER No. / N º D E C YLI NDER

PRESION DE CARGA A 20ºC


FI LL P RESS URE AT 2 0ºC
PRES SI ON D E C HARGE A 20º C

PRESION ROTURA DI SCO SEGURIDAD


BUR STI NG PR ES SURE OF THE SAFET Y DISC
PRE SSION DE R UPTUR E DU DISQUE DE SÉC UR ITÉ
C OMPRESSE D GAS
NO INFL AMMABLE

Bar

Bar
AGENTE EXTINT OR
- 0062
EXTIN GUIS H AGENT / AGENT EXTIN CTEUR

N º. DE CI LI ND RO
CYLIN DER No. / N º DE C YLI NDER

PRESION DE CARGA A 20ºC


F ILL PRESS URE AT 2 0ºC
P RES S ION DE CHARG E A 20º C

PRESION ROTURA DI SCO SEGURI DAD


B UR ST ING PRE SSURE OF THE SAFE TY DISC
PR ESSI ON DE RUPT URE DU DISQUE DE SÉC URIT É
C OMPRE SSE D GAS
NO INFL AMMABLE

Bar

Bar
AGENTE EXTI NT OR
- 0062
EXTING UIS H A GENT / AGENT EXTIN CTEUR

Nº. D E CILI NDRO


CYLI NDER No . / N º D E CYLINDER

PRESION DE CARGA A 20ºC


F ILL PRESS URE AT 2 0ºC
P RES SI ON DE CHARGE A 20º C

PRESION ROT URA DISCO SEGURIDAD


B UR ST ING PRE SSURE OF THE S AFE TY DISC
PR ESSI ON DE RUPTUR E DU DISQUE DE SÉC URITÉ
C OMPRES SE D GAS
NO INFLAMMAB LE

Bar

Bar

CARGA / F ILL / CHA RGE Kgs. CARG A / FI LL / CHA RGE Kgs. CARGA / F ILL / CHA RGE Kgs.

PRESURIZADO CON PRESURIZADO CON PRESURIZ ADO CON


PRES SU RIZED WH IT / P RESS URI SÉ AU P RES S URIZED W HIT / PRES SURI SÉ AU P RES SU RIZED WH IT / PRES SURI SÉ AU

TARA / TARE / TARE Kgs. TARA / TARE / TARE Kgs. TARA / TARE / TARE Kgs.

PESO TOTAL PESO T OTAL PESO TOTAL


TOTAL WEIG HT / P OID S TO TA L Kgs. TOTAL WEIG HT / P OID S TO TAL Kgs. TOTAL WEIG HT / P OI DS TOTA L Kgs.

FECHA DE CARGA F ECHA DE CARGA FECHA DE CARG A


FI LL DATE / D ATE DE CHARGE F ILL DATE / D ATE DE CHARG E F ILL DATE / D ATE DE CHARG E

4
TEM PERATURA DE FUNCIONAMI ENTO DE -20ºC A 50ºC TEM PERATURA DE F UNCIONAMI ENTO DE -2 0ºC A 50ºC T EM PERATURA DE FUNCIO NAM IENTO DE -20ºC A 50ºC
W ORKI NG TEMPERATU RE FROM -20 ºC TO 5 0ºC W ORKIN G TEMPERATURE FROM -20 ºC TO 5 0ºC W ORKI NG TEMPERA TU RE FRO M -20 ºC TO 50º C
TEMP ÉRA TU RE DE F ONCTIO NNEMEN T DE - 20º C A 50º C TEMP ÉRA TURE DE F ONCTIO NNEMENT DE - 20º C A 50 ºC TEMP ÉRA TU RE DE F ONCTIO NNEMENT DE - 20º C A 50 ºC

POL. I ND. VILLALONQUEJAR POL . IND. VILLALONQUEJAR POL . IND. VILLALONQUEJAR


C/ M ERI NDAD DE M ONTIJA Nº6 C/ M ERI NDAD DE M ONTI JA Nº6 C/ M ERI NDAD DE M ONTI JA Nº6
0 90 01 (BURGOS) - SPAIN 09001 (BURGOS) - SPAI N 0 9001 (BURGOS) - SPAI N
Tel .: (34) 947 281108 F ax: (3 4) 947 2 81 112 Tel .: (34) 947 281108 F ax: (34) 947 281 112 Tel .: (34) 947 281108 Fax: (3 4) 947 2 81112

S S S
I I I
E E E

3
X
PO LIG ONO INDU STRIAL
X
PO LIG ONO INDU ST RIAL
X
PO LIG ONO INDU STRIAL
VIL LALO NQUEJ AR VIL LALO NQU EJAR VIL LALO NQUEJ AR
C/MER INDAD D E MONTIJAN 6º C/ME RINDAD D E MONTIJA Nº6 C/MER INDAD D E MONTIJA Nº6
09001 BURGO S 09001 BURG OS 09001 BURG OS

TEL. : 9 47 28 11 08 TEL. : 9 47 2 8 11 0 8 TEL.: 94 7 2 8 11 0 8


FAX. : 9 47 2 8 11 12 FAX. : 9 47 2 8 11 1 2 FAX.: 9 47 28 11 12

Figure 5. Double row cylinder bank with pilot bottle.

Nº Denomination Types
61 / 67,5 / 80 / 84 / 100 / 108,4 /
1 Manifold system
120 / 127 / 180
2 System cylinder bracket
3 Bracket type cage
4 Instructions cylinder sticker
5 CE marking cylinder sticker
6 PI marking cylinder sticker
7 Bridle
8 Container valve RGS-MAM-40 / RGS-MAM-50
9 Discharge hose FH-40HC 1 1/2" G / FH-50HC 2" G
10 Check valve VALAN-40-23 / VALAN-50-125
11 Pilot cylinder (1) 2 litres
12 Pilot cylinder bracket
13 Bridle
14 Pressure gauge 5140-P315 1/8” NPT
15 Pilot cylinder valve RGS-MAM-11/4
16 Re-assembled electrical actuator 227SOL
17 Manual actuator 227DM
18 Adaptor W 21.8x1/14” H - 1/4" G M
19 Flexible actuator hose FH-6PO 1/4" G (1000 mm)
20 "T" or elbow 1/4" G
21 Flexible actuator hose FH-6PO 1/4" G (500 mm)
22 Pneumatic actuator 227CN
Discharge manifold (2) Ø Pipe (2” – 5”)

a) Raccord union (Threaded) HFC-23 (2”)

Raccord union (Welded) HFC-23 (2 1/2" – 4”)


23
b) Bridle (Welded) HFC-227ea, HFC-125 (2” - 5”)

c) Colector cap (Threaded) HFC-23 (2”)

d) Colector cap (Welded) HFC-227ea, HFC-125 (2” - 5”)


HFC-23 (2 1/2" – 4”)
24 Pressure switch POINPRE

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 11/112


a)

c) 33
36 14 15 16 35
b)

d)
11

34

13
- 0786

- 0786

- 0786
G 306 011

G 306 011

G 306 011
VdS

VdS

VdS
WP137 BAR

WP137 BAR

WP137 BAR
FH-40HC

FH-40HC

FH-40HC
N - XXXXXX

N - XXXXXX

N - XXXXXX
RGS -MAM-40 RGS- MAM-40 RGS -MAM-40
E N 12094-4 E N 12094- 4 E N 12094-4

10
20
30
40

50 10
20
30
40

50 10
20
30
40

50
12 15
bar bar bar
0 60 0 60 0 60

KL . 1.6 KL . 1 .6 KL . 1.6

10
2

2
28 111

111

28 111
UN: UN: UN:
47 28
47

47
( 34) 9

( 34) 9

( 34) 9

M ASA MAX. AUTORIZADA MASA MAX. AUTORIZADA MASA MAX. AUTORIZADA


MAX. AUT HORIZED CHARGE MAX. AUT HORIZ ED CHARGE MAX. AUT HORIZED CHARGE
a Nº6

a Nº6

Te l.- Bur go s Mo nt ija Nº6

CHARGE MAX. AUT ORISÉE KG. CHARG E MAX. AUT ORISÉE KG . CHARGE MAX. AUTORISÉE KG.
Fax. -

Fax. -

Fax. -
0 90 01 da d de ue jar

0 90 01 da d de ue jar

0 90 01 da d de ue jar
Mo nt ij

Mo nt ij
Te l.- Bur go s (SPAIN)

Te l.- Bur go s (SPAIN)

(SPAIN)
11 08

11 08

11 08

GAS/GAZ: GAS/GAZ: GAS/GAZ:


C / Merind. Villalo nq

nq

C / Merind. Villalo nq
C / Merind. Villalo
47 28

47 28

47 28

ALM ACENAR EN LUGAR VENTI LADO / NO RESPIRAR EL GAS ALM ACENAR EN LUGAR VENTIL ADO / NO RESPIRAR EL GAS AL MACENAR EN LUGAR VENTI LADO / NO RESPIRAR EL GAS
PARA MANI PUL ACI ÓN Y PRECAUCIONES VER ETIQUET A CILINDRO PARA MANIPULACI ÓN Y PRECAUCI ONES VER ETIQUET A CILINDRO PARA M ANI PUL ACI ÓN Y PRECAUCIONES VERETIQUET A CILINDRO
( 34 ) 9

( 34 ) 9

( 34 ) 9

2 2 2
Pol. In

Pol. In

Pol. In

T O BE STO RED IN A WELL VENT ILAT ED AREA / DO NOT INHALE T O BE STORED IN A WELL VENT ILAT ED AREA / DO NOT INHALE T O BE STO RED IN A WELL VENT ILAT ED AREA / DO NOT INHALE
F OR HANDLI NG INST RUCTI ONS SEE CYLINDER'S LABEL F OR HANDL ING I NST RUCTI ONS SEE CYLINDER'S LABEL F OR HANDLI NG INST RUCTI ONS SEE CYLINDER'S LABEL

ST OCKER DAN S UN ENDROIT VENTIL É / NE PAS INHALER LE GAZ POUR ST OCKER DANS UN ENDROIT VENTI LÉ / NE PAS INHALER LE GAZ POUR ST OCKER DANS UN ENDROIT VENTIL É / NE PAS INHALER LE GAZ POUR

35
MANIPULATI ON ET PRECAUT IONS, VO IR L'ETIQUETTE SUR LE RESERVOIR MANIPULAT ION ET PRECAUT IONS, VOIR L 'ETIQUETTE SUR LE RESERVOIR MANIPULAT ION ET PRECAUT IONS, VO IR L'ETIQUETTE SUR LE RESERVOIR

TPED TPED TPED


1999/36/CE 1999/36/CE 1999/36/C E
Organismo N ot ific ado/ Noti fied body/Organisme Notif ié Organismo N ot ific ado/ Noti fied body/Organisme Notif ié Organismo N ot ific ado/Noti fied body/ Organisme Not ifié
(00 62) BU REAU VERITAS (00 62) BUREAU VERITAS (00 62) BU REAU VERITAS
Cil in dro+ Vál vula +Di sco de ro tu ra+ El ementos de protección C il ind ro+ Válvu la+ Di sco de rotu ra+ El ementos de protección Cil in dro+ Vál vula +Di sco de ro tu ra+ Elementos de protección

9
Cyli nder+Val ve+Bursti ng disc+Protect ions device Cylinder+Val ve+Bursti ng disc+Prot ecti ons device Cyli nder+Val ve+Bursti ng disc+ Protect ions devic e
Cyl indre+Valve+Di sque de rupture+El éments de protecti on Cyl indre+Valve+Disque de rupture+Eléments de protect ion C yl indre+Valve+Disque de rupture +Eléments de protect ion
N º de Seri e N º de Serie N º de Seri e
Se ri al Number Seria l Number Seri al Number
Nº de Série Nº de Séri e Nº de Série

POS ICION DEL CILINDRO / CILINDER PO SITIONING / POSITI ON DE LA BOUTEILLE

- 0786
POS ICION DEL CILINDRO / CILINDER POSITIONING / POSITION DE LA BOUTEILLE

- 0786
POS ICION DE L CILINDRO / CILINDER PO SITIONING / POSITI ON DE LA BOUTEILLE

- 0786

8 23 32
P ARED / WALL / MUR

P ARED / WALL / MUR

P ARED / WALL / MUR

Manomet ro ha ci a arriba Manomet ro ha ci a arriba Manomet ro ha ci a arriba


Upwards press ure gauge Upwards press ure gauge Upwards press ure gauge
J auge de la hauss e J auge de la hauss e J auge de la haus se

Ma nome tro ha ci a abajo Ma nom et ro ha ci a abaj o Ma nom et ro ha ci a abaj o


Downwards pres su re gauge Downwards pres s ure gauge Downwards press ure gauge
Jauge à J auge à Jauge à
SUE LO / FLO OR / SOL S UE LO / FLO OR / SOL S UE LO / FLO OR / SOL

FALS O S UE LO / SU B-FLO OR / FAU X SOL AMBI ENTE / H AZA RD / EN VIR O NNEMENT F AL SO T ECHO/ SUB-C EILI NG /FA UX PL AFOND FALS O S UE LO / SUB -FLOO R / FAU X SOL AMBI ENTE / H AZA RD / EN VIR ON NEMENT F AL SO T ECHO/ SUB-C EILI NG /FA UX PLA FO ND F ALS O S UE LO / SU B-FLO OR / FAU X SOL AMBI ENTE / H AZA RD / EN VI RO NNEMENT F AL SO T ECHO/ SUB-C EILI NG /FA UX PL AFOND

Not a: M arque con una X el que proceda / No te: Ti ck whi t a X the correc t one / No te: Met tre le c as échéa nt X Not a: Marque con una X el que proceda / No t e: Ti ck wh i t a X t he correct on e / N ote: M et tr e le cas éch éant X Nota: M arque con una X el que proceda / No t e: Ti ck w hi t a X t he co rrect on e / No te: M et tr e le c as éch éant X

A GENTE EXTINTOR
- 0062
EXTINGUISH AGENT / AGE NT EXTINCTE UR

Nº. DE CILINDRO
CYLINDER No. / Nº DE CYLINDER

PRESION DE CARGA A 20º C


FILL PRESSURE AT 20ºC
PRESSION DE CHARGE A 20ºC
C OMPR ES SED GAS
NO INFL AMM AB LE

B ar
A GENTE EXTINTOR

Nº. DE CILINDRO
- 0062
EXT INGUISH AG ENT / AGENT EXTINCTEUR

CYLINDER No. / Nº DE CYLINDER

PRESION DE CARGA A 20º C


FILL PRESSURE AT 20ºC
PRESSION DE CHARGE A 20ºC
COMPR ES SED GAS
NO INFLAMMABL E

Bar
A GENTE EXTINTOR

Nº. DE CILINDRO
- 0062
EXTINGUISH AGENT / AGENT EXTINCTEUR

CYLINDE R No. / Nº DE CYLINDER

PRESION DE CARGA A 20º C


FILL PRESSURE AT 20ºC
PRESSION DE CHARGE A 20ºC
C OMPR ES SED GAS
NO INFL AMM AB LE

B ar
7 ON
OFF
31
22
PRESION ROTURA DISCO SEGURIDAD PRESION ROTURA DISCO SEGURIDAD PRESION ROTURA DISCO SEGURIDAD
BURSTIN G PRESS URE O F THE SAFETY DI SC B ar BURS TI NG PRESS URE OF THE SAFETY DISC Bar BURS TI NG P RES SURE OF THE SAF ETY DISC B ar
P RESS ION DE R UPTURE D U DIS QUE DE SÉCURI TÉ P RES SIO N DE RUPTURE DU DI SQUE DE S ÉCURITÉ P RES SIO N DE RUPTURE DU DI SQUE DE S ÉCURITÉ

24
CARGA / FILL / CHARGE K gs. CARGA / FILL / CHARGE Kgs. CARGA / FILL / CHARGE K gs.

6 30
PRESURIZADO CON PRESURIZADO CON PRESURIZADO CON
PRESSURIZED WHIT / PRESSURISÉ AU PRESSURIZED WHIT / PRESSURISÉ AU PRESSURIZED WHIT / PRESSURISÉ AU

TARA / TARE / TARE K gs. TA RA / TARE / TARE Kgs. TARA / TARE / TARE K gs.

PES O TOTAL PES O TOTAL PES O T OTAL 227DM


TOT AL WE IG HT / POIDS TOTAL
K gs. TO TAL WEIGHT / POIDS TOTAL
Kgs. TOT AL W EIGHT / POIDS TOTAL
K gs.
Nº LOTE
FECHA DE CARGA FECHA DE CARGA FECHA DE CARGA xxxxx
LOT No.
FILL DATE / DAT E DE CHARGE FILL DATE / DATE DE CHARGE FILL DATE / DAT E DE CHARGE

TEMPERATURA DE FUNCIONAMIENTO DE -20º C A 50ºC TEMPE RATURA DE FUNCIONAMIENTO DE -20º C A 50ºC TEMPERATURA DE FUNCIONAMIENTO DE -20º C A 50ºC
WORKING T EMPERATURE FROM -20ºC TO 50ºC WORKING TEMPE RATURE FROM -20ºC TO 50ºC W ORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRA TURE DE FONCTIONNEMENT DE -20ºC A 50ºC TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC TEMPÉRATURE DE FONCTIONNE MENT DE -20ºC A 50ºC

POL. IND. VILLALONQUEJAR POL. IND. VILLALONQUEJAR POL. IND. VILLALONQUEJAR


C/ M ERINDAD DE MONTIJA Nº6 C/ M ERINDAD DE MONTIJA Nº6 C/ M ERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN 09001 (BURGOS) - SPAIN 09001 (BURGOS) - SP AIN
Tel.: (34) 947 281108 Fax : (34) 947 281112 Tel.: ( 34) 947 281108 Fax : (34) 947 281112 Tel.: ( 34) 947 281108 Fax: ( 34) 947 281112

21 25
S
I
E
S
I
E
S
I
E
5 227SOL-A
24V (DC)
0,60 A
Nº xx

29
X X X

4
POLIGON O IN DU STRIAL POLIGONO IN DU STRIA L POLIGON O IN DU STRIAL
V ILLALON QU EJAR VILLA LON QU EJAR VILLA LONQUEJAR
C /MER IND AD DE MON TIJA Nº 6 C /MER IN DA D D E MON TIJA N º6 C /MER IND AD D E MON TIJA Nº 6
09001 B UR GOS 09001 B UR GOS 09001 B UR GOS

TEL.: 947 28 11 08 T EL.: 947 28 11 08 TEL.: 947 28 11 08


FA X.: 947 28 11 12 FA X. : 947 28 11 12 FA X.: 947 28 11 12
EN 837-1

20 28
bar

KL. 1.6

3 19
- 0062

SSION DE CHARGE A 20ºC

SION ROTURA DISCO S EGURIDAD


COMPR ES SED GAS
NO INFL AMM AB LE

27
S TING P RES SU RE OF THE SAF ETY DISC
S IO N DE R UP TURE DU DI S QUE DE S ÉCURI TÉ

RGA / FILL / CHARGE

SURIZADO CON
SURIZ ED WHIT / PRESSURISÉ AU

A / TARE / TARE

O TOTAL
AL WE IG HT / POIDS TOTAL

HA DE CARGA
DATE / DATE DE CHARGE

TEMPERATURA DE FUNCIONAMIENTO DE -20º C A 50ºC


WORKING TEMPE RATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

18
POL. IND. V ILLA LONQUEJA R
C/ MERINDAD DE MONTIJA Nº 6
09001 ( BURG OS) - SPAIN
Tel.: (34) 947 281108 F ax: (34) 947 281112

1 17 26

Figure 6. Single row cylinder bank with pilot bottle and selector valve.

Nº Denomination Types
1 Manifold system 61 / 67,5 / 80 / 84 / 100 / 108,4 / 120 / 127 / 180
2 System cylinder bracket
3 Instructions cylinder sticker
4 CE marking cylinder sticker
5 Cylinder positioning sticker
6 PI marking cylinder sticker
7 Cylinder sticker toxic gas
8 Bridle
9 Container valve RGS-MAM-40 / RGS-MAM-50
10 Discharge hose FH-40HC 1 1/2" G / FH-50HC 2" G
11 Check valve VALAN-40-23 / VALAN-50-125
12 Pneumatic actuator 227CN
13 "T" or elbow 1/4" G
14 Flexible actuator hose FH-6PO 1/4"G (500 mm)
15 Teflon hose 1/4" G or cupper tube 6x4mm
16 1/4”G non-return valve
17 Pilot cylinder (1) 2 litres
18 Pilot cylinder bracket
19 Bridle
20 Pressure gauge 5140-P315 1/8” NPT
21 Pilot cylinder valve RGS-MAM-11/4
22 Re-assembled electrical actuator 227SOL

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 12/112


23 Manual actuator 227DM
24 Adaptor W 21.8x1/14” H – 1/4" G M
25 Adaptor 1/4" G H – Ø6mm
26 Selector cabinet
27 Copper tube 6x4mm
28 “T” for copper pipe 6x4mm.
29 Solenoid 24V(DC) by-pass
30 Male adaptor 1/8”G M - Ø6mm
31 Manual openning valve 1/4" G by-pas
32 male adaptor 1/4”G M - Ø6mm
33 Selector valve SVD SVD20 / 25 / 32 / 40 / 50 / 65 / 80 / 100
34 Female cup
35 Selector valves manifold Ø Tubo / Pipe (2” - 5”)
Discharge manifold (2) Ø Pipe (2” – 5”)
a) Raccord union (Threaded) HFC-23 (2”)
Raccord union (Welded) HFC-23 (2 1/2" – 4”)
36 b) Bridle (Welded) HFC-227ea, HFC-125 (2” - 5”)
c) Colector cap (Threaded) HFC-23 (2”)
d) Colector cap (Welded) HFC-227ea, HFC-125 (2” - 5”)
HFC-23 (2 1/2" – 4”)
37 Pressure switch POINPRE

c) a)
25 10 11 22 24 23
d) b)
18
ON
OFF
21
17 227DM
Nº LOTE
LOT No.
xxxxx
19 20
16 227SOL-A
24V (DC)
0,60 A
Nº xx

10
E N 8 37 -1
F H-4 0HC F H-4 0HC F H-40 HC
WP 137 WP 137 WP 1 37
Nº Lotexxxx Nº Lotexxxx Nº Lote xxxx

15
bar

KL . 1.6

RG S-MAM-40 RG S-MAM-40 RGS-MAM-40


EN 12094-4 EN 12094-4 EN 12 094-4

14 9
- 0062 CO MPRESSED GAS
NO I NFLA MMAB LE

30 30 30
20 40 20 40 20 40

S SI ON D E CHARG E A 20º C
10 50 10 50 10 50
SIO N ROT URA DISCO SEGURIDAD 0 bar 60 0 bar 60 0 bar 60
S TING PRE SSUR E OF THE SAF ETY DISC
S ION DE R UPTURE DU DISQUE DE SÉC URITÉ
K L. 1.6 KL . 1.6 KL. 1.6

RG A / FI LL / CHA RGE

SURIZADO CON
S URI ZED WHI T / P RESS URIS É AU

A / TAR E / TARE

O T OTAL
AL WEIG HT / POI DS TOTAL

HA DE CARGA
DA TE / DATE DE CHA RGE

T EMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC


W ORKI NG TEMPERA TU RE FRO M -2 0ºC TO 50º C

8
TEMPÉRATUR E D E FO NCTION NEMEN T DE -2 0ºC A 50 ºC

13
POL. IND. VILLALONQUEJAR
C/ MERINDAD DE MONTIJA Nº6
09001 (BURG OS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112

A LMA CEN AR E N LUGAR VEN TILADO / N O R ESP IRAR EL GA S A LMA CEN AR E N LUG AR VEN TILADO / NO RE SPIR AR E L GAS ALMAC ENA R EN LUG AR V ENTILA DO / NO RES PIR AR EL G AS
P ARA MA NIP ULAC IÓN Y P RE CAU CIONE S VE R E TIQUE TA CILINDR O PA RA MA NIPU LACI ÓN Y P REC AUC IO NES VE R ETIQ UETA C ILINDRO PA RA MA NIPU LACI ÓN Y P REC AUC IO NES VE R ETIQ UETA C ILINDRO

TO B E STORE D IN A WELL VE NTILATE D AR EA / D O NOTIN HALE 2 TO BE STO RED IN A W ELL VE NTILATED ARE A / DO N OT INH ALE 2 TO BE S TO RED IN A W ELL VEN TILATED ARE A / DO NO T INH ALE 2
F OR HAN DLIN G IN STR UCTIONS SE E CY LINDE R' S LABEL FO R H AN DLING IN STRU CTIO NS SEE CY LINDER 'S LA BEL FO R H AN DLING IN STRU CTIO NS SEE CYL INDER 'S LA BEL

STOCK ER D ANS UN E NDR OI TV ENTILÉ / NE PAS NI HA LER LE GA Z POUR STO CKE R DA NS U N EN DRO IT V ENTILÉ / NE P AS IN HALE R LE G AZ P OU R STO CKE R DA NS U N EN DRO IT V ENTILÉ / NE P AS IN HALE R LE G AZ P OU R
MA NIP ULATION ET PR ECA UTIONS , VOIR L' ETIQU ETTE SUR LE RES ERV OIR MAN IPU LATIO N E T PRE CA UTIO NS, VO IR L' ETIQ UE TTE SUR LE RESE RVO IR MAN IPULA TIO N ET P RE CAU TION S, V OIR L'E TIQ UETTE S UR LE R ESER VO IR

TPED TPED TPED

7
19 99 /3 6/CE 199 9/36 /CE 199 9/36 /CE
Orga nismo Notifica do/No tified body /Organisme Notifié O rga nis mo N otific a do/N o tified body /O rganis me N otifi é O rgan is mo N otific ad o/N o tified b ody /O rg anis m e No tif ié
(0062) BUREAU VE RI TAS (0062) BUREAU V E RITA S (0062) B URE AU V ERITA S
Cilindro+V álvula+Disco de rot ura+El em entos de prot ección Cilindro+Válvula+Di sco de rotura+Elem ent os de protección Cilindro+Válvula+Disco de rotura+Element os de protección

12
Cyli nder+Valve+Bur sti ng disc+Pr otections device Cylinder +Valve+Burstin g disc+Pr otections device Cylinder+ Valve+Bursting d isc+ Pro tecti ons device
Cylind re+Valve+Disque de ru ptur e+ Elément s de pr otect ion Cylindr e+Valve+Disque de rup ture+E léments de prot ect ion Cyl indr e+ Valv e+ Disq ue de ruptu re+E léments de p rot ectio n
Nº de S erie Nº de Serie Nº de Serie
Seri al Number Seri al Num ber S erial Num ber
Nº d e S érie Nº d e S érie Nº de S ér ie

POSICION DEL CILINDRO / CILINDER POSITION ING / POSITION DE LA BOUTEILLE POSICION DEL CILINDRO / CILINDER POSITION ING / POSITION DE LA BOUTEILLE POSICION DEL CILINDRO / C ILINDER POSI TIONIN G / P OSITIO N DE LA BOUTEILLE

- 0786 - 0786 - 0786


PARED / W ALL / MUR

PARED / W ALL / MUR

PARED / W ALL / MUR

Ma no met r o h acia arr iba Ma no met ro h acia a rr iba Man om et ro ha cia ar rib a
U pwards pr es sur e gauge U pw ards pr es sur e gauge Upw ar ds pr ess ure gauge
J auge de la haus se J auge de la haus se Jauge de la hauss e

M ano me tr o h aci a ab ajo M ano me tr o h aci a aba jo Ma no met ro h acia abajo


Downw ar ds pre ss ure gauge D ownwar ds pre ss ur e gauge D ow nwards pres sur e gauge

6
J auge à J auge à J auge à
SUELO / FLOOR / S OL S UELO / FLOOR / S OL SU ELO / F LOOR / S OL

FALSO SUE LO / S UB-FLOOR / FAUXS OL A MB IENTE / HAZARD / ENVIRONNEM ENT FALS O TEC HO / S UB-CEIL ING / FAUXPLAFOND FALSO SUELO / S UB-FLOOR / FAUXS OL AMBIE NTE / HAZARD / ENVIRONNEMENT FALSO TECHO/ S UB-CEILIN G / FAUXPLAFOND FALSO SUELO / SUB-FLO OR / FAUXS OL AMBIENTE / HAZARD / ENVIRONNEMENT FALSO TECHO/ S UB-CEILING / FAUXPLAFOND

Nota: M arque con una X el q ue p roceda / No te: Tick w hit a X th e correct on e / Note: Mettr e le cas éch éant X Nota: M arque co n una X el q ue p roceda / Not e: Tick wh it a X the correct one / Note: Mettr e le cas éch éant X Nota: Marq ue co n u na X el qu e pro ceda / Not e: Tick whi t a X t he correct one / N ote: Met tre le cas échéant X

- 0062 C OMPR ESSED GAS


NO INFLAMM ABLE
- 0062 C OMPR ES SE D GAS
NO INFL AMMABLE
- 0062 COMPRESSED GAS
NO I NFLAMMAB LE

AG ENT E EX TINTOR AG ENT E EX TINTOR AGE NTE E XT INTOR


E XT IN GUI SH AGE NT / AG EN T EX TI NCT EU R EX T ING UIS H A GE NT / AGE NT E XT I NCT EUR EX TI NGU IS H A GE NT / AGE NT E XT I NCT EUR

Nº . DE CILINDRO Nº. DE CILINDRO Nº. DE CI LINDRO


CYL IN DE R No. / N º D E C YLI NDE R CYL IND E R No. / N º DE C YLI NDE R C YLI NDE R N o. / Nº DE CYL I NDE R

P RE SI ON DE CARGA A 20ºC P RE SI ON DE CARGA A 20ºC P RES IO N DE CA RGA A 20ºC


F ILL P RE SS URE AT 2 0ºC B ar FI LL P RE SS URE AT 20 ºC B ar FI LL P RE SS URE AT 20 ºC B ar
P RES SI ON D E C HARG E A 20 ºC PRE SS IO N DE CH ARGE A 20º C PRE SS IO N DE CH ARGE A 20º C

5
P RE SI ON RO TURA DI SCO SE GURI DAD P RE SI ON RO TURA DIS CO SE GURI DAD P RES IO N ROT URA DIS CO SE GURIDA D
B UR STING PR ESSUR E OF THE SAFET Y DISC B ar BURS TING PRE SSURE OF T HE SAFETY DISC B ar BURS TING P RE SSURE OF T HE SAFETY DISC B ar
PR ESSION DE R UPT UR E DU DI SQUE DE SÉC UR ITÉ PRE SSION DE RUPT UR E DU DI SQUE DE S ÉCURI TÉ PRE SSION DE RUPTUR E DU DIS QUE DE SÉ CURI TÉ

CARGA / F IL L / CHARG E K gs. CA RGA / F IL L / CHARG E K gs. CA RGA / F IL L / CH ARGE K gs.

P RE SURI ZA DO CON P RE SURI ZA DO CON P RES URIZ ADO CON


P RES S URIZ E D W HI T / PR ES SU RIS É A U PRE S SU RIZ E D W HIT / PRE S SURI SÉ AU PRE S SUR IZ E D WH IT / PRE S SURI SÉ AU

TA RA / TA RE / T ARE K gs. TA RA / T AR E / TA RE K gs. T ARA / T ARE / TA RE K gs.

P E SO TOT AL P E SO TOT AL P ES O TOTA L


K gs. K gs. K gs.
T OT AL WE I GHT / PO IDS T OT AL TO T AL WE IG HT / P OI DS TO TA L T OT A L W E IGH T / P OID S TOT AL

F ECHA DE CARGA F ECHA DE CARGA F ECHA DE CA RGA


F IL L DAT E / D AT E DE CHARG E FI LL D AT E / D AT E DE CHARGE FI LL D AT E / D AT E DE CHARGE

TE MP ERA TURA DE FUNCIONAM IE NTO DE -20ºC A 50ºC TEM PE RAT URA DE F UNCI ONAM IE NTO DE -20ºC A 50ºC T EM PE RATURA DE FUNCIO NA MI ENT O DE -20ºC A 50ºC
WORK ING TE MP E RAT URE F ROM - 20º C T O 50 ºC WORK ING TE MP E RAT URE FR OM - 20º C T O 50 ºC W ORKI NG TE MP ERA T URE FRO M -2 0ºC TO 50º C
T EMP É RAT URE D E F ONC TI ONN EME NT D E - 20 ºC A 50 ºC T EMP ÉR AT URE DE F ONCT IO NNE ME NT DE - 20º C A 50º C T E MP ÉRA TU RE DE F ONCT IO NNE ME NT DE - 20º C A 5 0ºC

P OL. IND. VI LLALONQUE JA R PO L. IND. V ILLA LONQUE JA R POL. I ND. V ILLALONQUEJAR


C/ ME RI NDAD DE M ONTI JA Nº6 C/ ME RI NDAD DE M ONTIJA Nº6 C/ M ERI NDAD DE M ONTIJA Nº6
09001 (BURGO S) - S PAI N 09001 (B URGOS ) - SP AIN 09001 (B URGOS ) - SPA IN
Tel .: (34) 9 47 281108 Fax: (34) 947 281112 T el. : (34) 947 281108 Fax: (34) 947 281112 T el. : (34) 947 281108 Fax: (34) 947 281112

4 S
I
S
I
S
I
E E E
X X X

3
PO LIGO NO INDUSTRIAL POLIGON O INDUSTRIAL POLIGON O INDUSTRIAL
VILLA LO NQUEJAR VILLALONQ UEJAR VILLALONQ UEJAR
C/MERINDA D DEM ON TIJ ANº6 C /M ERINDAD DE M ONTIJA Nº6 C /M ERINDAD DE M ONTIJA Nº6
09001 BURGO S 09001 BU RGOS 09001 BUR GOS

TEL .: 94 7 2 8 11 08 TEL. : 9 47 28 11 0 8 TEL. : 9 47 28 11 0 8

E
2

1 D

Figure 7. Single row cylinder bank with continuous weighing and pilot bottle

Nº Denomination Types
61 / 67,5 / 80 / 84 / 100 /
1 Manifold system
108,4 / 120 / 127 / 180
2 System cylinder bracket
3 Instructions cylinder sticker
4 CE marking cylinder sticker
5 Cylinder positioning sticker
6 PI marking cylinder sticker
7 Cylinder sticker toxic gas
8 Bridle

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 13/112


9 Container valve RGS-MAM-40
10 Discharge hose FH-40HC 1 1/2" G
11 Check valve VALAN-40-23
12 Pilot cylinder (1) 2 litros / litres
13 Pilot cylinder bracket
14 Bridle
15 Pressure gauge 5140-P315 1/8” NPT
16 Pilot cylinder valve RGS-MAM-11/4
17 Re-assembled electrical actuator 227SOL
18 Manual actuator 227DM
19 Adaptor W 21.8x1/14” H - 1/4" G M
20 Flexible actuator hose FH-6PO 1/4" G (1000 mm)
21 "T" or elbow 1/4" G
22 Flexible actuator hose FH-6PO 1/4”G (500 mm)
Discharge manifold (2) Ø Pipe (2” – 5”)

a) Raccord union (Threaded) HFC-23 (2”)

Raccord union (Welded) HFC-23 (2 1/2" – 4”)


23
b) Bridle (Welded) HFC-227ea, HFC-125 (2” - 5”)

c) Colector cap (Threaded) HFC-23 (2”)

d) Colector cap (Welded) HFC-227ea, HFC-125 (2” - 5”)


HFC-23 (2 1/2" – 4”)
24 Pressure switch POINPRE
25 Weighing device SIEX-WD

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 14/112


The dimensions of these systems are shown in the three following tables:

CYLINDER CYLINDER BANK

Volume Dia.
(litres) (mm) 2 3 4 5 6 7 8 9 10
A B A B A B A B A B A B A B A B A B
61 300 700 880 1100 1280 1500 1680 1900 2080 2300 2480 2700 2880 3100 3280 3500 3680 3900 4080
67.5 267 617 830 967 1180 1317 1530 1667 1880 2017 2230 2367 2580 2717 2930 3067 3280 3417 3630
80 267 617 830 967 1180 1317 1530 1667 1880 2017 2230 2367 2580 2717 2930 3067 3280 3417 3630
84 300 700 880 1100 1280 1500 1680 1900 2080 2300 2480 2700 2880 3100 3280 3500 3680 3900 4080
100 360 715 880 1115 1280 1515 1680 1915 2080 2315 2480 2715 2880 3115 3280 3515 3680 3915 4080
108.4 374
120 360 756 880 1156 1280 1556 1680 1956 2080 2356 2480 2756 2880 3156 3280 3556 3680 3956 4080
127 374 824 930 1274 1380 1724 1830 2174 2280 2624 2730 3074 3180 3524 3630 3974 4080 4424 4530
180 450

NOTE 1: Cylinders 2 to 5 do not have a pilot bottle fitted. Pilot bottles are fitted from cylinder 6.

NOTE 2: The cylinder dimensions, diameter and length, may vary depending on the manufacturer.

CYLINDER VOLUME D E
(litres) (mm) (mm)
61 300 800
67,5 500 1300
80 500 1300
84 500 1000
100 500 1300
108,4 300 800
120 500 1300
127 400 1100
180 400 1100

SINGLE ROW DOUBLE ROW


CYLINDER VOLUME
F F
(litres)
(mm) (mm)
61 370 710
67,5 337 644
80 337 644
84 370 710
100 385 740
108,4 444 858
120 426 622
127 444 858
180 476 922

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 15/112


The technical features of these systems are shown in the following tables:

CYLINDER VOLUME
CYLINDER TYPE GAS
(litres)
67.5
80 HFC-227ea
High pressure cylinder HFC-125
(seamless) 100 HFC-23
120 (1)
150
25
61
84 HFC-227ea
Low pressure cylinders
HFC-125
(welded) 108.4 (2)
127
180

NOTE 1: The high and medium pressure (seamless) cylinders filled with HFC-227ea and
HFC-125 are pressurised with dry nitrogen at 24 or 42 bar (at 20ºC).

NOTE 2: The low pressure (welded) cylinders filled with HFC-227ea and HFC-125 are
pressurised with dry nitrogen at 24 (at 20ºC), never at 42 bar.

NOTE 3: In the case of HFC-227ea and HFC-125 the cylinder banks are not to be fully
charged.

CYLINDER
CONTAINER DISCHARGE
VOLUME CHECK VALVE
VALVE HOSE
(litres)
61
67,5
80 FH-40HC 1 1/2”
RGS-MAM-40 VALAN-40-23
84 BSP
100
120
84
108,4
RGS-MAM-50 FH-50HC 2” BSP VALAN-50-125
127
180

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 16/112


1.1.4 SMS System (small spaces)

These systems are specially designed for small spaces, using only halogenated gases HFC-227ea
and HFC-125. It is a single (modular cylinder) design, as shown in Fig. 8 with an electrical and manual
discharge head.

0,3 MAX
ON ON
OFF OFF

227DM 227DM
Nº LOTE Nº LOTE
xxxxx xxxxx
LOT No. LOT No.

POSICION 1 : SIN POSICION 1 : SIN


POSITION 1: STA POSITION 1: STA

POSICION 2 : AC POSICION 2 : AC
POSITION 2: ACT POSITION 2: ACT
Atención: Antes de ros car el actuador eléctrico al puerto d Atención: Antes de roscar el actuador eléctrico al puerto d
Warning: Before threading the electrical actuator to the activ Warning: Before threading the electrical actuator to the activ

- 0786 - 0786
VdS VdS
G 307013 G 307013
227SOL 227SOL
24V (DC) 24V (DC)
0,6 A 0,6 A
Nº xx Nº xx

TPED TPED
1999/36/CE 1999/36/CE
Organismo Notificado/Notified body/Organisme Notifié Organismo Notificado/Notified body/Organisme Notifié
(0062) BUREAU VERITAS (0062) BUREAU VERITAS
Cilindro+Válvula+Disco de rotura+Elementos de protección Cilindro+Válvula+Disco de rotura+Elementos de protección
Cylinder+Valve+Bursting disc+Protections device Cylinder+Valve+Bursting disc+Protections device
Cylindre+Valve+Disque de rupture+Eléments de protection Cylindre+Valve+Disque de rupture+Eléments de protection
Nº de Serie Nº de Serie
Serial Number Serial Number
Nº de Série Nº de Série

- 0062 COMPRESSED GAS


NO INFLAMMABLE
- 0062 COMPRESSED GAS
NO INFLAMMABLE

AGENTE EXTINTOR AGENTE EXTINTOR


EXTINGUISH AGENT / AGENT EXTINCTEUR EXTINGUISH AGENT / AGENT EXTINCTEUR

Nº. DE CILINDRO Nº. DE CILINDRO


CYLINDER No. / Nº DE CYLINDER CYLINDER No. / Nº DE CYLINDER

PRESION DE CARGA A 20ºC PRESION DE CARGA A 20ºC


FILL PRESSURE AT 20ºC Bar FILL PRESSURE AT 20ºC Bar
E
D

TARA / TARE / TARE Kgs. TARA / TARE / TARE Kgs.


C

PESO TOTAL PESO TOTAL


Kgs. Kgs.
TOTAL WEIGHT / POIDS TOTAL TOTAL WEIGHT / POIDS TOTAL

FECHA DE CARGA FECHA DE CARGA


FILL DATE / DATE DE CHARGE FILL DATE / DATE DE CHARGE

TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC


WORKING TEMPERATURE FROM -20ºC TO 50ºC WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

POL. IND. VILLALONQUEJAR POL. IND. VILLALONQUEJAR


C/ MERINDAD DE MONTIJA Nº6 C/ MERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN 09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 2 Tel.: (34) 947 281108 Fax: (34) 947 2

S S
B

I I
E E
X
POLIGONO INDUSTRIAL
X
P OLIGONO INDUSTRIAL
VILLALONQUEJAR VILLALONQUEJAR
C/MERINDAD DE MONTIJA Nº6 C/MERINDA D DE MONTIJA Nº6
09001 BURGOS 09001 BURGOS

TEL.: (34) 947 28 11 08 TEL.: (34) 947 28 11 08


FAX.: (34) 947 28 11 12 FAX.: (34) 947 28 11 12

Figure 8. Single cylinder system (SMS system)

Nº Denomination Types
1 Cylinder 2,7 / 4,7 / 6.7 / 13.4
2 Instructions cylinder sticker
3 CE marking cylinder sticker
4 Modular cylinder bracket
5 PI marking cylinder sticker
6 Container valve RGS-MAM-11-4 ó 12-4
7 Re-assembled electrical actuator 227SOL
8 Manual actuator 227DM
9 Discharge hose FH-15CO ½”G-W21.7x1/14”
10 Discharge pipe 3/8” / 1/2" / 3/4"
FEDR10 / FEDR15 / FEDR20
11 Nozzle
(180º-360º)
12 Cupper washer Ø 16x22x1,4
13 Adaptor W 21,8x1/14” H – ½” BSP M
14 Nozzle FEDR15 (180º-360º)

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 17/112


The dimensions are shown in the following table:

CYLINDER
ØA B C D E
VOLUME
(mm) (mm) (mm) (mm) (mm)
(liters)
2,7 100 300 425 460 520
4,7 140 300 435 470 530
6,7 140 300 560 595 655
13,4 204 300 550 585 645

Cylinder size (l) Filling ratio (kg.) Filling ratio (kg.) Cylinder position Aproximated tare
HFC-227ea HFC-125 (kg)

2 1,0-2,0 1,0-1,5 Vertical-Horizontal 4,2

4,7 2,5-5,5 2,0-4,0 Vertical-Horizontal 10

6,7 3,5-7,5 4,0-6,0 Vertical-Horizontal 14

13,4 7,0-15,0 6,0-12,0 Vertical-Horizontal 26,8

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 18/112


1.2 DISTRIBUTION PIPING AND FITTINGS

This section refers to design by computer calculations or pre-engineered systems with pipework.
Examine the planned configuration to ensure that the pipework and nozzles do not interfere with
objects in the hazard area, and make any necessary changes before proceeding with the installation.
The pipework and fittings must comply with the limitations detailed below:

1.2.1 Piping

All the installed piping must be in accordance with the latest requirements included in NFPA-2001,
ISO-14520 or UNE-23570. They must be of non-combustible material, and have physical and
chemical characteristics that guarantee their integrity under the stresses to which they will be
subjected. For the wall thickness calculation we must take into account that they have to withstand a
pressure equal to that of the extinguishing gas when stored at 50ºC.

Working pressure at 50ºC with HFC-227ea (filled at 24 bar) 34 bar


(filled at 42 bar) 56 bar
Working pressure at 50ºC with HFC-125 (filled at 24 bar) 40 bar
(filled at 42 bar) 75 bar
Working pressure at 50ºC with HFC-23 137 bar

Acceptable piping includes galvanised or black steel to pipe Standard


ANSI B31.1. The types of pipe that must not be used are cast iron, steel pipes to ASTM A 120
specifications and all non-metallic pipes.

1.2.2 Pipe joints (fittings)

The mode of joining the pipes must meet the most recent requirements of the NFPA 2001, ISO 1450
or the UNE-23570. Acceptable accessories include those which are threaded, with bridles, soldered
high pressure grooved and those of brass.

Grooved accessories must be approved for Halocarbonated Gases (HFC-227ea, HFC-125, HFC-23)
applications and only those of high pressure in systems that use cylinders charged with 24 bar at 20º.

Common grooved accessories for sprinkler networks must not be used.

Wrought iron accessories must be a minimum of 300lb.


Standard cast iron accessories or those of 150 lbs are not acceptable.

Use threaded accessories of 3000 lbs according to regulation ANSI B.16.11.


Use soldered accessories of 3000 lbs according to regulation ANSI B.16.9.

1.2.3 Reducers

All reductions in the pipe size must be made using reducing fittings such as concentric reducers.
Double elbow reducers are not acceptable.

The system installation drawings (calculation software) must be taken as a reference for sizes and
lengths of pipes. The maximum pipe diameters and lengths indicated in this manual must be adhered
to.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 19/112


1.2.4 Cleaning

All pipe sections must be fitted and assembled with the appropriate sealants, e.g. Teflon tape or paste
(in the case of threaded pipe). All rough edges and residual oils must be removed afterwards.

1.2.5 Threads

It is recommended that Teflon tape be used, applied only to the male threads of the pipe. When Teflon
paste is used, impregnate at least one turn of the male thread and one of the female thread. The
threads of all the pipes and fittings must be properly sealed.

When 3000 lb fittings with NPT threads are used, ensure that the pipes also have NPT threads.

1.2.6 Installation

All piping must be installed in line with industry best practice. The pipework must be secured with
supports that allow for its expansion and contraction.

DISTANCES BETWEEN PIPE SUPPORTS


Pipe diameter
15 20 25 32 40 50 65 80 100 125
DN (mm)
Pipe diameter
1/2" 3/4" 1” 1 1/4" 1 1/2" 2” 2 1/2" 3” 4” 5”
(inches)
Maximum distance
between supports 1.5 1.8 2.1 2.4 2.7 3.4 3.5 3.7 4.3 4.8
(m)

• Supports must be located between elbows that are 600 mm apart (see figure A).
• Supports must be fitted 300 mm from any discharge nozzle (see figure B).
• Supports must be secured to structures capable of supporting the pipework.

Figure A Figure B

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 20/112


1.2.7 Approximate diameters
Pipes with a nominal diameter of less than 10 mm must not be used, except for specific applications.
Pipe sections that may be subjected to static pressure (closed sections) must be protected by a relief
valve (burst disc valve piped to atmosphere).

APPROXIMATE PIPE DIAMETERS


DEPENDING ON THE DISCHARGE CALCULATION FOR HFC-227ea
SYSTEMS FILLED at SYSTEMS FILLED at
PIPE DIAMETERS
24 bar a 42 bar
3/8” 0-8 kg. 0-11 kg.
½” 5-14 kg. 12-24 kg.
¾” 9-27 kg. 25-36 kg.
1” 15-39 kg. 36-47 kg.
1 ¼” 26-60 kg. 48-116 kg.
1 ½” 39-90 kg. 117-194 kg.
2” 60-150 kg. 195-310 kg.
2 ½” 90-260 kg. 311-480 kg.
3” 150-420 kg. 481-645 kg.
4” 260-570 kg. 646-780 kg.
5” 420-1000 kg.
6” 570-1400 kg.

APPROXIMATE PIPE DIAMETERS


DEPENDING ON THE DISCHARGE CALCULATION FOR HFC-125
SYSTEMS FILLED at SYSTEMS FILLED at
PIPE DIAMETERS
24 bar a 42 bar
3/8” 0-10 kg. 0-11 kg.
½” 6-16 kg. 5-18 kg.
¾” 11-27 kg. 14-31 kg.
1” 19-39 kg. 25-47 kg.
1 ¼” 34-60 kg. 39-112 kg.
1 ½” 47-90 kg. 88-145 kg.
2” 78-160 kg. 125-268 kg.
2 ½” 114-270 kg. 212-370 kg.
3” 180-440 kg. 296-564 kg.
4” 310-600 kg. 450-780 kg.
5” 480-1010 kg.
6” 710-1420 kg.

NOTE 1: The flow dependent diameters set out in the above table are only approximate and are for guidance only. They must
not under any circumstance be taken as final installation diameters. To determine the final installation diameter
hydraulic calculations must be carried out using the appropriate software.
Diameters may vary depending on the amount of extinguishing agent in the cylinder, the pipe runs, the length and
distance of pipe runs, etc.

NOTE 2: All halocarbonated gases systems (HFC-227ea, HFC-125, HFC-23) must discharge in a maximum of 10 seconds.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 21/112


1.2.8 Electrical clearances

Where electrical conductors are present, the minimum distances stipulated in the High Voltage
Regulations must be observed. Should it not be possible to comply with these distances, approved
insulators must be fitted to the pipes. It is recommended that the system pipework be earthed in order
to discharge any static electricity generated during the discharge of the extinguishing agent (HFC-
227ea, HFC-125, HFC-23).

SAFETY DISTANCES
Maximum Distance to closest non- To the closest part of an insulator not at earth
nominal voltage insulated live conductor potential used as a support for a live conductor.
(kV) (m) (m)
15 2.59 -
33 2.74 -
44 2.89 -
66 3.05 -
88 3.20 2.5
110 3.35 2.5
132 3.50 2.5
165 3.81 2.5
220 4.27 2.5
275 4.57 2.5

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 22/112


1.3 INSTALLING DISCHARGE NOZZLES, WITH OR WITHOUT A
CALIBRATED ORIFICE

FEDR type discharge nozzles for SIEX-HC fixed extinguishing systems using halogenated gases
(HFC-227ea, HFC-125 and HFC-23) are used to discharge the extinguishing agent within the
protected area and in systems for total flooding hazard protection (not used in local application
systems).

The extinguishing agent (halogenated gas) is dispersed within the protected area by discharge
nozzles, to ensure a proper dispersion of the extinguishing agent within the protected area.

The discharge nozzles are screwed into the discharge piping (DIN 2440, schedule 40 or 80) in a
vertical position, and can be 360º and 180º, with threads from 3/8” BSP to 2” BSP for halogenated
gases. In all cases the transverse nozzle diameter decreases in the direction of the flow, to avoid
obstruction of the nozzle by dry ice.

Normally, when the extinguishing agent is discharged through several nozzles in the risk area, the
same amount of gas is discharged through each nozzle. When it is necessary to discharge a different
amount of gas through each nozzle, a calibrated orifice plate must be fitted in each one.

The calibrated orifice is located inside the discharge nozzles in order to control exactly the amount of
gas to be discharged. As its name indicates, it is a circular plate with a central orifice calibrated
according to the hydraulic calculations (calculation software), and its size depends on the amount of
gas to be discharged through each nozzle. The diameter of the central calibrated orifice is marked on
the lower flat part of the nozzle. Its size is expressed in millimetres to one decimal place (for example,
12.2 mm) (see Figure 8), and corresponds to a value in the calibrated orifice tables for halogenated
gases.

Mark on the lower flat part of the nozzle with the


diameter of the central calibrated orifice
(is expressed in millimetres to one decimal place).

xx.x

Calibrated orifice according


to hydraulic calculations.

1 NOZZLE
2 CALIBRATED ORIFICE

df022ci1.dwg

Figure 9

The calibrated orifices must always be fitted into every nozzle that are connected to cylinders or banks
of cylinders that have more than one nozzle to protect one or several hazard areas. In modular
cylinders with a single nozzle, it is not necessary to use a calibrated orifice. Nor are they necessary in
pre-engineered and balanced systems with 2 or 4 nozzles, provided that the distances and
requirements of those systems are complied with.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 23/112


The calibrated orifices are supplied from the factory assembled in the corresponding nozzles, which
are marked with the diameter of the calibrated orifice (see Figure 9).

The discharge nozzles, with or without a calibrated orifice, are connected directly to the discharge
pipe:

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 24/112


CAUTION

TO AVOID UNNECESSARY RISKS


IT IS ADVISABLE TO INSTALL THE DISCHARGE NOZZLES
BEFORE ASSEMBLING THE CYLINDERS OR CYLINDER BANKS.

OTHERWISE,
ENSURE THAT THE RELEASE AND ACTUATION ELEMENTS
ARE DISCONNECTED OR NOT IN USE.

1 CYLINDER
2 DISCHARGE PIPE
3 NOZZLE

df001ci3.dwg

Figure 10

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 25/112


1.3.1 Installation instructions:

To install the nozzles, with or without a calibrated orifice, the instructions below must be followed:

1. Take the installation drawings and study the positioning of the nozzles in the hazard area.
Check that there are no light objects or items that are susceptible to move during the gas
discharge.

2. Check that the number and size of nozzles supplied agrees with the approved installation
plans. If they are to be fitted with calibrated orifices, check that they are suitable for the
nozzles in which they are to be fitted.

3. Check that the pipe rises and drops where the nozzles are to be screwed in are at the correct
distance and in optimum condition.

4. Check that the bottom surfaces of the pipe rises and drops are totally flat and perpendicular to
their axes. The threaded length of the pipe must be greater than that of the nozzle (see figure
8).

The threaded length of the


pipe must be greater than
that of the nozzle
3 3
Surfaces of the pipe rises and
drops are totally flat and
perpendicular to their axes 1 Nozzle
2 2 Calibrated orifice 2
3 PIpe
1

df022ci2.dwg

Figure 11

5. Apply Teflon tape to the male thread of the pipe drop where the nozzle is to be fitted.

6. Hold the nozzle by hand and fit the calibrated orifice in its seat (if one is to be fitted). Check
that the diameter of the central calibrated orifice is marked on the lower flat part of the nozzle.

7. Screw in the nozzle (with its orifice if appropriate) with a fixed width spanner on the pipe drop
or pap. Tighten fully until the pipe drops touch the calibrated orifices, so that they are
completely screwed in and the plate is firmly fixed.

1.3.2 Positioning the installed nozzle

The usual position of the installed nozzle is vertical, as shown in Figure 10 and 11.

When positioning the nozzle in the discharge pipe, the assembly steps above must be followed, while
ensuring that it is free of any obstacles which could impede the proper discharge of the extinguishing
agent.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 26/112


CEILING

0,3 MAX

ON
OFF

K:\ SIEX-s i st e ma s d e e x tn
i co
i n \ Bib o
il t e ca \ Blo q u e
s\ m
i agene
s \ SIEX.b m p

227DM
Nº LOTE xxxxx
LOT No.

227SOL-A
24V (DC)
0,60 A
Nº xx

RGS-MAM-20 K :\ IE
S X si- te m
a sd e xe n
ti co
i n
\B b
i o
il te
c a
\ o
lB q
u e
s m
\i g
a e n
e s\S E
X
I b
m
. p

EN 12094-4

30
20 40

10 50
bar
0 60

KL. 1.6

K :\S IE
X -s ste
i m
a sd e
x n
ti co
i \B ib
n l o
c a
te \B o
l u
q s m
e \i a
g e
s \S IE
n X .b
m p
TPED
1999/36/CE
Org anis mo Notif icado /Not ified body /Orga nisme Not fi é
i
(0062) BUREAU V ERITA S
Cilindro+Válvula+Di sco de rotura+Elementos de protección
Cyli nder +Val ve+Bur sting disc+Pr otections dev ice
Cylin dre+ Valve+ Disqu e de ru ptur e+Eléments depr otection
Nº de Serie
Ser ial Num ber
Nº de S ér ie

- 0062 CO MPRESSED GA S
NO INFLA MMA BLE

AGENT E EXTINTOR
EXTING UISH A GENT / AGENT EXTI NCTEUR

Nº. DE CILINDRO
CYLIN DER No . / Nº D E CYLIN DER

PRESION DE CARGA A 20ºC


FI LL PRESSU RE AT 20º C Bar
PR ESSION DE CHA RGE A 2 0ºC

PRESION RO TURA DISCO SEGURIDAD


BUR STI NG P RES SUR E OF T HE SAFE TY DISC Bar
PR ESSION DE R UPTUR E DU DISQUE DE SÉ CUR ITÉ

CARGA / FILL / CH ARGE Kgs.

PRESURIZADO CON
PR ESS URIZED WHI T / P RESS URI SÉ AU

TARA / TARE / TAR E Kgs.

PESO TO TAL
Kgs.
TOTAL WEI GHT / PO IDS TOTAL

F ECHA DE CARGA
FI LL DATE / DATE DE CH ARGE

T EMPERATURA DE FUNCIONAMIENT O DE -20ºC A 50ºC


WORK ING TEMPERATU RE FRO M -2 0º C TO 50º C
TEMPÉRATURE D E FO NCTIO NNEMENT DE -20 ºC A 5 0ºC

POL. IND. VILLALONQ UEJAR


C/ MERINDAD DE MONT IJA Nº6
09001 (BURGOS) - SPAIN
T el.: (3 4) 947 281108 F ax: (34) 947 281112

S
I
E
X
POLIGO NO IND USTRIAL
VILLALONQ UEJAR
C /M ERIN DAD DE M ONTIJA Nº6
09001 BUR GOS

TEL. : 9 47 28 1 1 08
FAX. : 9 47 2 8 1 1 12

Figure 12

As shown in Figure 12, it must be remembered that the two types of nozzle, 360º and 180º, can be
fitted at a maximum of 0.3 m below the ceiling (or the highest protected point when the nozzles are
stacked).

180º nozzles can be located at a maximum of 0.3 m from the wall, special attention must be paid to
the fitting of the 180º nozzle, that it is in the correct position for its effective operation, with the orifices
facing out and not towards the wall, as shown in Figure 11.

360°

180°

Figure 13

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 27/112


1.4 INSTALLING THE CONTAINER, CYLINDER OR BOTTLE

CAUTION

YOU ARE HANDLING PRESSURISED EQUIPMENT


FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN
THE CYLINDERS DISCHARGING VIOLENTLY,
LEADING TO SERIOUS PERSONAL INJURY
AND/OR DAMAGE TO THE PROPERTY.

From the factory, all cylinders assembled with valves are protected with caps and protective plugs for
transport, which must not be removed until the cylinders have been securely fixed to their fixing
brackets (keep the protective caps for future use).

All cylinders are sent from the factory assembled with a protective flange, with its corresponding
cylinder valve, RGSRGS-MAM-20/40/50/12-4 or 11-4, together with the cylinder stickers marked with
CE, PI and cylinder instructions, with the valve outlet safety plug in place, and with the protective cap
screwed into the flange.

The cylinder valve itself comes equipped with a pressure gauge, the burst disc and its end cap, the
valve outlet safety plug in the actuation port, and those corresponding to the pilot port and pressure
switch connection, if these components are not connected.

The cylinders must be located in an area protected from extreme temperatures and accessible for
service and maintenance. The cylinder must be firmly secured to a wall.

CAUTION

DO NOT REMOVE THE CYLINDER PROTECTIVE CAPS


UNTIL IT IS FIXED IN ITS BRACKETS, THE CYLINDER MUST ONLY
BE MOVED WITH ITS VALVE PROTECTIVE CAP IN PLACE
UNTIL IN ITS FINAL POSITION.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 28/112


ON O FF

x
227DME x xxx
OT
Nº L No.
L OT

7 SOLP
22 V(DC)

xx
24 0 A
1

0,6

837-
E N

ba r

. 1.
16
.
KL
KL

fié fié
PE D
T me
Noti
ció
n
T PE
D
nisme
Noti
ción
protec
nis ec
9/36/CEody/ Orga e prot 9/36/CEody/ Orga
199 o tifi ed b VER IT AS s d ice 199 o tifi ed b VERI TASos de ice
/N sdev /N enton sdev
Elementoon
ti fic BUREAU +Elem
ado ado
ti fic BUREAU Protecti Protecti
No otura+
r d isc+ No roturad isc+
ni smo (0062)o de ni smo (0062)o de
sc Bursting
la+Di
Orga Bursting Orga
a+Disc
v ul
lin der+
Valve+
V álvu der+ Valve+
ro+VálCy e dro+ Cy lin e er
Cilind Seri
Nº a l Numb
er Cilin Nº SeriNumb
al
S eri S eri

2 2
- 006 - 006

S. S.
MESE MESE
S (6) S (6)
SE I SE I
DA DA
S CA S CA
E NO E NO
AL M AL M
RO S RO S
C LI
I ND C ILI ND
LOS LOS
DE : DE :
ESO DR O ESO DR O
E LP .
LIN E LP .
LIN
SY UC TO EL CI SY UC TO EL CI
TR O RO D EN TR O RO D EN
N OME LP QU
E
N OME LP UE
MÁ LD E I DO
MÁ LD E I DO TA Q
LOS UA CO N
TEN H A STA ES LOS UA CO N
TEN H AS ES
N EN R AL
MAN CT O RC I A) T APO N ) N EN IC IO . R AL
MAN CT O RI C A) T APO N )
SI Ó IC IO . UD I DU E FAB CO N RT E. SI Ó UD I DU FAB N RT E.
PR E RV , AC PR O NS PO PR E E SE RV , AC PR O DE CO NS PO
LA E SE D EL DE SDN DR OS LA D EL D ES N DR OS
I CA AL D S IS TEMA ES IS TRO SC ILI LT RA I CA A NU AL
D
S IS TEMA ES RO ILI T RA
I OD MA NUA 50ºC. TAL MI N AE 46ºC. ULA I OD TAL NI ST SU SC A EL 46ºC.
P ER AL TO D
EL IÓN D EN (SU DO S
SU PAR R DE A VÁLV P ER IR A L 0ºC A
M 50ºC.
TO D
EL IÓN D EN (S UMI DO S P AR ER D E V ÁLV ULA
MA D IR D E 0ºC MI EN AC CI CI AL P IA DO CE DE AC CI C I AL A DO
F OR A CU NI T ALAC AS IN I
TO
PR O
L MA
F OR N A CU JE: D
D E MI EN T ALAC AS IN I
TO OP I E XC ED I RÁ LA
DE I ÓN CE NA JE: MAN TE INS AR G C IÓ N E N OR
IG EN
IO A A EX RI RÁ TE NI INS AR G CI ÓN E N OR
IG EN A PR DA
B AR A Y LA DE SC U ED Ó N AB S) DE I Ó CE NA MAN LA DE SC DI O UE N ABR S)
RO FO RMAC AL M C IÓ N DE BI CA MED RA P CI AJE DO B AR
RO IN FO RMAC MA NY DE BI CA ME RA P C CI Ó AJE A DO
C OMP S IN DE ES E VI
TAR SU U MIN IS TRA R UN RA TU ST A AC HE RR O FI AJ E AL ZA C IÓ ES E VI
TAR SU U MIN IS TRA R UN RA TU STA A HE RR D O FI J
LIZA ANT DE TILI ZA E SU S SI D C OMP MÁ S RA D LI ANT DE ILI ZA MPE Q UE E SU S
RA MÁRA TU RA , U TI S PA
RA R AS S IE X SU . (U LA T EMPETO Q UE E. (A H A YA RA RA TU , U TI S PA
RA RA S S IE X SU . (UT LA TE O
SI
PA SE ÑO C IA TO . PA SE ÑO C IA TO . E. (A H A YA
T EMPE EL DI CILINDROS ER TEN O TEC RI D AD VE RLO N DE , PU ES NT
ME Q U E NO T EMPE EL DI CILINDROS ER TEN O TEC RI D AD VE RLO ND E , P U EST ME NT E NO
RA L OS A DV AS PR S EG U MO
LO Ó A RE S I LIN DR
DO O ER TE RA L OS A DV
PR
ZA S N S EG
U MO
LO Ó AR E S IL IN DR
DO O ER TE QU
PA DE ER UZ C O N FU STA PA FU STA
NT ES IR AR LU G DE LC JET O RO HA A. DE NT ES CA PE S C
RU O IR AR LUG D EL C JET O RO HA A. N
U IE Y C AP OS A G L ÓE N A É SU LI ND SC ARG E EN U IE S Y IJA D O AG EN SU ND ARG EE
MANEJO S IG ES F IJA D RO PARE LS O V ÁLV UL U E EST D EL CI D E DE . MANEJO S IG PAR S OL Ó ÁLV ULA EST É CI LI E DE SC . ME NT
LAS PO N N TO AD AMENT LAS PO NE N F D RO EL V Q U E LA D EL ÍA D TO DA
GU I R S TA E STE S. LI ND B AJO D E LA Q LA ÍA IM I EN DEC U GU I R S TA E STE S. LIN BA JO D E LA IM I EN EC UA
SE LO NO ULA EL CI S L S ER VÁ LVU T UB ER EN A SE LO NO ULA EL CI S L S ER VÁ LVU T UB ER EN AD
IT AR O S ÁLV LA D ND RO UA A NO A LA MA NT R AD OS IT AR O S ÁLV LA D N D RO A N UA A NO A LA MA NT RA DO S
QU DR EV LVU LI MAN TE , ÓN A L OA OY U QU DR EV VU LI M TE , ÓN A L OA OY U
1-NO C IL IN R ES D LA VÁ LO S CI AR O MEN CI TAD E NT A SE G 1-NO C IL IN R ES D L A VÁL LO S CI AR O MEN CI C TAD E NT A SE G
LO S TE CT O LI ZAR A DI SP NTA TI VA NE C NA MI ÉN S TEMA. LO S TE CT O LI ZAR U NC A DE D I SP LE NTA AC TI VA CO NE NA MI ÉN IS TEMA.
TI NU NC A D E D O VI LE D E AC ÓN Y CO O C IO NO EST D EL SI IA S
I LAS TI N A VI E Y O C IO NO E ST DE LS IA S
I LAS
P RO CA U EN AR NC NI TO CI NT F UN S AS P RO CA U EN AR NC NDI O TO D CI ÓN ENT F UN S AS

S S
UN P ALA O NTE MEN S UJE IÓ N, N D RO UB ER Í EC U
ENC UN P ALA O NTE MEN S UJE IÓ N, N DR O UB ER Í EC U
ENC
2-N A LMAC R LA C ST RU DE ONAMIE TAL AC CI LI T FR S. 2-N A LMAC R LA C ST RU DE ONAMI TAL AC S C I LI T FR S.
3-NO A CTI VA AR Á SU Ú N IN R AJE S UNCI IN S E LO S RE D DE YO R UI DO 3-N O AC TI VA AR Á SU Ú N IN R AJE S UNCI IN S LO D DE YO R UI DO
O AR G Y F ÑO , U ON MA OB STR . O AR G YF ÑO , Q U E A RE ON MA OB STR .
4N - SC AR NI LOS
NG H ER ÓN DI SE AQ A LA OC 4N - AR NI LOS
NG H ER ÓN DI SE AL OC
Y DE O LOC A ACI D E N HA ST RA D A TÉN NA DO A, SC
Y DE O LOC AC I D E N HA STA RA DA TÉN NA DO A,
C NT E AL L SI EX CI Ó A SE GU C LUS O ES AT UR NT E
A AL L SI EX CI Ó A SE GU C LUS O ES AT UR
5-NO INST UA VA O IN E N D E LLE MPER C
INST O IN E N D E LLE MPER
TEME MAN E AC TI A ES TÁ NT E R QU SO TE 5-NO TEME UA
MAN E AC TI A ES TÁ
VA NT E R QU SO TE
FU ER DE ME O BA S U PE DE FU ER DE ME O BA S U PE DE

I I
AL D SU AL TE S AL D SU AL TE S
IONES U DI R NI SMO ES CA RG OMPR D E U DI R NI SMO ES CA RG OMPR D E
RUCC , AC D S MEN A C N 5 % A A JUS RUCCIONES LAR , AC ME CA D E D S MEN A C N 5 % A A JUS
LAR ME CA N DE NA DO S P AR EU NA DO S P AR EU
INST I NS TA N IN G ÚN NE XI Ó C IO AD O MÁS D N, D EB
I DO
. IN ST I NS TA N N ÚN ÓN C IO AD O MÁS D N, D EB
I DO
DE O EC MIN N Ó Ó
I N DE I G O NE XI EC MIN N Ó IÓ N
.
TE S CT AR Y L AC IN SP E XA I ER DE PR ESI FI JAC TE S CT AR Y LA C IN SP E XA I ER DE PR ESI FI JAC
AN CO NE SE R S ER SI P DE AN C O NE SE R S ER SI P DE
NO RA JES Á N RE N. RÍ AN A DO S B AJA
SU
O. JES NO RA JES Á N RE N. RÍ AN A DO S B AJA
SU
O. JES
H ER E BER QU IE BE G SI AD H ER
RA H ER E BER QU IE BE G SI AD H ER
RA
L OS OS D L O RE RE S DE R EC AR AD O S LL EN L OS N: C. ) LO S OS D L O RE RE S DE R EC AR AD O S LL EN L OS N: C. )
L IN DR CI AS I FUS O R A RG MA L DE R, ET L IN DR CI AS I FUS O R A RG MA L DE R, ET

E E
SCI AN D A N SE R EC R O DE OR DE SO SCI A N SE R EC R O DE OR DE LO SO
L O CU ST Y LOS ER Í OR ILI ND NT E A, EX PLO L O CU ST Y LOS
AN D
ER Í OR ILI ND NT E ,E XP
S ER Ó N N EL C SI GU IE S ER Ó N N EL C SI GU IE
C IR S S D EB ER ÁN PR ES I , BO B
IN C IR S S D EB ER ÁN PR ES I O
, BO BI
NA
TU BO ND RO D EB LA IT AR EL TU BO ND RO D EB IT AR EL TO
LO CI LI R OS DE CILINDRO D E QU N C ON , PI LO TO LO CI LI R OS DE
LA CILINDR D E QU N C ON PI LO
LO S CI LI ND 10% DEL
NT ES TU AC
IÓ I DE LO S CI LI ND 10% DEL
NT ES TU AC
IÓ ID E,
S UN ICIO ES A LE NO S UN ICIO ES A LE NO
LO S DE NT S D E AC LA S O LO S DE NT S D E AC LA SO
EN MÁ DE
SERV GU IE O EN MÁ SERV GU IE O
S SI AN SI M O (VA LVU TI CO . GA . DE S SI AN IS M O (VA LVU TI CO . GA .

X X
DA . .
IRA PA SO MEC IC Á IC O AR DA
PA SO MEC IC MÁ IC O AR
RET LO S OS TR - N EU M UMÁT D ESC RET
IRA
LO S L OS ÉC TR - N EU NE UMÁT DE D ESC
U I R I TAR L E E LÉC U AL O NE BO S DE UIR E EL U AL PAR O TU BO S
SE G U DO PAR TU SE G QU I TAR UA DO
1-Q A C TUA DO R MAND E D IS LOS Ó 1- A CT MAN
DO R S D E D IL LOS
IS Ó
a) S IL
CT UA LLO IG U . a) CT UA LLO IG U .
RIAL b) A TI GU I S LAT ULA RIAL b) A TI GU I S LAT ULA
IN DUST 6 LA LO V ÁLV IN DUST º6 LA LO V ÁLV
QUEJARTIJ A Nº c) AR LA UEJARTIJ AN c) AR LA
GO NO TI R ZA A GO NO TI R ZA A
POLI VI LLALONDE MON 2-RE PE RU POLI VILL ALONQ DE
M ON 2-RE PE RU
AD BUR GOS NDA D BUR GOS
ND
I L A CA L A CA
C/ MER 09001 11 08 2 ON ER C/M ERI 09001 11 08 2 ON ER
28 1 28 1
947 28 1 1 3-P 9 47 28 11 3-P
TEL.: 9 47 TEL.: : 94 7
FAX.: FAX.

ci005ci1.dwg

No cover or external operating device should be removed at this stage.

Safeti cup on the


valve outlet

PELIGRO :

0062 ESTO ES UN CONTENEDO R DE ALTA


NO QUITAR LOS ACCESORIO S,
MANIPULARLO HASTA QUE ESTE BIEN
MEDIANTE SUS HERRAJES.

P E LIGRO:

0062 ES TO E S UN CONTE NEDOR DE ALTA


NO QUIT AR LOS ACCE SORIOS ,
MA NIPULARLO HAS TA QUE E ST E B IEN
M EDIA NT E S US HERRAJES .

2 2

TPED TPED
1999/36/CE 1999/36/CE

Cylinder+Valve+Bursting disc+Protections device Cylinde r+Valve+Bursting disc +Prote ctions device


Cylindre+Valve+Disque de rupture+Eléments de protection Cylindre+Valve+Disque de rupture+Eléments de protection

Serial Number Serial Number


Nº de Série Nº de Série

POSICION DEL CILINDRO / CILIN DER POSITIONING / POSITION DE LA BOUTEILLE POSICION DEL CILINDRO / CILIN DER POSITIONING / POSITION DE LA BOUTEILLE
W ALL /M UR

W ALL /M UR

M anom etro hacia arri ba M an om etro hacia arri ba


Upw ard s pressure gauge Upw ard s pressure gauge
Jau ge de l a hausse Jau ge de l a hausse

M an ometro hacia abaj o M an ometro hacia abaj o


Down wa rds p ressure gau ge Down wa rds p ressure gau ge
Jau ge à Jau ge à
F LOO R / FL OO R /
SO L SOL
FALSO SUELO / SU B-F LOOR /FA UX SOL AM BIENTE / HA ZA RD / E NV IR ONN EMEN T FALSO TECHO / SUB -C EI LI NG / F AUX PLA FOND FALSO SUELO / SUB -F LOOR / FA UX SOL AM BIENTE / HA ZA RD / E NV IR ONN EMEN T FALSO TECHO / SU B-C EI LI NG / F AU X PLA FOND

No ta: Marque con u na X el que proceda / Note: Tic k whit a X the c orre ct one / Note: Me ttre le cas éché ant X No ta: Marq ue con u na X el que proceda / Note : Tic k whit a X the c or re ct one / Note: Me ttre le c as échéa nt X

- 0062 COM PRESSE D GA S


NO INFL AMMABL E
- 0062 COMP RE SSE D GAS
NO INFL AMMABL E

EXTINGUISH AGENT / AGENT EXTINCTEUR EXTINGUISH AGENT / AGENT EXTINCTEUR

CYLINDER No. / Nº DE CYLINDER CYLINDER No. / Nº DE CYLINDER

FILL PRESSURE AT 20ºC FILL PRESSURE AT 20ºC


PRESSION DE CHAR GE A 20ºC PRESSION DE CHAR GE A 20ºC

BURSTING PRESSURE OF THE SAFETY DISC BURSTING PRESSURE OF THE SAFETY DISC
PR ESSION DE R UPTURE DU DISQUE DE SÉCURITÉ PR ESSION DE R UPTURE DU DISQUE DE SÉCURITÉ
FILL / CHARGE FILL / CHARGE

PRESSURIZED W HIT / PRESSURISÉ AU PRESSURIZED W HIT / PRESSURISÉ AU

TARE / TARE TARE / TARE

TOTAL WEIGHT / POIDS TOTAL TOTAL WEIGHT / POIDS TOTAL

FILL DATE / DATE DE CHARGE FILL DATE / DATE DE CHARGE

WORKING TEMPERATURE FR OM -20ºC TO 50ºC WORKING TEMPERATURE FROM -20ºC TO 50ºC


TEMPÉRATURE DE FONC TIONNEMENT DE -20ºC A 50ºC TEMPÉRATURE DE FONC TIONNEMENT DE -20ºC A 50ºC

COMPROBAR DE FO RMA PERIODICA LA PRESIÓN EN LOS MÁNOMETROS Y EL PESO DE LOS CILINDROS AL MENO S CADA SEIS (6) MESES. COMPROBAR DE FO RMA PERIODICA LA PRESIÓN EN LOS MÁNOMETROS Y EL PESO DE LOS CILINDROS AL MENO S CADA SEIS (6) MESES.
PARA MÁS INFO RMACIÓN ACUDIR AL MAN UAL DE SERVICIO. PARA MÁS INFO RMACIÓ N ACUDIR AL MANUAL DE SERVICIO.
TEMPERATURA DE ALMACENAJE: DE 0ºC A 50ºC. TEMPERATURA DE ALMACENAJE: DE 0ºC A 50ºC.
PARA EL DISEÑ O, UTILIZACIÓN Y MAN TENIMIENTO DEL SISTEMA, ACUDIR AL MANUAL DEL PRODUCTO . PARA EL DISEÑ O, UTILIZACIÓN Y MANTENIMIENTO DEL SISTEMA, AC UD IR AL MANUAL DEL PRODUCTO.

M AN EJO DE LOS CILINDROS ANTES DE LA INSTALACIÓN M ANEJO DE LOS CILINDROS ANTES DE LA INSTALACIÓN

S S
SEG UIR LAS SIGUIENTES ADVERTENCIAS PARA EVITAR DESCARG AS ACCIDENTALES D EL PRO DUCTO CONTENIDO EN EL CILINDRO: SEG UIR LAS SIGUIENTES ADVERTENCIAS PARA EVITAR DESCARG AS ACCIDENTALES D EL PRO DUCTO CONTENIDO EN EL CILINDRO:

1 -NO Q UITAR LOS TAPONES Y C APERUZAS PRO TECTO RAS D E SU UBICACIÓ N INICIAL (SUMINISTRO D ESDE FABRICA) HASTA QUE LOS CILINDROS NO 1-N O Q UITAR LOS TAPON ES Y CAPERUZAS PROTECTO RAS DE SU UBICACIÓN INICIAL (SUMINISTRO DESDE FABRICA) HASTA QUE LO S CILINDROS NO
ESTEN FIJADOS CO N SEGURID AD. SIEX SUMINISTRA EN O RIG EN TO DOS SUS CILINDRO S CON TAPO NES PROTECTORES DE VÁLVULAS. ESTEN FIJADOS C ON SEGURIDAD. SIEX SUMIN ISTRA EN ORIG EN TO DOS SUS CILINDRO S CON TAPONES PROTECTO RES DE VÁLVULAS.
2-NUNCA UTILIZAR LA VÁLVULA DEL CIL INDRO PARA GIR ARLO Ó MOVERLO . (UTILIZAR UN MEDIO APROPIADO PARA EL TRANSPORTE.) 2-NUNCA UTILIZAR LA VÁLVULA DEL CIL INDRO PARA GIR ARLO Ó MOVERLO . (UTILIZAR UN MEDIO APROPIADO PARA EL TRANSPORTE.)
3-NO ALMACENAR NUNCA LOS CILINDROS BAJO EL SOL Ó EN LUG ARES DONDE LA TEMPERATURA PUEDA EXCEDER DE 46ºC. 3-NO ALMACENAR NUNCA LOS CILINDROS BAJO EL SOL Ó EN LUG ARES DONDE LA TEMPERATURA PUEDA EXCEDER DE 46ºC.

I I
4-NO ACTIVAR LA PALANCA DE DISPARO MANUAL DE LA VÁLVULA DEL CILIN DR O, PUESTO Q UE ESTA ACCIÓN ABRIRÁ LA VÁLVULA Y DESCARGARÁ 4-NO ACTIVAR LA PALANCA DE DISPARO MANUAL DE LA VÁLVULA DEL CILIN DR O, PUESTO Q UE ESTA ACCIÓN ABRIRÁ LA VÁLVULA Y DESCARGARÁ
SU CO NTEN IDO VILENTAMENTE, A NO SER Q UE ESTÉ SUJETO FUERTEMENTE. (A SUS HERRAJES) SU CO NTEN IDO VILENTAMENTE, A NO SER Q UE ESTÉ SUJETO FUERTEMENTE. (A SUS HERRAJES)
5-NO COLOCAR NING ÚN INSTRUMENTO DE ACTIVACIÓN A LA VÁLVUL A DEL CILINDRO HASTA QUE N O HAYA SIDO FIJADO FUERTEMENTE A LOS 5-NO COLOCAR NING ÚN INSTRUMENTO DE ACTIVACIÓN A LA VÁLVUL A DEL CILINDRO HASTA QUE N O HAYA SIDO FIJADO FUERTEMENTE A LOS
HERRAJES DE SUJECIÓN Y CONECTADO A LA TUBERÍA DE DESCARGA. HERRAJES DE SUJECIÓ N Y CONECTADO A LA TUBERÍA DE DESCARGA.

INSTRUCC IONES DE INSTALACIÓN Y FUN CIONAMIENTO INSTRUCC IONES DE INSTALACIÓN Y FUNC IONAMIENTO

E E
ANTES DE INSTAL AR, ACUDIR AL MANUAL SIEX DE DISEÑO , INSTALACIÓ N, FUNCIO NAMIENTO Y MANTENIMIENTO. ANTES DE INSTAL AR, ACUDIR AL MANUAL SIEX DE DISEÑO , INSTALACIÓ N, FUNCIO NAMIENTO Y MANTENIMIENTO.
NO CONECTAR NINGÚN MECANISMO DE ACTIVACIÓ N HASTA QUE LOS CILINDRO S NO ESTÉN ASEGURADOS ADECUADAMENTE EN LO S HERRAJES Y NO CONECTAR NINGÚN MECANISMO DE ACTIVACIÓ N HASTA QUE LOS CILINDRO S NO ESTÉN ASEGURADO S ADECUADAMENTE EN LOS HERRAJES Y
LA CONEXIÓ N DE DESCARG A ESTÁ ASEGURADA A LA RED DE TUBERÍAS DEL SISTEMA. LA CONEXIÓN DE DESCARG A ESTÁ ASEGURADA A LA RED DE TUBERÍAS DEL SISTEMA.

LOS CILIN DR OS DEBERÁN SER INSPECCIO NADO S MENSUALMENTE O INCLUSO CON MAYOR FRECUENCIA SI LAS CIRCUSTANCIAS LO REQUIEREN. LOS CILINDRO S DEBERÁN SER INSPECCIO NADO S MENSUALMENTE O INCLUSO CON MAYOR FRECU ENCIA SI LAS CIRCUSTANCIAS LO REQ UIEREN.
LO TUBOS Y LO S DIFUSORES DEBERÍAN SER EXAMINADOS PARA COMPR OBAR Q UE NO ESTÉN OBSTRUIDOS. LO TUBOS Y LO S DIFUSORES DEBERÍAN SER EXAMINADOS PARA COMPRO BAR Q UE NO ESTÉN OBSTRUIDOS.

X X
LOS CILIN DR OS DEBERÍAN SER RECARG ADO S SI PIERDEN MÁS DE UN 5 % DE SU PESO DE LLENADO. LOS CILINDRO S DEBERÍAN SER RECARG ADOS SI PIERDEN MÁS DE UN 5 % DE SU PESO DE L LENADO.
LOS CILIN DR OS DEBERÁN SER RECARGADOS SI BAJA SU PRESIÓN , DEBIDO A AJUSTES DE TEMPERATURA, EN MÁS DE UN 10 % DE LA PRESIÓN LOS CILINDRO S DEBERÁN SER RECARGADOS SI BAJA SU PRESIÓN, DEBIDO A AJUSTES DE TEMPERATURA, EN MÁS DE UN 10 % DE LA PRESIÓN
NORMAL DE LLENADO . NORMAL DE LLENADO.

R ETIRADA D E SERVICIO DEL CILINDRO R ETIRADA DE SERVICIO DEL C ILINDRO

POLIGONO I NDUS TR IAL


SEG UIR LOS PASO S SIGUIENTES ANTES DE QU ITAR EL CILINDRO DE LO S HERRAJES DE FIJACIÓN. POLIGONO I NDUS TR IAL
SEG UIR LOS PASO S SIGUIENTES ANTES DE QU ITAR EL CILINDRO DE LO S HERRAJES DE FIJACIÓN.
GAMONAL - VI LLI MAR 1-QUITAR LO S MECANISMOS DE ACTUACIÓN CON EL SIGU IENTE ORDEN: GAMON AL - VILLI MAR 1-QUITAR LO S MECANISMOS DE ACTUACIÓN CON EL SIGU IENTE ORDEN:
NAV ES C OR REA - N AVE C -4 NAV ES C OR REA - N AVE C -4
a) ACTUADOE ELÉCTRICO (VALVUL A SO LENO IDE, PILO TO,BO BINA,EXPLO SO R,ETC.) a) ACTUADOE ELÉCTRICO (VALVUL A SO LENO IDE, PILO TO,BO BINA,EXPLO SO R,ETC.)
09007 BUR GOS 09007 BUR GOS
b) ACTUADO R MANUAL - NEU MÁTICO. b) ACTUADO R MANUAL - NEU MÁTICO.
TEL.: 947 28 11 08 c) LATIG UILLO S DE DISPARO NEUMÁTICO . TEL.: 947 28 11 08 c) LATIG UILLO S DE DISPARO NEUMÁTICO .
F AX.: 947 28 11 12 2-RETIRAR LOS LATIG UILLOS Ó TUBOS DE DESCARGA. FAX.: 947 28 11 12 2-RETIRAR LOS LATIG UILLOS Ó TUBOS DE DESCARGA.
3-PONER L A CAPERUZA A LA VÁLVULA. 3-PONER L A CAPERUZA A LA VÁLVULA.

Figure 14. Valve protective cap and output safety plug

1.4.1 Identification labels

With each delivery, SIEX supplies adhesive labels on each cylinder supplied. This label identifies the
gas contained in the cylinder, the gas quantity, weight of the empty cylinder, working pressure,
identification number of the cylinder and fill date, regular inspection date, fill capacity, minimum
cylinder wall thickness, type of cylinder thread, country of origin UN number, manufacturing serial
number, product identification number, etc.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 29/112


PELI GRO:

0062 ESTO ES U N CO NTENEDO R DE AL TA


NO QUITAR L OS ACC ESORIO S,
MANIPUL ARLO HASTA Q UE ESTE BI EN
MEDIA NTE SU S HERRAJES.

TPED
1999 /36/CE
Orga nis mo Notifica do /N otified b ody /Orga ni sme Notifié
(0062) BUREAU VERITAS
Cilindro+V álvula+Disco de ro tura+Ele mentos de pro tección
C ylin der+Valv e+Bu rsting disc+Protectio ns device
Cy lind re+Valv e+Disque de ru pture+Elémen ts d e pr otection
Nº d e Serie
Ser ial Numb er
Nº de Série

1 Cylinder instruction label


2 Cylinder label with CE marking
3 Cylinder position label
- 0062 C OM PR ESSED GAS
N O IN FLA MMA BLE

AGENTE EXTINTOR
EXTINGUISH AGENT / AGENT EXTINCTEUR

Nº. DE CILINDRO
CYLINDER No . / Nº DE C YLINDER

P RESION DE CARGA A 20ºC


FILL PR ESSUR E AT 20ºC Bar
PR ESSION DE C HARGE A 2 0ºC

P RESION ROTURA DISCO SEGURIDAD


BURS TING PRES SURE OF THE SAFETY DISC Bar

4 Cylinder label with PI marking


PRESS ION DE RUPT URE DU DISQUE DE SÉCURITÉ

CARGA / FILL / CHARGE Kgs.

P RESURIZADO CON
PR ESSUR IZED WHIT / PRESSURISÉ AU

TA RA / TARE / TARE Kgs.

P ESO TOTAL
Kgs.
TOTAL WEIGHT / POIDS TOTAL

FECHA DE CA RGA
FILL DATE / DATE DE C HARGE

TEMPERATURA DE FUNCIONAMI ENTO DE -20ºC A 50ºC


WORKING TEMPERATURE FR OM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

POL. I ND. VIL LALONQUEJAR


C/ ME RINDAD DE MONTIJA Nº6

5 Cylinder label with UN number


090 01 (BURGOS) - SPAIN
Tel.: (34) 94 7 281 108 Fax: (34 ) 94 7 281112

S
I
E
X
POLIGONO INDUSTRIAL
VILLALONQUEJAR
C/M ERINDAD DE MONTIJA Nº6
09001 BURGOS

TEL.: 947 28 11 08
FAX.: 947 28 11 1 2

- 0062 GAS COMPRIMIDO


NO INFLAMABLE
COMPRESSED GAS
NO INFLAMMABLE

AGENTE EXTINTOR
EXTINGUISH AGENT / AGENT EXTINCTEUR

Nº. DE CILINDRO
CYLINDER No. / Nº DE CYLINDER
PRESION DE CARGA A 20ºC
FILL PRESSURE AT 20ºC Bar TPED
PRESSION DE CHARGE A 20ºC
PRESION ROTURA DISCO SEGURIDAD 1999/36/CE
Organismo Notificado/Notified body/Organisme Notifié
BURSTING PRESSURE OF THE SAFETY DISC Bar
(0062) BUREAU VERITAS
PRESSION DE RUPTURE DU DISQUE DE SÉCURITÉ
Cilindro+Válvula+Disco de rotura+Elementos de protección
Cylinder+Valve+Bursting disc+Protections device
CARGA / FILL / CHARGE Kgs. Cylindre+Valve+Disque de rupture+Eléments de protection
Nº de Serie
PRESURIZADO CON Serial Number
PRESSURIZED WHIT / PRESSURISÉ AU Nº de Série

TARA / TARE / TARE Kgs.

PESO TOTAL
TOTAL WEIGHT / POIDS TOTAL
Kgs.

FECHA DE CARGA
FILL DATE / DATE DE CHARGE
TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC
WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC
Contiene gases fluorados de efecto invernadero regulados en el protocolo de Kioto
Contains fluorinated greenhouse gases covered by the Kyoto Protocol / Contient de gas à effet de senne fluorés relevant du protocole de kyoto
Sellado herméticamente / Hermetically Sealed / Hermétiguement sallé
POL. IND. VILLALONQUEJAR
C/ MERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112

CYLINDER LABEL WITH CE MARKING

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 30/112


COMPROBAR DE FORMA PERIODICA LA PRESIÓN EN LOS MÁNOMETROS Y EL PESO DE LOS CILINDROS, AL MENOS CADA SEIS (6) MESES.
PARA MÁS INFORMACIÓN ACUDIR AL MANUAL DE SERVICIO.
TEMPERATURA DE ALMACENAJE: DE -20ºC A 50ºC.
PARA EL DISEÑO, UTILIZACIÓN Y MANTENIMIENTO DEL SISTEMA, ACUDIR AL MANUAL DEL PRODUCTO.
MANEJO DE LOS CILINDROS ANTES DE LA INSTALACIÓN
SEGUIR LAS SIGUIENTES ADVERTENCIAS PARA EVITAR DESCARGAS ACCIDENTALES DEL PRODUCTO CONTENIDO EN EL CILINDRO:
1- NO QUITAR LOS TAPONES Y CAPERUZAS PROTECTORAS DE SU UBICACIÓN INICIAL (SUMINISTRO DESDE FABRICA) HASTA QUE LOS CILINDROS
NO ESTEN FIJADOS CON SEGURIDAD. SIEX SUMINISTRA EN ORIGEN TODOS SUS CILINDROS CON TAPONES PROTECTORES DE VÁLVULAS.
2- NUNCA UTILIZAR LA VÁLVULA DEL CILINDRO PARA GIRARLO Ó MOVERLO (UTILIZAR UN MEDIO APROPIADO PARA EL TRANSPORTE).
3- NO ALMACENAR NUNCA LOS CILINDROS BAJO EL SOL Ó EN LUGARES DONDE LA TEMPERATURA PUEDA EXCEDER DE 46ºC.
4- NO ACTIVAR LA PALANCA DE DISPARO MANUAL DE LA VÁLVULA DEL CILINDRO, PUESTO QUE ÉSTA ACCIÓN ABRIRÁ LA VÁLVULA Y DESCARGARÁ
SU CONTENIDO VIOLENTAMENTE, A NO SER QUE ESTÉ SUJETO FUERTEMENTE (A SUS HERRAJES).

S
5- NO COLOCAR NINGÚN INSTRUMENTO DE ACTIVACIÓN A LA VÁLVULA DEL CILINDRO HASTA QUE NO HAYA SIDO FIJADO FUERTEMENTE A LOS
HERRAJES DE SUJECIÓN Y CONECTADO A LA TUBERÍA DE DESCARGA.
INSTRUCCIONES DE INSTAL ACIÓN Y FUNCIONAMIENTO
ANTES DE INSTALAR, ACUDIR AL MANUAL SIEX DE DISEÑO, INSTALACIÓN, FUNCIONAMIENTO Y MANTENIMIENTO.
NO CONECTAR NINGÚN MECANISMO DE ACTIVACIÓN HASTA QUE LOS CILINDROS NO ESTÉN ASEGURADOS ADECUADAMENTE
EN LOS HERRAJES Y LA CONEXIÓN DE DESCARGA ESTÉ ASEGURADA A LA RED DE TUBERÍAS DEL SISTEMA.

LOS CILINDROS DEBERÁN SER INSPECCIONADOS MENSUALMENTE O INCLUSO CON MAYOR FRECUENCIA SI LAS CIRCUSTANCIAS LO REQUIEREN.
LAS TUBERIAS Y LOS DIFUSORES DEBERÍAN SER EXAMINADOS PARA COMPROBAR QUE NO ESTÉN OBSTRUIDOS. LOS CILINDROS DEBERÍAN SER

I
RECARGADOS SI PIERDEN MÁS DE UN 5% DE SU PESO DE LLENADO. LOS CILINDROS DEBERÁN SER RECARGADOS SI BAJA SU PRESIÓN, DEBIDO
A AJUSTES DE TEMPERATURA, EN MÁS DE UN 10% DE LA PRESIÓN NORMAL DE LLENADO.
RETIRADA DE SERVICIO DEL CILINDRO
SEGUIR LOS PASOS SIGUIENTES ANTES DE QUITAR EL CILINDRO DE LOS HERRAJES DE FIJACIÓN.
1- QUITAR LOS MECANISMOS DE ACTUACIÓN CON EL SIGUIENTE ORDEN: 2- RETIRAR LOS LATIGUILLOS Ó TUBOS DE DESCARGA.
A) ACTUADOR ELÉCTRICO (VALVULA SOLENOIDE, PILOTO, BOBINA, EXPLOSOR, ETC.) 3- PONER LA CAPERUZA A LA VÁLVULA.
B) ACTUADOR MANUAL - NEUMÁTICO.
C) LATIGUILLOS DE DISPARO NEUMÁTICO.

E
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

PERIODICALLY VERIFY THE PRESSURE IN THE PRESSURE GAUGE AND THE CYLINDER WEIGHT AT LEAST EVERY SIX (6) MONTHS.
FOR FURTHER INFORMATION SEE SERVICE GUIDE.
TEMPERATURE OF STORAGE: FROM -20ºC TO 50ºC.
FOR THE DESIGN, USE AND MAINTENANCE OF THE SYSTEM, SEE THE PRODUCT GUIDE.
CYLINDER HANDLING BEFORE INSTALLATION
FOLLOW THE WARNINGS TO AVOID ACCIDENTAL DISCHARGES OF THE PRODUCT CONTAINED IN THE CYLINDER.
1- DO NOT CLEAR THE CAPS AND PROTECTIVE CORKS OF IT’S INITIAL LOCATION (FACTORY FITTED) UNTIL THE CYLINDERS ARE NOT FIXED SURELY.
SIEX PROVIDES IN ORIGIN ALL THEIR CYLINDERS WHIT PROTECTIVE VALVE CAPS.

X
2- NEVER USE THE CONTAINER VALVE TO TURN IT OR TO MOVE IT AROUND (USE APPROPIATE MEANS FOR TRANSPORT).
3- NEVER STORE THE CYLINDERS UNDER THE SUN OR IN PLACES WHERE THE TEMPERATURE CAN EXCEED 46ºC.
4- DO NOT ACTIVATE THE MANUAL RELEASE LEVER OF THE CONTAINER VALVE, SINCE THIS ACTION WILL OPEN THE VALVE AND DISCHARGE IT’S
CONTENT VIOLENTLY, UNLESS IT’S SUBJECTED STRONGLY (TO IT’S BRACKETS).
5- DO NOT PLACE ANY ACTIVATION INSTRUMENT TO THE CONTAINER VALVE UNTIL IT HAS NOT BEEN FIXED STRONGLY TO THE SUBJECTION BRACKETS
AND CONNECTED TO THE DISCHARGE PIPE.
INSTALLATION AND OPERATION INSTRUCTIONS
BEFORE INSTALLING, SEE THE DESING, INSTALLATION, WORKING AND MAINTENANCE SIEX GUIDE.
POLIGONO INDUSTRIAL DO NOT TO CONNECT ANY MECHANISM UNTIL THE CYLINDERS ARE NOT SUITABLY INSURED IN BRACKETS AND THE DISCHARGE
CONNECTION IS ASSURED TO THE SYSTEM PIPE NETWORK.
VILLALONQUEJAR
C/MERINDAD DE MONTIJA Nº6 CYLINDERS WILL EVEN HAVE TO BE INSPECTED MONTHLY OR MOST FREQUENTLY IF THE CIRCUNSTANCES REQUIRE IT. THE PIPES AND THE NOZZLES
09001 BURGOS SHOULD BE EXAMINED TO VERIFY THAT THEY ARE NOT OBSTRUCTED. CYLINDERS SHOULD BE RECHARGED IF THEY LOSE MORE OF A 5% OF IT’S FILLING
WEIGHT. CYLINDERS WILL HAVE TO BE RECHARGED IF LOW THEIR PRESSURE, DUE TO TEMPERATURE ADJUSTMENTS IN MORE OF A 10% OF THE NORMAL
TEL.: (34) 947 28 11 08 FILLING PRESSURE.
FAX.: (34) 947 28 11 12 CYLINDER SERVICE RETIREMENT
FOLLOW THE NEXT STEPS BEFORE CLEARING THE CYLINDER OF SUBJECTION BRACKETS:
1- REMOVE THE MECHANISMS OF PERFORMANCE WHIT THE FOLLOWING ORDER: 2- RETIRE THE HOSES OR DISCHARGE TUBES.
A) ELECTRIC ACTUATOR (SOLENOID VALVE, PILOT, COIL, PYROTHECHNIC..) 3- PUT THE CAP TO THE VALVE.
B) MANUAL-PNEUMATIC ACTUATOR.
C) PNEUMATIC ACTUATOR HOSES.

CYLINDER INSTRUCTION LABEL

CYLINDER LABEL WITH UN NUMBER

CYLINDER POSITION LABEL

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 31/112


1.4.2 Cylinder inscriptions
As a legal requirement, all cylinders must include a series of markings on their shoulders that detail,
among other information: the manufacturer, quality marks, hydraulic test pressure, gas contained, UN
number, π marking, CE marking, manufacturing mark, manufacturing serial number, non-destructive
testing mark, weight of empty bottle plus valve, fill weight and type of gas, country of origin, type of
thread, minimum wall thickness, fill capacity, test month, test pressure and year, regular inspection
date, product identification number. Detailed below are the positions of the markings on the SIEX
cylinders.

S I EX

Marca de rosca
Mark of thread Inspeccion por ultrasonidos
Ultrasonic inspection

XX
Minimo espesor de la pared en mm

0 B /X U T
Minimum wall thickness in mm

07 /
20 R
2,5 1 0

A
XX
5E
MM 1

Fecha de prueba (Año/mes)


8
2

XX 4 5 67 25 0 Test date (year/month)

3
Marca de conformidad 7 - X KG 1 2 PH 1 17 Presión de prueba
40 4,7L
Conformity mark
ºC E -1 CZ Test pressure

N 1 96 4
Sello de organismo notificado
Peso de la botella vacía
Stamp of notified body
Weight of empty cylinder

Norma de fabricacion
Manufacturing standards Número de serie y el marcado de los productos de
ensayo del grupo (letra o número de colada /
Capacidad minima de llenado número de lote de tratamiento térmico)
Min. water capaciy Serial number and marking of test group (letter or
number of heat/batch number of heat treatment)

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 32/112


1.5 INSTALLING CYLINDER FIXING BRACKETS

1.5.1 Brackets for a single (modular) cylinder

Safety cup on valve


outlet:

P ELIGRO:

0062 E STO ES UN CONTENEDOR DE ALTA


NO QUITAR LOS ACCE SORIOS,
MANIPULARLO HAS TA QUE ESTE BIEN
MEDIANTE SUS HERRAJES.

EN 837-1

EN 837-1
bar EN 837-1

bar KL. 1.6


bar

KL. 1.6
KL. 1.6

Figure 16

CAUTION

AT THIS STAGE OF THE INSTALLATION,


DO NOT REMOVE EITHER THE PROTECTIVE VALVE CAP
OR THE OUTLET SAFETY PLUG.

The brackets assemblies for a modular cylinder comprise a nut, a bolt, a washer, two straps, a rear
channel, and two decorative end pieces. To ensure the container or cylinder is securely attached, it is
recommended that two fixing brackets per bottle be used, for all 40.2 litre cylinders and above.

1 Back carril

3 Fixing nuts and bolts

Figure 16

Each strap has a slot for insertion in the rear channel, to allow the cylinder to be correctly aligned. The
assembly channel is designed to be fixed to a rigid surface with the cylinder supported on the floor.

To install the modular cylinder bracket, follow the instructions below:

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 33/112


1. Place the modular cylinder’s rear wall channel at the height above the floor indicated in table
1, and mark on the wall the centre of the holes to be drilled.

Safety cup on valve


RGS-MAM-20
EN 12094-4

30

outlet.
20 40

10 50
bar
0 60

KL. 1.6

TPED
1999/36/CE

Cylinder+Valve+Bursti ng di sc+Protections device


C ylindre+Valve+Disque de rupture+Eléments de prot ection

Serial Number
Nº de Série

P OSICION DEL CILINDRO / CILINDER POSITIONING / POSITION DE LA BOUTEILLE

W ALL /M UR
Ma nometro h acia arriba
U pw ards pressure gauge
Jau ge d e l a hau sse

Man ometro h acia abajo


D ow nw ards pressure g auge
Jau ge à
FLOOR /
S OL
FALSO SUELO / SUB- FLO OR / FAUX SOL AMBIEN TE / HAZARD / E NVI RONNEME NT FALSO TECHO / SUB -CEI LI NG / FAUX PLAFOND

Nota: Marque con una X el que proceda / Note: Tick w hit a X the correct one / Note: Mettre le cas échéant X

- 0062 COM PRESSED G AS


N O IN FLA MMABLE

EXTINGUISH AGENT / AGENT EXTINCTEUR

CYLI NDER No. / Nº DE CYLINDER

FILL PRESSURE AT 20ºC


PRESSION DE CHARGE A 20ºC

BURSTING PRESSURE OF THE SAFET Y DISC


PRE SSION DE RUPTURE DU DISQUE DE SÉCURITÉ
FILL / CHARGE

PRESSURI ZED WHIT / PRESSURISÉ AU

TAR E / TARE

TOTAL WEIGHT / POIDS TOTAL

FILL DATE / DATE DE CHARGE

WORKI NG TEMPER ATURE FROM -20ºC TO 50ºC


TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

S
I
E
X
POL IGO NO I NDUSTRIAL
VILL ALO NQ UEJAR
C/MER INDAD DE MONTIJA Nº6
09 00 1 BURGOS

TEL.: 9 47 28 11 08
FAX.: 9 47 28 11 12

TPED
1999/36/CE

Cylinder+Valve+Bursting d isc+Protections d evice


Cylindre+Valv e+Disque de ru pture+Eléments de protectio n

Serial Nu mber
Nº d e Série

- 0062 C OMPRESSED GAS


NO INFLAMMABLE

EXTINGUISH AGENT / AGENT EXTINCTEUR

CYL INDER No . / Nº DE CYLINDER

FILL PRESSURE AT 20ºC

TARE / TARE

TOTAL WEIGHT / POIDS TOTAL

FILL DATE / DAT E DE CHARGE

EN 837-1
WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

bar

KL. 1.6

S
I
E
X
POLIGONO INDUSTRIAL
VILLALONQUEJAR
C/MERINDAD DE MO NT IJA Nº6
09001 BURGOS

TEL.: ( 34) 947 28 11 08


FAX.: ( 34) 947 28 11 12

Figure 17

TABLE 1

Type of Cylinder volume Length A Length B


Code
bracket (litres) (mm) (mm)
POHE2,7 Modular 2.7 200 -----
POHE6 Modular 4.7 - 6.7 400 -----
POHE13 Modular 13.4 400 -----
POHE25 Modular 25 300 -----
POHE26 Modular 26.8 600 -----
POHE40 Modular 40.2 400 1000
POHE61 Modular 61 300 800
POHE67 Modular 67.5 500 1300
POHE80 Modular 80 500 1300
POHE84 Modular 84 400 1100
HE100 Modular 100 500 1300
HE120 Modular 120 450 1250
HE108 Modular 108.4 300 800
HE127 Modular 127 400 1100
HE180 Modular 180 400 1100

2. Drill two 10 mm diameter holes at the marks on the surface where the rear channel is to be
secured and bolt the channel to the wall.

3. Ensure that the cylinder has its valve protective cap and outlet safety plug in place.

4. Place the cylinder (still with its valve protective cap and outlet safety plug in place) in the
centre of the channel and against it.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 34/112


5. Put the cylinder straps in the channel using their slots, and encircling the cylinder. The straps
must be offered up in a horizontal position, until reaching the slots, and then rotated 90º until
vertical, in such a way as the slots in the straps engage in the channel, as shown in Figure 18.

Figure 18

6. Tighten the straps with the bolt, nut and washer until the cylinder is properly secured.

7. At this point, the protective valve cap can be removed and the cylinder orientated so that the
valve pressure gauge is facing forward and can be read. To be able to orientate the cylinder,
the straps have to be loosened slightly, and retightened afterwards.

8. Do not remove the outlet safety plug until indicated in the corresponding chapter of this
manual.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 35/112


1.5.2 Brackets for a single (modular) cylinder installed horizontally on the
floor

The usual position of a cylinder with its valve is vertical, but it may also be fitted in a horizontal
position, taking into account that the position of the valve, in this case, is with the pressure
gauge facing upwards and the curved part of the syphon tube downwards (see Figure 6).

It is expressly prohibited to position the cylinder with its valve in an inclined position, as shown
in Figure 7.

The steps to follow for the installation of a modular cylinder in a horizontal position are the same for
those in a vertical position. In addition the following aspects must be taken into account:

1. The cylinders must be located in an environment protected from adverse weather conditions
and where the temperature does not exceed 50°C nor fall below 0°C. Where these
temperatures cannot be maintained exterior heating or cooling will be required. The following
installation instructions must be followed precisely and in the exact order to avoid any
accidental discharge that might cause personal injury or material damage.

2. When the cylinder is fixed by its brackets, in a horizontal position, the valve pressure gauge
must be in view facing the ceiling. The valve outlet will thus be in a horizontal position parallel
to the floor. (see figure 19).

3. When the cylinders are installed in a horizontal position, a minimum of two fixing brackets are
required per cylinder.

4. The cylinders that may be used in a horizontal position are: 2.7, 4.7, 6.7, 13.4, 26.8 40.2 litres.
º
90
TO

EN 837-1

b ar

KL.
KL. 1.6
1.6

LE
G
AN
D
TE
IT
M
R
PE
EN 837-1

bar

K L. 1.6

Figure 19. Typical cylinder installation – horizontal fixing.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 36/112


1.5.3 Brackets for a single row cylinder bank

CAUTION

AT THIS STAGE OF THE INSTALLATION,


DO NOT REMOVE EITHER THE PROTECTIVE VALVE CAP
OR THE OUTLET SAFETY PLUG.

The bracket assemblies for cylinders in single row banks consist of: two rear channels, straps, bolts,
nuts, washers and decorative end pieces, as shown in Figure 20.

10
9
8

6
5

4
Figure 20. Bracket positions for single row banks.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 37/112


No. Description
1 390x300 Manifold bracket
650x400 Manifold bracket
2 Cylinder bank cylinder channel
3 Flat washer A 10.5 DIN 125 ZP
4 Hex. bolt M-10x30 DIN 933 ZP
5 Hex. bolt M-10x40 DIN 933 ZP
6 Cylinder clamp
7 Hex. lock nut M-10 DIN 934 ZP
8 Bolt: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"
9 Manifold clamp
10 Nut: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"

To install single row cylinder bank brackets, follow the instructions below:

1. Position the rear channels of the cylinder bank up to the wall, at the height above the floor
indicated in table 2, and mark the centre of the holes to be drilled.

ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.

227SOL-A
24V (DC)
0,60 A
Nº xx
- 0786

- 0786

- 0786
G 306011

G 306011

G 306011
Vd S

Vd S

Vd S
WP137 BAR

WP137 BAR

WP137 BAR
FH-40HC

FH-40HC

FH-40HC
N - XXXXXX

N - XXXXXX

N - XXXXXX

R GS-M AM-40 R GS-M AM-40 R GS-M AM-40


EN 12 094-4 EN 12 094-4 EN 12 094-4

30 30 30
20 40 20 40 20 40

10 50 10 50 10 50
bar bar bar
0 60 0 60 0 60

KL. 1. 6 KL. 1. 6 KL. 1. 6


947 281112

947 281112

281112

UN: UN: UN:


947

MASA MAX. AUTORIZADA M ASA MAX . AUTO RI ZAD A M ASA MAX . AUTO RI ZAD A
(34)

(34)

(34)

MAX. AU TH OR IZED C HARGE M AX . AU TH OR IZED C HARG E M AX . AU TH OR IZED C HARG E


(SP AIN) Nº6

(SP AIN) Nº6

Tel.- Burgos Mont ija Nº6


Fax. -

Fax. -

Fax. -

CHAR GE MAX . AUTORISÉE KG. CHAR GE MA X. AU TO RI SÉE KG. CHAR GE MA X. AU TO RI SÉE KG.
ija

ija
Vi llalonquejar

Vi llalonquejar

Vi llalonquejar

(SP AIN)
de Mont

de Mont
281108

281108

281108

GAS/GAZ: GAS/GAZ: GAS/GAZ:


de
Tel.- Burgos

Tel.- Burgos

ALMAC ENAR EN LUGAR VENTILAD O / NO RES PIRAR EL GAS


C/ Merindad

947

C/ Merindad

947

ALM AC ENAR EN LU GAR VENTI LAD O / NO RE SPIRAR EL G AS


C/ Merindad

947

AL MAC ENAR EN LU GAR VENTI LAD O / NO R ESPIRAR EL G AS


PARA MANIPU LAC IÓN Y PREC AUCI ON ES VER ETIQUETA CILIND RO PARA M ANIPU LA CIÓ N Y PREC AUCI ON ES VE R ETIQ UETA CI LIND RO PAR A M ANIP ULA CIÓ N Y PREC AUC ION ES VE R ETIQ UETA CI LIN DRO
Ind.

Ind.

Ind.

2 2 2
(34)

(34)

(34)

TO BE STORED IN A WELL VENTILATED AREA / DO NOT IN HALE


09001

09001

TO BE S TO RED IN A WE LL VENTIL ATED AREA / DO NO T IN HALE


09001

TO BE S TO RED IN A W ELL VENTI LATED AREA / DO NO T IN HALE


Pol.

Pol.

Pol.

FOR HA NDLING IN STRUC TION S SEE CYLIND ER'S LA BEL FO R H ANDL ING I NSTRU CTIO NS SE E CYL IND ER'S L ABEL FO R H ANDL ING I NSTRU CTIO NS SE E CYL IND ER'S L ABEL

STOCKER DANS UN ENDR OIT V ENTILÉ / NE PAS IN HALER LE GAZ POUR STO CKER DANS UN ENDR OIT V ENTIL É / NE PAS IN HALER L E G AZ PO UR S TO CKER DAN S UN END ROI T VENTIL É / NE PAS IN HAL ER L E G AZ PO UR
MANIP ULATION ET PR ECAU TION S, V OIR L'E TI QU ETTE SUR LE RESE RVOI R M ANI PUL ATION ET P RECAU TION S, VOI R L 'ETI QU ETTE SUR L E RES ERVOI R M AN IPUL ATIO N ET PRECA UTIO NS, VOI R L 'ETIQ UETTE SUR LE R ESERVO IR

T PED T PED TPED


19 99 /36 /C E 19 99 /36 /C E 1999/36/CE
Organism o Notificado/Notified body/Organism e Notifié Organism o Notificado/Notified body/Organism e Notifié Organism o Notificado/Notified body/Organism e Notifié
( 0062) BUREAU VERITAS ( 0062) BUREAU VERITAS ( 0062) BUREAU VERITAS
Cilindro+Válvula+Dis co de rotur a+Elementos de protecc ión Cilindro+Válvula+Dis co de rotur a+Elementos de protecc ión Cilindro+Válvula+Dis co de rotur a+Elementos de protecc ión
C yl i nde r+Val ve+ Burst i ng disc +Prot ec ti ons devi ce C yl i nde r+Val ve+ Burst i ng disc +Prot ec ti ons devi ce Cylinder+Valve+ Bursting disc+Protections device
C yli ndre +Va lve +Di sque de rupture +El ém ent s de prote ct ion C yli ndre +Va lve +Di sque de rupture +El ém ent s de prote ct ion Cylindre+Valve+Disque de rupture+Eléments de protection
Nº de Serie Nº de Serie Nº de Serie
S eri al Numbe r S eri al Numbe r Serial Num ber
Nº de Sé ri e Nº de Sé rie Nº de Série

POSICION DEL CILINDRO / CILINDER POSITIONING / P OS ITION DE LA BOUTEILLE POSICION DEL CILINDRO / CILINDER POSITIONING / P OS ITION DE LA BOUTEILLE POSICION DEL CILINDRO / CILINDER POSITIONING / POS ITION DE LA BOUTEILLE

- 0786 - 0786 - 0786


PARED / WALL / MUR

PARED / WALL / MUR

PARED / WALL / MUR

Mano metro haci a arriba Mano metro haci a arriba Man ometr o haci a arriba
Upwa rds pressure g aug e U pwa rds pressure g aug e U pwa rds pressure g aug e
Jaug e de l a hausse Jaug e de l a hau sse Jaug e de l a hau sse

Mano metro haci a abaj o Mano metro haci a abaj o Man ometro haci a abajo
D ownwards pre ssure ga uge D ownwar ds pressure ga uge D ownwar ds pressure ga uge
Jaug e à Jaug e à Jaug e à
SUEL O / FLOOR / SOL SUEL O / FLOOR / SOL SU EL O / FL OOR / SOL

FA LSO SUELO / SUB- FLOOR / FAUX SOL A MBIENTE / HAZARD / E NVIRONNE MENT FALSO TECHO / SUB -CEI LI NG / F AUX PLAFOND FALSO SUELO / SUB -FLOOR / FAUX SOL A MBIENTE / HAZARD / E NVIRONNE MENT FALSO TECHO / SUB-CEI LI NG / F AUX PLAFOND FALSO SUELO / SUB -FLOOR / FAUX SOL A MBIENTE / HAZARD /E NVI RONNE ME NT FALSO TECHO / SUB-CE IL ING / FAUX PLAFOND

No ta: Marqu e co n un a X el qu e p roceda / Note: Tick whit a X the cor rec t one / Note: M ettre le c as éché ant X No ta: Marqu e co n un a X el qu e p roceda / Note: Tick whit a X th e c orre ct one / Note: Mettre le c as éché ant X N ota: Marqu e con u na X el q ue proceda / Note: Tick whit a X th e c orre ct one / Note : Mettre le c as éc hé ant X

- 0062 COMP RESS ED GA S


NO IN FLAMMABLE
- 0062 COMP RESS ED G AS
N O I NFLAMMABLE
- 0062 COMP RESS ED G AS
N O I NF LAMMABLE

AGENTE EXTINTOR AGENT E EXTINTOR AGENT E EXTINTOR


EX TIN GU ISH A GE NT / A GE NT EX TINC T EU R EX TIN GU ISH A GE NT / AGE NT EX TINC T EU R EX TINGU ISH A GENT / AGENT EX TINCTEU R

Nº. DE CILINDRO Nº. DE CILINDRO N º. DE CILINDRO


C YL IN DE R N o. / Nº D E C YL IND ER C YL INDE R No. / Nº DE C Y LIND ER CYLINDER No. / Nº DE CY LIND ER

PRESION D E C ARGA A 20ºC PRESION D E C ARGA A 20ºC PRESION DE CARGA A 20ºC


FIL L PR E SS UR E A T 20ºC Bar FIL L PR E S SUR E A T 20ºC Bar FIL L PR ES SU R E AT 20ºC Bar
PR E SSIO N D E C HA R GE A 20ºC PR E SSIO N D E C HA R GE A 20ºC PR E SSIO N DE C HA R GE A 20ºC

PRESION R OT URA DISC O SEGURIDAD PRESION R OT URA DISC O SEGURIDAD PRESION ROT URA DISCO SEGURIDAD
BURSTING PR ESSURE OF THE SAFETY DISC Bar BURSTING PR ESSURE OF THE SAFETY DISC Bar BURSTING PR ESSUR E OF THE SAFETY DISC Bar
PRESSION DE RUPTURE DU DISQUE DE SÉCURITÉ PRESSION DE RUPTURE DU DISQUE DE SÉCURITÉ PRESSION DE R UPTURE DU DISQUE DE SÉCURITÉ

CARGA / F IL L / C HA R GE Kgs. CARGA / FIL L / C HA R GE Kgs. CARGA / FILL / CH ARGE Kgs.

PRESURIZ ADO CON PRESURIZ ADO C ON PRESURIZ ADO CON


PR E SS UR IZ E D W H IT / PR E SSUR ISÉ A U PR E SS UR IZ E D WH IT / PR E SSUR IS É A U PRESS URIZED WH IT / PRESSU RIS É AU

TARA / T AR E / T AR E Kgs. TARA / T AR E / T AR E Kgs. TARA / TARE / TARE Kgs.

PESO TOTAL PESO TOTAL PESO T OTAL


TO TA L W EIG HT / POID S T OT AL
Kgs. TO TA L W E IGHT / PO ID S T OT AL
Kgs. TO TAL WEIGHT / PO ID S TOTAL
Kgs.

F ECHA DE CARGA F ECH A DE CARGA F ECH A DE CARGA


FIL L DA TE / DA TE D E C H AR GE FIL L DA T E / DA TE D E C HAR GE FILL D ATE / D ATE D E CHARG E

TEMPERATURA DE FUNC IONAMIENT O DE -20ºC A 50ºC TEMPERATUR A DE FUN CIONAMIEN TO DE -20ºC A 50ºC TEMPERATU RA DE FU NCIONAMIEN TO D E -20ºC A 50ºC
W OR KING T EM PER A TU R E FR O M -20ºC TO 50ºC W OR KING T EM PE RA TU R E FR O M -20ºC TO 50ºC WOR KING TEM PERA TU RE FRO M -20ºC TO 50ºC
TE M P É R AT UR E DE F ON C TIO NN EM E NT DE -20ºC A 50ºC TE M PÉ R AT UR E DE F ON C TIO NN EM E NT DE -20ºC A 50ºC TEM PÉRATUR E DE FON CTION NEM ENT D E -20ºC A 50ºC

POL. IND . VILLALONQUEJAR POL. IN D. VILLALONQUEJAR POL. IN D. VILLALONQUEJAR


C/ MERINDAD DE MONTIJA Nº6 C/ MERINDAD DE MONTIJA N º6 C/ MERINDAD DE MONT IJA Nº6
09001 (BURGOS) - SPAIN 09001 (BURGOS) - SPAIN 09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112 Tel.: (34) 947 281108 Fax: (34) 947 281112 T el.: (34) 947 281108 Fax: (34) 947 281112

S S S
I I I
E E E
X
POL IGONO INDUSTRIAL
X
POL IGONO INDUSTRIAL
X
POL IGONO INDUSTRIAL
VILL AL ONQUEJAR VILL AL ONQUEJAR VIL LALONQUEJAR
C/MERI NDAD DE M ONT IJA Nº6 C/MERINDAD DE M ONTIJA Nº 6 C/MERINDAD DE MONTIJA Nº 6

A
09 001 BURGOS 0 9001 BURGOS 0 9001 BURGOS

TEL.: 947 28 11 08 TEL.: 947 28 11 08 TEL.: 947 28 11 08


F AX.: 947 28 11 12 F AX.: 947 28 11 12 F AX.: 947 28 11 12

Figure 21

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 38/112


TABLE 2

Type of Cylinder volume Length A


Code Length B (mm)
bracket (litres) (mm)
POHE61 Bank 61 300 800
POHE67 Bank 67 500 1300
POHE80 Bank 80 500 1300
POHE84 Bank 84 400 1100
HE100 Bank 100 500 1300
HE120 Bank 120 500 1300
HE127 Bank 127 400 1100
HE180 Bank 180 400 1100

2. Drill 10 mm diameter holes at the marks on the surface where the rear channels are to be
secured and bolt the channels to the wall. It is recommended to make an anchoring hole for
each two cylinders and always at the ends of the channel.

3. The wall on which the bracket is to be fixed (when necessary) must be perpendicular to the
floor and sufficiently robust to support the cylinder during discharge. If the bank is to be
anchored to a partition wall, plates must be fitted so that the bracket can be secured to the
back face of the partition wall as shown below.

1
4

2 1 Partition
5 2 Support pad
3 3 Nut
4 Bracket
5 Anchor bolt

4. Ensure that all the cylinders in the bank have their valve protective caps and outlet safety
plugs in place.

5. Position the cylinders (without removing the valve protective caps and outlet safety plugs)
against the channel and aligned with reference to the manifold check valves and the discharge
hose. The bolt that supports the channel for the first cylinder channel must be located 50 mm
from the end of the channel.

6. If the manifold is not installed, measure the distance between the axes of two of the check
valves. This is the distance that must be left between the symmetrical axes of each cylinder.
(see figure 22).

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 39/112


- 0062 - 0062 - 0062
A.= Desfase entre válvula
antirretorno y botella,
correspondiente al latiguillo.
S S S
I I I
E E E
X X X

RGS-MAM-40 RGS-MAM-40 RGS-MAM-40


EN 12094-4 EN 12094-4 EN 12094-4

30 30 30
20 40 20 40 20 40

10 50 10 50 10 50
b ar bar ba r
0 60 0 60 0 60

KL. 1.6 KL. 1.6 K L. 1.6

T PED T PED TPED


1 999/36/CE 1999/36/CE 1999 /36/CE
Organ si mo Notificado/Notified bod y/Or ganis me Notifié Or ganismo Notificado/Notifie d body/Organisme Notifié Organismo Notificado/Notified body/Organisme Notifié
(0062) BUREAU VERITAS (0062) BU REAU VERITAS (0062) BUREAU VERI TAS
Cilindro+Válv ula+Disc o de rotura+Elementos de protec ción Cilin dr o+Vá lvula+Dis co de r ot ur a+Eleme n tos de p ro te cción Cilindro+Válv ula+Disco de rotura+Elementos de prot ección
C yl inder +Va lve +Bur sting dis c +Prote cti ons devic e C ylinder+Valve+B urs tingd isc+Protections device Cylinde r+V a lve+B urs ting disc +Pr otec tions devic e
C ylindre +V a lve+D is que de rupture +Elé me nts de prote c tion Cyli ndr e+Valve+Dis que de ruptur e+E léments de prot ection C ylindre +V alve +D isque de rupture +Elé ment s de prote ction
Nº de Serie Nº de Ser ie Nº de Serie
Se ria l Nu mbe r Serial Number S er ial N umbe r
N º de Sér ie Nº de Série N º de S érie

A GE NTE EXTI NTOR


- 0062
EXTINGUISH AGENT / AGENT EXTINCTEUR

Nº. DE CILINDRO
CYLINDER No. / Nº DECYLINDER
PRESI ON DE CARGA A 20ºC
FILL PRESSUREAT 20ºC
PRESSION DECHARGE A 20ºC
C OMPRESSED GAS
NO IN FLA MMABLE

Bar
AGENTE EX TINTOR

Nº. DE CI LI NDRO
- 0062
EXT INGUIS H AGENT / AGE NT E XTI NCT EUR

CYL INDE R No. / Nº DE CYL INDE R

P RES ION DE CA RGA A 20ºC


FILLPRESSURE AT 20ºC
PRESSION DE CHARGE A 20ºC
COMPRESSED GAS
N O INFLAMMA BLE

Bar
AGENTE E XTINTOR

Nº. DE CI LINDRO
- 0062
EXTINGUISH AGENT/ AGENT EXTINCTEUR

CYLINDER No. / Nº DE CYLINDER


PRE SI ON DE CARGA A 20ºC
FILL PRESSUREAT 20ºC
PRESSION D ECHARGEA 20º C
CO MPRESSED G AS
NO INFLAMMABLE

B ar
A = Lag in the check valve
and cylinder, corresponding
PRESI ON ROTURA DIS CO SE GURIDA D P RES ION ROTURA DI SCO SEGURIDAD PRE SI ON ROTURA DISCO SE GURI DAD
B UR STIN G PR ESSUR E OF TH E SAFET Y DISC Bar BU RSTIN G PR ESSU RE O F THE SA FETY D ISC Bar BU RST ING PRESSU RE O F TH E SAFETY DISC B ar
PR ESSION D E RU PTUR E D U D ISQU E D E SÉ CUR ITÉ PRESSIO N D E R UPTU RE D U DISQ UE D E SÉCU RITÉ PRE SS ION DE R UP TUR E DU DI SQU E DE SÉC UR ITÉ

CARGA / FILL / CHA RGE Kgs. CARGA / FI LL / CHARGE Kgs. CARGA / FILL/ CHARGE K gs .

PRESURI ZADO CON P RES URIZADO CON PRE SURIZA DO CON


PRESSURIZED WHIT / PRESSURISÉ AU PRESS URI ZE D WHIT / PRE SSURIS É AU PRESSURIZED WHIT/ PRESSU RISÉAU

TA RA / TARE / TARE Kgs. T ARA / TARE / T ARE Kgs. TARA / TARE / TARE K gs .

PES O TOTAL P ESO TOTAL PESO TOTA L


Kgs. Kgs. K gs .
TOTAL WEIGHT/ POIDS TOTAL T OT AL WE IGHT / POIDS TOT AL TOTAL WEIGHT / POIDS TOTAL

FECHA DE CARGA FE CHA DE CARGA F ECHA DE CARGA


FILL DATE / DATEDE CHARGE FIL L DAT E / DATE DE CHARGE FILL DATE / DATE DE CHARGE
TEM PERATURA DE FUNCI ONAMI ENTO DE -20ºC A 50ºC T EMPE RATURA DE FUNCIONA MIENTO DE -20ºC A 50ºC TEMPE RA TURA DE FUNCIONAMIE NTO DE -20ºC A 50ºC
WORKING TEMPERATUREFROM -2 0ºC TO 50º C WORKI NG TE MP ERATURE FROM -20ºC T O 50ºC WORK ING TEMPERATURE FROM -20 ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE-20ºC A 50ºC T E MPÉ RATURE DE FONCTI ONNE ME NT DE -20º C A 50ºC TEMPÉRATU RE DEFONCTIONNEMENT DE-20ºC A 50ºC

P OL. IND. V ILLA LONQUEJA R POL. I ND. VILLALONQUEJ AR P OL. IND. VI LLA LONQUEJAR
C/ MERINDAD DE MONTIJ A Nº6 C/ ME RI NDAD DE MONTI JA Nº6 C/ MERI NDAD DE MONTIJA Nº6
09001 (BURGOS ) - SPAI N 09001 (BURGOS) - SP AIN 09001 (B URGOS) - S PAIN
Tel. : (34) 947 281108 Fax: (34) 947 281112 Tel.: (34) 947 281108 F ax : (34) 947 281112 Tel.: (34) 947 281108 Fax : (34) 947 281112

for flexible actuator hose


S S S
I I I
E E E
X
POL IGONO INDUST RIAL
X
POL IGONO INDUSTRIAL
X
POLIGONO INDUST RIAL
VILL AL ONQUEJAR VIL LALONQUEJAR VIL LAL ONQUEJ AR
C/MERINDAD DE M ONTIJA Nº6 C/M ERINDADDE MONT IJ A Nº6 C/MERINDAD DE MONT IJA Nº6
0 90 01 BURGOS 09 00 1 BURGOS 09 00 1 BURGOS

TEL .: 947 2 8 11 08 TE L.: 94 7 28 11 0 8 T EL.: 947 28 11 08


F AX .: 947 28 11 12 F AX .: 94 7 28 11 1 2 FA X.: 947 28 11 12

Figure 22

7. Fit the clamps in the channel by sliding them along the slots so that they hold the cylinders
across their whole diameters. For this, the straps must be positioned horizontally, until
reaching the slots, and then rotated 90º until vertical, in such a way that the slots in the strap
engage in the channel, as shown in Figure 18.

8. Tighten the straps with the bolts, nuts and washers until the cylinders are properly secured.

9. At this point, the protective valve caps can be removed and the cylinders correctly oriented. To
facilitate this, the straps should be loosened slightly, and retightened afterwards.

10. Do not remove the outlet safety plugs until indicated in the corresponding chapter of this
manual.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 40/112


1.5.4 Brackets for a double row cylinder bank

CAUTION

AT THIS STAGE OF THE INSTALLATION,


DO NOT REMOVE EITHER THE PROTECTIVE VALVE CAP
OR THE OUTLET SAFETY PLUG.

The bracket assemblies for cylinders in double row banks consist of: two front and two rear channels,
straps, bolts, nuts, washers, threaded rod, connecting nuts, wide washers and decorative end pieces.
The manifold fixing consists of two vertical channels with two perpendicular horizontal ones, complete
with straps, bolts, etc., as shown in Figure 23.

Figure 23

No. Description
1 390x500 Manifold bracket
650x500 Manifold bracket
2 Bylinder bank cylinder channel
3 Flat washer A 10.5 DIN 125 ZP
4 Hex. bolt M-10x30 DIN 933 ZP
5 M-10 Unistrut channel nut without spring
6 M-10 ZP Threaded rod
7 Hex. bolt M-10x40 DIN 933 ZP
8 Hex. lock nut M-10 DIN 985 ZP
9 Cylinder clamp

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 41/112


10 Hex. nut M-10 DIN 934 ZP
11 M10x40x3 Wide washer
12 Bolt: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"
13 Manifold clamp
14 Nut: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"

For the assembly of the brackets of the cylinders in manifold system in double row, follow the next
guidelines:

1. Position the rear channels of the cylinder bank up to the wall, at the height above the floor
indicated in table 2 (lengths A and B), and mark the centre of the holes to be drilled.

2. Make hole with 10 mm of diameter in the quoted marks, in the surface where the rear
channels will be fixed and screw the channels to the wall. It is advisable to make a hole of
anchorage for each two cylinders and always in the end of the channels.

3. Ensure that all the cylinders in the bank have their valve protective caps and outlet safety
plugs in place.

4. Position the cylinders (without removing the valve protective caps and outlet safety plugs)
against the channel and aligned with reference to the manifold check valves and the discharge
hose. The bolt that supports the channel for the first cylinder channel must be located 50 mm
from the end of the channel.

5. If the manifold is not installed, measure the distance from axis to axis of their retain valves.
That will be the distance to be leaven between the symmetrical axis from cylinder to cylinder
(see Figure 21).

6. Once the cylinders are in place, place the threaded rod between them and at the ends of the
channel, together with their channel linkage nuts. To do this, the nuts must be inserted in a
horizontal position and then turned clockwise 90º to a vertical position, so that the slots in the
nuts engage in the channel.

7. Once the cylinders are placed, put between them and the ends of the channel, the threaded
rod with the join nuts to the channel. For this reason, it is necessary to introduce the nuts in
horizontal position and then turn to the right 90º to their vertical position, so that the notches fit
onto the channel.

8. Place the two front channels making them to pass by the threaded rods across their holes.

9. Insert the quoted join (point 8) with the respective nut and washer of wide wing.

10. Assemble the second row of cylinders as mentioned in the points from 4 to 7 of the previous
guideline “Brackets for cylinders in manifold system in single row”.

11. At this point, the protective valve caps can be removed and the cylinders orientated so that the
valve pressure gauges are facing forwards and can be read. To orientate the rear cylinders,
the threaded rods must be loosened slightly, and retightened afterwards. To orientate the front
cylinders, the straps must be loosened slightly, and retightened afterwards.

12. Do not remove the outlet safety plugs until indicated in the corresponding chapter of this
manual.
1.5.5 Brackets for a single cylinder with continuous weighing (modular,
single and double row)

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 42/112


This fixing system has a horizontal frame in the top part of the brackets, designed to anchor the
individual weighing systems on which the charged cylinders rest. This type of fixing is like a cage
enclosing the cylinders, anchored either to the wall or the floor, or both.

4
5

12

11

10

7
9

Fixing brackets for modular cylinders

Nº Denomination
1 Framework
2 Top horizontal side lane
3 Rear vertical side lane
4 Front vertical side lane
5 Manifold system cylinder channel
6 Varilla roscada M-10 HC / M-10 ZP Threaded rod
7 2 Holes square
8 Lower horizontal side lane
9 Ex. screw M-10x40 DIN 933 ZP
10 Washer flat A 10.5 DIN 125 ZP
11 2 Holes Billet
12 Ex. nut M-10 DIN 934 ZP
13 M10x40x3 Washer
14 M10 nut without spring lane unistrut

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 43/112


18
17
16

1
2
3 15

4 14
5
13
12
6

7
10
9
8

Bracket for single row cylinder bank with continuous weighing

Nº Denomination
1 Framework
2 Top horizontal side lane
3 Rear vertical side lane
4 Front vertical side lane
5 Manifold system cylinder channel
6 M-10 ZP Threaded rod
7 2 Holes square
8 Lower horizontal side lane
9 M10x40x3 Washer
10 Ex. nut M-10 DIN 934 ZP
11 Ex. screw M-10x40 DIN 933 ZP
12 Washer flat A 10.5 DIN 125 ZP
13 3 Holes billet
14 2 Holes Billet
15 M10 nut without spring lane unistrut
16 Screw: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"
17 Manifold clamp
18 Nut: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 44/112


19
18
17

1
2
3
4 16
5
6 15

14
13
7

8
11
9 10

Bracket for double row cylinder bank with continuous weighing

Nº Denomination
1 Framework
2 Top horizontal side lane
3 Rear vertical side lane
4 Central vertical side lane
5 Front vertical side lane
6 Manifold system cylinder channel
7 M-10 ZP Threaded rod
8 2 Holes square
9 Lower horizontal side lane
10 M10x40x3 Washer
11 Ex. nut M-10 DIN 934 ZP
12 Ex. screw M-10x40 DIN 933 ZP
13 Washer flat A 10.5 DIN 125 ZP
14 3 Holes billet
15 2 Holes Billet
16 M10 nut without spring lane unistrut
17 Screw: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"
18 Manifold clamp
19 Nut: M-6x30 => Pipe: 1/2" - 1 1/4"
M-8x35 => 1 1/2" - 3"
M-10x45 => 4" - 6"

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 45/112


1.6 INSTALLING THE MANIFOLD AND MANIFOLD BRACKETS

These consist of two channels that form a 90º angle. The channel that is against the wall is the wall
fixing and the one that supports the manifold is the manifold fixing.

Manifold

1.- Manifold fixing bands


2 - Manifold fixing channel
3.- Manifold fixing channel

Manifold

To install the discharge manifold and its brackets, follow the instructions below:

1. Fit the wall bracket channel at the correct height using suitable safety bolts. Before carrying
out this operation the correct height of the manifold must be calculated.

The joint between the two channels can be made using a 90º solid bracket bolted to the
channels, to allow the manifold support channel to be moved vertically to its correct position.

2. Fit the other channel (the manifold support) forming a 90º angle with the rear channel using
the corresponding steel bracket. Lightly tighten the solid bracket bolts without over-tightening.
The manifold support channel can be slid in the wall channel until it is in the ideal position.

3. Place the manifold clamps or straps in the channel.

4. Place the manifold between the clamps and gently tighten. Due to the form of the channel, the
manifold can be slid along it until it is in its ideal position.

5. Finally, when the manifold is installed in the correct position, fully tighten the solid bracket, and
the strap nut and bolt.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 46/112


1.- Manifold
2 - Check valve
3.- Manifold fixing band
4.- Manifold fixing channel

Installing the manifold brackets

1.7 INSTALLING CHECK VALVES IN THE DISCHARGE


MANIFOLD

These valves are connected between the discharge hose and the manifold, forcing the gas to flow in
only one direction, from the hose to the manifold. The valves prevent gas from escaping from the
pipework during a discharge (except, of course, into the protected hazard area), should a cylinder not
be connected to the manifold.

They are positioned perpendicular to the manifold centre line, or failing that, at no more than 45º to the
vertical. They are supplied from the factory screwed into the manifold socket.

These valves have a telescopic mechanism which slides up and down. This system avoids problems
which screwing in the discharge hoses, when the floor on which the cylinders rest is irregular, the
cylinders are of different heights or a weighing system is fitted.

The check valves can be installed when the manifold is already fitted to its brackets, or by putting the
manifold on a workbench. This instruction is valid for the following check valve models: VALAN-40-23
and VALAN-50-125.

CAUTION

THE CHECK VALVES ARE ASSEMBLED IN THE FACTORY


IN THE DISCHARGE MANIFOLD
AND THEREFORE DO NOT REQUIRE ANY FORM OF HANDLING.

NEVERTHELESS, THE INSTRUCTIONS IN THIS CHAPTER CAN BE


USED FOR OPERATIONS AND GUIDANCE FOR POSSIBLE
REPLACEMENT DUE TO MALFUNCTION OR BREAKDOWN.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 47/112


To install the check valves in the discharge manifold, follow the instructions below:

To install the check valves in the discharge manifold, follow the instructions below:

1. Ensure that the manifold is properly secured by its brackets or on the workbench.

2. Check that interior threads of manifold sockets are clean and free from impurities. Clean the
threads with a wire brush for threads.

3. Hold the valve by hand and put Teflon tape or paste on to the male thread that is to be
screwed into the manifold (2” thread for the VALAN-40-23 and 2 1/2” thread for the VALAN-
50-125). If using Teflon tape, wrap 20 turns around the male thread of the check valve, if using
paste cover the second turn or thread of the male thread, and to the female thread of the
manifold socket. If a liquid thread sealant is to be used, before starting, ensure that it is
compatible with the gas with which it will come in contact, in this case, halocarbonated gases
(HFC-227ea, HFC-125 or HFC-23).

4. Screw the check valve fully into the manifold socket with spanner for these valves. After this
operation, none of the male valve thread must be visible as it must be completely screwed in.

5. Check, pressing with the index finger on the spindle or ball, that the internal movement of the
check valve is right.

Positioning of the check valve once installed in the manifold

The usual position of the check valve, once installed, is vertical as shown in figure 1, but it may also
be fitted at up to 45º to the vertical plane (figure 25).

Figure 24 Figure 25

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 48/112


1.8 INSTALLING THE PRESSURE SWITCH
The pressure switch is actuated by the pressure of the extinguishing agent at the moment of
discharge. As it is actuated, an electrical signal is transmitted which can be used to signal to the fire
panel that the system has discharged.

It has two contacts, one NC (normally closed) and the other NO (normally open) which change state
when the switch is actuated, and either can be used depending on the requirements of each
installation.
It also incorporates a lever that must be reset after each discharge for the device to work again. Once
actuated, the resetting is done manually, by pulling the ball outwards.

NC

1.- Connection for cable


B A
22 21

NO 2.- Electrical connection cover


3.- Reset knob
14 13

4.- Body RGS-IMPE


5.- 1/2" G female socket
OFF ON
L:\Logos\SIEX 2001.bmp

Reset once activated


L:\Logos\SIEX 2001.bmp
WP 360 bar

WP 360 bar

Position at rest Actuation position


Figure 26

Technical and electrical features of the pressure switch are as follows:

Technical Information

Operating medium HFC-227ea, HFC-125, HFC-23


Location Discharge Manifold
Case Metallic
Pressure connection Brass
Connection thread 1/2" BSP
Working temperature -40ºC to 60ºC
Activation pressure 6 bar and up
Tolerance +/- 0.34 bar
Working pressure at 50ºC with HFC-227 at 24 bar 34 bar
Working pressure at 50ºC with HFC-227 at 42 bar 56 bar
Working pressure at 50ºC with HFC-125 at 24 bar 40 bar
Working pressure at 50ºC with HFC-125 at 42 bar 75 bar
Working pressure at 50ºC with HFC-23 137 bar
Mechanical durability in millions of operations 2
Protection grade IP66
Connection for cable 3 threaded inlets for a tow press M20x1.5
No corrosivo; en interiores
Instalation
/ Non corrosive; indoors

Normally the switch is installed on the discharge manifold of cylinder bank systems, in the ½” BSP
female socket welded on to the manifold. It may also be installed in the pilot port of the cylinder valve,
in modular (single) cylinder systems, through a flexible release hose, and a 1/2” BSP to 1/4” BSP
reducer.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 49/112


1.8.1 Installing the pressure switch on the discharge manifold (cylinder bank)

To install the latching pressure switch in the discharge manifold, follow the instructions below:

CAUTION

BEFORE FITTING THE PRESSURE SWITCH, ENSURE THAT THE


CYLINDER BANK MAIN VALVE DOES NOT HAVE EITHER THE
ELECTRICAL OR MANUAL RELEASE HEAD CONNECTED.

3 4

1 MANIFOLD BRACKETS
2 CHECK VALVE
3 MANIFOLD
2 4 SOCKET 1/2" H
1
5 PRESSURE SWITCH
6 DISCHARGE PIPE

Figure 27

1. Ensure that the discharge manifold is properly secured to its brackets and that the actuation
devices of the cylinder banks (electrical and manual release heads) are removed or out of service.

2. Disconnect the release hose screwed to the cylinder or pilot bottle to prevent accidental discharge
of the cylinder banks.

3. Before fitting the pressure switch, check that it operates properly by pressing with a screwdriver or
punch into the 1/2" BSP pressure sampling point orifice. On carrying out this operation, the
actuation pin (part on which the pressure is exerted) must be latched and the reset knob will move
to the ON position. To unblock it, pull the knob or ball of the resetting device outwards, the
actuation pin returns to its original position and the reset knob goes to the OFF position.

If, during the test, the pressure switch does not operate correctly, send it to SIEX for further
testing.

4. Hold the pressure switch by hand, and wrap Teflon tape around the 1/2” BSP male connecting
thread (18 turns approximately).

5. Screw it into the 1/2" BSP female socket on the upper part of the manifold - the socket that is
welded to the manifold. Use a 28 mm non-adjustable spanner placing the flat faces on the body of
the switch. Tighten it until all the threads have been screwed in.

6. Detach the electrical connection cover, by removing its two screws, in order to make the switch
electrical connection to the cable from the fire panel. It has two contacts inside, one normally
closed and the other normally open; either may be used depending on the installation
requirements (see diagram in point 10 of section 1.8.2.).

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 50/112


1.8.2 Installing the pressure switch on modular cylinder systems
To install the latching pressure switch in modular cylinder systems, follow the instructions below:

CAUTION

BEFORE FITTING THE PRESSURE SWITCH,


ENSURE THAT THE CYLINDER VALVE,
IS NOT CONNECTED TO
EITHER THE ELECTRIC OR MANUAL RELEASE HEAD.

1 Cylinder
2 Protective flange
3 Pressure gauge
4 Valve RGS-MAM-12-4 ó 11-4
5 Actuator hose 1/4" G
6 Reducer 1/4" M - 1/2" H
7 Pressuge gauge
8 Male elbow
7
7
6
6
5
5

Screw clamps M4x20

4 4
8
3 EN 837-1

bar

2 2
KL. 1.6

1 1

Figure 28

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 51/112


1. Ensure that the cylinder is properly secured to its brackets and that the actuation devices of
the cylinder banks (electrical and manual release head) are removed or out of service.

2. Install the 1/4" BSP elbow in the valve pilot port, as is indicated in point 1.13 of this manual
“Installing the main valve pilot port”.

3. Before fitting the pressure switch, check that it operates properly by pushing a screwdriver or
punch into the 1/2" BSP pressure port. When carrying out this operation, the actuation pin
(part on which the pressure is exerted) must be latched and the reset knob will move to the
ON position. To unblock it, pull the knob or ball of the resetting device outwards. The actuation
pin returns to its original position and the reset knob goes to the OFF position.

If, during the test, the pressure switch does not operate correctly, send it to SIEX for further
testing.

4. Hold the pressure switch by hand, and wrap Teflon tape around the 1/2” BSP male connecting
thread (18 turns approximately).

5. Screw the 1/2" BSP female to male 1/4" BSP reducer to the 1/2" BSP pressure sampling
point. Teflon paste may also be used (on the male thread of the switch and the female of the
reducer).

6. Position and screw the pressure switch to the wall. Check that the joint is secure and sound.

7. Screw the other end of the flexible release hose to the 1/4" BSP elbow of the cylinder valve.
Do not use Teflon or glue, or any other type of sealant, since the seal is made between the
male cone on the hose and the female cone of the elbow. Tighten these connections fully with
a spanner to avoid leaks.

CAUTION

THE FLEXIBLE DISCHARGE HOSE MUST BE CONNECTED TO THE


PRESSURE SWITCH BEFORE BEING SCREWED ONTO THE ELBOW
ON THE CYLINDER VALVE PILOT PORT.

8. To make the electrical wiring connection between the switch and the fire panel, take away the
electrical connection cover by removing its two screws. It has two contacts inside, one
normally closed and the other normally open; either may be used depending on the installation
requirements (See sketch).

9. Fully re-tighten the two swivel union nuts on the hose with a spanner to achieve a gas-
tight seal.

10. Detach the electrical connection cover, by removing its two screws, in order to make the
switch electrical connection to the cable from the fire panel. It has two contacts inside, one
normally closed and the other normally open; either may be used depending on the installation
requirements.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 52/112


► Remove the cover of the electrical system box.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 53/112


► Remove the electrical unit from the housing without disconnecting the wiring.

► Press on the lower switch until the upper terminals are shortcircuited by the connecting rod. Check
that the control panel receives the corresponding alarm signal.

► Replace the electrical unit of the switch in the housing and rest the pressure switch by pulling on
the built-in ball.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 54/112


1.9 INSTALLING THE MANIFOLD PRESSURE RELIEF VALVE
(BURST DISC)
This device is only used on cylinder systems with directional or isolating valves. In the event of an
accidental discharge of the extinguishing agent, the gas would remain blocked in the manifold until the
burst disc of the exhaust valve detected an excess pressure and allowed the gas to exhaust to the
outside in a controlled manner.

The safety membrane is factory fitted with the appropriate operating torque. The exhaust pipe should
discharge outside, away from the hazard area or the cylinder bank storage area.

This is a safety mechanism whose purpose is to prevent excess pressure was building up in the
manifold when there are stop valves fitted which prevent the extinguishing agent from discharging.

optional exhaust pipe

Socket 1/2" for exhaust pipe

Metaloplastic joint 1/2"

Pressure relief valve

Socket 3/4" welded to manifold

Figure 29: Manifold pressure relief valve. (Code: POVREC20)

Technical Information

Operating medium HFC-227ea, HFC-125, HFC-23


Location Discharge manifold
Material Brass
Body working pressure 137 bar
Body test pressure 1080 bar
Average bursting pressure 185 +-5 bar
Inlet connection 3/4" BSP
Outlet connection 1/2" BSP
Bore size Ø 6,30 mm

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 55/112


1.10 INSTALLING DISCHARGE HOSES

1.10.1 Single cylinder system (modular cylinder)

The discharge hose must first be screwed into the discharge pipe, and then to the cylinder valve, in
that order.

CAUTION

THE FLEXIBLE DISCHARGE HOSE OR VALVE OUTLET ADAPTOR IN


THE CASE OF SINGLE (MODULAR) CYLINDERS MUST BE CONNECTED
TO DISCHARGE PIPING BEFORE BEING SCREWED ONTO THE
CYLINDER VALVE.

5
1 Cylinder
4 2 Protective flange
3 Valve RGS-MAM-20/40/50
3 0062 D ANGER:
THIS IS HIGH PRESSUR E CONTAIN ER, NOT TO CLEAR THE
4 Dischage hose (3/4" - 1" - 1 1/2" - 2")
5 Nipple
ACCESO RIES U NTIL IT IS PROPERLY SUBJECTED BY ITS BRAC KETS

2
30

6 Pipe
20 EN 837-1 40

10 50
bar
0 60

KL. 1.6

7 7

6
6
5
3

2 VdS

1 Cylinder (SMS) 5
4 2 Protective flange
1
TPED
1999/36/CE

3 Valve RGS-MAM-11-4 ó 12-4


Cylinder+Valve+Bursting disc+Protections device
Cylindre+Valve+Disque de rupture+Eléments de protection

Serial Number
Nº de Série

4 Cupper washer Ø 12x18x1,4 mm.


5 Flexible dischage hose FH-15CO
6 Adapter 1/2 " (asiento conico)- 1/2 " G
7 Pipe

Figure 30

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 56/112


To install the discharge hose in to a modular cylinder system, follow the instructions below:

1. First screw the adaptor or male-female nipple onto the discharge pipe.

The male thread of the nipple must have a conical seating to ensure that it seals with the
swivel nut on the ½”, 3/4", 1”, 1 1/2" or 2” discharge hose. The female thread of the nipple
must be a standard pipe thread with a flat seating. To connect the adaptor or nipple to the
discharge pipe, use Teflon tape on the male thread of the pipe.

The table below shows the various adaptors or nipples that must be used for each one of the
discharge hoses used in modular cylinder halogenated gas systems.

Type Cylinder
Adaptor or nipple
Discharge hose valve

¾” BSP male thread with conical seating,


FH-20HC 3/4” BSP flexible hose
¾” female thread with flat seating
RGS-MAM-20
1” BSP male thread with conical seating,
FH-25HC 1” BSP discharge hose
1” BSP female thread with flat seating
1 1/2” BSP male thread with conical seating,
FH-40HC 1 1/2” BSP discharge hose RGS-MAM-40
1 1/2” BSP female thread with flat seating
2” BSP male thread with conical seating,
Discharge hose FH-50HC 2” BSP RGS-MAM-50
2” BSP female thread with flat seating
FH-15CO discharge hose ½” BSP male thread with conical seating, RGS-MAM-
W 21.8x1/14” F to 1/2” BSP ½” BSP female thread with flat seating 11-4 y 12-4

2. Screw one end of the corresponding discharge hoses (see table above) to the nipple. To do
this, screw the female swivel nuts of the hose onto the male thread of the nipple. Do not use
Teflon or glue, or any other type of thread sealant, since the seal is made between the male
cone on the hose and the female cone of the nipple. Fully tighten these connections with a
non-adjustable or adjustable spanner to avoid leaks.

3. Remove the cylinder valve protective caps, having first ensured that the cylinder is properly
secured to the wall by its brackets. Do not remove the outlet safety plug from the valve yet.

4. Place the cylinder in position, with the valve outlet facing the discharge hose that is already
connected to the discharge pipe, and secure it with its straps and bracket. In this operation,
sometimes it is necessary to slightly slacken off the cylinder straps to be able to correctly
orientate the valve outlet. Take care to re-tighten the straps so that the cylinder is properly
secured to the wall by its brackets.

Remember that the discharge hose has to be screwed in to the discharge pipe before being
screwed into the valve output, as stated in point 2.

5. Remove the safety plugs from the cylinder valve output ports. Check that the bracket straps
are properly tightened.

6. Screw the other end of the flexible or rigid discharge hose (½”, 3/4", 1”, 1 1/2" or 2”), into the
outlet port of the cylinder valve (RGS-MAM-20/40/50/11-4 or 12-4). To do this, screw the
hose’s female swivel nut onto the male thread of the valve. Do not use Teflon, glue or any
other type of thread sealant, since the seal is made between the male cone of the hose and
the female cone of the valve outlet in the case of valves RGS-MAM-20/40/50, and via a
copper washer in the case of valves RGS-MAM-11-4 and 12-4. Tighten this connection fully
with a spanner to avoid leaks.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 57/112


1.10.2 Cylinder bank

The discharge hoses must be screwed first to the manifold check valves and then to the cylinder
valves.

CAUTION

THE FLEXIBLE DISCHARGE HOSES OR VALVE OUTLET ADAPTORS IN


THE CASE OF CYLINDER BANK SYSTEMS MUST BE CONNECTED TO
THE MANIFOLD CHECK VALVES BEFORE BEING SCREWED ONTO THE
CYLINDER VALVES.

5
1 Cylinder
4
2 Protective flange
3 PELI G RO: P ELI GR O: P ELI G RO:
3 Valve RGS-MAM-40/50
0062 EST O ES U N CO NTE NED OR D E ALTA P RE SI ÓN
NO Q UI TAR L OS A CCE SO RI OS , NI
M AN IP ULA RLO HAS TA Q UE ES TE BI EN S UJETO
0062 EST O ES U N CO NTE NED OR D E ALTA PRE SI ÓN
NO Q UI TAR L OS A CC ESO RI OS , NI
M AN IP UL ARLO HAS TA Q UE ES TE BI EN S UJETO
0062 ES TO ES U N CO NTE NED OR D E ALT A PRE SI ÓN
NO Q UI TA R LOS A CC ESO RI OS , NI
M A NI PUL ARL O HAS TA Q UE E STE BI EN S UJETO

4 Discharge hose 1 1/2" - 2" G


M ED IA NTE SU S HE RRA JES. M ED IA NTE S US HE RR AJES . M ED IA NTE S US HE RR AJES .

2 5 Check valve (VALAN 40-23 / 50-125)


6 Discharge manifold
1
Figure 31

To install the discharge hoses in a cylinder bank system, follow the instructions below:

1. The check valves come ready assembled from the factory in the discharge manifold and so do
not require any manipulation. Nevertheless, if it is necessary to replace them due to a
malfunction or failure, bear in mind the steps described in chapter 1.7 of this manual (Installing
check valves on the discharge manifold).

The following table shows the relationships between the discharge hoses, the check valves
and the cylinder valves used in cylinder bank halogenated gas systems.

Type
Check valve Cylinder valve
Discharge hose

FH-40HC 1 1/2” BSP discharge hose VALAN-40-23 RGS-MAM-40


Rigid hose FH-50HC 2” BSP VALAN-50-125 RGS-MAM-50

2. Screw one end of the corresponding discharge hoses (see table above) to the manifold check
valves. To do this, screw the female swivel nuts of the hose onto the male thread of the check
valves. Do not use Teflon or glue, or any other type of thread sealant, since the seal is
made between the male cone on the hose and the female cone of the check valve. Fully
tighten these connections with a non-adjustable or adjustable spanner to avoid leaks
(approximate torque 15 Nm).

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 58/112


1 Body VALAN 40-23 / 50-125
2 Telescopic nut VALAN 40-23 / 50-125
3 Telescopic part VALAN 40-23 / 50-125
4 Lock bolts

vr034cid.dwg

When performing this operation, if the telescopic part of the check valve should rotate, tighten
its two lock bolts with a 2.5 mm Allen key to prevent this turning movement.

3. Remove the cylinder valve protective caps, having first ensured that the cylinder is properly
secured to the wall by its brackets. Do not remove the outlet safety plug from the valve yet.

4. Position the cylinders, with the valve outputs facing the discharge hoses, which are already
screwed onto the manifold, and secure them with their straps and brackets. In this operation, it
is sometimes necessary to slightly slacken off the cylinder straps to be able to correctly
orientate the valve outlets. Take care to re-tighten the straps so that the cylinders are properly
secured to the wall by their brackets.

Remember that the discharge hoses must be screwed onto the manifold before being screwed
into the valve outputs, as stated in point 2.

5. Check that the bracket straps are properly tightened. Remove the safety plugs from the
cylinder valve output ports.

6. Screw the other end of the rigid discharge hoses (1”, 1 1/2" or 2”), into the outlet ports of the
cylinder valves (RGS-MAM-40/50). To do this, screw the female swivel nuts of the hoses onto
the male thread of the valve outlets. Do not use Teflon or glue, or any other type of thread
sealant, since the seal is made between the male cone on the hose and the female cone of
the valve outlet. Tighten these connections fully with a spanner to avoid leaks.

6
5

4
1 Cylinder
3 PELIGRO: PELIGRO: PEL IGRO:
2 Protective flange
0062 EST O ES U NC ONT ENEDOR DE ALT A PRESIÓ N
NO QUIT AR L OS ACCESOR O I S, NI 0062 EST O ES UN CONT ENEDORDE ALT A PRESIÓN
NO QUIT AR L OS ACCESORIO S, NI 0062 ESTO ES UN CONT ENEDORDE AL TA PRESIÓN
N OQ UIT ARL OS ACCESORIOS, NI

3 Valve RGS-MAM-40/50
MANIPUL AR LO HAST A Q UE ESTE BIEN SUJ ET O MANIPUL ARLO HAST A QUE ESTE BIENSUJET O MANIPUL ARLO HAST A QUE ESTE BIENSUJET O
M ED IA NT E SU S HERRAJES. M EDIANT E SUS HERRAJ ES. M EDIA NT E SUS HERRAJ ES.

4 Discharge hose 1 1/2" - 2"


2 5 Check valve (VALAN 40-23 / 50-125)
6 Discharge manifold
1

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 59/112


1.11 INSTALLING 227CN PNEUMATIC DISCHARGE HEAD

The purpose of this discharge head is to pneumatically actuate the valves of the cylinders on which it
is fitted. Once all the discharge hoses are connected the head will activate when the system is
released and pressure reaches the head.

The pneumatic activator can be installed to the upper part of the container valve (activation port) or to
the upper part of the electrical firing head (in cylinders that also possess electrical firing). Its function
is to pneumatically activate the valve (RGS-MAM-50/40/20) on which it is assembled.

All the pneumatic heads have an integral “T” or an elbow/bend in its pneumatic activation port. This
element is supplied from the manufacturer ready-adjusted together with its metal-plastic sealed joint.

CAUTION

BEFORE SCREWING IN THE PNEUMATIC RELEASE HEAD


TO THE VALVE ACTUATION PORT,
CHECK THAT THE ACTUATION PIN
IS WITHDRAWN (POSITION 1).

IF THE ACTUATION PIN IS IN POSITION 2,


WHEN SCREWING IN THE PNEUMATIC RELEASE HEAD,
THE EXTINGUISHING GAS CONTAINED IN THE CYLINDER
WILL DISCHARGE VIOLENTLY,
WHICH MIGHT CAUSE SERIOUS INJURY TO
TO THE PERSON HANDLING IT.

227DM
227CN
WP 137 bar
N - xxxxx

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 60/112


Technical Information

Operating medium HFC-227ea, HFC-125, HFC-23, N2


Valve type RGS-MAM-20/40/50/11-4/12-4
Material Brass
Re-set requirements Automatic (spring)
Working temperature -20ºC to +50ºC
Connection to the valve (activation port) or to the electrical actuator (227SOL) 3/4" BSP (female)
Thread of the pneumatic activation port (for Tee or Elbow) 1/4" BSP (female)
Link between pneumatic actuator and Tee or Elbow 1/4“ metal plastic joint
Average pressure when N2 pilot bottle is used 90 bar
Effective force at 50ºC with N2 pilot bottle 1760 N
Design pressure 137
Resistance test pressure to the internal pressure 205.5
Test pressure for the actuator strength 411
Minimum duration of the activation pressure 10 sg

To install the pneumatic discharge head, follow the instructions below:

1. Make sure that the cylinder is well attached by its fittings. Check that the valve outlet is threaded
to the discharge nipple and that this is threaded to the collector (cylinder bank) or discharge piping
(single cylinder system).

2. Hold the pneumatic discharge head and visually check that the piston is in POSITION 1.

3. Remove the plastic safety cap from the activation port of the valve and thread the rotary nut of the
pneumatic firing head into place. Do not use Teflon, adhesive, or any other type of thread sealant,
simply manually tighten it completely.

6
6
5
1.- Cylinder. 4
4
P ELI GRO:
2.- Protected bridle. 0062
P ELIGRO:

E STO ES UN CONTENEDOR DE A LTA PRE SIÓN


NO QUITA R LOS A CCE SORI OS , NI
MANI PULA RLO HA STA QUE ESTE B IEN SUJETO
MEDI ANTE S US HE RRA JES .

0062 E STO E S UN CONT ENEDOR DE A LTA PRES IÓN

3.- RGS-MAM-20/40/50 valve.


NO QUITAR LOS ACCES ORIOS, NI
M ANI PULA RLO HAS TA QUE ESTE BI EN SUJ ETO
ME DI ANTE SUS HERRAJ ES.

3 3
4.- Pneumatic actuator.
2 5.- Metalic-plastic washer 1/4" 2
6.- Tee or male elbow.
1 1

Remember that the link between the discharge head and the valve is made by a swivel nut
mechanism that allows the head to be turned up to 360º to the desired position.

4. Point 3 of this section (above), in which the tightening of the pneumatic release head to the valve
was described, must be qualified by the following point. It is advisable, before definitively
tightening the swivel nut with the hand, to orientate the pneumatic release head with its tee or
elbow towards the release hose. Once orientated the definitive tightening can be done. For more
information, read chapter 1.12 (Installation of flexible release hoses), of this manual below.

5. In the case of threading directly to the electrical firing head follow the same instructions as in point
3 of this section.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 61/112


CAUTION

BEFORE SCREWING IN THE ELECTRICAL RELEASE HEAD


TO THE VALVE ACTUATION PORT,
CHECK THAT THE ACTUATION PIN
IS WITHDRAWN (POSITION 1).

4
3
227DM
4
2 227CN
WP 137 bar
N - xxxxx

227DM

1.- Eléctrical actuator. 2 227CN


WP 137 bar
N - xxxxx

2.- Pneumatic actuator.


1 POSICION 1 : SIN
POSITION 1: STA

POSICION 2 : AC
POSITION 2: ACT
3.- Metalic-plastic washer 1/4". 1 POSICION 1 : SIN
POSITION 1: STA

POSICION 2 : AC
POSITION 2: ACT

4.- Tee or male elbow


Atención: Antes de roscar el actuador eléctrico al puerto d Atención: Antes de roscar el actuador eléctrico al puerto d
Warning: Before threading the electrical actuator to the activ Warning: Before threading the electrical actuator to the activ

- 0786 - 0786
V V
G 307013 G 307013
227SOL 227SOL
24V (DC) 24V (DC)
0,6 A 0,6 A
Nº Nº

6. Connect the corresponding flexible release hose as indicated in chapter 1.12 (Installing the flexible
release hoses).

7. To remove the pneumatic release head from the valve, gently loosen the swivel nut by hand or
with the hand. If it was screwed directly to the valve, the valve cover must not be turned during this
operation, because if it is, the contents of the cylinder might discharge violently, possibly causing
serious injury.

Never remove the pneumatic release head when the cylinder is not secured to the wall by
its brackets.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 62/112


1.12 INSTALLING FLEXIBLE DISCHARGE HOSES

These are used as a conduit to pneumatically actuate or release the extinguisher gas cylinder valves.
Their serial connections allow the gas, from the cylinder or pilot bottle, to flow through them and to
actuate the various pneumatic heads of the auxiliary valves. They are linked together by pneumatic
heads with a tee or elbow.

CAUTION

BEFORE SCREWING ON THE FLEXIBLE HOSES, ENSURE THAT THE MAIN


VALVE (PILOT CYLINDER), DOES NOT HAVE ITS ELECTRIC OR MANUAL
RELEASE HEAD FITTED.

5 6 7

1 Cylinder
4 227CN
Nº LOTE
227CN
Nº LOTE

2 Protective bridle
LOT No. LOT No.

0062
PELI GRO :

ESTO ES UN CO NTENEDO R DE ALTA PRESI ÓN


N O Q UITAR L OS ACCESORI OS, NI
MANIPUL ARLO HASTA Q UE ESTE BIEN SUJ ETO
MEDIAN TE SUS H ERRAJES.
0062
PELI GRO:

ESTO ES UN CO NTENEDO R DE ALTA PRESI ÓN


N O Q UITAR L OS ACCESORI OS, NI
MANIPUL ARLO HASTA Q UE ESTE BIEN SUJ ETO
MEDIAN TE SUS H ERRAJES.

3 Valve RGS-MAM-20/40/50
3 4 Pneumatic actuator 227CN
5 Male tee
2 6 Flexible actuator hose
7 Male elbow
1

To install the flexible release hoses, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this is connected to the manifold or discharge pipe.

2. Check that the pneumatic release heads are correctly orientated as indicated in the figure. If
not, loosen the swivel nut and re-position them in the correct position. Tighten the pneumatic
release heads as indicated in chapter 1.11 (Installing the 227CN pneumatic release head).

3 5
2 1
9 4
8

10 11 7 6

1.- Cylinder. 7.- Pressure gauge.


2.- RGS-MAM-20/40/50 valve. 8.- Pilot port.
3.- Male tee assembled into the pneumatic actuator. 9.- Presure switch connection.
4.- Male elbow assembled into the pneumatic actuator.10.- Electric actuator (227SOL).
5.- Flexible actuator hose 11.- Manual actuator (227DM).
6.- Valve outlet

3. For banks of less than 5 cylinders (one of them being the pilot cylinder), screw in, of the ends
of the first hose to the pilot port elbow of the cylinder valve, without using Teflon nor any other
type of sealant, since they are sealed by a metal-to-metal bicone.

To avoid possible accidental discharges of the cylinder banks, it is recommended to leave the
end of the first hose, which has to be connected to the pilot cylinder, loose (not screwed in) at
this time. When the system is completely finished and correctly installed, this hose will be the
last to be connected.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 63/112


4. The other end of the hose is screwed to the tee or elbow (in a bank of two cylinders) of the
pneumatic release head, in the same way as described above, without using Teflon or any
type of sealant, since they are sealed by a metal-to-metal bicone.

5. Repeat this operation successively until arriving at the last pneumatic release head which will
have an elbow.

6. Once all the release hoses are installed, fully tighten, with a non-adjustable spanner, all the
threaded joints between the hoses and the tees or elbows of the pneumatic release heads, to
achieve a gas-tight seal.

7. In banks of more than 5 cylinders follow the same instructions, with the exception that the first
cylinder will be a 2 litre pilot bottle. In this case, the first hose will be screwed to the adaptor
that is located on the outlet of the pilot bottle valve. The following steps are the same as for a
bank of fewer than 5 cylinders. Ensure, before screwing in the first hose, that the pilot bottle
outlet does not have a small leak (easily checked with soapy water).

8. Re-check that all the swivel nuts of the pneumatic release heads are tight.

3 5
2 1
4

9
8
7 10
9 7 6
8 1 Cylinder 7 Pressure gauge
10
7 2 Valve RGS-MAM-20/40/50 8 Valve RGS-MAM-11-4 ó 12-4
3 Male tee assembled into the pneumatic actuator 9 Electric actuator 227SOLP
4 Male elbow assemble into the pneumatic actuator 10 Pneumatic actuator 227DM
5 Flexible actuator hose
6 Valve outlet

EN 837-1

bar

KL. 1.6

1 Pilot bottle
- 0062 COMPRESSED GAS
NO INFLAMMABLE
2 Valve RGS-MAM-11-4 ó 12-4
3 Electrical actuator 227SOL
4 Pneumatic actuator 227DM
SSION DE CHARGE A 20ºC

STING PRESSURE OF THE SAFETY DISC


SION DE RUPTURE DU DISQUE DE SÉCURITÉ

FILL / CHARGE

5 Cupper washer ∅ 16 x 22 x 1,4 mm


SURIZED WHIT / PRESSURISÉ AU

TARE / TARE

AL WEIGHT / POIDS TOTAL

6 Adapterr W 21,8x1/14" H - 1/4" G M


DATE / DATE DE CHARGE

WORKING TEMPERATURE FROM -20ºC TO 50ºC


TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

7 Actuator hose FH-6PO

NOTE 1: It is recommended that, at this time, the end of the first hose that has to be connected to the cylinder or pilot
bottle (points 3 and 7) is left loose (without screwing in). In this way, possible accidental discharges of the
cylinder bank can be avoided.
When the system is completely finished and correctly installed, this hose will be the last to be connected.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 64/112


1.13 INSTALLING THE CYLINDER VALVE PILOT PORT

All the RGS-MAM-20/40/50 valves have a ¼” BNP connection (pilot port), that is used so that the
valve can operate as the main one in banks of fewer than 5 cylinders. When the main valve is
actuated (by its release head), the gas flows through its outlet and pilot port, actuating the various
pneumatic release heads, which, in turn, actuate the valves of the remaining cylinders.

When a bank of fewer than nine cylinders is used, the first acts as the pilot or main cylinder, and the
rest as ordinary secondary cylinders.
In secondary cylinders, pre-installed in the factory, a ¼ ” BSP plug threaded with Teflon tape will be
fitted in the pilot port.
In the pilot cylinder, however, there is a threaded elbow fitted with Teflon tape. Then, at the customer’s
site, the flexible Teflon hose is fitted, without the need for sealant because the seal is made with a
bicone.

CAUTION

THE PILOT PORT IN BANKS OF FEWER THAN 9 CYLINDERS,


IS DELIVERED ALREADY ASSEMBLED FROM THE FACTORY,
THEREFORE IT NEED NOT BE HANDLED.

THE INSTRUCTIONS IN THIS CHAPTER


ARE FOR OPERATIONAL AND GUIDANCE USE
FOR POSSIBLE REPLACEMENTS IN THE SYSTEM.
To install the pilot port, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe. The pilot
port may also be installed or replaced without the cylinder being connected to the discharge
hose, in which case, do not remove (or put on) the valve outlet safety plug while the cylinder is
being handled (secured, of course, to its bracket).

2. Check that the manual or electric release head is not connected to the valve. If it is, remove it.

6 6

1.- 1/4" pilot port.


5 2.- 1/4" male elbow.
3.- Burst port (burst disc).
1
4.- Cylinder connection.
5.- Outlet valve. 5
2
1 6.- Actuation port.
7.- Pressure gauge.
8 8.- Pressure switch connection. 3

3 4 7 4

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 65/112


RGS-MAM-12 RGS-MAM-12

5 5

4 4

1 1

2 2
6 6

3 3

1.- Pilot port.


2.- Burst port (burst disc).
3.- Cylinder connection.
4.- Outlet valve.
5.- Actuation port.
6.- Pressure switch connection.
7.- 1/4" male elbow.

3. Remove the 1/4" BSP pilot port end cap, with a non-adjustable spanner, from the valve that is
to be the main one.

4. Hold the 1/4" BSP elbow that connects to the pilot port and wrap Teflon tape onto one of its
terminals (18 turns approximately).

5. Screw the elbow terminal with the Teflon into the pilot port. Try to keep the elbow terminal
without the Teflon facing towards the first pneumatic release head with an angle of 45º to the
horizontal as shown in the figure.

CAUTION

BEFORE SCREWING THE ELBOW INTO THE PILOT PORT,


POSITION THE PNEUMATIC RELEASE HEAD OF THE FIRST SLAVE CYLINDER
WITH ITS DISCHARGE HOSE TO ENSURE PROPER
POSITIONING OF THE ELBOW.
THE INSTALLATION OF THE MALE ELBOW IN THE PILOT PORT
MUST BE ORIENTATED TOWARDS THE NEXT SLAVE CYLINDER
IN THE CYLINDER BANK AT AN ANGLE OF 45º
TO THE HORIZONTAL. OTHERWISE, THE HOSE WILL BE TOO
SHORT AND WILL NOT BE ABLE TO BE CONNECTED.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 66/112


- 0786

- 0786

- 0786
G 306011

G 306011

G 306011
VdS

VdS

VdS
WP137 BAR

WP137 BAR

WP137 BAR
FH-40HC

FH-40HC

FH-40HC
N - XXXXXX

N - XXXXXX

N - XXXXXX
RGS-MAM-40 RGS-MAM-40 RGS-MAM-40
EN 12094-4 EN 12094-4 EN 12094-4

30 30 30
20 40 20 40 20 40

10 50 10 50 10 50
bar bar bar
0 60 0 60 0 60

KL. 1.6 KL. 1.6 K L. 1.6


281112

281112

947 281112
UN: UN: UN:
947

947
M ASA MAX. AUTORIZ ADA M ASA M AX. AUTORIZ ADA M ASA M AX. AUTORIZ ADA
(34)

(34)

(34)
M AX. AUT HORI ZED CHARGE M AX. AUT HORI ZED CHARGE M AX. AUT HORI ZED CHARGE
(SP AIN) Nº6

(SP AIN) Nº6

(SP AIN) Nº6


KG. KG. KG.
Fax .-

Fax .-

Fax .-
CHARG E MAX. AUTORISÉE C HAR GE M AX. AUTORISÉE C HAR GE M AX. AUTORISÉE
Villalonquejar

Burgosde Montija

Villalonquejar

Burgosde Montija

onquejar
Burgosde Montija
947 281108

947 281108

947 281108
GAS/GAZ: GAS/GAZ: GAS/GAZ:

Villal
ALM ACENAR EN LUGAR VEN TI LADO / NO RESPIRAR EL GAS AL MACENAR EN LUG AR VENTI LADO / NO RESPIRAR EL GAS AL MACENAR EN LUG AR VENTI LADO / NO RESPIRAR EL GAS
C / Merindad

C / Merindad

C / Merindad
PARA MANI PULACIÓ N Y PRECAUCI ONES VER ETI QUET A CIL INDRO PARA M ANIPULACI ÓN Y PRECAUCIONES VER ET IQUET A CILINDRO PARA M ANIPULACI ÓN Y PRECAUCIONES VER ET IQUET A CILINDRO
Pol. Ind.

Pol. Ind.

Pol. Ind.
(34)

(34)

(34)
2 2 2
09001

09001

09001
T O BE ST ORED I N A WEL L VENT IL ATED AREA / DO NOT INHALE T O BE ST ORED I N A WEL L VENT IL ATED AREA / DO NOT INHALE T O BE ST ORED IN A WELL VENTI LATED AREA / DO NOT INHALE
Tel.-

Tel.-

Tel.-
F OR HANDLI NG I NSTR UCTI ONS SEE CYLI NDER'S LABEL F OR HANDLI NG I NSTR UCTI ONS SEE CYLI NDER'S LABEL F OR HANDLI NG I NSTR UCTI ONS SEE CYLI NDER'S LABEL

ST OCKER DANS UN END ROIT VENT IL É / N E PAS INHALER LE GAZ POUR STO CKER DANS UN ENDROI T VENT IL É / NE PAS INHALER LE GAZ POUR STO CKER DANS UN ENDROI T VENT IL É / NE PAS INHALER LE GAZ POUR
MANI PUL ATI ON ET PRECAUT IO NS, VOI R L 'ET IQUET TE SUR LE RESERVOIR MANI PULAT ION ET PREC AU TI ONS, VO IR L 'ET IQUETTE SUR LE RESERVOIR MANI PULAT ION ET PREC AU TI ONS, VO IR L 'ET IQUETTE SUR LE RESERVOIR

TPED TPED TPED


199 9/36/CE 199 9/36/CE 19 99/36 /CE
Organis mo N ot ific ado/N ot ified body /Organisme N ot ifié Organis mo N ot ific ado/N ot ified body /Organisme N ot ifié Organis mo N ot ific ado/N ot ified body /Organisme N ot ifié
(0062) BURE AU VERITAS (0062) BUREAU VERITAS (0062) BUREAU VERITAS
Cili ndro+Vál vul a+Di sco de rotura+Elementos de protecci ón Cili ndro+Vál vul a+Di sco de rotura+Elementos de protecci ón Cili ndro+Vál vul a+Di sco de rotura+Elementos de protecci ón
C yl inde r+Valve+Bursting di sc+Protec ti ons de vi ce C yl inde r+Val ve+B ursti ng disc+Prote cti ons devi ce C yl inde r+Val ve+B ursti ng disc+Prote cti ons devi ce
C yl indre+Valve+Disque de rupt ure+El éments de prot ec tion C yl indre+Val ve+Disque de rupture +Eléme nt s de prot ec ti on C yl indre+Val ve+Disque de rupture +Eléme nt s de prot ec ti on
Nº de Serie Nº de Serie Nº de Serie
Seria l Number Seria l Number Seria l Number
Nº de Série Nº de Série Nº de Série

RGS-MAM-40

FRONT VIEW OF A 3 CYLINDER BATTERY 45º


EN 12094-4
N-XXXXXX

UN CONTENEDOR DE ALTA PRESIÓN, NO QUITAR LOS ACCESORI OS NI MANIPULARL


E BIEN SUJETO MEDIANTE SUS HERRAJES.
GH PRESSURE CONTAINER, NOT TO CLEAR THE ACCESOR IES UNTIL IT IS PROPERLY SUBJECTED BY

RGS-MAM-40
EN 12094-4
N-XXXXXX

UN CONT ENEDOR D E ALT A PRESIÓN, NO QUI TAR LOS ACCESORIO S NI M ANIPULARL


E BI EN SUJET O M EDIANT E SUS HERRAJES.
GH PR ESSURE CONTAINER , NOT TO CLE AR T HE AC CE SORIE S UNT IL IT I SPR OPERLY SUBJE CTED BY

REAR VIEW OF A 3 CYLINDER BATTERY

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 67/112


1.14 INSTALLING THE RESETTABLE 227SOL AND 227SOL-E
ELECTRICAL DISCHARGE HEAD

The 227SOL or 227SOL-E resettable electric discharge head is installed on top of the cylinder valve
(actuation port). Its function is to electrically actuate the cylinder valve (RGS-MAM-20/40/50/11-4 and
12-4) on which it is fitted.

WARNING

BEFORE THREADING THE ELECTRICAL FIRING HEAD


TO THE ACTIVATION PORT OF THE VALVE,
CHECK THAT THE PISTON IS RETRACTED (POSITION 1).

IF THE PISTON IS IN POSITION 2 WHEN THREADING THE ELECTRICAL


FIRING HEAD, THE GAS EXTINGUISHER CONTAINED IN THE CYLINDER
COULD BE DISCHARGED VIOLENTLY, CAUSING SERIOUS
INJURIES TO THE PERSON HANDLING IT.

POSITION 1: STA

POSITION 2: ACT
Atención: Antes de roscar el actuador eléctrico al puerto d
Warning: Before threading the electrical actuator to the activ

- 0786
POSITION 1 : NOT ACTIVATED
V
G 309000
POSITION 2 : ACTIVATED
227SOL
2 24V (DC)
0,60 A

1 Connection for manual / neumatic actuator


2 Electrical connection
3 Rotating bolt. Actuation port

To install the resettable electrical release head, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe.

2. Holding the electric release head by hand, visually check that the actuation pin is in
POSITION 1.

3. Remove the head’s electrical connector and connect it to the cable from the fire panel. As it
has a polarity, respect the polarity as indicated below.

- The terminal marked 1 corresponds to the positive of the power supply.


- The terminal marked 2 corresponds to the negative of the power supply.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 68/112


- 2

1 D1
+ 1
+ Electroim n
24 V D2
- Electromagnet

2 2
3
1

227SOL 227SOL-E
Operating medium HFC-227ea, HFC-125, HFC-23
Valve type RGS-MAM-20/40/50 and RGS-MAM-11-4/12-4
Body Brass – Zinc steel
Actuator pointer Stainless steel
Actuation type Launching
Re-assembled requirements It means manual strength
Working temperature -20ºC to +50ºC
Valve connection (Activation port) 3/4" G (female)
Stroke 4 mm
Nominal tension 24V (DC)
Nominal current 0.6 A 0.98 A
Nominal power at 20ºC 14 W 23.56 W
Effective force provided by the actuator 115 N 200 N
Minimum duration of the activation electrical signal 2 seg.
Operation Continuos duty
Supervisión tensión 24 V
Max. Supervisión current 230 mA
Max. Supervisión power 5.5 W
Electrical connection 3-pin electrical plug (2poles+earth) DIN-43650
Diode type 1N4007
Minimum lifetime 20 years after manufacturing
Test Check 100%

4. Once the electrical connection is made, re-connect the electrical connector to the release
head.

5. With the discharge head in your hand (still not screwed into the valve), do a proper functional
test with power from the fire panel. When the head is energised, the actuation needle moves
to POSITION 2. If this is not the case, one of the screws may be loose; disconnect the
electrical circuit and proceed as follows:

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 69/112


6. Manually reset the 227SOLP or 227SOL electrical release head. To do this, apply force with
the resetting screw, or failing that with a sharp instrument (e.g. a punch) until the actuation pin
moves to POSITION 1. To check that the resetting has been carried out properly, give the
head a light sharp tap on a hard surface, and then check that the actuation pin is still in
POSITION 1.

227SOL
24V (DC)
0,60 A
Nº xx
POSITIONN 1 : NOT ACTIVATED
POSITIONN 2 : ACTIVATED

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 70/112


7. Remove the plastic safety plug from the valve actuation port and screw in, in its place, the
swivel nut of the electrical release head. Do not use Teflon, adhesive or any other type of
thread sealant; Just finger-tighten as far as possible, and then finally turn the nut 15º with a
32 mm non-adjustable spanner.

- 0786
V

4
G 309000
227SOL
24V (DC)
0,60 A

- 0786
V

4
G 309000
227SOL
24V (DC)
0,60 A

0062
PE LIGR O:

E ST O E S U N CONTE NE DOR D E ALTA P RES IÓN


N O QUITAR LOS A CC ESOR IOS , NI
MAN IPUL ARL O H AS TA QUE ES TE B IEN SUJETO
MEDIA NT E SU S HER RA JE S.
1 Cylinder 0062
PE LIGRO:

ES TO ES UN CONT ENE DOR DE ALTA P RE SIÓN


N O QUITA R LOS A CC ES OR IOS, NI
MAN IPU LAR LO H AS TA QU E ES TE B IEN SUJE TO
MED IAN TE S US HE RRA JES.

2 Protective bridle
3 3
3 Valve RGS-MAM-20/40/50
2 4 Electrical actuator 227SOL or 227SOL-B 2
1 1

4
4
3 1 Cylinder (SMS)
2 Protective bridle
3 Valve RGS-MAM-12-4 ó 11-4 3
4 Pneumatic actuator 227SOLP
2
EN 837-1

bar

KL. 1.6
EN 837-1

bar

KL. 1.6
2

1
1

CAUTION

BEFORE SCREWING THE ELECTRICAL RELEASE HEAD


TO THE VALVE ACTUATION PORT,
CHECK THAT THE ACTUATION PIN
IS WITHDRAWN (POSITION 1).

Remember that the link between the release head and the valve is made by a swivel nut
mechanism that allows the head to be turned through 360º to the desired position.

8. To remove the electrical release head from the valve, slowly loosen the swivel nut by hand or
with a non-adjustable spanner. When carrying out this operation, the valve cover must not be
turned, because if it is, the contents of the cylinder might discharge violently, possibly causing
serious injury.

Never remove the electrical release head when the cylinder is not secured to the wall by
its brackets.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 71/112


1.15 INSTALLING 227DM MANUAL DISCHARGE HEAD

The purpose of this discharge head is to actuate by manual force the valves of the cylinders on which
it is fitted. Once the safety ring the head is removed the manual lever can be turned in the opposite
direction from its resting position. This will move the needle and produce the release.

The rearmable manual activator can be installed in the upper part of the container valve (activation
port) or in the upper part of the electrical firing head (cylinders that also electrical firing). Its function is
to manually activate the valve (RGS-MAM-20/40/50/11-4 and 12-4) on which it is assembled.

CAUTION

BEFORE SCREWING THE MANUAL DISCHARGE HEAD ONTO THE


ACTUATION PORT OF THE VALVE, CHECK THAT THE ACTUATION
NEEDLE IS WITHDRAWN (POSITION 1).

WITH THE ACTUATION NEEDLE IN POSITION 2, SCREWING ON THE


MANUAL DISCHARGE HEAD WOULD CAUSE THE SUDDEN AND VIOLENT
DISCHARGE OF THE EXTINGUISHING GAS IN THE CYLINDER, WHICH
COULD CAUSE SERIOUS INJURY TO THE PERSON INVOLVED.

Manual actuator 227DM

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 72/112


2 227DM
Nº LOTE
LOT No.

1 Electrical actuator 227SOL


227DM
Nº LOTE
LOT No.
2
2 Manual actuator 227DM

1 227SOL 227SOL
1
24V (DC) 24V (DC)
0,60 A 0,60 A
Nº Nº

Technical Information

227DM/DMP
HFC-227ea, HFC-125,
Operating medium
HFC-23, N2
RGS-MAM-20/40/50
Valve type
RGS-MAM-11-4/12-4
Material Brass
Re-assembled requirements Automatic (spring)
Working temperature -20ºC to + 50ºC
Connection to the valve (activation port) or to the electrical
3/4" G (female)
actuator (227SOL)
Route of the lever to obtain the activation 86º

CAUTION

BEFORE SCREWING THE MANUAL RELEASE HEAD


TO THE VALVE ACTUATION PORT,
CHECK THAT THE ACTUATION PIN
IS WITHDRAWN (POSITION 1).

IF THE ACTUATION PIN IS IN POSITION 2,


ON SCREWING IN THE MANUAL RELEASE HEAD
THE EXTINGUISHING GAS CONTAINED IN THE CYLINDER
WILL DISCHARGE VIOLENTLY,
WHICH MIGHT CAUSE SERIOUS INJURY TO
TO THE PERSON HANDLING IT.

To install the manual release head, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe.

2. Holding the manual release head by hand, visually check that the actuation pin is in
POSITION 1.

3. Remove the plastic safety plug from the valve actuation port and screw in, in its place, the
swivel nut of the manual discharge head. Do not use Teflon, adhesive or any other type of
thread sealant; just finger-tighten as far as possible.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 73/112


Remember that the link between the discharge head and the valve is made by a swivel nut
mechanism that allows the head to be turned through 360º to the desired position.

4
227DM
Nº LOTE
LOT No.

1 Cylinder 4 227DM
Nº LOTE
LOT No.

2 Protective bridle
0062
DANGER:
THIS IS HIGH PR ESSURE CONTAINER , NOT T O CLE AR THE
AC CESOR IE S UNT IL IT IS PROPER LY SUBJE CTED B Y ITS BR ACKETS
3 Valve RGS-MAM-20/40/50 0062
DANGER :
THIS IS HIGH PRESSUR E C ONTAINER, NOT TO C LEAR THE
ACC ESORIES UNTIL IT IS PR OP ERLY S UB JEC TED B Y ITS B RAC KETS

4 Manual actuator 227DM 3


3 30
10

0
20
30
EN 8 37-1

bar
40

60
50

20 EN 837-1 40 KL. 1.6

10 50

2
bar
0 60

K L. 1.6

2
1
1
vc416cim.dwg

4
4
3 1 Cylinder (SMS)
2 Protective bridle
3 Valve RGS-MAM-12-4 ó 11-4 3
4 Pneumatic actuator 227DM
2
EN 837-1

bar

KL. 1.6
EN 837-1

bar

KL. 1.6
2

1
1
4. If screwing it directly to the electrical release head 227SOL, follow the same principles of point
3 above.

CAUTION

BEFORE SCREWING THE ELECTRICAL RELEASE HEAD


TO THE VALVE ACTUATION PORT,
CHECK THAT THE ACTUATION PIN
IS WITHDRAWN (POSITION 1).

5. Check that the safety ring and its seal are in perfect condition and are properly fitted to the
head. Do not remove the safety ring except if the discharge head is to be operated
manually.

6. To remove the manual release head from the valve, gently loosen the swivel nut by hand, and
always with the safety ring in place, as a precaution, so that the release head cannot be
accidently operated. If it was screwed directly to the valve, the valve cover must not be turned
during this operation, because if it is, the contents of the cylinder might discharge violently,
possibly causing serious injury.

Never remove the manual release head when the cylinder is not secured to the wall by
its brackets.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 74/112


1.16 INSTALLING THE 227DEE ELECTRIC SQUIB RELEASE HEAD

The 227DEE electric squib discharge head may be installed on the upper part of the cylinder valve
(actuation port) or on top of the electrical discharge head (for cylinders that also have electric release).
Its function is to electrically actuate the valve (RGS-MAM-20/40/50/11-4 and 12-4) on which it is fitted.
It consists of an explosive device which generates enough pressure to actuate the valve when
triggered by an electrical pulse.

This discharge head is supplied from the factory disassembled and consists of three parts, a
pneumatic discharge head, a ¼” copper joint and a CPER electric squib discharge head.

CAUTION

BEFORE SCREWING THE ELECTRICAL SQUIB DISCHARGE HEAD ONTO


THE ACTUATION PORT OF THE VALVE, CHECK THAT THE ACTUATION
NEEDLE IS WITHDRAWN (POSITION 1).

WITH THE ACTUATION NEEDLE IN POSITION 2, SCREWING ON THE


ELECTRICAL SQUIB DISCHARGE HEAD WOULD CAUSE THE SUDDEN
AND VIOLENT DISCHARGE OF THE EXTINGUISHING GAS IN THE
CYLINDER, WHICH COULD CAUSE SERIOUS INJURY TO THE PERSON
INVOLVED.

1 Rotating bolt 227CN


3 2 Body 227DEE ó DEEP
3 Joint 1/4 "
2 4 Exploding squib
227DEE
0,6A-24V (DC)
Nº LOTE
LOT No. 1

POSITION 1 : NOT ACTIVATED


POSITION 2 : ACTIVATED

227DEE

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 75/112


To install the electric squib discharge head, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe.

2. Holding the pneumatic discharge head by hand, visually check that the actuation head is in
POSITION 1.

3. Screw the explosive squib to the actuation port of the pneumatic discharge head (upper part)
fitting a ¼” copper joint as indicated in the figure, so that the seal is gas-tight.

4. Connect the electric cables of the explosive squib to the cable from the fire panel.

5. Visually check that the actuation pin of the electric squib discharge head is in POSITION 1.
The exploding squib cannot be actuated to check its operation because it can only be used
once, that is, if it is actuated electrically the internal explosive charge is fired, and cannot be
used again, but will have to be replaced with a new one.

6. Remove the plastic safety plug from the valve actuation port and screw in, in its place, the
swivel nut of the electric squib discharge head. Do not use Teflon, adhesive or any other
type of thread sealant; just finger-tighten as far as possible.

5
1 Cylinder
4 227DEE
2 Protective bridle
3 Valve RGS-MAM-20/40/50
0,6A-24V (DC)
Nº LOTE
LOT No.

4 Body 227DEE
3 5 Joint 1/4" 227DEE
0,6A-24V (DC)
Nº LOTE
LOT No.

6 Exploding squib
0062
DANGER:
THIS IS HIGH PRESSURE CONTAINER, NOT TO CLEAR THE
ACCESORIES UNTIL IT IS PROPERLY SUBJECTED BY ITS BRACKETS
0062
DANGER:
THIS IS HIGH PRESSURE CONTAINER, NOT TO CLEAR THE
ACCESORIES UNTIL IT IS PROPERLY SUBJECTED BY ITS BRACKETS
3

30 30

2
20 EN 837-1 40 20 EN 837-1 40

10 50 10 50

2
bar bar
0 60 0 60

KL. 1.6 KL. 1.6

1
1

5
1 (SMS) Cylinder
4
2 Protective bridle
227DEE
0,6A-24V (DC)
Nº LOTE
LOT No.

3 Valve RGS-MAM-12-4 ó 11-4


4 Body 227DEE 227DEE

3
0,6A-24V (DC)
Nº LOTE
LOT No.

5 Joint 1/4"
6 Exploding squib 3

2
EN 837-1

bar

KL. 1.6
EN 837-1

bar

KL. 1.6
2
1
1

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 76/112


Remember that the link between the discharge head and the valve is made by a swivel nut
mechanism that allows the head to be turned through 360º to the desired position.

7. If it is screwed directly to the electrical discharge head, follow the same principles of point 6
above.

CAUTION

BEFORE SCREWING THE ELECTRICAL DISCHARGE HEAD ONTO THE


ACTUATION PORT OF THE VALVE, CHECK THAT THE ACTUATION
NEEDLE IS WITHDRAWN (POSITION 1).

227DEE

2 0,6A-24V (DC)
Nº LOTE
LOT No.

227DEE
0,6A-24V (DC)
Nº LOTE
2
LOT No.

1 1
227SOL 227SOL
24V (DC) 24V (DC)
0,60 A 0,60 A
Nº Nº

1 Electrical actuator 227SOL


2 Pneumatic actuator 227DEE
8. To remove this discharge head from the valve, gently loosen the swivel nut by hand or with a
non-adjustable spanner. If it was screwed directly to the valve, the valve cover must not be
turned during this operation, because if it is, the contents of the cylinder might discharge
violently, possibly causing serious injury.

Never remove the electric squib discharge head when the cylinder is not secured to the
wall by its brackets.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 77/112


Instructions following the use of the electric squib discharge head 227DEE:

‰ When this head has been fired to release the cylinder system, the CPER percussion head
must be replaced with a new one. Unscrew the unit paying special attention to the release
of any residual pressure in the chamber of pneumatic head 227CN.

1 Rotating bolt 227CN


2 Pneumatic actuator 227CN/CNP
3 Joint 1/4 "
4 Exploding squib CPER

2 Residual pressure

227DEE 227DEE
0,6A-24V (DC)
0,6A-24V (DC)
Nº LOTE
1 Nº LOTE
LOT No. LOT No.

POSITION 1 : NOT ACTIVATED


POSITIONN 2 : ACTIVATED

‰ Pneumatic head 227CN resets itself thanks to an internal spring. However, after a release the
inside of the chamber of pneumatic head 227CN must be inspected, cleaned and blown out to
remove any residual dirt which may have entered during the explosive release.

‰ If the head does not reset after the process, use a punch or screwdriver to push the tip of the
needle. If it still does not reset, contact SIEX.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 78/112


1.17 INSTALLING THE PILOT BOTTLE (for banks of more than 5
cylinders)

2 litre pilot bottle with RGS-MAM-11-4 and 12-4 valve

This consists of a 2 litre cylinder, a protective flange and a RGS-MAM-11-4 or 12-4 valve.
The RGS-MAM-11-4 or 12-4 valve has a built-in 227SOL solenoid discharge head, together with a
227DM manual discharge head or a 227DEE electric squib discharge head, in addition to the
corresponding pressure gauge (0-200 bar).

Charged with dry nitrogen to 100 bar, it is actuated by an electric or manual signal and its purpose is
to actuate the extinguishing agent cylinder bank. When the pilot bottle is actuated, pressurised gas
flows through the release hoses and pneumatically actuates the various pneumatic discharge heads,
227CN, which, in turn, actuate the valves (RGS-MAM-20/40/50/11-4 and 12-4) on the slave or
secondary cylinders that contain the extinguishing agent.

CAUTION

YOU ARE HANDLING PRESSURISED EQUIPMENT

FAILURE TO FOLLOW THESE INSTRUCTIONS


MIGHT RESULT IN
THE PILOT BOTTLE DISCHARGING VIOLENTLY,
LEADING TO SERIOUS DAMAGE OR INJURY
TO THE SURROUNDING AREA OR TO THE PERSON HANDLING IT.

ON
OF
F

227DEE
227DM
0,6A-24V (DC)
Nº LOTE
Nº LOTE xxxxx
xxxxx LOT No.
LOT No.

1.- Manual discharge head (227DM).


2.- Electrical squib release head (227DEE)
3.- Electrical release head (227SOL)
4.- Valave RGS-MAM-12-4.
5.- Pilot bottle 2L.
6.- Modular braket
227SOL-A
24V (DC)
0,60 A
Nº xx

7.- Sticker SIEX.


8.- Protective bridle
9.- Pressure switch
EN 837-1

bar

KL. 1.6

- 0062 COMPRESSED GAS


NO INFLAMMABLE

SION ROTURA DISCO SEGURIDAD


STING PRESSURE OF THE SAFETY DISC
SION DE RUPTURE DU DISQUE DE SÉCURITÉ

RGA / FILL / CHARGE

SURIZADO CON
SURIZED WHIT / PRESSURISÉ AU

A / TARE / TARE

O TOTAL
AL WEIGHT / POIDS TOTAL

HA DE CARGA
DATE / DATE DE CHARGE

TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC


WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

POL. IND. VILLALONQUEJAR


C/ MERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112

Figure 32

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 79/112


ON
OF
F

227DEE
227DM
0,6A-24V (DC)
Nº LOTE
Nº LOTE xxxxx
xxxxx LOT No.
LOT No.

1.- Manual discharge head (227DM).


2.- Electrical squib release head (227DEE)
3.- Electrical release head (227SOL)
4.- Valave RGS-MAM-12-4.
5.- Pilot bottle 2L.
227SOL-A
24V (DC)
0,60 A
Nº xx 6.- Modular braket
7.- Sticker SIEX.
8.- Protective bridle
EN 837-1

bar

KL. 1.6

- 0062 COMPRESSED GAS


NO INFLAMMABLE

SION ROTURA DISCO SEGURIDAD


STING PRESSURE OF THE SAFETY DISC
SION DE RUPTURE DU DISQUE DE SÉCURITÉ

RGA / FILL / CHARGE

SURIZADO CON
SURIZED WHIT / PRESSURISÉ AU

A / TARE / TARE

O TOTAL
AL WEIGHT / POIDS TOTAL

HA DE CARGA
DATE / DATE DE CHARGE

TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC


WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

POL. IND. VILLALONQUEJAR


C/ MERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112

Figure 33

Technical Information

Cylinder capacity 2L 6,7L 13,4L


Contained gas in the cylinder N2
Valve type RGS MAM 11-4 ó 12-4
Actuator port Electric (Model 227SOL),
Actuation mechanism pneumatic (Mod. 227 CN) or manual (Mod.
227 DM)
Working temperature -20ºC to 60ºC
W28.8 x 1/14” W28.8 x 1/14” W28.8 x 1/14”
Valve-cylinder connection thread
o 1” NPT o 1” NPT o 1” NPT
Outlet valve thread W21.8 x 1/14”
Pressure switch connection thread (only RGS-MAM-12-4) 1/8” NPT
Pilot port connection thread (only RGS-MAM-12-4) 1/4” BSP
Cylinder ext. Diameter 100 mm 140 mm 204 mm
Cylinder min. Thickness 2.5 mm 2.5 mm 4.3 mm
Cylinder total lenght 640 mm 850 mm 820 mm
Necessary power 24V (DC) / 0,6 Amp / 10W
Pressure gauge 0-200 bar
Filling pressure at 20º C 100 bar
Cylinder pressure test 300 bar
Approval 99/36 CE

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 80/112


To install the pilot bottle, follow the instructions below:

1. First install the pilot bottle fixing bracket as indicated in chapter 1.5.1 of this manual (Installing
cylinder fixing brackets). Brackets for a single (modular) cylinder.

Before starting, carefully calculate its position, so that the distance from the pilot bottle to the
first cylinder is correct and the first flexible release hose is not too short (it should be either
500 or 1000 mm). Adjust the RGS-MAM-11-4 or 12-4 valve output so that it faces the
pneumatic discharge heads of the cylinders which are to be actuated.

2. Check with soapy water that the output valve is not leaking. To do this, remove its protective
or safety plug. Keep the plug for later use.

3. Connect the electrical (227SOL) and manual (227DM) discharge heads, ensuring that they are
reset (as indicated in 1.14 and 1.15 of this manual).

CAUTION
Never put over the actuation port electric-solenoid (Mod. 227 SOL) when valve core 2 is
assembled in to the valve

Valve core 2 Valve core 1

4. Carefully remove the safety plug, gradually to make sure there is no leak, and screw in the
female W21.8x1/14” adapter to the ¼” BSP male thread of the valve outlet, placing a
12x18x1.4 copper washer inside the female thread of the W21.8x1/14” adaptor. Firmly tighten
this joint with a 30 mm non-adjustable spanner.

1 Pilot bottle
227DM
Nº LOTE
LOT No.
2 Valve RGS-MAM-11-4 ó 12-4
3 Electrical discharge head 227SOL
4 Manual release head 227DM
5 Cupper washer ∅ 16 x 22 x 1,4 mm
227SOL
24V (DC)
0,60 A

6 Adapter W 21,8x1/14" H - 1/4" G M
7 Release hose FH-6PO

EN 837-1

bar

KL. 1.6

5. Finally, manually connect the flexible release hose (500 or 1000 mm) to the tee of the first
pneumatic discharge head of the cylinder bank. Do not use Teflon or any other type of
sealant, since it is sealed with a metal-to-metal bicone.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 81/112


227DM
Nº LOTE
LOT No.

227SOL
24V (DC)
0,60 A

EN 837-1

bar

KL. 1.6

227CN
WP 137 bar
Nº LOTE
LOT No.

0062 DANGER:
TH IS IS HIGH PRESSURE CO NTAINER, NOT TO CLEAR THE
ACCESORIES UNTIL IT IS PROPERLY SUBJECTED BY ITS BRACKETS

1 Cylinder
2 Valve RGS-MAM-20/40/50 20
30
EN 837-1 40

3 Pneumatic release head 227CN


10 50
bar
0 60

KL. 1.6

4 Release hose FH-6PO


5 Tee or elbow 1/4" G

6. Go back and firmly tighten, with a 19 mm non-adjustable spanner, the threaded joints of the
two ends of the hose (at the pneumatic discharge head of the bank of cylinders end, and the
W21.8x1/14” F - 1/4" BSP M adaptor end) to achieve a gas-tight seal.

11

10
13 14
ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.

9 227SOL-A
24V (DC)
0,60 A
Nº xx

EN 837-1

bar

8
KL. 1.6
- 0786
G 306011
VdS

12
WP137 BAR
FH-40HC

N - XXXXXX

- 0062 COMPRESSED GAS

7
NO INFL AMMABL E

RGS-M AM-40
EN 12094-4

SSION DE CHARGE A 20ºC

SION ROTURA DISCO SEGURIDAD


S TING PRESS URE OF THE SAF ETY DIS C
S ION D E RUP TURE D U DISQ UE DE S ÉCU RITÉ

R GA / FILL / CHARGE

SURIZADO CON
SURIZED WHIT / PRESSURISÉ AU

4
A / TARE / TARE

O TOTAL 30
AL WEIGHT / POID S TOTAL
20 40
H A DE C ARGA

6
10 50
DATE / DA TE DE CHARGE

TEM PERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC 0 bar 60


WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATU RE D E FONCTIO NNEMENT DE -20ºC A 50ºC
KL. 1.6

POL. IND. VILLALONQUEJAR


C / MERIND AD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN
T el.: (34) 947 281108 Fax: (34) 947 281112

5 3
281112

UN:
(34) 947

MASA MAX. AUTO RIZADA


MAX. AUTHORIZED CHARGE
Tel.- Burgos Montij a Nº6

Fax.-

CH ARGE MAX. AUTO RISÉE KG .


ill alonquejar

(SPAIN)
947 281108

GAS/GAZ:
de
C/ Merindad

ALMACENAR EN LUG AR VENT ILADO / NO RESPIRAR EL GAS


Ind. V

PARA MANIPULACIÓN Y PRECAUCIONES VER ET IQUETA CILINDRO


(34)

2
09001

TO BE ST ORED IN A WEL L VENTILAT ED AREA / DO NOT INHALE


Pol.

FO R HANDLING INSTRUCT IO NS SEE CYLINDER'S LABEL

ST OCKER DANS UN ENDRO IT VENTILÉ / NE PAS INHALER LE GAZ POUR


MANIPULAT IO N ET PRECAUTIONS, VOIR L'ET IQUETTE SUR LE RESERVOIR

TPED
1999/36/CE
Organism o Notific ado/Notified body/Organisme Notifié
(0062) BUREAU VERITAS
Cilindro+Válvula+Disco de rotura+Elementos de protección
Cylinder+Valve+Bu rsting d isc+Protections d evice
Cylin dre+Valv e+Disq ue de rup ture+Eléments d e pro tection

2
Nº de Serie
Serial Number
Nº de Série

Nº Denomination Types
1 PI marking cylinder sticker
2 Cylinder sticker toxic gas
3 Bridle
4 Container valve RGS-MAM-40 / RGS-MAM-50
5 Pilot cylinder (1) 2 litres
6 Pilot cylinder bracket
7 Bridle
8 Pressure gauge 5140-P315 1/8” NPT
9 Pilot cylinder valve RGS-MAM-11-4 ó 12-4
10 Re-assembled electrical actuator 227SOL
11 Manual actuator 227DM
12 Adaptor W21.8x1/14” H – 1/4" G M
13 Actuator hose FH-6PO
14 "T" or elbow 1/4" G

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 82/112


Operational test with the charged pilot bottle (installed)

There are two ways to perform this test, during maintenance or operation.
In both cases adaptor 14W21.8x1/14” F - 1/4" BSP M must be removed from the valve outlet and the
safety plug inserted in its place.

ƒ To perform this test, either during maintenance or operation, adaptor 14W21.8x1/14” F - 1/4"
BSP M must be removed from the valve outlet and the safety plug inserted in its place.

ƒ Detach and unscrew resettable electric discharge head 227SOL and manual discharge head
227DM from their position in the RGS-MAM-11-4 or 12-4 valve actuation port.

ƒ Holding the discharge head by hand (still not screwed into the valve), visually check that the
actuation pin is in POSITION 1. Carry out a true functional test with power from the fire panel.
When the head is energised, the actuation pin will move to POSITION 2.

ƒ Manually reset the electrical release head. To do this, apply force to the actuation pin with a
sharp instrument (e.g. a punch) until the actuation pin goes to POSITION 1. To check that the
resetting has been done properly, give the head a light sharp tap on a hard surface, and then
check that the actuation pin is still in POSITION 1.

227SOL

- 0000
V
G 307000
227SOL
24V (DC)
0,60 A

Reset screw

POSITION 1 : NOT ACTIVATED


POSITION 2 : ACTIVATED

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 83/112


1.18 INSTALLING THE PILOT BOTTLE WITH AN INDIRECT
PNEUMATIC DELAY

The function of the pilot bottle with a pneumatic delay is to delay release of the cylinders (for 30 or 60
seconds) to give time to evacuate the hazard area.
It is fitted between the pilot bottle and the first slave or auxiliary cylinder.
ON
OF
F

227DM
Nº LOTE
xxxxx
LOT No.

ON
OF
F

227DM
227SOL-A Nº LOTE
xxxxx
LOT No.
24V (DC)
0,60 A
Nº xx

ENTRADA / INLET
RGS-MAM-4

Tiempo de retardo:
Delay time: S

EN 837-1

SALIDA / OUTLET
bar

KL. 1.6

1.- Pilot bottle 2L.


- 0062
2.- CE marking sticker
COMPRESSED GAS
NO INFLAMMABLE

ENTE EXTINTOR
INGUISH AGENT / AGENT EXTINCTEUR

3.- Protective bridle


DE CILINDRO
INDER No. / Nº DE CYLINDER

SION DE CARGA A 20ºC


PRESSURE AT 20ºC
SSION DE CHARGE A 20ºC

SION ROTURA DISCO SEGURIDAD

4.- Adapter 1/2" G M - 1/4" G M.


STING PRESSURE OF THE SAFETY DISC
SION DE RUPTURE DU DISQUE DE SÉCURITÉ

RGA / FILL / CHARGE

SURIZADO CON
SURIZED WHIT / PRESSURISÉ AU

5.- 1/4" Metalic-plastic joint A / TARE / TARE

O TOTAL
AL WEIGHT / POIDS TOTAL

HA DE CARGA

6.- Valve RGS-MAM-4 DATE / DATE DE CHARGE

TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC


WORKING TEMPERATURE FROM -20ºC TO 50ºC
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

POL. IND. VILLALONQUEJAR

7.- Manual release head 227DM


C/ MERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112

Valve RGS-MAM-4 has a built-in manual discharge head (227DM) on top, whose function is to abort
the delay and release the bank of cylinders immediately.

When the pilot bottle or cylinder is actuated, gas flows to the pneumatic delay via its RGS-MAM-4
valve and fills the previously empty bottle. When it is full (after a specific, adjustable time) to the
necessary pressure, the piston of valve RGS-MAM-4 operates, gas flows through the discharge hoses
and pneumatically actuates all the valves on the slave or secondary cylinders containing the
extinguishing agent.

To install the pneumatic delay, follow the instructions below:

1. First install the pilot bottle fixing bracket as indicated in chapter 1.5.1 of this manual (Installing
cylinder fixing brackets). Brackets for a single (modular) cylinder.
Before starting, carefully calculate its position, so that the distance from the pilot bottle to the
delay is correct and the first flexible release hose is not too short (either 500 or 1000 mm).
Adjust the RGS-MAM-4 valve outlet so that it faces the cylinders to be released.

2. Use soapy water to check that the pilot valve is not leaking. To do this, remove its protective
or safety plug. Keep the plug for later use.

3. For the indirect delay: Both 1/2" BSP M - 1/4" BSP M adaptors are factory screwed into the
inlet and outlet of valve RGS-MAM-4, with a ½” metaplastic washer on the male threads of the
adaptors. Firmly tighten this connection with a 26 mm non-adjustable spanner.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 84/112


CAUTION

BOTH 1/2" BSP M - 1/4" BSP M ADAPTORS ARE FACTORY FITTED AND DO
NOT NEED TO BE ADJUSTED.

THE INSTRUCTIONS IN THIS CHAPTER CAN BE USED FOR OPERATION


AND GUIDANCE FOR POSSIBLE CHANGES TO THE SYSTEM.

ON
OF
F

227DM
Nº LOTE
xxxxx
LOT No.

INLET 1/2" BSP


RGS-MAM-4

Tiempo de retardo:
OUTLET 1/2" BSP
Adapter Delay time: S

1/2" G M - 1/4" G M
Adapter
1/2" G M - 1/4" G M
Metalic-plastic washer 1/2" BSP

4. Manually connect the two flexible discharge hoses (500 or 100 mm) to the 1/4“ BSP M threads
of the adaptors (factory fitted) without using Teflon or any other type of sealant, as there is a
metal-to-metal bicone seal. One of these will come from the hose from the outlet port of the
pilot bottle and the other from the tee of the first pneumatic discharge head on the cylinder
bank. Firmly tighten this joint with a 19 mm non-adjustable spanner.

5. Retighten the connections between the two hoses and the delay on the pilot bottle and the
first cylinder on the bank, using a non-adjustable spanner to make a gas-tight seal.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 85/112


ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.

ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.
227SOL-A
24V (DC)
0,60 A
Nº xx

227CN
Nº LOTE
xxxxx
LOT No.
RGS-MAM-4

Tiempo de retardo:

- 0786
Delay time: S

G 306011
VdS
WP137 BAR
FH-40HC

N - XXXXXX
EN 837-1

bar

KL. 1.6

RGS-MAM-40
EN 12094-4

30
20 40

10 50
bar
0 60

- 0062 COMPRESSED GAS


NO INFLAMMABLE
- 0062 COMP RES SED GAS
NO INF LAMMABLE K L. 1.6

SSION DE CHARGE A 20ºC


SSION DE CHARGE A 20ºC

SION ROTURA DISCO SEGURIDAD SION ROTURA DISCO SEGURIDAD


STING PRESSURE OF THE SAFETY DISC STING PRESSURE OF THE SAFETY DISC
SION DE RUPTURE DU DISQUE DE SÉCURITÉ SION DE RUPTURE DU DISQUE DE SÉCURITÉ

RGA / FILL / CHARGE RGA / FILL / CHARGE

SURIZADO CON SURIZADO CON


SURIZED WHIT / PRESSURISÉ AU SURIZED WHIT / PRESSURISÉ AU

A / TARE / TARE A / TARE / TARE

281112
O TOTAL O TOTAL
UN:

(34) 947
AL WEIGHT / POIDS TOTAL AL WEIGHT / POIDS TOTAL
MASA MAX. AUTORIZADA
MAX. AUTHORIZED CHARGE
HA DE CARGA HA DE CARGA

Tel.- Burgos Montija Nº6

Fax.-
CHARGE MAX. AUTORISÉE KG.

uejar
DATE / DATE DE CHARGE DATE / DATE DE CHARGE

(SPAIN)
947 281108
Villalonq
TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC TEMPERATURA DE FUNCIONAMIENTO DE -20ºC A 50ºC GAS/GAZ:

de
WORKING TEMPERATURE FROM -20ºC TO 50ºC WORKING TEMPERATURE FROM -20ºC TO 50ºC

C/ Merindad
ALMACENAR EN LUGAR VENTILADO / NO RESPIRAR EL GAS
PARA MANIPULACIÓN Y PRECAUCIONES VER ETIQUETA CILINDRO

Pol. Ind.
TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC TEMPÉRATURE DE FONCTIONNEMENT DE -20ºC A 50ºC

(34)
2

09001
TO BE STORED IN A WELL VENTI LATED AREA / DO NOT INHALE
FOR HANDLING INSTRU CTIONS SEE C YL INDER'S LABEL

POL. IND. VILLALONQUEJAR POL. IND. VILLALONQUEJAR STOCKER DANS UN ENDROIT VENTILÉ / NE PAS INHALER LE GAZ POUR
MAN IPULATION ET PRECAUTIONS, VOIR L'ETIQU ETTE SUR LE RESERVOIR
C/ MERINDAD DE MONTIJA Nº6 C/ MERINDAD DE MONTIJA Nº6
09001 (BURGOS) - SPAIN 09001 (BURGOS) - SPAIN
Tel.: (34) 947 281108 Fax: (34) 947 281112 Tel.: (34) 947 281108 Fax: (34) 947 281112

TPED
1999/36/CE
Organismo Notificado/Notified body/Organisme Notifié
(0062) BUREAU VERITAS
Cilindro+Válvula+Disco de rotura+Elementos de protección
Cylinder+Valve+Bursting disc+Protections device
Cylindre+Valve+Disque de rupture+Eléments de protection
Nº de Serie
Serial Number
Nº de Série

Installing the indirect pneumatic delay

Nº Denomination Types
61 / 67,5 / 80 / 84 / 100 / 108,4 /
1 Manifold cylinders 120 / 127 / 150 / 180
2 Slave container valve RGS-MAM-20/40/50
3 Pilot cylinder (1) 2 litres
4 Pilot cylinder valve RGS-MAM-11-4 ó 12-4
5 Cupper washer Ø 16 x 22 x 1,4 mm.
6 Adaptor W21.8x1/14” H – 1/4" BSP M
7 Actuator hose FH-6PO
8 “Tee” or elbow ¼” BSP M
9 Manual actuator 227DM
Pneumatic delayer
h) Cylinder
10 h) 2 litres
i) Valve
i) RGS-MAM-4
j) Adapter
j) 1/2” BSP M – ¼”” BSP M

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 86/112


1.19 INSTALLING THE REMOTE RELEASE PNEUMATIC LINE

The remote pneumatic release line may be used in cylinder banks or in modular cylinders, but its
actuation must always be at a distance of less than 90 metres.

The remote release will be carried out by a pilot bottle (with electric and manual release) and a line of
pneumatic pipe that carries the pressurised gas to actuate all the pneumatic discharge heads of the
cylinders.

The line of pneumatic pipe may be installed in 4x6 copper pipe with bicone fittings or in 1/4" BSP
schedule 40 steel pipe.

The pilot bottle can also be supplied inside a sheet steel cabinet painted black or red.

The following limitations must be taken into account if 4 x 6 copper pipe is used:

A. Maximum total length of copper pipe: 20 metres (for greater lengths contact SIEX).

B. Maximum length between the first pneumatic actuator head and the last: 20 metres.

C. The maximum length of copper pipe between the pilot bottle and the first pneumatic release
head is 20 metres.

Maximum lenght: 90 m

Maximum lenght: 20 m Maximum lenght: 30 m

ON
O FF

227DM
Nº LOTE xxxxx
LOT No.

227SOL-A
24V (DC)
0,60 A
Nº xx

E N 837-1

bar

KL. 1.6

- 0062 COMP RE SSE D GAS


NO INFL AMM ABLE

SSION DE CHARGE A 20ºC

SION ROTURA DISCO SEGURIDAD


S TI NG PRESS URE OF THE S AFETY DISC
S ION DE RU PTURE DU DI SQU E D E S ÉCURITÉ

RGA / FILL / CHARGE

SURIZADO CON
SUR IZED WHIT / PRESSURISÉ AU

A / TAR E / TARE

O TOTAL
AL WEIGHT / POIDS T OT AL

HA DE CA RGA
DAT E / DATE DE C HARGE

TE MPERATURA DE FUNCIONA MIENTO DE -20ºC A 50ºC


WOR KING T EMPE RATURE FROM -20ºC TO 50ºC
T EMPÉR ATUR E DE FONC TIONNEMENT DE -20ºC A 50ºC
RGS-MAM-20 RGS-MAM-20 RGS-MAM-20
POL. IND. V ILLALONQUEJA R EN 12094-4 EN 12094-4 EN 12094-4
C/ ME RINDAD DE MONTIJA Nº6
09001 (B URGOS ) - SP AIN
Tel.: (34) 947 281108 Fax: (34) 947 281112

30 30 30
20 40 20 40 20 40

10 50 10 50 10 50

0 bar 60 0 bar 60 0 bar 60

KL. 1 .6 KL. 1.6 KL . 1.6

Nº Denomination Types
1 Pilot cylinder (1) 2 litres
2 Adaptor W21.8x1/14” H – 1/4" BSP M
3 ¼” to bi-cone cooper tube adaptor
4 6x4 mm cooper tube
5 “Tee” or elbow 1/4" BSP M
6 Pneumatic actuator 227CN
7 Discharge hose 3/4”-1 ½”-2”

D. The distance mentioned in point C may be increased to up to 70 metres when only one
pneumatic release is being fed (modular cylinder), or a bank of a maximum of 8 cylinders. In
this case the design of the cylinder bank would be standard, with all the cylinders connections
linked by flexible release hoses. The 70 metres is measured between the pilot cylinder and the
first release head of the cylinder bank.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 87/112


Maximum lenght: 70 m
ON
O FF

227DM
Nº LOTE
xx xxx
LOT No.

227 SOL-A
24V (DC)
0,60 A
Nº x x

EN 8 37 -1

bar

K L.
K L. 1.6
1.6

- 0062 C OMPRESSED GAS


NO INFLAMMA BLE

- 0786

- 0786

- 0786

- 0786
G 306011

G 306011

G 306011

G 306011
VdS

VdS

VdS

VdS
S SI ON DE CHARGE A 20ºC

S ION RO TURA DIS CO SE GURIDAD


ST ING P RESSU RE OF TH E SAFE TY D ISC
SI ON DE RU PT UR E D U D ISQU E DE SÉCU RITÉ

RGA / FI LL / CHARGE

WP137 BAR

WP137 BAR

WP137 BAR

WP137 BAR
S URIZADO CON

FH-40HC

FH-40HC

FH-40HC

FH-40HC
N - XXXXXX

N - XXXXXX

N - XXXXXX

N - XXXXXX
S URIZED WHIT / P RESS URISÉ AU

A / TA RE / TARE

O TOTAL
AL WEI GHT / P OI DS TOTAL

HA DE CARGA
DATE / DATE DE CHARGE

TE MPE RATURA DE FUNCIONAMI ENTO DE -20ºC A 50ºC


WORKI NG TEMPERATURE FROM -20º C TO 50ºC
TEMP ÉRATURE DE F ONCTIONNEMENT DE - 20ºC A 50ºC

P OL. IND. V ILLA LONQUEJ AR


C/ MERINDAD DE MONTI JA Nº6
09001 (B URGOS ) - S PA IN
Tel .: (34) 947 281108 Fax : (34) 947 281112

RGS-MAM-40 RGS-MAM-40 RGS-MAM-40 RGS -M AM -40


EN 12094-4 EN 12094-4 EN 12094-4 E N 12094-4

30 30 30 30
20 40 20 40 20 40 20 40

10 50 10 50 10 50 10 50
bar bar bar bar
0 60 0 60 0 60 0 60

K L. 1.6 KL . 1 .6 KL. 1.6 KL. 1. 6

947 281112

947 281112

281112

281112
UN: UN: UN: UN:

947

947
- (34)

- (34)

- (34)

- (34)
MASA MAX. AUTO RIZADA M ASA M AX. AUTORIZADA MASA MAX. AUTO RI ZADA MAS A MAX. AUTORIZADA
M AX. AU THOR IZED CHARGE MAX. AUTHO RIZED CHARGE M AX. AUTHO RIZED CHARGE MAX. AUTHORIZED CHARGE

º6

º6

º6

º6
KG.

Fax.

Fax.

Fax.

Fax.
KG . KG. KG .

Tel.- Burgos M ontija N

Tel.- Burgos M ontija N

Tel.- Burgos M ontija N

Tel.- Burgos M ontija N


C HA RG E M AX. AUTORISÉE CHARG E MAX. AUTO RISÉE CHARGE M AX. A UTORISÉE CHARGE MAX. A UTORISÉE

V illalonquejar

V illalonquejar

V illalonquejar

V illalonquejar
947 281108N)

N)

947 281108N)

947 281108N)
281108
(SPAI

(SPAI

(SPAI

(SPAI
GAS/GAZ: GAS/GAZ: GAS/GAZ: GAS/GAZ:

de

de

de

de
C / Merindad

C / Merindad

947

C / Merindad

C / Merindad
AL MACENAR EN L UG AR VENTI LADO / NO RESPIRAR EL GAS A LMACENAR EN LUGAR VENTIL ADO / NO RESPIR AR EL GAS AL MACENAR EN L UGAR VENTILADO / NO RESPIRAR EL GAS ALMACENAR EN LUGAR VENTILADO / NO RESPIRAR EL GAS
PARA MA NI PULACI ÓN Y PRECAUCIONES VER ETI QUETA CILINDRO

Ind.

Pol. Ind.

Ind.

Ind.
PARA MANI PULACI ÓN Y PRECA UC IONES VER ETIQ UETA CILI NDRO PARA M ANIPUL ACIÓN Y PRECAUCIO NES VER ETIQUETA CIL INDRO P AR A MANI PULACIÓ N Y P RECAUCI ONES VE R ETIQ UETA CILINDRO

(34)

(34)

(34)

(34)
2 2 2 2

09001

09001

09001

09001
TO BE STORED IN A WELL VENTI LATED AREA / DO NOT INHALE TO BE S TORED IN A WELL VENTILATED AREA / DO NO T I NHAL E TO BE STO RED IN A WELL VENTIL ATED AREA / DO NOT INHALE TO BE STORED IN A WELL VENTI LATED AREA / DO NOT INHALE

Pol.

Pol.

Pol.
FOR HANDL ING INSTRUCTI ONS SEE CYLINDER'S LABEL FO R HANDL ING INSTRUCTIO NS SEE CYL INDER'S L ABEL FOR H AN DL ING INSTRUCTI ONS S EE CYLINDER'S LABEL FOR HANDLING INSTRUCTI ONS S EE CYLI NDER'S LABEL
STOCKER DANS UN ENDRO IT VENTIL É / NE PAS INHALER LE G AZ PO UR STO CKER DANS UN ENDROI T VENTILÉ / NE PAS I NHALER L E GAZ PO UR STOCKER DANS UN ENDRO IT VENTIL É / NE PAS INHAL ER LE G AZ PO UR STOCKER DANS UN ENDROIT VENTILÉ / NE PAS INHALER LE GAZ POUR
M ANIPUL ATIO N ET PRECAUTI ONS, VOI R L'ETIQU ETTE SUR L E RESERVOIR MANI PULATIO N ET PRECAUTIO NS, VO IR L'ETI QUETTE SUR LE RESERVOIR M ANIPUL ATIO N ET PRECAUTIONS, VOI R L 'E TIQ UETTE SUR L E RESERVOIR MANIPULATION ET PRECAUTIONS, VOI R L'ETIQUETTE SUR LE RESERVOIR

Nº Denomination Types
1 Pilot cylinder (1) 2 litres
2 Adaptor W21.8x1/14” H – 1/4" BSP M
3 Adaptor 1/4” H –cooper tube
4 cooper tube
5 “Tee” or elbow 1/4" BSP M
6 Pneumatic actuator 227CN
7 Discharge hose ¾”-1 ½”-2”
8 ¼” to bi-cone cooper tube adaptor
9 Adaptor ¼” M – ¼” M
10 Actuator hose FH-6PO

E. The pneumatic line and its fittings must have a working pressure of 120 bar.

To install the remote release pneumatic line, follow the instructions below:

1. Ensure that the cylinders are properly secured by their brackets. Check that the valve outlets
are screwed to the discharge hoses and these, in turn, to the manifold or discharge pipe.

2. Install the pilot bottle with or without a cabinet, in the ideal position for remote operation. For
the installation follow the steps described in chapter 1.17 of this manual. (Installation of a pilot
bottle (bank of more than 5 cylinders)).

Do not connect the pilot valve output valve yet and check that the pressure gauge reads at
least 120 bar.

3. Install the pneumatic pipes using 4 x 6 copper pipe or 1/4" BSP schedule 40 steel pipe. Place
supports for the pipework at a maximum distance of 1.3 metres.

4. Ensure that the fitting of the pneumatic pipes is firm, not subject to knocks, and free from
harsh atmospheres and extreme temperatures.

5. Once the pipes are installed (pneumatic line), perform a gas-tightness test at 120 bar. To do
this, plug one end of the pipe and pressurise it with nitrogen up to 120 bar from the other end.

6. Connect the end of the pipe that goes to the first pneumatic discharge head.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 88/112


a. Cylinder bank: In the case of cylinders in a bank, instead of joining to the first pneumatic
discharge head, the line must be joined to the first flexible release hose.

ƒ If 4x6 copper pipe is used, a copper pipe adaptor must be fitted, with a ¼” BSP
female conical seat, screwed with a ¼” metal-to-plastic washer to a ¼” BSP male-
to-male adaptor with a conical seat in both ends. The copper pipe is connected to
one end of the adapter joint, with the ¼” BSP flexible release hose at the other,
without using Teflon or any other type of sealant, as there is a metal-to-metal
bicone seal in both cases.

1 1/4¨ male connection to hose


2 1/4" male adaptor (hose) to Cu 6x4 pipe
3 Connection to Cu 6x4 pipe (with hexagon and bicone)

vc162ci1.dwg

ƒ If 1/4" BSP schedule 40 steel tube is used, a 1/4" BSP female to 1/4" BSP male,
with a conical seat must be fitted to the male thread. The steel pipe is connected to
the female threaded end of the adaptor using Teflon tape. The flexible release
hose is connected directly to the male threaded end of the adaptor, without using
Teflon, or any other type of sealant, as the seal is a metal-to-metal bicone.

b. Modular cylinders: In this case, the end of the pneumatic pipe is joined to the elbow of
the pneumatic discharge head of the first modular cylinder.

ƒ If 4x6 copper pipe is used, connect a ¼” BSP female to copper pipe with conical
seat adapter to the elbow of the pneumatic discharge head. For this connection, fit
a 1/4" metal-to-plastic washer, which will make the connection between the adaptor
and the elbow gas-tight, without using Teflon or any other type of sealant. Next,
screw the copper tube with its bicone to the adaptor, also without using Teflon or
any other type of sealant, as the seal is a metal-to-metal bicone.

1 1/4" metal-to-plastic washer


2 1/4" female connection to release head tee
3 1/4" female adaptor (tee) to Cu 6x4 pipe
4 Connection to Cu 6x4 pipe (with hexagon and bicone)

vc163ci1.dwg

ƒ If 1/4" BSP schedule 40 steel pipe is used, connect a 1/4" BSP female to 1/4" BSP
female adaptor to the elbow of the pneumatic discharge head. For this connection,
fit a 1/4" metal-to-plastic washer, which will make the connection between the
adaptor and the elbow gas-tight, without using Teflon or any other type of sealant.
Next, screw the steel pipe to the female threaded end of the adaptor using Teflon
tape.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 89/112


7. Connect the other end of the pneumatic line to the pilot bottle. Use the steps described in
section 1.17 of this manual. (Installation of a pilot bottle (bank of more than 5 cylinders)).

a. 2 litre pilot bottle with RGS-MAM-11-4 and 12-4 valve: In this case, the pneumatic line
must be connected to the W21.8x1/14” male thread of the pilot bottle output valve.

ƒ If 4x6 copper pipe is used, screw a W21.8x1/14” female to 1/4" BSP male adaptor
into the pilot bottle output valve, fitting a 12x18x1.4 copper washer into the
W21.8x1/14” female thread of the adaptor. Then wrap Teflon tape to the ¼” BSP
male thread of the adaptor and screw another adapter – a ¼” BSP female to
copper tube with a conical seat, to the male thread. Next, screw the copper tube
with its bicone to the adaptor, without using Teflon or any other type of sealant, as
it is a metal-to-metal bicone seal.

1 1/4" Metatl-to-plastic washer


227DM
Nº LOTE
2 1/4 female adapter (tee) to Cu 6x4 pipe.
3 Connectio to Cu 6x4 pipe (con hexagon y bicone)
LOT No.

4 Cupper washer Æ 16 x 22 x 1,4 mm


5 Adapter W 21,8x1/14" H - 1/4" G M
6 Cupper pipe
227SOL
24V (DC)
0,60 A

EN 837-1

bar

KL. 1.6

ƒ If ¼” BSP schedule 40 steel pipe is used, screw a W21.8x1/14” female to ¼" BSP
male adapter into the pilot bottle outlet valve, fitting a 12x18x1.4 copper washer
inside the W21.8x1/14” female thread of the adaptor. Then, wrap Teflon tape to the
¼” BSP male thread of the adaptor and screw in a ¼” BSP female nipple. Then,
wrap Teflon around the steel pipe male thread and screw it to the threaded nipple.

227DM
Nº LOTE
LOT No.

1 1/4" BSP schedule 40 steel pipe.


2 Cupper washer Æ 16 x 22 x 1,4 mm
227SOL
24V (DC)
0,60 A

3 Adapter W 21,8x1/14" H - 1/4" G M

EN 837-1

bar

KL. 1.6

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 90/112


1.20 INSTALLING REMOTE RELEASE MANUAL PULL STATION
AND PULLEY ELBOWS

This is used for modular cylinders or cylinders in banks to manually actuate the extinguishing system
remotely by acting on the cylinder or pilot bottle. The manual handle is linked by a steel cable in a pipe
(protective pipework) to the manual discharge head of the cylinder or pilot bottle. It can be located up
to 39.5 metres from the extinguishing system.

The cable is mounted inside a steel pipe with pulley elbows for changes of direction.

IN CASE OF FIRE 1 Steel cable outlet


2 Cover fixing screw
3 Protective pipe fixing screw
4 Removable cover
5 Safety pin6 Handle
7 Body
REMOVE THE PIN PULL
8 Allen screw for tightening cable
ON THE HANDLE

To install the remote release pneumatic line, follow the instructions below:

1. Ensure that the cylinder or cylinders are properly secured by their brackets. Check that the
valve outlets are screwed to the discharge hoses and these, in turn, to the manifold.

2. Calculate the length of steel cable necessary to reach the remote manual release handle from
the cylinder or cylinder bank. Always add 10% to the estimate in case of unforeseen problems
that might arise during the installation. Remember that the maximum distance is 39.5 metres.

3. Remove the detachable cover and handle in order to fit the pull station body to the wall or
structure where it is to be located. Use the four fitting holes with appropriate screws and plugs.

1 Steel cable outlet


2 Cover fixing screw
3 Protective pipe fixing screw
4 Orifice for fixing body
5 Manual pull station body
6 Orifice for handle

4. Pass the steel cable from the hole where the handle is fitted to the cable outlet (1), via the
removable cover. Feed the end of the cable into the handle and fully tighten the Allen screw to
secure it.
5. Fit the detachable cover in position with its fixing screws.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 91/112


6. Fit the handle in its original hole and put its safety catch on.

7. Pass the other end of the cable through the first section of protective pipe. Join this section to
the manual pull station using its fixing screw.

8. Continue with the cable and pipe installation until arriving at the manual discharge head of the
bottle. Use pulley elbows for changes in direction. Remember that the maximum number of
pulley elbows that may be used per installation is 20 units.

1 Manual cable release head CMC


2 Steel cable
3 Pulley elbow POPC
4 Pulley elbow bearing
5 Protective pipe
6 Manual cable pull POTMC

ON
OF
F

227CMC
Nº LOTE
xxxxx
LOT No.

227SOL-A
24V (DC)
0,60 A
Nº xx

EN CASO DE INCENDIO

EN 837-1

bar

QUITAR EL PASADOR KL. 1.6

TIRAR DE LA MANILLA

vc164ci1.dwg

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 92/112


9. Once all the cable and protective pipe installation is completed, remove the safety catch of the
manual pull station and check that the cable slides within the pipe. This test is carried by
placing one person at each end of the cable, in order to be able to slide it in both directions.

10. Link the last section of cable to the manual discharge head with an end-of-line device. Before
tensing the cable leave a small amount of slack so that the head lever is not under pressure.

11. Remove the safety ring from the manual discharge head.

CAUTION

TO LEAVE THE SYSTEM READY FOR OPERATION,


DO NOT FORGET TO REMOVE THE SAFETY RING FROM
THE CABLE-OPERATED MANUAL RELEASE HEAD.
IF THIS OPERATION IS NOT CARRIED OUT,
THE SYSTEM WILL NOT BE OPERATIVE.
12. Check that the remote manual pull station has its safety catch in position with its
corresponding seal.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 93/112


1.21 INSTALLING 227CMC CABLE-OPERATED MANUAL
RELEASE HEAD

The 227CMC cable-operated manual discharge head may be installed on the upper part of the
cylinder valve (actuation port) or on top of the electrical discharge head (for cylinders that also have
electric release). Its function is to remotely actuate the valve (RGS-MAM-20/40/50/11-4 and 12-4) on
which it is mounted, using a cable pull.

CAUTION

BEFORE SCREWING THE MANUAL CABLE-OPERATED DISCHARGE


HEAD ONTO THE ACTUATION PORT OF THE VALVE, CHECK
THAT THE ACTUATION NEEDLE IS WITHDRAWN (POSITION 1).

IF THE ACTUATION PIN IS IN POSITION 2,


SCREWING ON THE MANUAL CABLE-OPERATED DISCHARGE HEAD
WOULD CAUSE THE SUDDEN AND VIOLENT DISCHARGE OF THE
EXTINGUISHING GAS IN THE CYLINDER, WHICH COULD
CAUSE SERIOUS INJURY TO THE PERSON INVOLVED.

NOT ACTIVATED ACTIVATED

Lever 227 CMC


Stainless steel cable
1.5 mm dia.

Safety ring

Actuation pin 227CN

FLAT PIN POSITION 1: NOT ACTIVATED


POSITION 2: ACTIVATED

Rotating nut 227CN

cd041ci1.dwg
To install the cable-operated manual discharge head, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe.

2. Holding the manual discharge head by hand, visually check that the actuation pin is in
POSITION 1.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 94/112


3. Remove the plastic safety plug from the valve actuation port and screw in, in its place, the
swivel nut of the manual discharge head. Do not use Teflon, adhesive or any other type of
thread sealant; just finger-tighten as far as possible.

4 1 Cylinder 4
2 Protective bridle
3 Valve RGS-MAM-20/40/50
PELIG RO:

0062 EST O ES UN CO NT ENED OR DE AL TA PRESIÓN


NO QUIT AR L OS ACCESORIOS, NI
MANIPULARLO HASTA QUE ESTE BIEN SUJETO
MEDIANT E SUS HERRAJES.

PELIGRO:

0062 EST O ES UN CO NT ENED OR DE AL TA PRESIÓN


NO QUIT AR L OS ACCESORIOS, NI
MANIPULARLO HASTA QUE ESTE BIEN SUJETO
MEDIANT E SUS HERRAJES.

4 Manual release head 227CMC 3


3
2
2
1
1

4
1 Cylinder (SMS) 4
3 2 Protective bridle
3 Valve RGS-MAM-12-4 ó 11-4 3
EN 837-1

4 Pneumatic release head 227CMC EN 837-1

2
2 bar

KL. 1.6
bar

KL. 1.6

1
1

Remember that the link between the discharge head and the valve is made by a swivel nut
mechanism that allows the head to be turned through 360º to the desired position.

4. If it is screwed directly to the electrical discharge head, follow the same principles of point 3
above.

CAUTION

BEFORE SCREWING THE ELECTRICAL DISCHARGE HEAD


ONTO THE ACTUATION PORT OF THE VALVE, CHECK THAT THE
ACTUATION NEEDLE IS WITHDRAWN (POSITION 1).

1 227SOL
24V (DC)
227SOL
24V (DC)
1
0,60 A 0,60 A
Nº Nº

1 Electrical release head 227SOL/SOL-E


2 Manual release head 227CMC

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 95/112


5. Check that the safety ring and its seal are in perfect condition and are properly fitted to the
head. Do not remove the safety ring at this stage of the installation.

6. Pass the stainless steel cable through the hole in the lever of the discharge head and screw in
the retaining bolt until it is firmly secured. Check, by tugging on the cable, always with the
safety ring in place, that the cable is properly secured and not loose.

7. Once the cable is located inside the protective pipe and tied to the manual cable operating
handle, which is positioned at a distance depending on the installation, check that the cable is
tight and that it is properly installed.

8. At this point, remove the seal and the safety ring from the discharge head so that the
system can operate correctly, and the valve can be actuated manually and remotely from a
cable pull.

9. To remove the cable-operated manual discharge head, first replace the safety ring, as a
precaution, so that the discharge head cannot actuate accidentally, and then gently loosen the
swivel nut by hand or with a non-adjustable spanner. If it was screwed directly to the valve, the
valve cover must not be turned during this operation, because if it is, the contents of the
cylinder might discharge violently, possibly causing serious injury to the person involved.

Never remove the cable-operated manual discharge head when the cylinder is not secured to
the wall by its brackets.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 96/112


1.22 FITTING THE ABORT OR ISOLATION VALVE TO THE
MANIFOLD

Abort valves for fixed SVA gas model extinguishing systems are used to stop the extinguishing gas
discharging in the protected area.

At all times during the installation when a hazardous situation for personnel might arise, the abort
valve must be positioned to prevent the extinguishing agent discharging and producing a
concentration of gas hazardous to human life. In multiple area installations, an abort valve is provided
for each individual flooding area.

In normally occupied areas, or areas not normally occupied for concentrations greater than the
LOAEL, an abort valve must be fitted to prevent an escape of gas to the outside when there is
personnel within the protected area (in accordance with ISO-14520 and UNE-23570).

The abort valve must remain in the closed position when the protected area is inhabited, to prevent
gas escaping when there are people within the protected hazard area, and in the open position when
there is no personnel in the area.

It is also used when the installation is being maintained or inspected, to prevent accidental discharge,
thus avoiding any kind of accidental discharge (automatic or manual) during maintenance work in the
protected area.

The abort valves are fitted by screwing them into the discharge manifold with sealant or Teflon tape.

CAUTION

BEFORE SCREWING IN THE ABORT OR ISOLATION VALVE,


ENSURE THAT THE MAIN VALVE (CYLINDER OR PILOT BOTTLE), DOES NOT
HAVE ITS ELECTRIC OR MANUAL RELEASE HEAD FITTED.

1 2 3

Discharge nozzles Cylinders bank 1 BALL VALVE


2 LEVER
3 SLEEVE ON LEVER
Discharge pipe 4 END OF LINE

Open position

Close position

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 97/112


A 2-pole microswitch may be fitted, with one normally open (NO) contact and one normally closed
(NC), set to change state when the valve is opened or closed, sending an electrical signal to the fire
panel to indicate that the system is isolated or operative. Either contact may be used, depending on
the requirements of the installation.

Stand-by position Actuation position

Figure 34

Loose and open

Zb
NC

22 21
2151 XE2SP
NO

14 13

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 98/112


Technical Information

Location Selector valve


Case Plastic
Working temperature -40ºC to 60ºC
Tension 24V (DC)
Current 3A

Response time in miliseconds >1,5

Mechanical durability per milion operations 10


Operation minimum torque 6N
Positive opening minimum torque 10 N
Protection grade IP65
Connection for cable 1 thread inlet for a tow press M20x1.5
Instalation Non corrosive; indoors

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 99/112


1.22.1 Installation instructions:

- 0000
SVAXXX
Discharge
S dV

nozzles
Nº Serie
XXXXX
G 307000 Serial No.

ON
OFF

227DM
Nº LOTE
xxxxx
LOT No.

227SOL-A
24V (DC)

- 0 786

- 0 786

- 0 786
0,60 A
Nº xx

G 306011

G 306011

G 306011
VdS

VdS

VdS
WP137 BAR

WP137 BAR

WP137 BAR
FH-40HC

FH-40HC

FH-40HC
N - X XXX XX

N - X XXX XX

N - X XXX XX
R GS-MAM-40 RGS-MAM-40 R GS-MAM-40
EN 837-1 EN 1209 4-4 EN 12 094-4 EN 1209 4-4

bar

KL. 1.6

10

0
20
30

bar

KL. 1 .6
40

60
50 10

0
20
30

bar

KL. 1.6
40

60
50 10

0
20
30

bar

KL. 1.6
40

60
50 1 ABORT VALVE SVA
- 0062

SSION DE CHAR GE A 2 0º C

SION ROT URA D ISCO SEG URIDAD


C OM PR ESSED GAS
NO IN FLA MMABLE

2 DISCHARGE MANIFOLD
1112

7 28 1112

1112
3 BANK OF CYLINDERS
STI NG P RE SSURE OF THE SAFETY DISC
94 7 28

94 7 28
SION DE RUPT URE DU DISQUE DE SÉCURIT É
UN: UN: UN:

- (34 ) 94
(34 )

(34 )
MAS A MA X. AU TORIZAD A MASA MAX. AUT OR Z I ADA MAS A MA X. AU TORIZAD A
RGA / FILL / CHA RGE MAX. AU THORIZ ED C HAR GE MA X. A UTH OR IZE D CH ARGE MAX . AU THOR IZED CHA RGE
Nº6

Nº6

T el.- 1 Bur gos Mo ntija Nº6


Fax. -

Fax. -
C HA RGE MAX . AU TORISÉ E KG. CH AR GE MA X. A UTORIS ÉE K G. C HA RGE MAX . AU TORISÉ E KG.

Fax.
Mo ntija

Mo ntija
0 900 rinda d de uejar

0 900 1 rinda d de uejar

0 900 rinda d de uejar


T el.- (31 Bur gos (SPAIN)

T el.- (3 Bur gos (SPAIN)

(3 4) 9 47 (SPAIN)
SUR IZADO CON
281 108

281 108

281 108
C/ MeIn d. Villalonq

C/ Me d. Villalonq

C/ MeIn d. Villalonq
SUR IZED W HIT / PRESSUR ISÉ AU GAS/GAZ: GAS/GAZ: GAS/GAZ:
A LMACE NA R E N LUGAR VE NTILA DO / NO RE SP IR AR EL GAS ALMA CEN AR EN LUGAR VEN TILAD O / N O RES PIR AR EL GA S A LMACE NA R E N LUGAR VE NTILA DO / NO RE SP IR AR EL GAS
4) 9 47

4) 9 47
P ARA MAN IPU LAC IÓN Y P RE CA UC ION ES VE R E TIQU ETA C ILIN DRO PA RA MA NIP ULA CIÓN Y P REC AU CIONE S V ER ETIQUET A CILIND RO P ARA MAN IPU LAC IÓN Y P RE CA UC ION ES VE R E TIQU ETA C ILIN DRO
A / TARE / TARE 2 2 2

Pol. In
T O B E S TOR ED IN A WELL V EN TILATE D A RE A / DO NOT INH ALE TO BE STORE D IN A WE LL VE NTILAT ED ARE A / D O N OT IN HALE T O B E S TOR ED IN A WELL V EN TILATE D A RE A / DO NOT INH ALE
Pol.

Pol.
FOR H AN DLIN G IN ST RU CTIONS SE E C YLIND ER 'S LAB EL FOR HAN DL IN G INS TRU CT IO N S S EE CYL INDE R'S LABE L FOR H AN DLIN G IN ST RU CTIONS SE E C YLIND ER 'S LAB EL

O TO TAL STOCK ER DAN S U N E NDR OI T VEN TILÉ / NE P AS INHA LER LE GAZ P OU R S TOC KE R D ANS UN END ROIT V ENT ILÉ / N E PA S IN HAL ER LE GA Z POUR STOCK ER DAN S U N E NDR OI T VEN TILÉ / NE P AS INHA LER LE GAZ P OU R
MA NIPU LATION ET PR EC AU TIONS, V OIR L'E TIQUET TE S UR LE RE SER VOIR MANIP ULA TION ET PRE CAU TIONS , VOIR L'ETIQUE TTE SUR LE R ESE RV OIR MA NIPU LATI ON ET P REC AU TIONS, V OIR L'E TIQUET TE S UR LE RE SE RVOIR
A L WEIG HT / PO ID S TO TA L

HA DE CARG A
D ATE / DATE D E CHA RGE

T EMPERATURA DE F UNCIO NAMIENTO DE -2 0ºC A 50ºC


WORK IN G TEMPERATURE FRO M -20º C TO 50º C
TEMPÉRATURE D E FONC TION NEMENT D E -2 0ºC A 50 ºC

PO L. IND. VILLALO NQUEJAR

4 ISOLATION VALVE SVA6-3W


C/ MERIND AD DE MONT IJA Nº6
09001 (BU RGOS) - SPAIN
Te l.: (34 ) 947 28110 8 F ax: (3 4) 947 281 112

5 PILOT BOTTLE
Venting
to the
atmosphere

1. Ensure that the discharge manifold is properly secured to its brackets and that the actuation
devices of the cylinder banks (electrical and manual discharge heads) are removed or out of
service.

2. Check that the external threads on the discharge pipework are clean and free from impurities.
Clean with a wire brush for threads.

MODELO DE
Piping to Piping SVA20 3/4” G
discharge to SVA25 1” G
nozzles bottles SVA32 1 1/4” G
SVA40 1 1/2” G
2 1 2 SVA50 2” G
1 BALL VALVE SVA65 2 1/2” G
2 THREADED END PIPING TO BOTTLES SVA80 3” G
3 THREADED END PIPING TO DISCHARGE NOZZLES SVA100 4” G

DRAWING OF THE VALVE WITH PIPE AND TABLE OF VALVE THREADS

3. Wrap Teflon tape or put paste on the male thread of the discharge pipe where the abort valve
is to be screwed in. If using Teflon tape put 20 turns around the male thread of the pipe; if
using paste cover the second thread of the female thread of the abort valve and to the
threaded end of the pipe (male). If a liquid thread sealant is to be used, first ensure that it is
compatible with the gas it will come in contact with, i.e. inert gas (HFC-227ea, HFC-125 and
HFC-23).

4. Fully screw in the valve to the fixed threaded end of the pipe closest to the manifold. In this
operation the pipe will be fixed and the valve mobile, therefore, to screw the valve in it must be
turned with a non-adjustable or adjustable spanner. Try to ensure that the valve is well
positioned, and free from obstacles that might make access for its opening and closing
difficult.

5. Manually open and close the abort valve to check that it is operating correctly.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 100/112


6. Then screw the other end of the pipe to the abort valve. At this stage the valve will be fixed
and the pipe mobile, so the pipe must be screwed in using a pipe wrench.

7. If the abort valve has a microswitch with a contact for an electrical signal, open the electrical
connection cover by removing the two screws to make the cable connection. It has two
contacts inside, one normally open (NO) and one normally closed (NC), either of which may
be used depending on the requirements of each installation.

8. Once the electrical connection is made, manually open and close the valve to check that the
electrical contact is operating correctly. The abort or isolation valve must send an electrical
signal in the closed position, but not in the open position.

NOTE 1: For greater safety, it is recommended that the abort valve be connected before the cylinder actuation fittings (electric,
manual pneumatic etc.) are fitted. For the same reason, although the cylinders are fixed in their brackets, they must have their
safety plugs screwed into their valve outputs. This will prevent accidental discharges due to poor handling.

1.22.2 Positioning the installed abort valve

The usual position of the installed abort valve is horizontal, as shown in Figure 35, but it may also be
fitted vertically or at an angle as shown in figure 36.

When fitting the valve in the installation, the size and travel of the closing handle or lever for opening
and closing the valve must be taken into account. The travel of the handle must be free of any
obstacles that might prevent the abort valve opening and closing correctly.

HORIZONTAL VERTICAL ANGLED


POSITION POSITION POSITION

Figure 35 Figure 36

Technical Information

Denomination Material
Ball valve SKH-G 1 1/4" - 2" Steel
Short lever 1 1/4" SVA
Short lever 1 1/2" SVA Zinc steel F-275 ST-42
Short lever 2" SVA

Short lever handle 30x6x110 SVA Flexible black pvc ref: RRWA-91689-110

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 101/112


1.23 FITTING THE ISOLATION VALVE TO THE RELEASE LINE

Its function is to isolate the pilot bottle or cylinder release line in cylinder bank systems. This prevents
accidental actuation of the system.

The isolation valve is installed in the pilot release line, after the pilot bottle or cylinder discharge hose.

For this purpose a 1/4” BSP, 2 position, 3-way ball valve is used, in order to vent to atmosphere in the
closed position and thus avoid a build up of pressure due to possible leaks in the pilot bottle. This type
of valve has three connections, the pilot bottle input, an output to the cylinder bank and another vented
to atmosphere.

CAUTION

BEFORE SCREWING IN THE ISOLATION VALVE,


ENSURE THAT THE MAIN VALVE (CYLINDER OR PILOT BOTTLE),
DOES NOT HAVE ITS ELECTRIC OR MANUAL RELEASE HEAD FITTED.

Open position

227DM
N º LO TE
LO T No.

227S OL-A
24V (DC)
0,60 A

Vd S

Vd S

Vd S

RGS -M AM-40 RGS-MAM -40 RGS -M AM-40


EN 8 37 -1 E N 12094-4 EN 12094-4 EN 12094-4

bar

KL. 1.6

30 30 30
20 40 20 40 20 40

10 50 10 50 10 50

0 ba r 60 0 b ar 60 0 bar 60

KL. 1.6 K L. 1.6 K L. 1.6

- 0062 CO MPR ESSED G AS


N O IN FL AMMABLE

SS ION DE CHARGE A 20ºC

STI NG PRE SSUR E OF THE SAFETY DISC


SION DE R UPTUR E DU DISQUE DE SÉC UR ITÉ

FIL L / CHARGE

SURI ZE D WHIT / PRE SSURISÉ AU

T ARE / TARE 2 2 2

AL WEI GHT / P OIDS TOTAL

DAT E / DAT E DE CHARGE

WORKING T E MPE RATURE FROM -20ºC TO 50ºC

Closed position
TE MPÉ RAT URE DE F ONCTI ONNEME NT DE -2 0ºC A50 ºC

Venting Bank of cylinders


Pilot bottle to the
atmósphere

1 3 WAY 1/4" BSP BALL VALVE


2 LEVER 1/4" SVA Venting
3 1/4" BSP 3 WAYS NUT PLATE to the
atmosphere

To install the isolation valve, follow the instructions below:

1. The pilot bottle input connection and the output connection to the cylinder bank are done in
the same way, screwed to a 1/4” BSP Teflon hose. To do this, a 1/4” BSP male to male
connector with a 1/4” metal-to-plastic washer is screwed to the valve outlet, and then the 1/4”
BSP hose swivel nut is manually screwed to the 1/4" BSP male to male connector, without
any type of sealant, as it is a conical seal (metal-to-metal). Fully tighten this link with a 19 mm
non-adjustable spanner to ensure its gas-tightness (approximate torque 15 Nm).

2. A 1/4” BSP vent plug is screwed with its 1/4" metal-to-plastic washer to the vent to
atmosphere connection. It can also be done with 1/4” BSP pipe to vent the gas to wherever is
desired.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 102/112


POSITION CLOSE
Manifold system

Pilot cylinder

FLOW

OP
EN
.

CLOS
FLOW

ED

Ventilation to the atmosphere

1 Isolation valve SVA6 (3W)


H2

DE

2 Metallic-plastic washer 1/4"


H1

3 Punching discharge cap 1/4" G


4 Male-male adapter 1/4" G
5 Teflon hose 1/4" G

L1
L2
Figure 37

Technical Information

Operating medium N2
Activation valve Manual
Connection pipe Thread GAS
Working temperature -20º C to 50º C
Test temperature 20º C
Working pressure 360 bar
Test pressure 540 bar
Resistance test pressure 1080 bar
Nominal pressure of the ball valve 400 bar

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 103/112


1.24 INSTALLING OR REPLACING PRESSURE SWITCHES

Assembled in the factory directly onto the cylinder valve with a 1/8" NPT thread, the pressure switch is
used to send an electrical signal directly to the fire panel when the cylinder pressure falls. There are
two variants, NC (normally closed, with open pressure) or NO (normally open, with closed pressure).

To install or change a pressure switch with the cylinder charged with extinguishing agent, follow the
instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe. The
pressure switch may also be installed or replaced without the cylinder being connected to the
discharge hose, in which case, do not remove (or put on) the valve outlet safety plug while the
cylinder is being handled (secured, of course, to its bracket).

CAUTION

BEFORE SCREWING IN THE PRESSURE SWITCH,


ENSURE THAT THE MAIN VALVE (PILOT CYLINDER),
DOES NOT HAVE ITS ELECTRICAL, MANUAL, PNEUMATIC
OR ELECTRICAL SQUIB RELEASE CONNECTED.

2. Holding the pressure switch by hand, wrap Teflon tape around the 1/8” NPT connecting thread
(18 turns approximately).

5 5
PELIGRO:
PELIGRO:

0062 ESTO ES UN CONTENEDOR DE ALTA PRESIÓN


NO QUITAR LOS ACCESORIOS, NI
0062 ESTO ES UN CONTENEDOR DE ALTA PRESIÓN
NO QUITAR LOS ACCESORIOS, NI
MANIPULARLO HASTA QUE ESTE BIEN SUJETO
MANIPULARLO HASTA QUE ESTE BIEN SUJETO
MEDIANTE SUS HERRAJES.
MEDIANTE SUS HERRAJES.

1
1 Outlet valve
2 Cylinder connection 1
3 Pressure switch connection
4 Pressure gauge 4
6
4 5 Release port
6 Pressure switch
7 Choke screw
3 3
2 2
7
RGS-MAM-12 RGS-MAM-12

4 4
4 4

1 Cylinder connection
7 2 Pressure gauge connection
3 Valve outlet
3 3 4 Release port
5 Choke screw
6 Pressure switch connection
2 2 7 Pressure switch
6 6
1 1
5 5
vc144ci1.dwg

3. Slowly remove the 1/8” NPT plug or faulty pressure switch from the port where the item is
going to be connected. During this operation a small amount of gas will leak through the choke

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 104/112


Allen screw inside the valve. This screw is for regulating this small gas leak. If the gas leak is
too great, turning the screw clockwise will reduce the flow, and if the flow is too small turning
the screw in the opposite direction will increase it. Bear in mind that this small gas leak must
exist (as small as possible) so that when the pressure switch is fitted, it is under pressure.

It is advisable to reduce the fitting time to a minimum; otherwise a small quantity of gas will be
lost. The estimated time to carry out this operation is 10 seconds.

4. Quickly screw in the pressure switch with a 24 mm non-adjustable spanner until it is fully
tightened.

5. Check with soapy water that there are no leaks in the joint between the valve and the pressure
switch. If there is a leak, repeat all the above operations.

6. Check the continuity of its Faston terminals with a tester. Depending on whether the chosen
pressure switch is normally open or normally closed (NO/NC), it will give a different type of
electrical signal.

7. If the required signal is not the one being received, and the chosen pressure switch is the
correct one, turn the regulator screw to the left or right until an optimal position is found as
shown in the picture.

8. If on following point 7 of this section, you still do not get the desired results, it means that the
choke screw is too tight and therefore the pressure switch must be removed and the
operations carried out again (from point 2).

Regulation screw

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 105/112


Technical Information

Operating medium HFC-227ea, HFC-125, HFC-23, N2


RGS-MAM-20/40/50
Valve type
RGS-MAM-11-4/12-4
Body Bicromathed steel
Valve connection 1/8” NPT
electrical terminals Faston
Maximum voltaje 48 V
Inductive current 0.2 A
Resistant current 0.5 A
Protection index IP 54
Working temperature -5ºC to 60ºC
Mechanical life 106 cicle
Contact type NA / NC
HFC-227ea, HFC-125 20-80 bar (Model PMN 80)
Regulation field
HFC-23 50-150 bar (Model PMN 150)
Max. Static pressure 300 bar
Weigh 85 gr

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 106/112


1.25 INSTALLING OR REPLACING PRESSURE GAUGES

Assembled in the factory directly on the cylinder valve, it indicates at all times the pressure (in bar) in
the cylinder charged with extinguishing agent.

CAUTION

THE PRESSURE GAUGE IS ASSEMBLED IN THE FACTORY


ON THE CYLINDER VALVE
AND THEREFORE
DOES NOT REQUIRE ANY FORM OF HANDLING

HOWEVER,
THE INSTRUCTIONS IN THIS CHAPTER
ARE FOR OPERATIONAL AND GUIDANCE USE
FOR POSSIBLE REPLACEMENTS
DUE TO MALFUNCTION OR BREAKAGE.

To install or replace a pressure gauge when the cylinder is charged with extinguishing agent, follow
the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe. The
pressure gauge may also be installed or replaced without the cylinder being connected to the
discharge hose, in which case, do not remove (or put on) the valve outlet safety plug while the
cylinder is being handled (secured, of course, to its bracket).

CAUTION

BEFORE SCREWING IN THE PRESSURE GAUGE,


ENSURE THAT THE MAIN VALVE (PILOT CYLINDER),
DOES NOT HAVE ITS ELECTRICAL, MANUAL, PNEUMATIC
OR ELECTRIC SQUIB RELEASE CONNECTED.
2. Holding the pressure gauge by hand, wrap Teflon tape around the 1/8” NPT connecting thread
(18 turns approximately).
6

1 Pilot port
2 Pressure gauge connection
3 Safety cup (Bursting disc)
5 4 Cylinder connection
1 5 Volve outlet
6 Release port
7
3
7 Pressure gauge
8 Choke screw
2
4
8

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 107/112


RGS-MAM-12 RGS-MAM-11

6
7 6

5
5
1

7
3 3
2
2
8
4 8 4

1 Pilot port
2 Pressure gauge connection
3 Safety cup (Bursting disc)
4 Cylinder connection
5 Valve outlet
6 Release port
7 Pressure gauge vc142ci1.dwg
8 Choke screw

3. Slowly remove the 1/8” NPT plug or broken pressure gauge from the port where the item is to
be connected. During this operation a small amount of gas will leak through the choke Allen
screw inside the valve. This screw is for regulating this small gas leak. If the gas leak is too
great, turning the screw clockwise will reduce the flow, and if the flow is too small turning the
screw in the opposite direction will increase it. Bear in mind that this small gas leak must exist
(as small as possible) so that when the pressure gauge is fitted, it is under pressure.

It is advisable to reduce the fitting time to a minimum; otherwise a small quantity of gas will be
lost. The estimated time to carry out this operation is 10 seconds.

4. Quickly screw in the pressure gauge with a 14 mm non-adjustable spanner until it is fully
tightened.

5. Check with soapy water that there are no leaks in the joint between the valve and the pressure
switch. If there is a leak, repeat all the above operations.

6. Check that the pressure gauge shows pressure on its dial. If it does not show the correct
pressure, weigh the cylinder to check whether extinguishing gas has been lost. If it has, send
the cylinder to SIEX to be recharged.

7. If the pressure gauge does not show any pressure on its gauge, repeat all the operations of
this section, because the choke screw is probably too tight.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 108/112


1.26 INSTALLING THE CYLINDER VALVE BURST DISC

The burst disc is factory pre-installed in the escape or burst port of the RGS-MAM-20/40/50/11-4/12-4
cylinder valve, and does not require any form of handling.

CAUTION

THE BURST DISC IS ASSEMBLED IN THE FACTORY AND


THEREFORE DOES NOT REQUIRE ANY HANDLING.

HOWEVER, THE INSTRUCTIONS IN THIS CHAPTER CAN BE


USED FOR OPERATION AND GUIDANCE FOR POSSIBLE
LATER CHANGES TO THE SYSTEM.

RGS-MAM-50/40/20

1 Body
2 Bursting disc 65/110/185 bar
3 Burst disc cover

A
Painted surface

Brass surface

Figure 38

The burst disc must only be replaced with an original SIEX 2001, SL spare.

It may only be replaced with the cylinder discharged (unpressurised) and never with the
cylinder charged (pressurised).

To install or change a burst disc with the cylinder discharged, follow the instructions below:

1. Ensure that the cylinder is properly secured by its brackets. Check that the valve outlet is
screwed to the discharge hose and this, in turn, to the manifold or discharge pipe. The burst
disc can also be installed or changed without the cylinder being connected to the discharge
hose, in which case do not remove (or put on) the valve outlet safety plug while the cylinder is
being handled (secured, of course, to its bracket).

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 109/112


CAUTION

BEFORE REPLACING THE BURST DISC, MAKE SURE


THAT THE CYLINDER IS DISCHARGED (NO PRESSURE).

NEVER INSTALL A BURST DISC WITH THE


CYLINDER CHARGED (PRESSURISED)

2. Unscrew the end cap of the burst disc from the valve body (exhaust or burst port) using a
spanner.

3. Remove the broken burst disc and discard it.

4. Place the new burst disc, exclusively supplied by SIEX, in the valve body, in the burst or
exhaust port.

Place the smooth brass surface of the disc against the valve body seat, with the
painted or coloured side of the disc facing outwards, so that it can be seen from the
outside.

The characteristics of the burst disc to be fitted are in the following table:

TABLE 10

Burst disc material Nickel/brass/copper


Average burst for HFC-227ea charged to 24 bar (20ºC) 65 bar +/-6.5%
charged to 42 bar (20ºC) 110 bar +/-11%
Average burst for HFC-125 charged to 24 bar (20ºC) 65 bar +/-6.5%
charged to 42 bar (20ºC) 110 bar +/-11%
Average burst for HFC-23 185 bar +/-18%
65 bar Red
Colour of the burst disc 110 bar Blue
185 bar Green
RGS-MAM-20 11 mm
Burst disc diameter RGS-MAM-40 13.9 mm
RGS-MAM-50 13.9 mm
RGS-MAM-11/-4 or 12/-4 11 mm
RGS-MAM-20 1/4” BSP
Burst disc cap thread RGS-MAM-40 3/8” BSP
RGS-MAM-50 3/8” BSP
RGS-MAM-11/-4 or 12/-4 1/4” BSP
18 Nm (1/4" BSP, thread)
Thread torque
20 Nm (3/8" BSP thread)

5. Screw in the burst disc end cap, supplied exclusively by SIEX, into the valve body escape or
burst port, without any type of sealant, but it must be tightened to 18 or 20 ± 2 Nm, depending
on the valve, see table 10 above. Do not use Teflon, adhesive, or any other type of thread
sealant, simply finger-tighten as much as possible, and then finally turn the nut 15º with a
spanner.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 110/112


1.27 INSTALLING THE WARNING SIGNS

There are two types of warning signs for SIEX-HC halogenated gas fixed extinguishing systems. A
sign at each entry door to the hazard area to indicate that it is a hazard area and a warning sign at
each point where a manual release can be carried out. These signs are specific to the halogenated
gas system used.

Door sign:

A warning note is required on all the entrance doors to the protected hazard area to advise
personnel that they are entering a protected area.

For protected areas with concentrations greater than the NOAEL, a warning must be made to
this effect.

Place the sign on the door itself, in such a way that it is visible and it cannot fall off or be
removed.

Sign that shows a manual actuation can be carried out:

A warning note is required to indicate that the system can be actuated manually, at each point
where this is the case.

The sign is fixed next to the manual actuation device in such as way that it is visible and cannot
fall off or be removed.

CAUTION

WARNING SIGNS MUST BE PLACED VISIBLY ON ALL


THE ENTRANCE DOORS TO THE HAZARD AREA AND
AT ALL POINTS WHERE MANUAL ACTUATION IS POSSIBLE.

1.28 FINAL INSTALLATION CHECK


After carrying out the installation of the SIEX-HC system, the appropriate inspection and tests must be
carried out.

1. Check that the cylinders have the correct weight and pressure and are installed in accordance
with the installation drawings.

2. Check that the brackets and straps are correctly installed and all the fittings are properly
tightened.

3. The system pipework must be inspected according to the drawings in the manual, in
accordance with the ISO-14520 (UNE-23570) standard and the design limitations in this
manual.

4. Check that the discharge and actuation pipes are fully secured. Check that all the fittings are
properly screwed in and tightened to prevent any dangerous movements during discharge.
The means of carrying out pipe size reductions and the position of the tees must be checked
depending on the requirements of the design.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 111/112


5. System pipework must be clean inside, free of pores and internally inspected so as to avoid
the presence of oils or foreign particles that could dirty the hazard area, or affect the dispersal
of the agent due to a reduction in the nozzle surface area.

6. The pipework must be pressure tested in accordance with the requirements of the authority
having jurisdiction.

CAUTION

BEFORE CARRYING OUT THE INSPECTION TEST OF THE PNEUMATIC


RELEASE LINE (RELEASE HOSES), THE RELEASE HEADS
(ELECTRICAL, MANUAL, PNEUMATIC ETC)
MUST BE REMOVED FROM THE VALVES SO THAT ACCIDENTAL
DISCHARGES OF THE SIEX-HC SYSTEM ARE AVOIDED.
7. Carry out the test on the pneumatic release line with nitrogen at 124 bars (1800 psig), to
check its integrity and gas tightness.

8. Check that the nozzles are installed in the correct position (according to the installation
drawings) with its bore number marked on the lower flat part of the nozzle. The discharge
nozzles must be oriented to optimise agent dispersal. Check the nozzle orifices to avoid any
obstructions.

9. The discharge nozzles, pipework and assembly straps must be installed in such a way that
they cannot cause personal injury. The extinguishing agent must not be discharged directly on
personnel, as they could suffer injury. The discharge must not be aimed directly at objects or
shelves, upper parts of cupboards or similar surfaces where loose or portable objects could be
thrown or displaced by the gas during discharge.

10. The remote actuation stations must be correctly installed, easily accessible and appropriately
identified. All the manual stations used to actuate the SIEX-HC for halocarbonated gases
systems must be appropriately identified for this purpose. Special care must be taken when
the manual pull stations for more than one system are very close and could be confused. In
this case, the manual stations must be clearly identified as to the hazard area they affect.

11. A test of the electric release head must be carried out, following the description in chapter 6
on the cylinders equipped with this head.

12. Carry out a pressure switch test of all the pressure switches installed as specified in chapter
1.2.4.

SIEX-HC (HFC-227ea / HFC-125 / HFC-23) Installation manual - Versión 00 112/112