You are on page 1of 13

TRANSFORMER 1

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 8 6,200 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 11 28,325 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 0 0
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 19 34,525 VA
TRANSFORMER 2

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 7 5,425 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 6 15,450 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 2 7,386 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 1 5,993 VA
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 16 34,254 VA
TRANSFORMER 3

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 8 6,200 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 5 12,875 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 2 7,386 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 1 8,293 VA
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 16 34,754 VA
TRANSFORMER 4

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 2 1,550 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 11 28,325 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 1 3,693 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 14 33,568 VA
TRANSFORMER 5

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 4 3,100 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 9 23,175 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 2 7,386 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 33,661 VA
TRANSFORMER 6

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 5 3,875 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 6 15,450 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 4 14,772 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 34,097 VA
TRANSFORMER 7

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 2 1,550 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 8 20,600 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 1 4,415 VA
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 2 7,386 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 13 33,951 VA
TRANSFORMER 8

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 3 2,325 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 5 12,875 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 1 4,415 VA
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 4 14,772 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 13 34,387 VA
TRANSFORMER 9

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 5 3,875 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 7 18,025 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 1 4,415 VA
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 2 7,386 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 33,701 VA
TRANSFORMER 10

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 4 3,100 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 6 15,450 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 1 4,415 VA
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 3 11,079 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 14 34,044 VA
TRANSFORMER 11

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 3 2,325 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 8 20,600 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 1 4,415 VA
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 1 6,255 VA
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA -- -
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 13 33,595 VA
TRANSFORMER 12

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 3 2,325 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 11 28,325 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA - -
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA - -
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 1 3,693 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 34,343 VA