Professional Documents
Culture Documents
INTRODUCTION
1.1: Overview of EHV/ UHV Substation Grounding
The capacity and size of the power stations and substations continue to increase
to meet the increasing power demand. Day by day due to addition of more generating
power sources and more interconnection of lines, power systems network become
more and more complicated. At present highest transmission ac voltage in India is 765
kV AC and 1200 kV AC is under test and going to be installed in near future. It is the
highest ac system voltage in the world which is indigenously designed by joint
venture of Power Grid Corporation of India, Central Power Research Institute of
India, Central Electricity Authority (CEA) and India’s leading industries. The
National Test Station 1200 kV AC phases–I has been charged in 2012 for single
circuit and double circuit at Bina, Madhya Pradesh. In future, 1200 kV UHV lines
will be erected for bulk power transmission across the country. Therefore, efficient,
safe and economic grounding practices are needed to adequately protect the substation
equipments and operating personals.
The touch and step voltages inside the grounding grid or adjacent to it are
mainly a function of topsoil resistivity. In contrast, the grounding grid resistance is
primarily a function of deep soil resistivity. For this, the deep soil resistivity refers to
depths roughly the extent of horizontal grid electrode or for simple electrode like
vertical rod; up to ten times the depth of burial.
1
The complete analysis of EHV/UHV ac substation grounding that shall consider
the grounding system resistance, ground potential rise, surface potential, touch and
step potential, various factors which affects these parameters, economic and efficient
design of grounding grids, factors governing the resistance of grounding grid,
seasonal influence on performance of substation grounding system, Laboratory test
measurements, analysis of various earthing models installed by using Auto Grid Pro
(AGP) grounding software and field test measurements has been carried out in this
thesis.
2
Figure 1.1: Basic shock situations; A. Step voltage B. Touch voltage C. Mesh voltage
D. Transferred potential
During ground faults in the power systems, fault current flows into grounding
grid and discharge into earth in all directions. The flow of fault current
through earth produces surface potential in the substation which is a function
of x and y coordinates. The potential distribution in grounding area is more or
less uniform. However, at the periphery of ground electrode, potential gradient
exist which decreases when one moves away from perimeter of the grid. Earth
surface potential depends on
Soil resistivity
Magnitude of current that flows between grounding grid and surrounding soil
3
Geometric configuration of grounding grid defined by shape, size, grid
conductor spacings, conductor diameter and depth of burial.
It is the resistance offered to the flow of grid current between ground electrode
and the remote earth. Ground resistance is the function of
Resistance of first three parts is known as metallic resistance RL and that of the
fourth part is dissipation resistance RD. Resistivity of metallic conductor is generally
in the order of few µΩ-cm and that of the soil, at the minimum may be few Ω-m. The
difference is of the order of 10 or more. Therefore, resistance of metallic parts is
negligible as compared to dissipation resistance. Thus, usually the grounding
resistance is considered to be equal to the dissipation resistance RD and here after
referred as ground resistance Rg. The grounding resistance Rg of the ground electrode
depends on the soil resistivity ρ as well as the ground electrode geometry [2].
4
1.2.4: Effect of shape of electrode on resistance
In order to achieve low values of Rg, the current density at electrode to earth
interface should be as low as possible i.e. the volume of earth through which the
current flows should be as large as possible. Once the current flows from metal to
earth, it spreads out radially, reducing current density. If the electrode is physically
small, say a point electrode, this effect is very large, but it is very much less for a
plate electrode where spreading is effective only at the edges. Therefore, for the same
surface area; rod, pipe, or wire offers very much lower ground resistance than, a plate
electrode. Note that low current density extends electrode life [3].
= (1.1)
2 ′
Vertical ground electrode or pipe electrode: Rod electrodes can penetrate into deep
soil. It provides low ground resistance as it comes in contact with low resistivity deep
soil. Rods are very useful, when the soil structure having high resistivity at shallow
depth and very low resistivity in deep soil. They discharge large amount of current
into deep low resistivity soil resulting in less ground resistance. However, rods have
very unfavourable surface potential distribution. In practice, combination of grid and
rods are used to provide low resistance and desirable surface potential. The grounding
resistance of vertical rod or pipe as shown in figure1.3 is given by Prof. Dwight [5]
5
Figure 1.3: Vertical ground rod
= −1 (1.2)
4
= (1.3)
2
The formula derived from rotating ellipsoid by Tagg, Ollendorf and Zingraff is [6]
2
= (1.4)
2
Where
The ground resistance of horizontal round conductor buried in the soil at a depth h
(m) depicted in fig. 1.4 is given by
2
= −1 (1.5)
√ ℎ
If the conductor is strip having width w (m) and thickness t (m), then equivalent
diameter is approximately given by = /2 when ≤ /4
Plate Electrode: The formula for ground resistance of vertically buried plate
electrode is given by
6
= (1.6)
4 2
Where
16 ′
= (1.7)
2 ′ ℎ
Where
Grounding grid usually consists of horizontal equally spaced bare grid conductors
interconnected to each other in X and Y directions and burred in the soil at a certain
depth; provides a common grounding to all substation equipments and steel structures.
It is often supplemented by several vertical ground rods at the corner, perimeter of the
grid and inside the grid as per statutory requirement of substation equipments.
Grounding grid resistance is a function of soil resistivity, grid configuration and area
available for the grid. Once the area of grounding grid and soil structure/model is
defined; grid resistance is almost fixed and there is very little scope to decrease the
grid resistance by adding more number of grid conductors, increasing its diameter and
burial depth. However, there are other techniques to decrease the grid resistance.
Figure 1.6 shows the typical substation grounding grid with vertical rods.
7
Figure1.6: Typical substation grounding grid with ground rods
As per IEEE Std. 80 -2000 [1], a good grounding system provides low
resistance to remote earth in order to minimize GPR and thereby dangerous touch
voltages within the respective maximum permissible limits. The earth resistance may
be made as low as possible. For large EHV/UHV ac substations the ground resistance
is usually less than 0.5 Ω and that of the distribution substations, the acceptable range
is from 1 Ω to 5 Ω, depending on the local conditions.
= = (1.8)
.
The formula in equation (1.8) is modified by adding additional term with length of
ground conductors by Laurent and Niemann [7]
= + (1.9)
8
Where,
LT is the total buried length of grid conductors in m.
= + 1+ ⁄
(1.10)
√
Where,
h is the burial depth of grid in m
It does not consider the influence of well type grounding electrodes, mutual resistance
between grid conductors and ground rods, conductor separation and conductor
diameter.
Schwarz [9] developed the equations to take into account the vertical rods (well type)
in uniform soil. It consists of formula for horizontal grid, vertical rods and mutual
resistance between horizontal grid and vertical rods.
.
= (1.11)
Where,
R1 is the grounding resistance of (horizontal) grid in Ω
R2 is the resistance of all vertical ground rod beds in Ω
Rm is the mutual ground resistance between group of grid conductors R1 and
group of ground rods R2 in Ω.
The resistance of the horizontal grid, vertical rod and mutual resistance between them
are given by
.
= .
+ − (1.12)
√
.
= −1+2 . (√ − 1) (1.13)
. . √
.
= .
+ − +1 (1.14)
√
9
Where,
d' is √ℎ. grid conductors buried at depth h in m (when h=0, d' =0.5d 1)
d is the diameter of grid conductors in m
dr is the diameter of vertical rods
nr is the total number of ground rods
Lr is the average length of vertical ground rods in m
k1, k2 are the coefficients related to geometry of grounding grid
A is the area of grounding grid in m2
= .
Where,
When the length of ground rods is greater than the equivalent radius of grounding
grid, the resistivity of soil ‘ρ’ should be considered at the depth of ground rod because
most of the current is mainly dissipated into ground from bottom of the vertical rods
Y. L. Chow and M. M. A. Salam [11] had developed a simple but accurate formula
for the calculation of substation grounding resistance. The basis of proposed method
is a theoretical manipulation of the numerical moment method.
10
1 1 1 0.165 ∆ 2ℎ
= + 1− 1.128 (1.16)
4 ∆ √2 √
Where
k number of meshes in the grid
∆ length of one side of mesh in square grid
Electrical resistivity of soil in and around the substation grounding grid affects
its performance. Soil resistivity affects the grid resistance. For the similar electrode
configuration, higher the soil resistivity, higher will be the ground resistance. Soil
resistivity is mainly the function of depth. It decreases to large extent when water
table is reached. If the grounding electrode is close to water table, ground resistance is
reduced. One of the important reasons of burying grounding grid about 0.6 m below
the earth surface is that top layer of earth may be prone to drying up in summer
season and freezing in winter; both phenomenon increases the soil resistivity. Also
grounding grid conductors must be buried such that it forms good contact with the
surrounding soil and safe from mechanical damage.
11
Table 1.1 Resistivity of various soils [12]
12
depends upon the type of the soil, its grain size, compactness, and variability of the
grain sizes. Dry soil is generally very poor conductor of electricity.
The resistivity of soil increase very slowly, when temperature decrease from
25℃ to 0℃ .But, below 0℃, moisture in the soil start freezing and resistivity of soil
increases to very high. Dissolved substances in the soil such as NaCl, CaCl2, decrease
the soil resistivity.
In uniform soil model, the soil is assumed to have uniform resistivity ρ (Ω-m)
to a very large depth below earth surface. Actually the soil is rarely homogeneous in
all directions; this approximate representation is used when non-uniformity is ± 30
% of average value of resistivity.
A two-layer soil model is shown in figure 1.7. It consists of top layer having
uniform resistivity (Ω-m) up to depth ℎ , overlaying a bottom layer of infinite
depth and uniform resistivity of (Ω-m). Both the layers are of very large extent in
the transverse direction.
=( − ) ⁄( + ) (1.17)
Where,
K = Reflection factor
13
ρ = Soil resistivity of bottom layer up to infinite depth.
Maximum permissible limit of touch and step voltages which are related to
safety of peoples are based on the permissible limits of shock current flowing through
human body without ventricular fibrillation of heart. Permissible touch and step
voltages are the functions of
1 1 Threshold of perception
14
1.4.1: Body Current path
Figure 1.8 shows the touch and step voltage situation. For the step voltage, the
current flows in from one foot, passes through the body and flows out through the
other foot. The total resistance encountered is the body resistance plus resistance of
two feet in series. Where as in case of touch voltage, it flows in from the one hand,
through body and flows out from the both feet in parallel. Thus, the total resistance is
the resistance of human body plus resistance of two feet in parallel. As per IEEE Std
80, an average value of body resistance ( ) is treated as 1000 ohm.
Ground resistance of foot; modeled as a circular disc having equivalent radius of ‘b’
meter placed on soil of uniform resistivity of surface layer ρ is given by
R = ρ ⁄(4 b) (1.18)
R ≅ 3 ρ , assuming b = 0.08 m
E = R + 1.5 C . ρ × I ⁄ t (1.19)
E = R + 6 C .ρ × I ⁄ t (1.20)
15
E = 1000 + 1.5 C . ρ × 0.116⁄ t (1.21)
. ρ⁄ρ
C = (1.23)
h .
ρ is soil resistivity
C is the surface layer de rating factor
During earth fault, the current flows through the grounding grid. It has several
alternate paths such as overhead ground wire, cable sheath, and system neutral and via
earth it return to sources from where fault was feed. The part of the fault current that
flows between grounding grid network and surrounding earth is known as grid current
Ig. It may vary from zero to 100% of the fault current depending on location of fault,
type of fault, transformer connections, conductor configuration, parameters of
overhead ground wires and phase conductors, soil resistivity along the power lines,
grounding grid resistance of the station (Rg). Sizing of grid conductor is based on
magnitude of fault current whereas magnitude of grid current (max value) Ig is
responsible for most stringent safety criterion i.e. dangerous voltages such as step,
touch and transfer potential. The maximum value of grid current is given by
I = C .D .S .I (1.27)
Where,
16
is the fault current
C is the projection factor to account for future expansion of grid over the life
span of the substation.
D is the decrement factor to account for D.C, offset component of fault current.
The maximum permissible values of step and touch voltages are the function of
shock duration. Lesser the shock duration time, more will be the permissible values of
touch and step voltages which enhances the safety level. On the other hand, higher the
shock duration time, lesser the magnitude of safety voltages limit and there by
endanger the personal safety in the substation. Therefore, for stations using digital
relays the shock duration time of 0.5 second and for stations using electromagnetic
relays, shock duration time of one second may be used for determination of maximum
permissible values of Estep and Etouch.
Grid conductor sizing is the function of fault duration and magnitude of fault
current. The fault duration, tf, is greater than shock duration ts. To calculate the
conductor cross-section, the time tf should be the maximum possible fault clearing
time including backup. Therefore, fault duration time (tf) of 1 second for stations
using solid state or digital relays and 3-second for stations using electromagnetic
relays may be adopted [14].
The capacity of grounding system to carry and dissipate ground fault current
without creating a fire or explosive hazard in the area during the entire service life
depends mainly on type of material and size of various elements of the grounding
system. Every element of the substation grounding system, such as horizontal grid
conductors, down lead conductors, connecting leads, vertical ground rods and all
17
primary electrodes, should possesses the following properties throughout the
expected design life span [15].
Should have good conductivity, so that it will not produce local potential
differences.
Should resist fusing and mechanical deterioration of joints during adverse
condition of fault current and its duration.
Be mechanically rugged and strong.
Should withstand and maintain the integrity of grid and its function even when
exposed to corrosion.
Copper: Copper was very commonly used in the past. It has high conductivity and is
resistant to underground corrosion. However, a grid of copper forms a galvanic cell
with other buried steel structures and pipes and is likely to hasten the corrosion of the
latter in the substation. One of the drawbacks for the use of copper is the theft which
may threaten the integrity of the grounding grid. It is also costly as compared to other
materials.
Galvanized steel: The material, most commonly used presently is galvanized steel.
The use of steel avoids galvanic action between grid and other underground structures
and pipes. However, the grid itself may suffer corrosion. The zinc coating gets
destroyed over a period of time. It is desirable that a suitable allowance for corrosion
be made while determining the size of conductor.
Mild steel: It is popularly used in India with suitable corrosion allowance. It is cheap
and readily available. It is used in the form of rectangular strips as well as round grid
conductors. For the same area of cross section of grid conductor, the rectangular strip
has more surface area as compare to round conductor and hence, more corrosion for
the same value soil resistivity. However, rectangular conductor can be easily bent,
bolt and weld. Both mild steel strip conductors and mild steel circular conductors are
used for fabricating the grounding grids. Mild steel material is also used for vertical
ground rods.
18
1.6.2: Corrosion of Ground Conductors
The corrosion reduces its effective area of cross-section and current carrying
capacity. The degree of corrosion depends upon the properties of soil. Generally, soil
with acidic in nature, high moisture content and high dissolved substances like
sodium chloride, calcium chloride are the characteristics of corrosive soil. Lesser the
soil resistivity more is the corrosion of metals buried in it. Ferrous products corrode
more easily.
19
Table 1.3 continue
Type of material Standard electrode potential Remark
Tin (Sn) -0.14 --
Lead (Pb) -0.13 --
Hydrogen (H2) 0.00 --
Copper (Cu) +0.35 --
Mercury (Hg) +0.80 --
Silver (Ag) +0.80 --
Platinum (Pt) +1.20 --
Gold (Au) +1.42 Cathodic or most noble
or protected end
Ph Value: The acidity or alkalinity of the soil is measured by its Ph value. Ph value is
numerically equal to 7 for neutral soil. The soil is said to be acidic in nature when Ph
< 7, whereas for alkaline soil Ph value is more than 7. Ph value of soil can be
measured with a number of commercially available battery-powered meters. Bare
steel is more susceptible to corrosion in acidic rather than neutral or alkaline media
i.e. it corrodes more easily in soils of Ph value less than 7. As far as corrosion is
concern, the ph value of soil in immediate vicinity of grid conductor material is of
consequence. The corrosion is mainly due to low resistivity of soil. Corrosiveness of
soil is based on magnitude of soil resistivity as shown in table 1.4.
20
1.6.3: Size of earth conductors
= Density of material ⁄
= Ambient temperature, ℃
= 40 ℃
When above values of mild steel are substituted in Eq. 1.28, we get
21
1.7: Calculation of Actual step and mesh voltages
Empirical formulae for determination of actual touch and step voltages in a uniform /
homogeneous soil available in IEEE Std 80-2000 [1] are produced here
E = ρ. K . K . I ⁄L (1.31)
= . . . ⁄ (1.32)
E = Mesh voltage
E = Step voltage
( ) h
K = ln + − + . ln )
(1.33)
π h π(
K =π + + (1 − 0.5 ) (1.34)
Where,
D = Spacing between parallel conductors, m
K = 1⁄(2n)( / )
(1.35)
K = For grid with no or few vertical ground rods, with none on corner or in
periphery; =1. It is the corrective weighting factor that adjusts for the effects of inner
conductors on the corner mesh.
.
= (1 + ℎ ) (1.36)
= . . . (1.37)
22
n= Geometric factor composed of factors , ,
n = 2L ⁄L (1.38)
.
n = .
(1.40)
=0.644+0.148 n (1.41)
.
= ⁄ + (1.42)
When, vertical rods are placed on the corner as well as on the perimeter of the grid.
= + --- very few rods, none located on the corner and perimeter
= Length of perimeter, m
23
1.8: Technical challenges
i) To achieve the low grounding resistance in a soil having high resistivity and area
constraint.
ii) To develop the accurate soil models which is very close to measured and
calculated values of soil resistivity.
iv) Design of grounding system that meet the increased fault level.
vi) Optimization of grounding system that will provide low ground resistance and
meet the touch, step voltage criterion. At the same time, reduce the length of
ground conductors which makes the saving.
vii) Measurement of soil resistivity in rocky and hilly area having high resistivity
terrain.
viii) Measurement of ground impedance, touch and step voltage for large extended
substation in urban areas; surrounded by buildings.
24
ix) High Quality equipments and skilled manpower to obtain the reliable data.
Selection of grid conductor material along with factors affecting the sizing of
conductors, types of material, their choice, corrosion of ground conductors, conductor
sizing formula for welded type and bolted type joints, selection of round Vs strip
conductors for grounding grid and conductor corrosion are discussed. Calculation of
actual touch and step voltages in uniform soil as per IEEE STD 80-2000, technical
challenges associated with substation grounding, organization of thesis and
contribution is covered.
26
Chapter 2 presents literature review on economic and efficient design of
substation grounding grid using unequally spaced grid conductors, cost optimization,
type and sizing of grid conductor materials. Determination of surface potential,
analysis of substation grounding grid in multilayer soil models, influence of deep
driven ground rods on grid resistance in uniform and multilayer soil models. Further,
it also explains the measurement of soil resistivity and its interpretation, measurement
of grid impedance in large extended EHV substation, influence of overhead ground
wires on grid resistance, measurement of ground resistance in hilly areas and urban
areas surrounded by public and commercial buildings.
27
design of grounding grids. The two methods of conductor spacing with and without
rod are proposed.The algorithm have been developed in MATLAB software which
gives minimum number of conductors along with their spacings for equally and
unequally spaced grid by keeping safety touch voltage within the maximum
permissible limit in accordance with IEEE Std 80. The data obtained shall be analysed
using Auto grid Pro [AGP] grounding software for several cases to evaluate the grid
resistance, GPR, safety touch and step voltages.
ii] 84 x 63 m rectangular grid IEEE STD 80-2000 with variation of grid current.
iii] 50 x 50 m grid
v] 107 x 72 grid
Further, the effect of ground rods at various locations on touch voltage has discussed.
Some of above grids are also analysed using method III which uses exponentially
spaced grid conductors ie using compression ratio (CR).
The effects of CR with and without rods on touch voltage have been presented
for uniform soil, two layer soil and multilayer soil models. The factors that govern the
resistance of grounding grid such as, depth of grid burial, diameter of the ground
conductors, conductor separation, use of long vertical ground rods, use of unequal
spacing of grid conductors, effect of shape and size of rods, concept of satellite
grounding have been described. Effect of seasonal variation of soil resistivity on
performance of substation grounding grid in uniform, two layers and multilayer soil
models have demonstrated with mitigations.
28
Further, methodology for laboratory tests such as soil resistivity measurement
by sampling method, effect of moisture contents, compaction of soil , addition of
salts like NaCl and KCL, and effect of temperature have been explained. The method
of testing wet rock resistivity and effect of contamination has been explained.
Moreover, methodology and system development for analysis of grid in three layer
soil models, soil treatments to rod electrodes and analysis of 12 x12 m grid in layered
soil by means of field measurements and software analysis have been devised.
Chapter 5 explains the results and analysis. Result analysis of all the eight
cases considered have been carried out using Algorithm developed in MATLAB for
ESG and UESG method I and method II.a. It presents the number of conductors
required for ESG and UESG along with % of saving in conductor length. The effect
of variation of soil resistivity and grid current on grid configurations are analysed
separately. Analysis for touch and step voltages using IEEE STD -80-2000 formulae
and AGP grounding software have been presented. The % of increase or decrease in
touch voltage, step voltage and grid resistance as compared to ESG is tabulated. The
comparisons of touch voltages using all the methods are shown. The % of increase or
decrease in touch voltage as compared to ESG is presented using bar charts.
29
Effect of CR on touch voltage with and without rods are analysed and
presented graphically for uniform, two layer and multilayer soil models. Further, the
effect of soil resistivity reflection factor K on touch voltage and OCR, effect of
ground rods and top layer thickness on touch voltage and OCR is analysed and
presented graphically.
The Effect of seasonal influence on soil resistivity, formation of soil models and
grid parameter like grid resistance, touch and step voltages are analyzed. Effect of
freezing and raining on grid resistance, touch and step voltages in uniform soil model
and two layer soil models are analyzed. Moreover, the impact of freezing, early spring
and raining seasons on grid resistance, touch voltage and step voltage are simulated in
multilayer soil models/ structures. Mitigation by using long vertical rods.
Analysis of artificially prepared grid in three layer soil models, soil treatment to
well type ground rods and analysis of 12m x12m grounding grid with rods in four
layer soil model has been verified by field measurements, analytically and by the use
of AGP grounding software. Field measurements include soil resistivity by Wenner
method, ground resistance by fall of potential method and measurements of touch and
step voltages. All the field measurements were carried out using DET4TCR2 Megger
make earth tester.
30
Chapter 6 covers discussions and conclusions on the basis of simulation
results of the various cases considered, laboratory test results and analysis of various
earthing models.
2] Analysis results of 765 kV, 497.5 x345 m and 1200 kV, 244 x 117 m grids. Use of
UESG method -II.b for analyse of the performance of substation grounding, effect of
ground rods at various locations.
3] Analysis results of CR on ground resistance touch and step voltage in single layer,
two layer and multilayer soil models with and without rods.
4] Factors governing the resistance of grounding grid such as grid layer depth,
diameter of grid conductors and ground rods, variation of number and length of
ground rods, conductor separation , satellite grounding, use of deep driven ground
rods. Effect of shape and size of ground rods on grid resistance.
7] Effect of soil treatment to ground rods using natural mother soil, loamy soil and
bentonite powder.
31
1.11: Contributions
1] The economic and efficient design of substation grounding grids have been
obtained by developing algorithm in Matlab software which gives minimum
number of conductors required along with their spacings for equally and
unequally spaced grid by keeping safety touch voltages within the maximum
permissible limit. It also provides number of conductors required in X and Y
directions of grid along with saving in conductor length. Further, it can be
applied to square as well as rectangular shape grids with and without ground
rods for uniform soil model. Moreover, it also gives conductor spacings for a
grid as small as 4x4 conductors to large grid 35 x35.
2] Suggested the formulae for unequal spacing of grid conductors with meshes
3≤ ≤6
3] One more method for unequal spacing of grid has been proposed.The method is
applicable to the grids having number of meshes (k) more than six. In this
method, the number of conductors used for equally and unequally spaced grid
remains same. By making only the three conductor spacings at the periphery of
the grid unequally safety can be enhanced by large margin. The peripheral three
conductor spacings are progressively decreases towards the periphery of the
grid. The proposed method is very simple but very powerful and superior to
published methods.
4] Suggested the formulae for unequal spacing of grid conductors with meshes
≥6
5] For unequally spaced grids with number of meshes 3 ≤ ≤ 6 , the best results
are possible when grid spacing factor kj1 lies in the range of 0.5 to 0.70.
6] For unequally spaced grids with number of meshes ≥ 6 , good results are
possible when grid conductor spacing factor Kj for method II.b varies from 0.70
to 0.80.
32
6] Limitations of IEEE STD 80-2000 empirical formulae such as ground resistance
touch and step voltages.
The outcome of research work will be useful to Indian utilities, power engineers,
substation grounding designers, consultants and various researchers.
33