The nominal value of ID must take into account the earth leakage current of the UPS and the

load, in normal operating conditions: ID = IDUPS + load leakage current. N.B. The maximum limit
for UPS earth leakage current is 5% of the nominal input current (see EN62040-1-1, Art. 4.5.13.)