SET FREE Σ
HEAT PUMP type NS SERIES
01
Hitachi VRF Systems
SET FREE Σ
HEAT PUMP type NS SERIES
02
What can Hitachi VRF offer ?
An average of up to 39% energy Meet any local requirements Overall cost/time reduction Delivering precisely the
savings for some applications and constraints with a thanks to the lightweight correct amount of heating or
compared to conventional HVAC number of improvements and modular VRF systems. cooling to each zone leads
systems. of Outdoor unit (e.g. Larger to the comfortability, and
capacity range or Smaller also quiet operation and
footprints). defrosting are upgraded.
- Higher efficiency ratio - Larger capacity with smaller footprint - Overall lighter cabinet - Smart compressor control:
in APF, EER and COP - Better piping limit (16% lighter on average) keep indoor temperature more
- Lower CO2 emissions - Available for the lift transportation constant
- Extended external static pressure
- Lower power consumption - New package design to be craned - Lower noise operation
more easily - New defrosting technology
03
System Better
Maintenance Ease Aesthetics
Integration life-cycle costs
Delivering the ability of Easier maintenance thanks VRF can operate for 20- Let alone total line-up of
Integrating all management to Both the elimination of 30 years with whole easier Ceiling Concealed type of
systems, from individual any water treatment like maintenance, that leads to IDU, Ceiling Cassette type of
IDU to whole building, which pumps etc., and Design “Better Lifecycle Costs”! IDU are also designed not to
leads to both time saving change in unit. be the noise in space.
and cost saving.
- H-LINK solution - All PCB visible and easily accessible - More Efficiency Operation thanks to - Higher ESP ODU: the better visual
- Advanced individual and centralized - Easy access to compressors and valves DX system aesthetics compared to outdoor
control system - Maintenance Ease installment
- Smart refrigerant pump-down
- Easy BMS connection - Higher Control capacity thanks - Wide range of ceiling concealed type
to Advanced Individual/Centralized of IDU (Ducted type) will suit to your
control system interior requirement
- Ceiling cassette type IDU are also
designed to be clean and simple
without any disturbance to indoor
space.
04
Line-up Overview
Line-up Overview
NS SERIES
Base Unit
1675mm
1675mm
1675mm
1675mm
1675mm
1675mm
Nomenclature
Unit Type
RAS: Outdoor Unit
RAS - 8 FS N S
Standard Type
Refrigerant Type
N: R410A
SET FREE System
FS: Heat Pump System (2 Pipes System)
05
Summary Table
Item Unit
Current Model
(FSXN1)
NS Series Features and
Capacity HP 8-54 8-54
Benefits Overview
* Please consult your distributor or dealer if the height different is over 50m.
** For more details, please consult your distributors or dealer, or, refer to technical manuals.
Benefit to
06
Features and Benefits Overview
ODU Compact footprint • Requires less indoor space than conventional systems • Expands options for positioning outdoor units
Piping flexibility: with pipe runs up to 1000 • Suitable for short or long runs; accommodates nearly all
• Allows design freedom
meter projects
Connectable IDU/ODU capacity ratio Up • Up to 130% for Combination Capacity • Reduces system costs
VRF Selection Software • Intuitive functionality that simplifies and speeds designs • Allows confident selection and right-sizing of systems
• 16 % lighter cabinet on average compared to Current • Ease of transportation leads to time/cost saving in
Lighter cabinet
Model (FSX N1) installation
New Package of ODU • Easy to understand for craning • Reduces installation time and cost
Comprehensive training • Modules tailored to specific job functions • Enables professional, high-quality, timely installation
MECHANICAL
CONTRACTOR • Ensures correct components are delivered to job sites on • Enhances installation efficiency
& Consistent, reliable product delivery
time • Allows efficient labor scheduling
INSTALLER
• The upper panel (on the side of an electric box)
independently detached from the lower panel (on the
compressor chamber side)
• All PCB visible and easily accessible including 7-segment
• Speeds up time spent on maintenance, repair, and
Easy maintenance access display
troubleshooting
• More Space in lower section, easy access to compressors
and each valve
• Refrigerant evacuation: Enforced operation to open ODU
EVO/EVB, IDU EVI, and Hi/Low pressure Bi-pass SVB
07
FEATURES ADVANTAGES BENEFITS
• In multiple-unit applications at partial load, outdoor • Optimizes efficiency
Rotational operation units operate alternately so that operating hours are • Extends service life
shared equally. • Increases reliability
• Allows one outdoor unit to be taken off-line for • Avoids system downtime
Backup operation function
maintenance while remaining units keep operating. • Protects occupant comfort
Compressor modulation in 0.1 • Smoothly delivers only the exact amount of refrigerant • Allows fine control for optimum comfort
Hz increments needed for the load • Saves energy
• Users can select from a wide variety of power settings • Limits electric demand charges
Demand control from 100% to 60% and program “not to exceed” a given • Limits equipment wear and tear
power level • Reduces noise
• Longer fan blades increase airflow quantity by 25%, • Operates more efficiently
New long blade propeller fan
resulting in higher static pressure • Extends motor life
As high as 200Pa static pressure • Offers adjustable speeds to match the static pressure
• Flexibility to accommodate long or short ductwork runs
in ducted systems requirement
Indoor Units Widest range of line-up • meets any of your indoor requirement • keeps aesthetic
Optional motion and radiant • Sets back temperature when space is unoccupied,
• Saves energy
sensors increasing efficiency even further
Controls • Adjusts in 0.5/1 degree C increments • Auto-adjusts for daylight saving time
Temperature control
• Adjustable fan speeds • Provides options to satisfy multiple projects/buildings
08
Design Flexibility
Design Flexibility
COMPACT
Current Model
(RAS-FSXN1)
Single Module Two Units Two Units Three Units Four Units
New
New Model
(RAS-FSNS)
Single Module Single Module Two Units Two Units Three Units
Space
11% Weight
New Model
Current
model
16%New Model
Current
model
reduction lighter
on average on average
1,210mm(47 5/8inch) 1,600mm(63inch)
1,920mm(75 3/5inch) 2,180mm(85 4/5inch)
Current
New Model Current Current
New Model model
New Model
model model
3,670mm(144 2/5inch)
3,670mm(144 2/5inch) 3,670mm(144 2/5inch)
09 4,380mm(172 11/25inch)
4,380mm(172 11/25inch) 4,380mm(172 11/25inch)
EASY TRANSPORTATION
Smaller Lighter
Can be
transported in an Lift Crane
New
New package
design to be
craned
more easily
1210
765
1350
Duct (Field
Duct (Field Supplied)
Supplied) Duct (Field Supplied)
Duct (Field Supplied)
10
Design Flexibility
Up to 110m*
Lower ODU 40m
30m
* Please consult your distributor or dealer if the height difference is over 50m.
Piping Direction
The pipes can be installed in three directions (front, rear or bottom side) from the bottom base.
For Piping from Front cover For Piping from Bottom base to Left, Right and Rear side
Transition
Wiring
Power Source
Wiring
Cover gaps with
packings
(field-supplied)
Liquid Pipe Gas Pipe
For more
service space
in front.
11
OPERATION TEMPERATURE RANGE
-5°C
-5°C
-5°C
-5°C0 0 52°C
48°C
52°C
48°C -20°C
-20°C
-20°C
-20°C 00 15°C
15°C
15°C
15°C
Cooling
Coolingmode
mode Heating
Heatingmode
mode
NOTES:
1. Cooling operation at maximum 48oC DB (for standard type) and 52oC DB (for high efficiency type) should be available only if the outdoor air inlet temperature increase temporarily according to the installation condition.
2. If install the units to the place where exceed ambient temperature 48oC continuously, the combination ratio must be lower 130% and not to operate all of the indoor unit simultaneously.
3. The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor unit than compatible building heat load.
4. The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is forbidden.
5. It must be avoided to install the units where affected by direct sunlight reflection and short circuit. There may be the possibility to activate protection control and alarm system if install the units to inappropriate place.
Also the life time of the products and parts must be considerably shortened.
6. Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion of dirt and clogging of sand to the outdoor unit heat exchanger.
7. Refer to the technical catalog for the detail.
Range of
combination capacity Standard Type (FSNS) : 50 to 130% (In case the combination ratio exceed 130%)
Maximum Connectable
13 16 19 23 26 26 33 36 40 43 47 50 53 56 59 64
IDU Quantity
Recommended Connectable
8 10 10 16 16 16 18 20 26 26 32 32 32 32 32 38
IDU Quantity
NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity
2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor unit capacity should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating performance and
operating limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor unit capacity is available up to 130% against the outdoor unit capacity.
4. When operating the outdoor unit in cold areas with temperatures of -10oC, or under the high heating load conditions, the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the total piping
length should be less than 300m.
5. The air flow volume for indoor units of 0.8 and 1.0HP is set higher than that for indoor units of 1.5HP or more. Make sure to select appropriate indoor units when installing indoor units where cold draft may occur during heating
operation. If installing indoor units in such places, refer to the recommended number of connectable indoor units.
6. If combination capacity of indoor units exceed 100% of outdoor unit capacity, there might be the possibility of insufficient capacity of 130% (standard) and 150% (high efficiency) combination ratio. Refer to the technical.
12
Adaptability
Adaptability
New Model
New Cover
Setting example
Day Night Day
Sound
Power
Level
Rigidity
improved !
86dB(A) 72.5dB(A) 86dB(A)
Nominal Step2 Nominal
18HP 42HP
Noise Reduction
Sound Power Level Sound Power Level
mode
Nominal 86 89
image
Step1 82.5 86
Step 2 77.5 81
Step3 72.5 76
*The range of performance and operation is limited, since the rotation frequency of
the compressor and ODU fan are forcibly decreased.
13
DEFROSTING
Prevention Improved!
for defrosting prevention, the model controls
frost and ice formation during heating operation by
running mid-temperature coolant (5°C-20°C) before
decreasing the pressure through a heat exchanger to frosting
control frost and ice formation on the lower part of the
cold
outdoor heat exchanger.
warm
defrosting
image hot
Room
Temperature
comfortable
Heating Defrosting
on
Heating duration
more than 200%
longer
Time Time
14
Adaptability
off on on
Combined ODU
Rotation
on on off on off on
MAINTENANCE EASE
Totally
New!
Total Structure Change
Newly adopted window for
7-segment display:
New Structure: Adopting access door to the
In upper section, all PCB visible electrical box in the upper panel,
and easily accessible which leads to easy access to
7-segment display, PSW & DSW
and so on.
New Structure:
More Space in lower section, easy
access to compressors or valves
open
15
High Efficiency
EFFICIENCY RATIO
1.5
0.0
8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
Old New
NOTES:
APF (As Reference in the Japanese seasonal performance benchmark for VRF)
APF is meant for cooling/heating capacity per 1kW of operating power consumption under certain conditions throughout the year.
APF = Accumulated cooling/heating loads (kWh) / Accumulated power input in cooling/heating (kWh)
NS Type
EER COP
7.00 7.00
7.00
6.00 6.00
6.00
5.01
5.01 4.91
4.91
5.00 5.00
5.00
4.35 4.27
4.27
4.00 3.93
4.00 4.00
4.00
3.49 3.49
3.49 3.44
3.44 3.44
3.44 3.52
3.52 3.58
3.58
3.26 3.32 3.07 3.18
3.18
3.00
3.00 2.94
2.94
3.00 3.00
3.00
2.00 2.00
2.00
1.00 1.00
1.00
8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0
22.0 24.0
24.0 8.0
8.0 10.0
10.0 12.0
12.0 14.0
14.0 16.0
16.0 18.0
18.0 20.0
20.0 22.0
22.0 24.0
24.0
HP HP
HP
NOTES:
1. The graphs below show the EER/COP of single units for Oceania.
2. The above values indicate the EER/COP per outdoor unit when it is combined with specified indoor units.
3. The specification of EER/COP of each country is different according to the regulation. Please contact to the Sales person for more information.
4. EER = Energy efficiency ratio = Cooling capacity or Heating capacity ÷ Power consumption of an air conditioner
5. COP = Coefficient of performance of an air conditioner = Output KW (cooling capacity) ÷ Input KW (power consumption)
WHAT'S IMPROVED?
16
High Efficiency
Twin-fan
1211mm 1210mm
Air outlets
are increased
Air volume area : 4403cm2 Air volume area : 6334cm2 by more than
40%
Improvement in bell-mouth
Current model New model
Narrower!
Less short
circuit
Smoother
air Flow
17
IMPROVED HEAT EXCHANGER
New shape
Current model (14,16HP) New model (14-24HP)
Split left-right
heat exchanger
New angle
Current model (14,16HP) New model (14-24HP)
Improved angle
of the curve
• The heat exchange area has been increased by more than 10% (12HP)
• Gre-ater heat exchange efficiency
18
High Efficiency
IMPROVED COMPRESSOR
Fixed Scroll
Orbiting Scroll
Oldham’s Coupling
Main Bearing
Thrust Bearing
Inverter Compressor
Inverter Compressor
Inverter Compressor
Control Capacity
Control Capacity
Control Capacity
*Example at 12HP
19
IMPROVED COMPRESSOR CONTROL
Smooth Drive
The model calculates the appropriate
amount of coolant supplied by the outdoor
units on the basis of information about
the required load from the individual
indoor units. The model employs smooth
operation control to control the number of Charge proper
revolutions of the inverter compressor. The amount of refrigerant
model supplies the appropriate amount of
coolant to the indoor units according to the
Calculation of proper Refrigerant flow
required load. The model increases energy- Piping
refrigerant amount
saving efficiency by operating smoothly
while controlling the switching on and off
of the compressor at low-load operation.
INV
compressor IDU IDU
Transmit Transmit
load load
information information
ODU
Transmission Wire
Room 30 Room 30
Temp Temp
(°C) (°C)
25 25
Unstable Temperature Constant Room Temperature
20 20
20
High Efficiency
(Reduction amount)
Reduction
About 2,665
kg/year
NOTE:
1. CO2 emissions are a trial calculation value based on JIS B 8616: 2015 (Tokyo office). The CO2 emissions coefficient is 0.534 kg-CO2/kWh.
2. Based on the end-use intensity of CO2 emissions (actual emission coefficient in FY 2014) specified by the Federation of Electric Power Companies.
3. As reference in Japanese domestic model
Reduced by
about % 51
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
(kwh/year)
NOTE:
1. Seasonal power consumption is a calculated value based on JIS B 8616: 2015 (Tokyo office), and it may vary depending on the area or usage conditions.
2. As reference in Japanese domestic model
21
Specifications /
Dimensions
Service space
NOTES:
The cooling and heating performances are the values when combined with our
specified indoor units.
Cooling Operation Heating Operation
Conditions Conditions
Indoor Air Inlet Temperature: Indoor Air Inlet Temperature:
1 27oC DB (80oF DB) / 19.0oC WB (66.2oF WB) 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: Outdoor Air Inlet Temperature:
35oC DB (95oF DB) 7oC DB (45oF DB) / 6oC WB (43oF WB)
Piping Length: 7.5 Meters
Piping Lift: 0 Meter
The sound pressure is based on the following conditions.
The above data is based on the cooling mode. In case of heating mode, the sound
2 pressure level increases by approximately 1~2 dB.
The above data was measured in an anechoic chamber so that reflected sound
should be taken into consideration in the field.
Except for the specified combination in the table (26~54HP), there is no other
3
combination of the base unit.
The width of outer dimension, it is the value when each distance between the base
4
outdoor units is specified to 20mm.
Specifications / Dimension
23
1 2 3 4 5 6 7 8
317T158469
80
65 80
382
(4-38×15 Long Hole]
245
87
205 ※N/A in This Unit
18
239 127
Refrigerant Piping Outlet (Gas,Liquid)
(Knockout Square Hole)
Service cover
267
C C
Refrigerant Piping and
Electrical Control Box Wiring Connection
Control Cable Outlet
Access Door
(Ø33 Knockout Hole)
TB Box
(Only 380-415V/50Hz Power Transition
380V/60Hz model) Cable Outlet
(Ø55 Knockout Hole)
1675
Piping Connection D
D
Refrigerant Piping and
225
Wiring Connection Hole
(Knockout Hole)
Hole for Suspention
32
100
253
248
269
14
60
331
92
95 92 576 92 117 Liquid Line Hole for Suspention
950 131 Gas Line 240 127
E E
765
NOTES: Power Source Refrigerant Not Used
1.Refer to "System Pipe Drawing"for diameters. Cable Outlet Piping Outlet
1 2 3 4 5 6 (Ø65 Knockout Hole) 7 (Gas,Liquid) 8
2.Drainage to come out during heating or defrost operation,and rain water,too. (Knockout
Square Hole)
317T158470
Choose a well drained place to install units or provide a ditch to drain.
A DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE A
RAS-14FSNS,
3.Do RAS-16FSNS
not install above the corridors.Drainage may AND
fall. RAS-18FSNS
If inevitable,provide the second drain pan to run drainage. ( OUTDOOR UNIT ,MODELS: RAS-14FSNS,RAS-16FSNS and RAS-18FSNS
4.Use a drain boss(optional)if drain setup for Outdoor Unit is necessary. DATE REVD. CHKD. APPD.
SYM.
Knockout Hole/Drain Hole REVISIONS
However,installation of the drain131 948
boss in regions where drainage may frozen 131 Power Source REMARKS TITLE PROJECTION SCALE
Cable Outlet (Top View)
DIMENSIONAL
152
F Follow the instructions on Installation Manual provided with drain boss. DWN. Y.KAGEYAMA 23- 01- 2017
Power Transition CHKD. Y.UCHINO 23- 01
- 2017 (Ø26×2)
Cable Outlet APPD. 23- 01
- 2017 317T158469
1 2 3 4 (Ø33 Knockout5 Hole) This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hongfor
Mounting Position Kong)Limi
ted CAD
Drain Cap (Optional)
(Ø26×2)
Control Cable Outlet
729
B
M12 Anchor Bolt B
(Ø33 Knockout Hole)
Mooting Hole
(4-38×15 Long Hole]
483
80
65 80
245
18
87
147 127
※N/A in This Unit
Refrigerant Piping Outlet
(Gas,Liquid)(Knockout Square Hole)
267
Service cover
Piping Connection
212 65
Refrigerant Piping and D
D
Wiring Connection Hole
(Knockout Hole) 132
Hole for Suspention
32
178
60
239 92 92
14
100
253
95 836
1210 130 Gas Line Hole for Suspention
93
765
E 147 127 E
NOTES:
1.Refer to "System Pipe Drawing"for diameters. Power Source Refrigerant Not Used
Cable Outlet Piping Outlet
2.Drainage to come out during heating or defrost operation,and rain water,too. (Ø65 Knockout Hole) (Gas,Liquid)
Choose a well drained place to install units or provide a ditch to drain. (Knockout
Square Hole)
3.Do not install above the corridors.Drainage may fall.
If inevitable,provide the second drain pan to run drainage.
4.Use a drain boss(optional)if drain setup for Outdoor Unit is necessary. DATE REVD. CHKD. APPD.
SYM.
However,installation of the drain boss in regions where drainage may frozen REVISIONS
REMARKS TITLE PROJECTION
is prohibited.Drainage in the pipes may frozen and cause cracks on the pipes. DIMENSIONAL
SCALE 24
DRAWING NTS
F Follow the instructions on Installation Manual provided with drain boss. DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMIZU DWG. NO. SH. REV.REGD. F
CHKD. Y.UCHINO 23- 01
- 2017
Specifications / Dimension
25
Knockout Hole/Drain Hole
Mounting Position
669 131 (Top View) for Drain Cap
Power Source (Optional)
(Anchor Bolt Hole Pitch) 339 462 339 239
Cable Outlet
(Ø26×2)
18
(Ø65 Knockout Hole)
Power Transition Mounting Position
729
635
80
65 80
250
110 ※N/A in This Unit
18
110
g Hole 147 127 Refrigerant Piping Outlet
(Gas,Liquid)(Knockout Square Hole)
C
267
D
160 Gas Line
Power Transition
1 2 3 4 5 Hole/Drain Hole
Knockout 6 7
Cable Outlet
Mounting Position
131 669 669 131
317T158471
(Top View)
(Ø55 Knockout Hole) for Drain Cap
DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE
Power Source
A (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) 339 462 339 239 (Optional)
Cable Outlet
( OUTDOOR UNIT ,MODEL: RAS-20FSNS,RAS-22FSNS and 24FSNS (Ø26×2)
18
60
635
152 Gas Line (Ø65 Knockout Hole) Power Transition E M
(Anchor Bolt Hole Pitch)
80
Cable Outlet fo
100
765
65 80
253
(Ø33 Knockout Hole)
248
(O
250
Hole for Suspention (Ø
B Control Cable Outlet
93
(Ø33 Knockout Hole)
Refrigerant Piping Outlet ※N/A in This Unit
729
110
18
110
(Gas,Liquid) 147 127
635
80
itch to drain. M12 Anchor Bolt Mooting Hole (Knockout Square Hole) 147 127 Not Used
Refrigerant Piping Outlet
65 80
(6-38 ×15 Long Hole] (Gas,Liquid)(Knockout Square Hole)
250
DATE
REVD. CHKD. APPD.
SYM.
REVISIONS
is necessary. REMARKS TITLE 110 PROJECTION
SCALE ※N/A in This Unit
18
Service cover
110
DIMENSIONAL
rainage may frozen
267
380/60Hz) Electrical
Control Box Wiring Connection
Gas Line
Refrigerant Access Door
Piping Connection Control Cable Outlet
1675
380-415V/50Hz, Refrigerant
259 Liquid Line
Refrigerant
160 Gas Line
D Refrigerant
160 Gas Line
Cable Outle
Refrigerant
132 (Ø55 Knock
177 Piping and wiring
239 92
Connection Hole 92
0
14
60
100
765 132
253
248
177
NOTES: 92 92
239 Hole for Suspention
14
60
765
253
248
REVISIONS
4.Use a drain
CONDITIONER,SET-FREE boss(optional)if drain setup for Outdoor Unit is necessary. REMARKS TITLE
Refrigerant Piping Outlet PROJECTION
SCALE
2.Drainage to come out during heating or defrost operation,and rain water,too. A (Gas,Liquid) DIMENSIONAL
However,installation of the drain boss in regions where drainage may frozen 147
DRAWING NTS
-20FSNS,RAS-22FSNS and 24FSNSin Choose
is prohibited.Drainage
a well drained place to install units or provide a ditch to drain.
the pipes may frozen and cause cracks on the pipes. DWN. Y.KAGEYAMA 23- 01
(Knockout Square Hole)
- 2017 SHIMIZU DWG. NO. SH.
3.Do not install above the corridors.Drainage may fall. CHKD. Y.UCHINO 23- 01
- 2017
Follow the instructions on Installation Manual provided with drain boss. 317T158471
If inevitable,provide the second drain pan to Knockout Hole/Drain Hole
run drainage. APPD. 23- 01
- 2017 SYM.
Mounting Position
This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong Kot
1 2
4.Use a drain boss(optional)if drain setup for Outdoor(Top
UnitView)
3is necessary. 4 for Drain Cap 5 REMARKS TITLE
Power Source (Optional) DIMENSIONAL
However,installation
Cable Outlet 339drainage may462
of the drain boss in regions where frozen 339 239
(Ø26×2) DRAWING
(Ø65isKnockout Hole)
prohibited.Drainage in the pipes may frozen and cause cracks on the pipes. DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMI
F
Power Transition
Follow the instructions on Installation Manual provided with drain boss. Mounting Position CHKD. Y.UCHINO 23- 01
- 2017
(Anchor Bolt Hole Pitch)
26
Refrigerant Piping and
Wiring Connection
Specifications / Dimension
27
to Indoor Unit
1 2 3 4 5 6 7 8
317T158472
A A
18
OUTDOOR UNIT A OUTDOOR UNIT B
Outdoor Unit Model
729
RAS-28FSNS RAS-16FSNS RAS-12FSNS
18
(8-38 ×15 Long Hole]
RAS-14FSNS 317T158470
C C
OUTDOOR UNIT A OUTDOOR UNIT B RAS-16FSNS 317T158470
RAS-18FSNS 317T158470
NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D 2.Check "Piping System" and "Dimensional Drawing" D
1675
OUTDOOR
RAS-34FSNS UNIT ARAS-18FSNS OUTDOORRAS-16FSNS
UNIT B
(Anchor Bolt Hole Pitch)
1210 1210
MIN.20
(2440) 765
SYM. DATE REVD. CHKD. APPD.
REVISIONS
REMARKS TITLE PROJECTION
SCALE
DIMENSIONAL
to Indoor Unit DRAWING NTS
Piping Connection Kit SHIMIZU DWG. NO. SH. REV.REGD. F
F DWN. Y.KAGEYAMA 23- 01
- 2017
CHKD. Y.UCHINO 23- 01
- 2017
APPD. 23- 01
- 2017 317T158473
1 2 3 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong ted 28
Kong)Limi
CAD
Specifications / Dimension
29
1 2 3 4 5 6 7 8
317T158474
A A
18
B RAS-38FSNS
OUTDOOR RAS-24FSNS
UNIT A RAS-14FSNS
OUTDOOR UNIT B B
729
Combination of
RAS-42FSNS Drawing NO.of
RAS-24FSNS RAS-18FSNS
Base Unit Models Dimension
RAS-14FSNS 317T158470
M12 Anchor Bolt Mooting Hole RAS-18FSNS 317T158470
18
(10-38 ×15 Long Hole]
C C
RAS-22FSNS 317T158471
OUTDOOR UNIT A OUTDOOR UNIT B RAS-24FSNS 317T158471
NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D 2.Check "Piping System" and "Dimensional Drawing" D
for the piping connection kit and piping
1675
connection size.
3.Check the "Dimensional Drawing" for the
Dimension of piping outlet and Cable outlet.
4.This drawing shows that there is 20mm clearance
between the base units.
For outdoor unit snowproof hood,clearance is
50mm or more.
TDs @ @ @ @@¦@ @ E
E
the mounting pitch dimension for anchor bolts.
1600 1210
MIN.20
(2830) 765
1 2 3 4 5 6 7 8
SYM. DATE REVD. CHKD. APPD.
317T158475
A to Indoor Unit REVISIONS A
Piping Connection Kit REMARKS TITLE PROJECTION
SCALE
DIMENSIONAL
DRAWING NTS
F DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMIZU DWG. NO. SH. REV.REGD. F
CHKD. Y.UCHINO 23- 01
- 2017
RAS-44FSNS, RAS-46FSNS AND RAS-48FSNS
( OUTDOOR UNIT ,MODELS: RAS-44FSNS,RAS-46FSNS and RAS-48FSNS APPD. -) 2017
23- 01 317T158474
1 2 3 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong ted
Kong)Limi
CAD
MIN.
131 669 669 282 669 669 131
(Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) Combination of Base
Combination Unit
of Base UnitModels
Models
Outdoor Unit Model
Outdoor Unit Model
OUTDOOR UNIT A OUTDOOR UNIT B
OUTDOOR UNIT A OUTDOOR UNIT B
18
RAS-22FSNS 317T158471
M12 Anchor Bolt Mooting Hole
18
NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D D
2.Check "Piping System" and "Dimensional Drawing"
for the piping connection kit and piping
1675
connection size.
3.Check the "Dimensional Drawing" for the
Dimension of piping outlet and Cable outlet.
4.This drawing shows that there is 20mm clearance
between the base units.
For outdoor unit snowproof hood,clearance is
50mm or more.
E TDs @ @ @ @@¦@ @ E
the mounting pitch dimension for anchor bolts.
1600 1600
MIN.20
(3220) 765
31
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8
317T158476 317T158476
A RAS-50FSNS,
A RAS-52FSNS AND RAS-54FSNS A
DIMENSIONAL
DIMENSIONAL DRAWING DRAWING
OF HITACHI OF HITACHI
AIR-TO-AIR AIR-TO-AIR
HEAT PUMP AIRHEAT PUMP AIR CONDITIONER,SET-FREE
CONDITIONER,SET-FREE
( ( OUTDOOR
OUTDOOR UNIT ,MODELS:UNIT ,MODELS: RAS-50FSNS,RAS-52FSNS
RAS-50FSNS,RAS-52FSNS and RAS-54FSNS
and RAS-54FSNS ) )
MIN. MIN. MIN. MIN.
131 131 948 948 282 282 948 948 282 282 948 948 131 131
(Anchor
(Anchor Bolt Bolt Hole Pitch)
Hole Pitch) (Anchor
(Anchor Bolt Bolt Hole Pitch)
Hole Pitch) (Anchor
(Anchor Bolt Bolt Hole Pitch)
Hole Pitch) Combination ofModels
Base Unit Models
Combination of Base Unit
Outdoor
Outdoor Unit Model Unit Model
18
18
OUTDOOR UNITOUTDOOR
A UNIT A
OUTDOOR UNITOUTDOOR
B UNIT B
OUTDOOR UNITOUTDOOR
C UNIT C
729
729
Combination of Combination of Drawing NO.of Drawing NO.of
Base Unit Models Dimension Dimension
Base Unit Models
18
18
(12-38 ×15 (12-38 ×15 Long Hole]
Long Hole]
RAS-16FSNS RAS-16FSNS 317T158470 317T158470
C C C
RAS-18FSNS RAS-18FSNS 317T158470 317T158470
OUTDOOR
OUTDOOR UNIT A UNIT A OUTDOOR
OUTDOOR UNIT B UNIT B OUTDOOR
OUTDOOR UNIT C UNIT C
NOTES: NOTES:
1.Make
1.Make sure that thesure thatunit
outdoor the Aoutdoor
is unit A is
placed on theplaced
indooron theside.
unit indoor unit side.
Arrangeunits
Arrange the outdoor the outdoor
according units according to the
to the
@@ @ @ C ` a b DC ` a b D
2.Check
2.Check "Piping "Piping
System" and System"
"Dimensionaland "Dimensional
D D D
Drawing" for Drawing"
the pipingfor the pipingkitconnection
connection and kit and
pipingsize.
piping connection connection size.
1675
1675
32
Service Space
SERVICE SPACE
Make the service space when outdoor unit
is installed as follows.
If the service spaces for air inlet and outlet
are insufficient, it may cause a performance
degradation and some abnormalities due to
insufficient air intake.
Additionally, the service space is required (Unit: mm)
Min.
1500
- In the case of no walls on the front side and the rear side,
the service space is required as follows.
Vent Hole
* Rear Side: Min. 300mm
* Right and Left Sides: Min. 10mm (In the case that the
field-supplied snow protection food or the air outlet duct
is amounted to the unit, the spaces of min. 50mm are
required.)
- If the wall on the front side is over 1,500mm high, the space
h1
Front Rear
of (500 + h2/2) mm for the front side is required.
Side Side
- If the wall on the rear side is over 500mm high, the space of
1500
500
shown in the following figures.
- If the space between the unit and an obstacle above the unit
is less than 1,500mm or the space above the unit is closed,
set up the duct at the air outlet side in order to prevent
short circuit.
- When there are obstacles above the unit, the four (front,
rear, right and left) sides of the unit shall be open in
principle. 765
33
No limit for No limit for No limit for
side wall height. side wall height. side wall height.
Front Side Front Side Front Side Front Side Front Side
Min. 500 + h2/2
<Top View> Min. 400 Min. 400
<Top View>
<Top View>
1) Walls on 2 Sides
In case that the units are installed adjacent
• SINGLE INSTALLATION
to tall buildings and there are no walls on
No limit for No limit for No limit for
2 sides, the minimum rear side space must No limit for Noside
limitwall
for height. No limit for Noside
limitwall
for height. “ ” limit for
No Noside
limitwall
for hei
side wall height. side wall height. side wall height. side wall height. side wall height. side wall heigh
be 300mm.
Min. 300 Min. 300
Min. 300 (Rear
Min. Side
300 Space) This indicates
Min. 300 the (Rear
Min.Side
300 Space) M
No limit for No limit for No limit for
(Rear Side Space)
Min.
*1) (Rear Side Space) Min. wall direction
(Rear
200 height. of the
Side Space) (Rear Side Space) (Rear
side10
wall height. side side wall hei
*1) *1)
Min. 200 Min. 200
unit(Front Side) when
Min. 10 Min. 10
Min. 300 + h1/2 installing the units.
Front Side Min. 300 Front Side Front Side Min. 300 Fro
(Rear Side Space) (Rear Side Space)
*1) Front Side Front
<Top Side
View> Front Side Front Side Front Side Min.Front
400 Side Front Side Front Side Front
Min. 10 *1) M
<Top View> Min. 10<Top View> Min.Min.
400 200 Min. 400
<Top View> Min. 400
<Top View> <Top View>
Front Side • MULTIPLE / SERIAL INSTALLATION
Min. 500 + h2/2 Front Side Front Side Front Side <Top View> Fro
NoNolimit
limit
forfor NoNolimit
limit
forfor NoNo
limit
limit
forfor
side
sidewall
wall
height.
height. side wall
side height. <Top View>
height.
wall side
side
wall
wall
height.
height. Min. 400
No limit for side wall height. <Top View>
<Top
Min.
Min. View>
300
300 Min.
Min. 300
300 Min.
Min.
300
300
(Rear
(Rear
Side
Side
Space)
Space) (Rear Side
(Rear Space)
Side Space) (Rear
(Rear
Side
Side
Space)
Space)
*1)*1)
Min.
Min.1010 Min.
Min.200
200
“
“ ” “
Front
Front
Side
Side Front
Front
Side
Side Front
Front
Side
Side Front
Front
Side
Side Front
Front
Side
Side
Min.
Min.
500
500
+ h2/2
+ h2/2
<Top
<TopView>
View> Min.
Min. 400
400 Min.
Min.400
400 This indicate
<Top
<TopView>
View> This indicates the direction
This of “t
indicates
unit(Front Si
Min. 500direction
+ h2/2 of the direction of the
<Top
<Top
View>
View>
Min. 300 + h1/2 Min. 300 + h1/2 unit(Front Side) when installingSide
unit(Front the
Front Side
*1) Min. 300 + h1/2
Min. 300 + h1/2 *1) installing the units. installing the u
Min.10 Min.10
2) Walls on 3 Sides *1) This indicate
Min. 10 (Side direction of t
*1) • SINGLE INSTALLATION
*1) Space)
Min. 10 Min. 10 unit(Front Si
Front Side
Min. 500 Min. 900 installing the
Front Side Min. 300 + h1/2
Min. 500 + h2/2
Front Side Front Side
Min.
*1)500 + h2/2 Min. 500 + h2/2
Min. 10 “ “ ” ”
No limit for side wall height.
FrontNo limit for <Top
sideView> Front
Min.20 side wall height.
No limit for wall height.
*1) *1) *1) *1)
Min.20 Side Min. 500 + h2/2 Min.20 Side Min.20 Min. 500 + h2/2
<Top View> <Top Front Side
View> Min. 500 + h2/2 This
Thisindicates
indicates the
the
No limit for side wall height. direction
Nodirection
limit forofof
the
side the
wall height.
<Top View> unit(Front
unit(Front
<TopSide)Side)
View> when
when
No limit for side wall height.
Min.
Min.
300
300+ h1/2
+ h1/2 installing
installingthethe
units.
units.
<Top View>
*1)*1)
Min.
Min.1010 • MULTIPLE / SERIAL INSTALLATION
[ INSTALLATION IN THE SAME DIRECTION ] [ REAR TO REAR INSTALLATION ]
Min. 300 + h1/2 Min. 5
Front
Front
Side
Side Front Side
Min.
Min.500
500
+ h2/2
+ h2/2 Min. 500 + h2/2 Min. 500
Min. 300 + h1/2 Min. 300 + h1/2
Min.10
*1) Front Side
Min.10
*1) Front Side
*1) *1) *1) *1)
NoNo
limit
limit
forfor
side
side
wall
wall Min.10
height.
height. Min.10 Min.10 (Side
Min.10
(Side Space)
(Side
<Top
<TopView>
View> Front Side
Min. 300 + h1/2 Space) Space) Min. 5
Min. 500
Front Side Min. 900
Front Side Front Side
Min. 500
*1) Min. 500 *1) Min. 900 Min. 900
Min.10 Min.10
(Side
Space)
*1) Front
FrontSide *1) Front *1) *1)
Min.20 Side Min.20
Min. 500 Min. 500 + h2/2 Min.20 Min.20Min. 900M
Side
*1) Front *1) *1) Front *1) *1) Front *1) Front
*1) *1)
Min.20 Side Min.20 Min.20Min. 500Side+ h2/2 Min.20 Min. 500 + h2/2 Min.20 Side Min.20 Min.20 Min. 500
Side+ h2/2 Min.20 Min.
No limit for side wall height. No limit for side wall height.
No limit for side wall height <Top
No. limit for sideView>
wall height. Min.
Min. No+ limit
500
500 h2/2 for side wall height
+ h2/2 <Top
No. limit for sideView>
wall height.
Min.
Min.300
300
+ h1/2
+ h1/2
<Top View> <Top
*1) View>
Front *1) Front
FrontSide
Side <Top View> <Top
*1) View>
Front *1)
*1)*1)
Min.20 Side Min.20
*1)*1) 20Min. 500 + h2/2 Min.20 Side P5417001
Min.20 M
Min.10
Min.10 Min.10
Min.10
*1): In the case that the field-supplied(Sidesnow protection hood or the air outlet duct is adopted, the space of minimum 50mm is
(Side
required. No limit for side wall height. No limit for side wall height.
Space)
Space)
Front
Front
Side
Side <Top View> <Top View>
Min.
Min.
500
500 Min.
Min.900
900
34
Service Space
No limit for
3) Walls on 4 Sides side wall height.
▼
No Min. 500 + h2/2
limit for
*2) side wall height.
Min. 800 <Top
Front Side View>
Open
*2): Partly open a wall if the unit is surrounded by walls on four sides. 1 Group (Max. 6 Outdoor Units)
Min. 1m
NOTES:
1. Keep the upper side open to prevent mutual interference of inlet and
outlet air of each outdoor unit. 1 Group (Max. 6 Outdoor Units)
2. The figure dimensions indicate sufficient spaces around outdoor units Min.
for operation and maintenance at typical installation conditions as
follows. [ Operation Mode: Cooling Operation, Outside Temp.: 35oC ]
In case that the outdoor unit ambient temperature is higher and
also the short circuit is likely to occur compared to the installation 1 Group (Max. 6 Outdoor Units)
condition, find an appropriate dimension by calculating air flow M
current.
3. For the multiple installation, 1 group shall consist of 6 outdoor units
(max.).Keep 1-meter interval between each unit group.
35
Options
Options
images:MC-NP30SA
Piping Connection
Kit 1 (Liquid)
Piping Connection
Kit 1 (Gas) Gas Piping
(Field-Supplied)
Piping Connection
Accessory Pipe
Kit 2 (Gas)
(L-Shape)
37
Dimensions
MC-NP21SA
158
ODU
130
ID38.1 ID28.58
95
80
ID19.05 ID15.88
130
95
80
IDU IDU
Insulation Insulation
ID28.58 ID28.5883 ID19.05 Insulation 61 61
158
Insulation ID19.05
130
95
83
80
382 382 IDU
IDU ODU 303 ODU
303 ODU
IDU ODU
Insulation ID28.58 ID19.05 61
382 83 Insulation
IDU OD28.58 ODU OD19.05
OD28.58 OD19.05 303 ODU
OD28.58 OD28.58
ID22.2 ID22.2
Reducer Reducer Reducer
Reducer Reducer
ID25.4 ID25.4
ID28.58 OD28.58
ID28.58 OD19.05
ID28.58 ID28.58
ID15.88 ID15.88
OD28.58
ID22.2 ID25.4 ID25.4
ID12.7
Reducer Reducer ID12.7
Reducer ID25.4 ID22.2 ID22.2
Reducer ID9.52 ID9.52
ID28.58 ID28.58 ID15.88
ID25.4
ID12.7
Reducer ID22.2
ID9.52
MC-NP30SA
80
130
158
IDU
95
80
IDU
130
158
95
80
Reducer OD15.88ID19.05Reducer
ID19.05
ID19.05
38
Options
2. MULTI-KIT
Line Branch
First branching pipes Pipe diameter after the first branch and multi-kit
Outdoor Unit HP Model Diameter (mm)
Total Indoor Unit HP Model
5 - 10 MW-NP282A3 Gas Pipe Liquid Pipe
12 - 16 MW-NP452A3 < 6 Φ 15.88 Φ 9.52
18 - 24 MW-NP692A3 6 - 8.99 Φ 19.05 Φ 9.52 MW-NP282A3
26 - 54 MW-NP902A3 9 - 11.99 Φ 22.2 Φ 9.52
12 - 15.99 Φ 25.4 Φ 12.7
MW-NP452A3
16 - 17.99 Φ 28.58 Φ 12.7
18 - 25.99 Φ 28.58 Φ 15.88 MW-NP692A3
26 - 35.99 Φ 31.75 Φ 19.05
MW-NP902A3
< 36 Φ 38.1 Φ 19.05
images:MW-NP282A3
Header branch
Total Indoor Unit HP No. of Header Branches Model
5-8 4 MH-NP224A
5 - 10 8 MH-NP288A
images:MH-NP224A
39
426
ID15.88 ID15.88 67
ID19.05 ID19.05
ID22.2 ID22.2
ID12.7
main piping Ins
Dimensions
206
ODU
ID19.05
178
Insulation ID15.88
ID12.7
ODU
MW-NP282A3
251 IDU
GAS Side Liquid Side Reducer
426 426 256 256 main piping
main piping
ID9.52
ID15.88 ID15.88ID15.88 ID15.88 67 67 ID6.35 50
ID6.35 50
ID19.05 ID19.05ID19.05 ID19.05 ID9.52 ID9.52
ID9.52 ID9.52
ID22.2 ID22.2ID22.2 ID22.2 OD6.35
Reducer
ID12.7 ID12.7
122
122
main piping
100
main piping
100
Insulation Insulation
206
206
ODU ODU
ID19.05 ID19.05 ID9.52 ID9.52
178
178
ODU
ID9.52 ID9.52 365 main piping
262
ID25.4 ID28.58 77
219
OD6.35 ID22.2 ID28.58 ID22.2
OD6.35 Insulation ID12.7
Reducer Reducer
ID19.05
ID15.88
MW-NP452A3 ODU
ID12.7
290 IDU
GAS Side Liquid Side Reducer
251
219
ID22.2
365 365 main piping main piping main piping
Insulation Insulation
262 262 main piping ID25.4
ID25.4 ID25.4 ID28.58 ID28.58 ID19.05 OD28.58 ID15.88 ID9.52
77 77 ID9.52 ID9.5256 56
ID22.2 ID22.2 ID28.58 ID28.58 ID12.7 ID12.7 ID15.88 173
ID12.7 ID12.7
ID12.7
ID12.7 ODU
OD6.35
290 IDU
Reducer ID22.2 ID19.05 Reducer
ODU ODU
ID12.7
163
ID12.7
163
ID25.4
139
139
OD28.58 ID15.88
251
ID9.52
251
ID9.52 ID9.52
219
219
ID12.7 ID12.7
OD6.35 OD6.35
Reducer ReducerID19.05
ID22.2 ID22.2 ID19.05 Reducer Reducer 60 ID15.88
3×60=180 ID12.7
MH-NP224A 400
OD6.35 ID9.53
109
109
60
3×60=180
60 375 ID15.88
60 ID15.88
3×60=180 ID6.35 ID12.7
3×60=180 ID12.7
Insulation
400
400
ID9.53 ID9.53
85
Insulation
Insulation
81
81
60
60
3×60=180
3×60=180
375
375
ID6.35
40
ID6.35 Insulation
Insulation
Options
Dimensions
ODU
251
219
Insulation ID22.2
365 365 main piping main piping 387 387 main piping main piping
ID25.4
ID22.2 ID22.2 ID28.58 ID28.58 77 77 ID15.88 ID15.88 ID12.7 ID12.7
67 67
ID25.4 ID25.4 ID19.05 ID19.05 ID15.88 ID15.88 OD28.58 ID15.88 ID9.52
ID28.58 ID28.58 ID22.2 ID22.2
ID12.7 OD6.35
Reducer ID22.2 ID19.05 Reducer
ID9.52 ID9.52
219
219
ODU ODU
251
251
191
191
ID15.88 ID15.88
219
219
Insulation Insulation
ID22.2 ID22.2 Insulation Insulation
ID12.7 ID12.7
ODU ODU ID19.05 ID19.05
ID9.52 ID9.52
ID15.88 ID15.88 ID6.35 ID6.35
ID12.7 ID12.7 main piping
251 251 IDU IDU 477
290 290 IDU IDU
ID31.75 87
ID38.1 ID38.1
ID25.4 ID25.4
OD28.58 OD28.58 ID15.88 ID15.88 ID9.52 ID9.52
ID34.92
257
ID12.7 ID12.7
OD6.35 OD6.35 main piping ID31.75
220
477 429
Reducer ID22.2Reducer
ID19.05
ID22.2 ID19.05 Reducer Reducer Insulation
ID31.75 87 ID15.88
ID38.1 ODU
ID38.1 ID19.05 ID19.0
MW-NP902A3 ID28.58 ID22.2 ID22.2
308 IDU
257
main piping main piping ID31.75
477 477 429 429 ID22.2220 OD28.58 Insulation O
Insulation ID25.4 ID15.88
ID31.75 ID31.75 87 87ID15.88 ID12.7
ID15.88 main ID12.7
piping main piping ID28.58 ODU I
ODU
ID38.1 ID38.1 ID38.1 ID38.1 ID19.05 ID19.05ID19.05 ID19.0567 67 ID9.52 I
ID22.2 ID22.2 ID22.2 ID22.2 ID28.58 ID12.7
ID6.35
308 OD31.75
IDU ID25.4 Reducer ID22.2 ID19.05 ID
Re
251
Reducer
ID34.92 ID34.92 ID15.88 ID15.88
257
257
240
220
220
212
ID22.2
Insulation Insulation ID28.58 ID25.4 ID15.88
ODU ID15.88
ODU ID15.88 ID9.52
ODU ODU
ID9.52 ID12.7 ID9.52 ID12.7 ID12.7
ID28.58 ID28.58
ID6.35 ID6.35
308 308
IDU IDU IDU IDU OD31.75 ID25.4 Reducer80ID22.2 ID19.05 55
Reducer
251 ID19.05 251
ID22.2 Reducer
ID15.88 Insulation
OD15.88 ID19.05 OD6.35 ID9.53
ID22.2 OD28.58
ID22.2 OD28.58 OD6.35 OD6.35
ID28.58 ID28.58 ID25.4 ID15.88 ID25.4 ID15.88
ID9.52 ID9.52
111
ID12.7 ID12.7
OD31.75 OD31.75Reducer ID22.2 ID15.88
ID25.4 Reducer ID22.2 Reducer
ID25.4 ID19.05 ID19.05 Reducer
Reducer Reducer ID12.7
60
MH-NP288A 7×60=420
615
ID15.88 Insulation
OD15.88 ID19.05 OD6.35 ID9.53
111
60
7×60=420
111
ID15.88 685
ID12.7 ID15.88
60 ID6.35 Insulation
ID9.53 ID12.7
7×60=420 60
ID9.53
ID12.7
85
615 7×60=420
615
Insulation
Insulation
84
84
60
7×60=420
60
685 7×60=420
685
ID6.35 Insulation
ID9.53
41 ID9.53
ID6.35 Insulation
ID9.53
ID12.7
85
ID9.53
ID12.7
85
3. DRAIN BOSS
The drain boss is for the drain pipe connection in order to use the bottom base of the outdoor unit as a drain pan.
images:DBS-TP10A Dimensions
Drain Boss + Rubber Cap Drain Cap + Rubber Cap Drain Boss×2 Drain Cap×2
To close the drain hall
43
43
43
30
30
30
30
Ø20 Ø20
Ø25 Ø25 Ø25 Ø25
43
43
43
30
30
30
30
42
42
3. Do not use the drain boss in a cold area. The drain water in the drain pipe may freeze, and the drain pipe may crack.
Ø20
90
90
Ø20
Ø25 Ø25 Ø25
Ø25
(48)
(48)
Drain piping
Drain piping bottom bas
bo
field supplyed
field supplyed install Drain
install
bollDrain
2 points
boll 2 points
ODU rearODUsiderear side
Drain boss
Drain boss Drain capDrain cap
How to use
Bottom view Side view
install Drain cap install Drain cap (247)
2 points (247)
2 points
(90) (90)
90
90
(48)
42
Options
4. CABINET COVER
Outdoor Unit
Fastening Fitting
(for Rear Side
Air Inlet) Anchor Bolt
(Field-Supplied)
(for Right Side
Air Inlet)
Foundation
43
Resistance to Salt Damage Specifications
Products for Order
About the installation location
Resistance to salt damage specifications Resistance to heavy salt damage specifications
such an atmosphere
ODU ODU
- A location where the outdoor unit is rinsed by the rain - A location where the outdoor unit receives little rain
installation location
- A location that is not exposed to sea breezes - A location that is directly exposed to sea breezes
Requirements for
- A location where the distance from the installation location of the - A location where the distance from the installation location of the outdoor unit to the
outdoor unit to the sea is between approximately 300 meters and sea is up to approximately 300 meters
one kilometer - A location where the outdoor unit is mounted on the front of a building (beach side)
- A location where the outdoor unit is in the shelter of a building - A location where corrugated iron roofs and the steel parts of balconies near the
installation location of the outdoor unit are often repainted
*If you install the device in a special atmosphere, you will need to undertake sufficient special consideration.
Units that are resistant to salt damage are based on the “Standard of Testing Resistance to Salt Damage of Air Conditioning Devices JRA9002” of the Japan Refrigeration and Air
Conditioning Industry Association (JRAIA).
44
Global Footprint
Global Footprint
45
46
Johnson Controls - Hitachi Air Conditioning
http://www.jci-hitachi.com
Manufactured by
Distributed by
ISO 9000 series The quality of our design and manufacturing systems has been approved.
We are a domestic business office designing and manufacturing air conditioners. We have obtained the
international standard ISO 9001 certification regarding quality management systems.
Shimizu Air Conditioning Headquarters, Professional-Use Air Conditioning Business Division, Johnson Controls
– Hitachi Air Conditioning
JQA-1084 JQA-1084 obtained in November 1995
ISO 14000 series Our environmental preservation activities have been approved.
We are a domestic business office designing and manufacturing air conditioners. We have obtained the
international standard ISO 14001 certification regarding environmental management systems.