UCM-CLD
Chiller Control System
RLC-SVU02F-E4
General Information 2
Principles of operation
of the UCM-CLD module 4
General Information 4
Operator’s Interface 5
Operational Features 9
Diagnostics 16
Diagnostics 16
Default Description 17
RLC-SVU02F-E4 3
ADAPTIVE CONTROL™
Module Functions
MCSP (Motor Compressor Start and Protection) Safety, protection, and control of the helical-rotary compressor and
its components
CPM (Chiller Protection and Management) Safety, protection, and control of the chiller
EXV (Electronic Expansion Valves) Control of both electronic expansion valves
CSR (Communication and Setpoint Reset) ,Control of the serial communication, unit external setpoints and
ice-making mode (optional module)
Local CLD (Local Clear Language Display) Operator interface located in the front panel of the unit
Remote CLD (Remote Clear Language Display) Operator interface located up to 1500m from the unit, able to
communicate with up to four units of the same type (optional module)
TCI IV, IPCB (Tracer Communication Interface 4, Inter Processor Protection of the internal communication bus in the unit from external
Communication Buffer) interferences (optional factory-mounted module, compulsory when
using a Remote CLD)
TCI IV, COM 3 (Tracer Communication Interface 4, COM 3) Interface between the control of the unit and a Building Management
System using Trane COMM 3 serial link
4 RLC-SVU02F-E4
RLC-SVU02F-E4 5
6 RLC-SVU02F-E4
RLC-SVU02F-E4 7
8 RLC-SVU02F-E4
RLC-SVU02F-E4 9
10 RLC-SVU02F-E4
RLC-SVU02F-E4 11
Module
IPC DIP A20-1 A20-2 A52 A9
Switch SW1 SW2 SW1 SW2 SW1 SW1
1 OFF Based OFF Based OFF OFF
2 OFF On OFF On OFF OFF
3 Motor Motor
4 RLA RLA
5
12 RLC-SVU02F-E4
Clamping Nut
Compression Fitting Body
Fitting
1/2" NPT x 1-1/2" Large Coupling
RLC-SVU02F-E4 13
14 RLC-SVU02F-E4
Local/ External unit control mode Refer to Table 4 for the setting rule.
From the Settings menu, the end - AI: External heating setpoint input
user can select the Control mode. (configurable)
- Control Mode: No This input will be powered in 0-1V
In this case, the active cool and heat or 4..20mA. The configuration will
setpoints and Heat/Cool selection allowed 0-1V or 4..20mA signals.
will come from the front panel (User This signal will create a heating
Settings 1). setpoint between 25°C and 60°C.
- Control Mode: Partial Note: The input configuration must
be done before any signal
In this case, the active cool and heat
connection.
setpoints will come from the front
panel (User Settings 1). The active Refer to Table 3 for the setting rule.
Heat/Cool selection will come from - DI: External ON/OFF input
the external Cool/Heat input.
This input will be normally powered
- Control Mode: Full in 24Vac. This input will be the
In this case, the active cool and heat external Auto/Off unit.
setpoints and Heat/Cool selection 0V "Open" : unit disabled
will come from the external analog
and digital inputs. 24Vac "Close" : unit enabled
This input will be powered in 0-1V This input will be normally powered
or 4..20mA. The configuration in 24Vac. This input will be the
(available from menu “User external Heat/Cool mode switch.
Settings 2) will allowed 0-1V or 0V "Open" : Cooling mode
4..20mA signals. This signal will 24Vac "Close" : Heating mode
create a cooling setpoint between
-17.8°C and 18.3°C.
Note: The A70 module will scale
automatically the value between
-12°C and 15°C.
Note: The input configuration must
be done before any signal
connection.
Table 4 - Input values vs. External chilled-water setpoint
Resulting hot-water
Voltage Current set point
(V(dc)) (mA) (°C)
3.6 7.2 -10
4.6 9.2 -5
5.6 11.3 0
6.7 13.3 5
7.7 15.4 10
RLC-SVU02F-E4 15
If there are no diagnostic messages, When a circuit shutdown - manual If more than one diagnostic is
the selected menu item will be reset (CMR) or a machine shutdown present, only the highest priority
displayed continuously. If the - manual reset (MMR) occurs, the active diagnostic will be explained
diagnostics key is pressed and there red LED to the right of the display in detail. For example, if the
are no active diagnostics, the will flash. Otherwise this alarm LED diagnostics occur in the following
readout on the display will be: is de-energized. order before the operator returns -
IFW, MMR, CMR - the display will
NO ACTIVE DIAGNOSTICS read:
PRESENT
*** A machine shutdown has
When a system malfunction occurs,
occurred ! ***
one of the following appropriate
diagnostic messages will be because the MMR has the highest
displayed: priority. However, as the operator
moves through the diagnostic menu
*** A machine shutdown has to the “Last diagnostic,” the
occurred ! *** [Diagnostic description] will show
the CMR diagnostic as well as the
A machine shutdown occurred
IFW. If the “Next” key is pressed,
but has cleared “press (Next)” the display will show all the other
active and historic diagnostics.
The active diagnostic priorities,
*** A circuit shutdown has listed from highest to lowest are:
occurred ! ***
Machine shutdown - manual reset
A circuit shutdown occurred (MMR)
Machine shutdown - automatic reset
but has cleared “press (Next)” (MAR)
Circuit shutdown - manual reset
*** Informational warning *** (CMR)
An informational warning occurred Circuit shutdown - automatic reset
(CAR)
but has cleared “press (Next)” Informational warning (IFW)
16 RLC-SVU02F-E4
Default description
Displayed Code Type Description
Fault 87
Check External Chilled Water Setpt : IFW - Value out of range
Fault 89
Check External Current Limit Setpt : IFW - Value out of range
Fault 8A
Chilled Water Flow (Ent Wtr Temp) : MMR 1) Entering water temperature < leaving WT
2) No water flow
3) Defective EVP sensor
Fault 8E
Evaporator Entering Water Temp Sensor : MMR - Defective sensor
Fault 8F
Condenser Rfgt Temp Sensor - Ckt 1 : MMR -Defective sensor
Fault 90
Condenser Rfgt Temp Senspr - Ckt 2 : MMR - Defective sensor
Fault 93
Evaporator Rfgt Temp Sensor - Ckt 1 : MMR - Defective sensor
Fault 94
Evaporator Rfgt Temp Sensor - Ckt 2 : MMR - Defective sensor
Fault 9A
Condenser Entering Water Temp Sensor : IFW - Defective sensor
Fault 9b
Condenser Leaving Water Temp Sensor : IFW - Defective sensor
Fault A0
Zone Temp Sensor : IFW - Defective sensor
Fault A1
Outdoor Air Temp Sensor : IFW - Defective sensor
Fault Ab
Evaporator Leaving Wtr Temp Sensor : MMR - Defective sensor
Fault b5
Low Pressure Cutout - Ckt 1 : CMR - LP pressure switch open
Fault b6
Low Pressure Cutout - Ckt 2 : CMR - LP pressure switch open
Fault bA
Overload trip - Cprsr A : CMR - Current exceeded
Fault bb
Overload Trip - Cprsr B : CMR - Current exceeded
Fault bC
Overload trip - Cprsr C : CMR - Current exceeded
Fault bd
Overload trip - Cprsr D : CMR - Current exceeded
Fault bE
High Pressure Cutout - Cprsr C : CMR - HP too high
Fault bF
High Pressure Cutout - Cprsr D : CMR - HP too high
Fault C5
Low Chilled Water Temp (Unit Off) : IFW - Antifreeze protection
Fault C6
Low Chilled Water Temp (Unit On) : MAR - Antifreeze protection
Fault CA
Contactor - Cprsr A : MMR - Welded compressor contactor
Fault Cb
Contactor - Cprsr B : MMR - Welded compressor contactor
Fault CC
Contactor - Cprsr C : MMR - Welded compressor contactor
Fault Cd
Contactor - Cprsr D : MMR - Welded compressor contactor
Fault d7
Over Voltage : MAR - Voltage 10% > nominal
Fault d8
Under Voltage : MAR - Voltage 10% < nominal
Fault Ed
Chilled Water Flow Interlock : MAR - Flow switch open more than 6 sec.
Fault F5
High Pressure Cutout - Cprsr A : MMR - HP too high
Fault F6
High Pressure Cutout - Cprsr B : MMR - HP too high
Fault Fd
Emergency Stop Input : MMR - Emergency stop input open
RLC-SVU02F-E4 17
Default description
Displayed Code Type Description
Fault 180
Starter Transition - Cprsr A : CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 181
Starter Transition - Cprsr B : CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 182
Starter Transition - Cprsr C : CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 183
Starter Transition - Cprsr D : CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 184
Phase Reversal - Cprsr A : CMR - Phase reversed
Fault 185 :
Phase reversal - Cprsr B CMR - Phase reversed
Fault 186
Phase reversal - Cprsr C : CMR - Phase reversed
Fault 187
Phase reversal - Cprsr D : CMR - Phase reversed
Fault 190
Low Superheat - Ckt 1 : CMR - Superheat < 1°C during more than 1333°C x sec
Fault 191
Low Superheat - Ckt 2 : CMR - Superheat < 1°C during more than 1333°C x sec
Fault 194 - Refrigerant temperature < Setpoint during more than
Low Evap Rfgt Temp. - Ckt 1 : CMR 30°C x sec
Fault 195 - Refrigerant temperature < Setpoint during more than
Low Evap Rfgt Temp. - Ckt 2 : CMR 30°C x sec
Fault 198
Low Oil Flow - Cprsr A : CMR - Oil flow switch open during more than 20 sec
Fault 199
Low Oil Flow - Cprsr B : CMR - Oil flow switch open during more than 20 sec
Fault 19A
low Oil Flow - Cprsr C : CMR - Oil flow switch open during more than 20 sec
Fault 19b
Low Oil Flow - Cprsr D : CMR - Oil flow switch open during more than 20 sec
Fault 19C
Phase Loss - Cprsr A : CMR - Loss of 1 or more phases
Fault 19d
Phase Loss - Cprsr B : CMR - Loss of 1 or more phases
Fault 19E
Phase Loss - Cprsr C : CMR - Loss of 1 or more phases
Fault 19F
Phase Loss - Cprsr D : CMR - Loss of 1 or more phases
Fault 1A0
Power Loss - Cprsr A : CAR - Loss of all three phases in operation
Fault 1A1
Power Loss - Cprsr B : CAR - Loss of all three phases in operation
Fault 1A2
Power Loss - Cprsr C : CAR - Loss of all three phases in operation
Fault 1A3
Power Loss - Cprsr D : CAR - Loss of all three phases in operation
Fault 1A4
Tracer Communication Loss : IFW - Loss of external information
Fault 1A5
Oil Flow Control - Cprsr A : CMR - Problem on oil circuit
Fault 1A6
Oil Flow Control - Cprsr B : CMR - Problem on oil circuit
Fault 1A7
Oil Flow Control - Cprsr C : CMR - Problem on oil circuit
Fault 1A8
Oil Flow Control - Cprsr D : CMR - Problem on oil circuit
Fault 1A9
EXV Elec Drtive Ckt - Rfgt Ckt 1 : CMR 1) EXV wiring
2) Defective UCM
3) Defective EXV
4) Defective EXV relay
18 RLC-SVU02F-E4
Default description
Displayed Code Type Description
Fault 1AA
EXV Elec Drtive Ckt - Rfgt Ckt 2 : CMR 1) EXV wiring
2) Defective UCM
3) Defective EXV
4) Defective EXV relay
Fault 1Ad - NOVRAM problem, unit is placed on default
Memory Error Type I : IFW setting operating
Fault 1AE
Low Differential Pressure - Ckt 1 : CMR - Delta P< 2,8bar during more than 2 min.
Fault 1AF
Low Differential pressure - Ckt 2 : CMR - Delta P< 2,8bar during more than 2 min.
Fault 1b2 - Phase imbalance >30%, check current transformer
Severe Phase Unbalance - Cprsr A : CMR and unit power supply
Fault 1b3 - Phase imbalance >30%, check current transformer
Severe Phase Unbalance - Cprsr B : CMR and unit power supply
Fault 1b4 - Phase imbalance >30%, check current transformer
Severe Phase Unbalance - Cprsr C : CMR and unit power supply
Fault 1b5 - Phase imbalance >30%, check current transformer
Severe Phase Unbalance - Cprsr D : CMR and unit power supply
Fault 1b6
Compressor Overload Setting - Cprsr A : IFW - Check setting of compressor overload
Fault 1b7
Compressor Overload Setting - Cprsr B : IFW - Check setting of compressor overload
Fault 1b8
Compressor Overload Setting - Cprsr C : IFW - Check setting of compressor overload
Fault 1b9
Compressor Overload Setting - Cprsr D : IFW - Check setting of compressor overload
Fault 1bA
Phase Unbalance - Cprsr A : CMR - Phase imbalance >15%
Fault 1bb
Phase Unbalance - Cprsr B : CMR - Phase imbalance >15%
Fault 1bC
Phase Unbalance - Cprsr C : CMR - Phase imbalance >15%
Fault 1bd
Phase Unbalance - Cprsr D : CMR - Phase imbalance >15%
Fault 1bE
Winding Temp - Cprsr A : CMR - Winding temperature > 105°C
Fault 1bF
Winding Temp - Cprsr B : CMR - Winding temperature > 105°C
Fault 1C0
Winding Temp - Cprsr C : CMR - Winding temperature > 105°C
Fault 1C1
Winding Temp - Cprsr D : CMR - Winding temperature > 105°C
Fault 1C6
High Differential Pressure - Ckt 1 : CMR - LB/HP pressure differential > 24,5 bar
Fault 1C7
High Differential Pressure - Ckt 2 : CMR - LB/HP pressure differential > 24,5 bar
Fault 1d1
Memory Error Type II : IFW - RAM error
Fault 1d2
Memory Error Type III : IFW - RAM error
Fault 1d3
Cprsr Suction Temp Sensor - Ckt 1 : CMR - Defective sensor
Fault 1d4
Cprsr Suction Temp Sensor - Ckt 2 : CMR - Defective sensor
Fault 1d7
Phase Reversal Prot Lost - Cprsr A : CMR - Phase reversal protection not operative
Fault 1d8
Phase Reversal Prot Lost - Cprsr B : CMR - Phase reversal protection not operative
Fault 1d9
Phase Reversal Prot Lost - Cprsr C : CMR - Phase reversal protection not operative
Fault 1dA
Phase Reversal Prot Lost - Cprsr D : CMR - Phase reversal protection not operative
Fault 1db
Slaved EXV Elec Drive Ckt - Rfgt Ckt 1 : CMR - EXV electric drive defective
Fault 1dC
Slaved EXV Elec Drive Ckt - Rfgt Ckt 2 : CMR - EXV electric drive defective
Fault 1dd
High Oil Temp - Cprsr A : CMR - Oil temperature > 77°C
RLC-SVU02F-E4 19
Default description
Displayed Code Type Description
Fault 1dE
High Oil Temp - Cprsr B : CMR - Oil temperature > 77°C
Fault 1dF
High Oil Temp - Cprsr C : CMR - Oil temperature > 77°C
Fault 1E0
High Oil Temp - Cprsr D : CMR - Oil temperature > 77°C
Fault 1E1 - Oil temperature < condenser saturated temperature
Oil System Fault - Cprsr A : CMR during more than 30 min
Fault 1E2 - Oil temperature < condenser saturated temperature
Oil System Fault - Cprsr B : CMR during more than 30 min
Fault 1E3 - Oil temperature < condenser saturated temperature
Oil System Fault - Cprsr C : CMR during more than 30 min
Fault 1E4 - Oil temperature < condenser saturated temperature
Oil System Fault - Cprsr D : CMR during more than 30 min
Fault 1E5
Entering Oil Temp Sensor - Cprsr A : CMR - Defective sensor
Fault 1E6
Entering Oil Temp Sensor - Cprsr B : CMR - Defective sensor
Fault 1E7
Entering Oil Temp Sensor - Cprsr C : CMR - Defective sensor
Fault 1E8
Entering Oil Temp Sensor - Cprsr D : CMR - Defective sensor
Fault 2A1
Cond Fan Vari Speed Drive Fault - Ckt 1 : IFW - Defective fan variator speed after 5 attemps
Fault 2A2
Cond Fan Vari Speed Drive Fault - Ckt 2 : IFW - Defective fan variator speed after 5 attemps
Note :
MMR : Machine shutdown manual reset.
MAR : Machine shutdown automatic reset.
CMR : Circuit shutdown manual reset.
CAR : Circuit shutdown automatic reset.
IFW : Informational warning.
20 RLC-SVU02F-E4
Communication Failures
Displayed Code Description
Fault 410 Loss of Local Display Panel Comm
Fault 412 Chiller Mod to Option Mod Comm Failure
Fault 413 Chiller Mod to EXV Mod Comm Failure
Fault 414 Chiller Mod to Cprsr A Mod Comm Failure
Fault 415 Chiller Mod to Cprsr B Mod Comm Failure
Fault 416 Chiller Mod Cprsr C Mod Comm Failure
Fault 417 Chiller Mod to Cprsr D Mod Comm Failure
Fault 418 Chiller Mod to Slv EXV Mod Comm Failure
Fault 431 EXV Mod to Chiller Mod Comm Failure
Fault 434 EXV Mod to Cprsr A Mod Comm Failure
Fault 435 EXV Mod to Cprsr B Mod Comm Failure
Fault 436 EXV Mod to Cprsr C Mod Comm Failure
Fault 437 EXV Mod to Cprsr D Mod Comm Failure
Fault 441 Cprsr A Mod to Chiller Mod Comm Failure
Fault 443 Cprsr A Mod to EXV Mod Comm Failure
Fault 445 Cprsr A Mod to Cprsr B Mod Comm Failure
Fault 451 Cprsr B Mod to chiller Mod Comm Failure
Fault 453 Cprsr B Mod to EXV Mod Comm Failure
Fault 454 Cprsr B Mod to Cprsr A Mod Comm Failure
Fault 461 Cprsr C Mod to Chiller Mod Comm Failure
Fault 463 Cprsr C Mod to EXV Mod Comm Failure
Fault 467 Cprsr C Mod to Cprsr D Mod Comm Failure
Fault 471 Cprsr D Mod to Chiller Mod Comm Failure
Fault 473 Cprsr D Mod to EXV Mod Comm Failure
Fault 476 Cprsr D Mod to Cprsr C Mod Comm Failure
Fault 481 Slv EXV Mod to Chiller Mod Comm Failure
Fault 483 Slv EXV Mod to EXV Mod Comm Failure
Fault 484 Slv EXV Mod to Cprsr A Mod Comm Failure
Fault 485 Slv EXV Mod to Cprsr B Mod Comm Failure
Fault 486 Slv EXV Mod to Cprsr C Mod Comm Failure
Fault 487 Slv EXV Mod to Cprsr D Mod Comm Failure
RLC-SVU02F-E4 21
User interface
1 2 3 4
Prg Esc
5 6 7
22 RLC-SVU02F-E4
Control logic Freeze protection resistance control • Pump change-over on pump start:
This application must control the When a new demand to start a
Turning the control on pump appears, a pump change-
electric heater command to protect
When switching on, all the outputs over will be done on the pump to
the unit during low ambient
will be disabled. preserve pump mechanical seals.
temperature when UCM-CLD
Reaction in case of failure • Freeze protection by pump
doesn't demand pump activation.
• Failure on entering water activation:
temperature sensor (EWT): Electric Heater ON/OFF When UCM-CLD does not require
A failure on this sensor (value out If the ambient air temperature is pump activation and that ambient
of range) will disable the return lower than the heater activation temperature is lower than the
water temperature control during setpoint -1°C, then the heater output electric heater freeze protection
the freeze protection by pump is activated. When the ambient setpoint but over 0°C, then a
activation. water pump is cyclically activated
temperature reaches +1°C over the
• Failure on ambient Air temperature (5 min ON, 10 min OFF
setpoint, the output is deactivated. programmable). If the ambient
sensor (OAT):
A failure on this sensor (Value out Pump control temperature is lower than 0°C,
of range) will turn on the heater This application must control 2 the pump is operating
output and enable the freeze pumps mounted in parallel on the continuously. This protection may
protection by pump activation. evaporator circuit of a RTAD unit. be deactivated.
• No water flow while pump is • Pump start and stop However, if the ambient air
activated (demanded) or WFP: When a pump demand is sent by temperature is lower than the low
If the water flow input is open (no the UCM-CLD module and when ambient setpoint (as a default
flow) for more than 20s while the system is enabled, the control -18°C), the freeze protection by
pump is demanded for cooling or is in charge of the activation of on pump activation is reactivated.
for freeze protection by pump the 2 pumps (1 at a time). A In all cases, a temperature control
activation, then an automatic hardware safety exists on the on the return water temperature
latching alarm is activated. During electrical panel not to start both will limit the water temperature of
the 10 first seconds of this flow pumps at the same time. the loop. If this temperature goes
alarm, the module will switch to • Automatic change-over on a pump over +15°C (programmable)
the backup pump to try to obtain a failure: during 5mn, then the pump is
water flow. When a failure appears on a pump stopped during 10mn
• Water flow without pump in operation, the control will (programmable) and then will
activation (demand): automatically switch on the other cycle according to these timers.
If the water flow input is closed pump and will stop the faulty
(flow detected) for more than 30s pump.
without pump demand and • Automatic change-over on failure
without manual forced activation, on water flow:
then an automatic latching alarm When a water flow loss is detected,
will be activated. the control will automatically
switch on the backup pump to try
to keep water flow in the loop. If
the alarm remains or if the second
pump is out of order, an auto
latching alarm is triggered.
RLC-SVU02F-E4 23
24 RLC-SVU02F-E4
Access to sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using
the Up and Down keys and selected using the Enter button.
RLC-SVU02F-E4 25
Analog Inputs
Return Wat T
Outside Air T
Digital Inputs
Digital Outputs
Counters
26 RLC-SVU02F-E4
Settings Menu
Access to each field within a mask using the Enter key. Change the field
value using the Up and Down keys and confirmation by Enter.
User Settings
Clock Menu
Clock Settings
RLC-SVU02F-E4 27
See Application
No Alarm No Alarm - none status on Main
display
Alarm
Faulty Pump 1 Manual Pump 1 OFF Failure on pump 1
Pump 1
Alarm
Faulty Pump 2 Manual Pump 2 OFF Failure on pump 2
Pump 2
Alarm
Could be due to Water Flow is
Flow Switch On Water Flow w/o
Auto a faulty water established but there
But no pump Pump
flow switch is no pump required
required
28 RLC-SVU02F-E4
Access to Sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using
the Up and Down keys and selected using the Enter button.
RLC-SVU02F-E4 29
Setpoint Source
1 = Setpoint Source (Front Panel, External, Air Reset, Return Water Reset)
2 = Active chilled water setpoint
30 RLC-SVU02F-E4
Digital Inputs
Digital Outputs
RLC-SVU02F-E4 31
3 Way Valve IO
Speed
Low
Relay
Off
Settings Menu
Access to each field within a mask using the Enter key. Change the field
value using the Up and Down keys and confirmation by Enter.
User Settings
32 RLC-SVU02F-E4
Clock Settings
RLC-SVU02F-E4 33
Faulty sensor,
Faulty LWT Free Cooling OFF
Alarm LWT Sensor Auto out of range
Sensor Chiller ON
-38..+ 60°C during + 30s
Faulty sensor,
Faulty EWT Free Cooling OFF
Alarm EWT Sensor Auto out of range
Sensor Chiller ON
-38..+ 60°C during + 30s
Faulty sensor,
Faulty OAT Free Cooling OFF
Alarm OAT Sensor Auto out of range
Sensor Chiller ON
-38..+ 60°C during + 30s
LWT or EWT
Alarm Free Cooling OFF
Low LWT or EWT Auto below LAW for
Low LWT or EWT Chiller OFF
more than 16.6°C*s
Alarm
LWT > EWT Free Cooling OFF LWT-EWT
Int (LWT-EWT) Manual
during +120s Chiller OFF above 120°C*s
>120°C*s
34 RLC-SVU02F-E4
Permanent display
Access to this mask using the Esc key from any mask. The program will
return automatically into it after 5min.
HR Application V1.0
00/00/00 00:00
Hot Wat Temp: 00.0°C
Cool&HR Mode Running
RLC-SVU02F-E4 35
Access to Sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using
the Up and Down keys and selected using the Enter button.
36 RLC-SVU02F-E4
Digital Inputs
Circuit 1: Running
Circuit 2: Running
HR Status: Enabled
NNSB: Off
Digital Outputs
1 2 3 CKT
FAN1: Off Off Off On
FAN2: Off Off Off On
PRG Relay: On
1 = Circuit 1 Fans stages (Off, On) Circuit 1 Enable Output (Off, On)
2 = Circuit 2 Fans stages (Off, On) Circuit 2 Enable Output (Off, On)
3 = Programmable Relay (Off, On)
Analog Outputs
RLC-SVU02F-E4 37
Settings Menu
Access to each field within a mask using the Enter key. Change the field
value using the Up and Down keys and confirmation by Enter.
User Settings
PRG Relay: HR ON
Clock Settings
38 RLC-SVU02F-E4
History Events
Alarm Screen Reset Type Unit status Description
Record
Heat
See unit status on
No Alarm No Alarm - Recovery ON
Main display
Chiller ON
Heat
Alarm HWT Faulty HWT Faulty sensor, out of range
Auto Recovery OFF
Sensor Sensor -38..+ 85°C during + 30s
Chiller ON
Heat
Alarm PRS1 Faulty PRS1 Faulty sensor, out of range
Auto Recovery ON
Sensor Sensor -0.5..+ 30 bars during + 15s
Circuit 1 OFF
Heat
Alarm PRS2 Faulty PRS2 Faulty sensor, out of range
Auto Recovery ON
Sensor Sensor -0.5..+ 30 bars during + 15s
Circuit 2 OFF
RLC-SVU02F-E4 39
Permanent display
Access to this mask using the "Esc" key from any mask. The program will
return automatically into it after 5 min.
Access to sub-menus
Access to this mask using the "Prg" key
40 RLC-SVU02F-E4
Binary Outputs
Active Setpoints
RLC-SVU02F-E4 41
Settings Menu
Access to each field within a mask using the "Enter" key. Change the field
value using the Up and Down keys and confirmation by "Enter".
1 = (0000 to 9999)
User Settings 1
User Settings 2
42 RLC-SVU02F-E4
Clock Menu
Clock Settings
Chiller
Alarm CDS Faulty CDS Auto stopped (in Faulty sensor, out of range
LWT Sensor LWT Sensor Heating -38..+70°C during +60s
mode only)