You are on page 1of 4

Capital Controls®

Series 2000
Chloromatic™ Gas Control Valve

The Series 2000 Chloromatic™ control And since manual system


valve is wall mounted and responds feed rates are based on
to control signals from a water flow peak flows, automatic feed
transmitter or a PLC. Valve characteristics reduces gas consumption.
are provided to directly accept a pacing Similar units of different
signal proportional to flow. materials may be used for
Automatic control eliminates the need feeding ammonia, carbon
for continuous operator monitoring and dioxide and sulfur dioxide
manual adjustment of the gas feed rate gases. The maximum
with changes in flow, especially where capacities for these
chemical discharge levels are regulated. feeders are approximately
50%, 75%, and 100%
respectively of the
chlorinator capacity; e.g.,
the ammonia feeder is rated
at 250 lb/day maximum.
Chloromatic valve is used in
conjunction with a vacuum
regulator, gas flowmeter
and an ejector to provide
a complete system.
(See Figure 1)
• Integrated circuits and a
single corrosion resistant
electrical enclosure
increase reliability.
• The Chloromatic valve
insures positive response
to electric signals
representing either water
flow or PLC control.

WATER MADE EASY

MARINE ENERGY MUNICIPAL INDUSTRIAL


Engineering Specifications
Capacities: Standard maximum capacities are: 10, 25, The control valve operator consists of a solid state
50, 100, 200, 300, 500, 1000, 2000, 4000, 6000, 8000, electronic circuit, a stepping motor, and a mechanism
and 10000 lb/day (200 and 500 g/h; 1,2,4,6, 10, 20, 40, to position the control valve plug. The single input
80, 120, 160 and 200 kg/h) of chlorine gas. valve operator can be adapted to respond to any one of
Control Modes: All automatic chlorinators utilize the the following signals: 4-20 mAdc; 1-5, 0-4, or 0-5 Vdc
Chloromatic™ valve. This unit has two major components, (normally from a flow transmitter).
the control valve and the electric operator. The control A dosage adjustment knob is provided to set the chlorine
valve consists of a housing, a shaped precision plug and to water ratio to compensate for differences in chlorine
a corrosion resistant plastic seat. The plug is positioned demand. The dosage adjustment is combined with an on-
with respect to the seat by the valve operator to provide off switch for power shut-off to the motor. With power to
precise control of chlorine feed rates in accordance with the motor shut off, the valve can be operated manually by
the electric input signal to the valve operator. means of a knob connected to the motor drive shaft.

Water Chlorine
Solution

Figure 1
Specifications
Process Connections: Manual Control: Manual Control Knob (multi-turn)
• 5/8" inlet and outlet vacuum tubing connector up to available to position valve plug
500 PPD (10 kg/h). when dosage control is in “off”
position or if power fails.
• 1" NPT Threaded inlet and outlet connections for
1000 PPD - 3000 PPD.
Physical Characteristics

Power Requirements: Outline Dimension: Approx. 16½ inch L x


7 inch W x 7 inch H
Voltage: 120 Vac ±10%; 50/60 Hz
Weight: 17 lb. (7.7 kg)
220/240 Vac ±10%; 50/60 Hz
Enclosure Classification: NEMA 3R; IEC 529 IP 54

Power Consumption:
Materials of Construction:
Quiescent: 5 VA maximum
Main Housing & Cover: Die cast aluminum with
Motor Operating: 18 VA maximum baked vinyl finish
Valve Plug: Silver, PVC or Austenitic
Electrical Characteristics: Stainless Steel (capacity
and gas type dependent)
Input Signal:
Orifice: Fluorosint
Single Input: 4-20 mAdc, 1-5, 0-4, 0-5 V dc
(Mica filled Teflon)
Output Signals (optional)
Retransmission: 4-20 mAdc into 750 ohms max
Equipment Description
High and Low Valve Limit The Chloromatic™ valve shall be stepping motor operated
Switch Contacts: Switching (Resistive) with the motor and electronic components mounted in a
corrosion resistant enclosure. The electronic components
Power: 60 W, 125 VA of the operator shall be mounted on printed circuit boards
Voltage: 220 V dc, 250 Vac of the latest electrical design including integrated circuits.
Current: 2 A ac/dc All circuit boards shall be coated with Humiseal with a
Carrying Current minimum thickness of 0.002" to meet the requirements
of MIL-E-5272, thus increasing the corrosion resistance of
Electrical Connections: (4) ½ inch NPT Internally the boards. The input signal shall be (4-20) (0-16) (0-20)
Threaded Conduit Entrances mAdc or (1-5) (0-4) (0-5) Vdc. An electric on-off switch
shall be provided and the device shall be equipped with
a thumb-wheel which shall quickly position the valve
Environmental Limits:
manually without the necessity of disconnecting linkages.
Ambient Temperature: 40 to 125°F (4 to 52°C) The valve shall be wall or wall panel mounted.
Shipping Temperature: -20 to 125°F (-29 to 52°C)
Vibration Limits: 5 to 14 Hz @ 0.05 inch
p-p disp.
14 to 200 Hz @ 0.5 g

Dosage Control Output: Input Ratio of 0.2:1 to 2.0:1


Capital Controls®
Series 2000 Wall Panel with Chloromatic™ Gas Control Valve

Easy to install, each Series 2000 wall panel feeder is factory


tested and needs no field adjustment prior to start-up.
Ten different flowmeter capacities ranging from 25 to
3000 PPD (500 g/h to 60 kg/h) provide versatility in
meeting gas flow requirements.
The Series 2000 wall panel feeder includes the Capital
Controls Series 2000 Chloromatic™ Gas Flow Control
Valve and gas flow indicator mounted on a corrosion-
resistent, heavy-duty panel. The wall panel feeder can be
provided with optional vacuum gauge or high and low
vacuum switches. The control valve receives signals from
a water flow transmitter or PLC.

Physical Characteristics:
Outline Dimension:
• 500 PPD (10 kg/h) w/out vacuum switches; approx.
24" H x 20" W x 8" D (61cm H x 51cm W x 21cm D)
• 3000 PPD (60 kg/h) w/out vacuum switches; approx.
24" H x 24" W x 8.5" D (61cm H x 61cm W x 22cm D)
• 500 PPD (10 kg/h) w/vacuum switches; approx.
24" H x 20" W x 8" D (61cm H X 51cm W X 21cm D)
• 3000 PPD (60 kg/h) w/vacuum switches;
24" H x 24" W x 8.5" D (61cm H x 61cm W x 22cm D)

Weight:
• 500 PPD (10 kg/h) w/out vacuum switches;
22.66 lbs (10.3 kg)
• 3000 PPD (60 kg/h) w/out vacuum switches;
38 lbs (17.3 kg)
• 500 PPD (10 kg/h) w/vacuum switches;
36.84 lbs (16.7 kg)
• 3000 PPD (60 kg/h) w/vacuum switches;
46.5 lbs (21 kg)

WATER MADE EASY

MARINE ENERGY MUNICIPAL INDUSTRIAL

info.dnwt@denora.com www.denora.com

© Copyright 2016 Industrie De Nora S.p.A. - All rights reserved.


De Nora, ON circle, Our research - your future, electrochemistry at your service (and any other
trademark name) are trademarks or registered trademarks of Industrie De Nora S.p.A. in Europe and/or
other countries. Other trademarks used herein are the registered trademarks of their respective owners.
The information contained herein is offered for use by technically qualified personnel at their discretion
and risk without warranty of any kind.

DNWT - Capital Controls® Series 2000 - 100.0310.7 - 07/2016