HEAT LOAD ESTIMATION SUMMARY & ROOM DATA SHEET

DESIGN
FLOOR FLOOR
INDOOOR DESIGN SELECTE SELECTE
TO TO FALSE OCCUPPA FRESH FRESH SUPPLY SUPPLY AS PER
AREA DRY INDOOOR LIGHTING LOAD EQUIP. LOAD D FRESH COOLING CAPACITY D SUPPLY AS PER BSL
SNO DESCRIPTION FLOOR CEILING NCY AIR * AIR AIR AIR CONSULTANT
BULB RH** AIR AIR QTY
HEIGHT HEIGHT
TEMPERA
sqft ft ft DEG F % w w/sqft kw w/sqft No.s ACPH cfm cfm TR DCFM ACPH CFM CFM TR CFM TR CFM

SECOND FLOOR
1 FEMALE WARD-1 3634 13.8 11.5 71.6 55 3997 1.1 3.6 1.0 95 0 693 695 17.8 7803 na 0 7805
2 STORE LINEN 66 13.8 11.5 71.6 55 72 1.1 0.0 0.0 0 0 4 5 0.2 98 na 0 100
3 TREATMENT ROOM 119 13.8 11.5 71.6 55 131 1.1 0.2 2.0 2 0 17 20 0.4 171 na 0 175 26.8 12095 30 12000
4 CORRIDOR 1810 13.8 11.5 71.6 55 1991 1.1 1.8 1.0 20 0 209 210 7.8 3813 na 0 3815
5 DOCTORS LOUNGE 66 13.8 11.5 71.6 55 73 1.1 0.3 3.8 3 0 19 20 0.5 196 na 0 200
6 FEMALE WARD-2 1658 13.8 11.5 71.6 55 1824 1.1 1.7 1.0 30 0 249 250 7.2 3299 na 0 3300 7.2 3300 9 3600
JOB NO: C10-46042
INPUT DATA
CUSTMOR NAME INKEL
FLOOR SECOND FLOOR DATE: 8/28/2019
AREA FEMALE WARD-1 TIME OF PEAK 1600 HRS LATITUDE 11.2 DEG N
MONTH OF PEAK MAY ALTITUDE 1 MTRS ABOVE MSL
CONDITIONED AREA 3634 SQ.FT DAILY RANGE 10
TOTAL WALL HEIGHT 13.8 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 11.5 FT. CONDITIONS CONDITIONS
O O
EXPOSURE N N-E E S-E S S-W W N-W DB - F 95 DB - F 71.6
GLASS AREA -SQ.FT 107 200 RH - % 58 RH - % 55
O O
WALL AREA- SQ.FT ** 298 619 WB - F 82 WB - F 61.07
PARTITION AREA 778 SQ.FT TH - BTU/LB 45.76 TH - BTU/LB 27.11
SKY GLASS AREA SQ.FT ** WALL AREA FIGURES GRAINS/LB 145.7 GRAINS/LB 63.7
NO OF AIR CHANGES PER HOUR ARE FOR THE HEIGHT
NO. OF PEOPLE 95 OF WALL UP TO FALSE FACTORS ADP/SHR VALUES FOR INSIDE DESIGN
CFM/PERSON 5.0 CEILING AND BALANCE WALL 0.33 DB 71.6 RH 55
CFM/SQFT 0.06 HEIGHT WILL BE TO GLASS 0.56
FRESH AIR QTY CFM RETURN AIR GAIN ALL GLASS 1.13 SHR ADP
LIGHTING LOAD 1.1 WATT/SQ.FT PARTITION 0.42 1 54.9
EQUIPMENT LOAD 3.6 KW CEILING 0.31 0.93 54
MISCELLANEOUS-SENS BTU/HR FLOOR 0.32 0.83 52
MISCELLANEOUS-LATE BTU/HR ROOF 0.12 0.77 50
EXPOSED FLOOR SQ.FT SKY GLASS 0.56
ROOF GAIN SQ.FT
CEILING GAIN 3634 SQ.FT
SH PER PERSON 260 BTU/HR
LH PER PERSON 90 BTU/HR
BYPASS FACTOR 0.1
HEAT LOAD ESTIMATE
CONDITIONED AREA 3634 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 11.5 FT. OUTSIDE 95 58 82 45.76 145.7
VOLUME 41719 CU.FT INSIDE 71.6 55 61.07 27.11 63.7
BYPASS FACTOR 0.1
PEOPLE - BASIS 95 x 5 + 0.06 = 693.04 DIFFERENCE 23.4 20.93 18.65 82
FRESH AIR QTY. 0 = 0
AIR CHANGE BASIS 0 x 41719 x 0.0166 = 0
TOTAL VENTILATION CFM 693

NORTH WALL 298 x 0.33 x 17.4 = 1713 RETURN AIR


= ((∑WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL 0 x 0.33 x 23.4 = 0 GAIN FOR
EAST WALL 0 x 0.33 x 31.4 = 0 WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL 0 x 0.33 x 31.4 = 0
SOUTH WALL 0 x 0.33 x 29.4 = 0 RETURN AIR GAIN ****
SOUTH WEST WALL 0 x 0.33 x 27.4 = 0
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN
WEST WALL 619 x 0.33 x 25.4 = 5190
FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE
NORTH WEST WALL 0 x 0.33 x 19.4 = 0
TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE
NORTH GLASS 107 x 0.56 x 35 = 2088
SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND
NORTH EAST GLASS 0 x 0.56 x 11.23 = 0
ADDED TO RETURN AIR GAIN
EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH GLASS 0 x 0.56 x 11.23 = 0
SOUTH WEST GLASS 0 x 0.56 x 70.9 = 0 SENSIBLE HEAT RATIO (ESHF) = 0.91
O
WEST GLASS 200 x 0.56 x 159 = 17820 APPARATUS DEW POINT F = 53.7
NORTH WEST GLASS 0 x 0.56 x 145.5 = 0 DEHUMIDIFIED CFM CFM = 7803
SKY GLASS 0 x 0.56 x 110 = 0 TOTAL SPACE HEAT BTU/HR = 149048
ALL GLASS 307 x 1.13 x 23.4 = 8109 VENTILATION HEAT BTU/HR = 52347
PARTITION WALL 778 x 0.42 x 18.4 = 6015 RETURN AIR GAIN **** BTU/HR = 2584
FLOOR 0 x 0.32 x 18.4 = 0 REFRIGERATION SUB TOTAL BTU/HR = 203979
CEILING 3634 x 0.31 x 18.4 = 20729 SAFETY (PUMP GAIN ETC.,) 5% BTU/HR = 10199
ROOF 0 x 0.12 x 43.4 = 0 REFRIGERATION TOTAL BTU/HR = 214178
VENTILATION 693 x 23.4 x 0.108 = 1751 REFRIGERATION LOAD TR = 17.85
PEOPLE 95 x 260 x 1 = 24700
LIGHTS 3997 x 1.5 x 3.41 = 20447 CONCLUDED PARAMETERS FOR AHU
EQUIPMENT 4 x 1 x 3410 = 12392 DEHUMIDIFIED CFM CFM
MISCELLANEOUS 0 x 1 x 1 = 0 SPACE SENSIBLE HEAT BTU/HR
SPACE SENSIBLE SUB TOTAL = 120954 REFRIGERATION LOAD TR
DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE 12.5 = 15119 AHU MAKE
TOTAL SPACE SENSIBLE HEAT = 136073 AHU MODEL NO:
VENTILATION 693 x 82 x 0.067 = 3808 FAN MAKE
PEOPLE 95 x 90 x 1 = 8550 FAN MODEL NO:
MISCELLANEOUS 0 x 1 x 1 0 COOLING COIL FACE AREA SQ.FT
O
SPACE LATENT SUB TOTAL = 12358 CH. WATER INLET TEMP. F
O
SAFETY PERCENTAGE 5 = 618 CH. WATER OUTLET TEMP. F
TOTAL SPACE LATENT HEAT = 12975 CHILLED WATER FLOW RATE USGPM
TOTAL SPACE SENSIBLE HEAT = 136073 FAN STATIC PRESSURE INCH WC
TOTAL SPACE HEAT = 149048 MOTOR RATING HP
JOB NO: C10-46042
INPUT DATA
CUSTMOR NAME INKEL
FLOOR SECOND FLOOR DATE: 8/28/2019
AREA STORE LINEN TIME OF PEAK 1600 HRS LATITUDE 11.2 DEG N
MONTH OF PEAK MAY ALTITUDE 1 MTRS ABOVE MSL
CONDITIONED AREA 66 SQ.FT DAILY RANGE 10
TOTAL WALL HEIGHT 13.8 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 11.5 FT. CONDITIONS CONDITIONS
O O
EXPOSURE N N-E E S-E S S-W W N-W DB - F 95 DB - F 71.6
GLASS AREA -SQ.FT RH - % 58 RH - % 55
O O
WALL AREA- SQ.FT ** WB - F 82 WB - F 61.07
PARTITION AREA 87 SQ.FT TH - BTU/LB 45.76 TH - BTU/LB 27.11
SKY GLASS AREA SQ.FT ** WALL AREA FIGURES GRAINS/LB 145.7 GRAINS/LB 63.7
NO OF AIR CHANGES PER HOUR ARE FOR THE HEIGHT
NO. OF PEOPLE 0 OF WALL UP TO FALSE FACTORS ADP/SHR VALUES FOR INSIDE DESIGN
CFM/PERSON 5.0 CEILING AND BALANCE WALL 0.33 DB 71.6 RH 55
CFM/SQFT 0.06 HEIGHT WILL BE TO GLASS 0.56
FRESH AIR QTY CFM RETURN AIR GAIN ALL GLASS 1.13 SHR ADP
LIGHTING LOAD 1.1 WATT/SQ.FT PARTITION 0.42 1 54.9
EQUIPMENT LOAD 0.0 KW CEILING 0.31 0.93 54
MISCELLANEOUS-SENS BTU/HR FLOOR 0.32 0.83 52
MISCELLANEOUS-LATE BTU/HR ROOF 0.12 0.77 50
EXPOSED FLOOR SQ.FT SKY GLASS 0.56
ROOF GAIN SQ.FT
CEILING GAIN 66 SQ.FT
SH PER PERSON 285 BTU/HR
LH PER PERSON 165 BTU/HR
BYPASS FACTOR 0.1
HEAT LOAD ESTIMATE
CONDITIONED AREA 66 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 11.5 FT. OUTSIDE 95 58 82 45.76 145.7
VOLUME 753 CU.FT INSIDE 71.6 55 61.07 27.11 63.7
BYPASS FACTOR 0.1
PEOPLE - BASIS 0 x 5 + 0.06 = 3.9349 DIFFERENCE 23.4 20.93 18.65 82
FRESH AIR QTY. 0 = 0
AIR CHANGE BASIS 0 x 753 x 0.0166 = 0
TOTAL VENTILATION CFM 4

NORTH WALL 0 x 0.33 x 17.4 = 0 RETURN AIR


= ((∑WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL 0 x 0.33 x 23.4 = 0 GAIN FOR
EAST WALL 0 x 0.33 x 31.4 = 0 WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL 0 x 0.33 x 31.4 = 0
SOUTH WALL 0 x 0.33 x 29.4 = 0 RETURN AIR GAIN ****
SOUTH WEST WALL 0 x 0.33 x 27.4 = 0
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN
WEST WALL 0 x 0.33 x 25.4 = 0
FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE
NORTH WEST WALL 0 x 0.33 x 19.4 = 0
TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE
NORTH GLASS 0 x 0.56 x 35 = 0
SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND
NORTH EAST GLASS 0 x 0.56 x 11.23 = 0
ADDED TO RETURN AIR GAIN
EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH GLASS 0 x 0.56 x 11.23 = 0
SOUTH WEST GLASS 0 x 0.56 x 70.9 = 0 SENSIBLE HEAT RATIO (ESHF) = 0.99
O
WEST GLASS 0 x 0.56 x 159 = 0 APPARATUS DEW POINT F = 54.7
NORTH WEST GLASS 0 x 0.56 x 145.5 = 0 DEHUMIDIFIED CFM CFM = 98
SKY GLASS 0 x 0.56 x 110 = 0 TOTAL SPACE HEAT BTU/HR = 1623
ALL GLASS 0 x 1.13 x 23.4 = 0 VENTILATION HEAT BTU/HR = 297
PARTITION WALL 87 x 0.42 x 18.4 = 669 RETURN AIR GAIN **** BTU/HR = 134
FLOOR 0 x 0.32 x 18.4 = 0 REFRIGERATION SUB TOTAL BTU/HR = 2054
CEILING 66 x 0.31 x 18.4 = 374 SAFETY (PUMP GAIN ETC.,) 5% BTU/HR = 103
ROOF 0 x 0.12 x 43.4 = 0 REFRIGERATION TOTAL BTU/HR = 2157
VENTILATION 4 x 23.4 x 0.108 = 10 REFRIGERATION LOAD TR = 0.18
PEOPLE 0 x 285 x 1 = 0
LIGHTS 72 x 1.5 x 3.41 = 369 CONCLUDED PARAMETERS FOR AHU
EQUIPMENT 0 x 1 x 3410 = 0 DEHUMIDIFIED CFM CFM
MISCELLANEOUS 0 x 1 x 1 = 0 SPACE SENSIBLE HEAT BTU/HR
SPACE SENSIBLE SUB TOTAL = 1422 REFRIGERATION LOAD TR
DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE 12.5 = 178 AHU MAKE
TOTAL SPACE SENSIBLE HEAT = 1600 AHU MODEL NO:
VENTILATION 4 x 82 x 0.067 = 22 FAN MAKE
PEOPLE 0 x 165 x 1 = 0 FAN MODEL NO:
MISCELLANEOUS 0 x 1 x 1 0 COOLING COIL FACE AREA SQ.FT
O
SPACE LATENT SUB TOTAL = 22 CH. WATER INLET TEMP. F
O
SAFETY PERCENTAGE 5 = 1 CH. WATER OUTLET TEMP. F
TOTAL SPACE LATENT HEAT = 23 CHILLED WATER FLOW RATE USGPM
TOTAL SPACE SENSIBLE HEAT = 1600 FAN STATIC PRESSURE INCH WC
TOTAL SPACE HEAT = 1623 MOTOR RATING HP
JOB NO: C10-46042
INPUT DATA
CUSTMOR NAME INKEL
FLOOR SECOND FLOOR DATE: 8/28/2019
AREA TREATMENT ROOM TIME OF PEAK 1600 HRS LATITUDE 11.2 DEG N
MONTH OF PEAK MAY ALTITUDE 1 MTRS ABOVE MSL
CONDITIONED AREA 119 SQ.FT DAILY RANGE 10
TOTAL WALL HEIGHT 13.8 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 11.5 FT. CONDITIONS CONDITIONS
O O
EXPOSURE N N-E E S-E S S-W W N-W DB - F 95 DB - F 71.6
GLASS AREA -SQ.FT RH - % 58 RH - % 55
O O
WALL AREA- SQ.FT ** WB - F 82 WB - F 61.07
PARTITION AREA SQ.FT TH - BTU/LB 45.76 TH - BTU/LB 27.11
SKY GLASS AREA SQ.FT ** WALL AREA FIGURES GRAINS/LB 145.7 GRAINS/LB 63.7
NO OF AIR CHANGES PER HOUR ARE FOR THE HEIGHT
NO. OF PEOPLE 2 OF WALL UP TO FALSE FACTORS ADP/SHR VALUES FOR INSIDE DESIGN
CFM/PERSON 5.0 CEILING AND BALANCE WALL 0.33 DB 71.6 RH 55
CFM/SQFT 0.06 HEIGHT WILL BE TO GLASS 0.56
FRESH AIR QTY CFM RETURN AIR GAIN ALL GLASS 1.13 SHR ADP
LIGHTING LOAD 1.1 WATT/SQ.FT PARTITION 0.42 1 54.9
EQUIPMENT LOAD 0.2 KW CEILING 0.31 0.93 54
MISCELLANEOUS-SENS BTU/HR FLOOR 0.32 0.83 52
MISCELLANEOUS-LATE BTU/HR ROOF 0.12 0.77 50
EXPOSED FLOOR SQ.FT SKY GLASS 0.56
ROOF GAIN SQ.FT
CEILING GAIN 119 SQ.FT
SH PER PERSON 285 BTU/HR
LH PER PERSON 165 BTU/HR
BYPASS FACTOR 0.1
HEAT LOAD ESTIMATE
CONDITIONED AREA 119 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 11.5 FT. OUTSIDE 95 58 82 45.76 145.7
VOLUME 1363 CU.FT INSIDE 71.6 55 61.07 27.11 63.7
BYPASS FACTOR 0.1
PEOPLE - BASIS 2 x 5 + 0.06 = 17.121 DIFFERENCE 23.4 20.93 18.65 82
FRESH AIR QTY. 0 = 0
AIR CHANGE BASIS 0 x 1363 x 0.0166 = 0
TOTAL VENTILATION CFM 17

NORTH WALL 0 x 0.33 x 17.4 = 0 RETURN AIR


= ((∑WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL 0 x 0.33 x 23.4 = 0 GAIN FOR
EAST WALL 0 x 0.33 x 31.4 = 0 WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL 0 x 0.33 x 31.4 = 0
SOUTH WALL 0 x 0.33 x 29.4 = 0 RETURN AIR GAIN ****
SOUTH WEST WALL 0 x 0.33 x 27.4 = 0
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN
WEST WALL 0 x 0.33 x 25.4 = 0
FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE
NORTH WEST WALL 0 x 0.33 x 19.4 = 0
TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE
NORTH GLASS 0 x 0.56 x 35 = 0
SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND
NORTH EAST GLASS 0 x 0.56 x 11.23 = 0
ADDED TO RETURN AIR GAIN
EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH GLASS 0 x 0.56 x 11.23 = 0
SOUTH WEST GLASS 0 x 0.56 x 70.9 = 0 SENSIBLE HEAT RATIO (ESHF) = 0.87
O
WEST GLASS 0 x 0.56 x 159 = 0 APPARATUS DEW POINT F = 52.9
NORTH WEST GLASS 0 x 0.56 x 145.5 = 0 DEHUMIDIFIED CFM CFM = 171
SKY GLASS 0 x 0.56 x 110 = 0 TOTAL SPACE HEAT BTU/HR = 3559
ALL GLASS 0 x 1.13 x 23.4 = 0 VENTILATION HEAT BTU/HR = 1293
PARTITION WALL 0 x 0.42 x 18.4 = 0 RETURN AIR GAIN **** BTU/HR = 0
FLOOR 0 x 0.32 x 18.4 = 0 REFRIGERATION SUB TOTAL BTU/HR = 4852
CEILING 119 x 0.31 x 18.4 = 677 SAFETY (PUMP GAIN ETC.,) 5% BTU/HR = 243
ROOF 0 x 0.12 x 43.4 = 0 REFRIGERATION TOTAL BTU/HR = 5095
VENTILATION 17 x 23.4 x 0.108 = 43 REFRIGERATION LOAD TR = 0.42
PEOPLE 2 x 285 x 1 = 570
LIGHTS 131 x 1.5 x 3.41 = 668 CONCLUDED PARAMETERS FOR AHU
EQUIPMENT 0 x 1 x 3410 = 809 DEHUMIDIFIED CFM CFM
MISCELLANEOUS 0 x 1 x 1 = 0 SPACE SENSIBLE HEAT BTU/HR
SPACE SENSIBLE SUB TOTAL = 2768 REFRIGERATION LOAD TR
DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE 12.5 = 346 AHU MAKE
TOTAL SPACE SENSIBLE HEAT = 3114 AHU MODEL NO:
VENTILATION 17 x 82 x 0.067 = 94 FAN MAKE
PEOPLE 2 x 165 x 1 = 330 FAN MODEL NO:
MISCELLANEOUS 0 x 1 x 1 0 COOLING COIL FACE AREA SQ.FT
O
SPACE LATENT SUB TOTAL = 424 CH. WATER INLET TEMP. F
O
SAFETY PERCENTAGE 5 = 21 CH. WATER OUTLET TEMP. F
TOTAL SPACE LATENT HEAT = 445 CHILLED WATER FLOW RATE USGPM
TOTAL SPACE SENSIBLE HEAT = 3114 FAN STATIC PRESSURE INCH WC
TOTAL SPACE HEAT = 3559 MOTOR RATING HP
JOB NO: C10-46042
INPUT DATA
CUSTMOR NAME INKEL
FLOOR SECOND FLOOR DATE: 8/28/2019
AREA FEMALE WARD-2 TIME OF PEAK 1600 HRS LATITUDE 11.2 DEG N
MONTH OF PEAK MAY ALTITUDE 1 MTRS ABOVE MSL
CONDITIONED AREA 1658 SQ.FT DAILY RANGE 10
TOTAL WALL HEIGHT 13.8 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 11.5 FT. CONDITIONS CONDITIONS
O O
EXPOSURE N N-E E S-E S S-W W N-W DB - F 95 DB - F 71.6
GLASS AREA -SQ.FT 184 RH - % 58 RH - % 55
O O
WALL AREA- SQ.FT ** 502 329 122 WB - F 82 WB - F 61.07
PARTITION AREA 243 SQ.FT TH - BTU/LB 45.76 TH - BTU/LB 27.11
SKY GLASS AREA SQ.FT ** WALL AREA FIGURES GRAINS/LB 145.7 GRAINS/LB 63.7
NO OF AIR CHANGES PER HOUR ARE FOR THE HEIGHT
NO. OF PEOPLE 30 OF WALL UP TO FALSE FACTORS ADP/SHR VALUES FOR INSIDE DESIGN
CFM/PERSON 5.0 CEILING AND BALANCE WALL 0.33 DB 71.6 RH 55
CFM/SQFT 0.06 HEIGHT WILL BE TO GLASS 0.56
FRESH AIR QTY CFM RETURN AIR GAIN ALL GLASS 1.13 SHR ADP
LIGHTING LOAD 1.1 WATT/SQ.FT PARTITION 0.42 1 54.9
EQUIPMENT LOAD 1.7 KW CEILING 0.31 0.93 54
MISCELLANEOUS-SENS BTU/HR FLOOR 0.32 0.83 52
MISCELLANEOUS-LATE BTU/HR ROOF 0.12 0.77 50
EXPOSED FLOOR SQ.FT SKY GLASS 0.56
ROOF GAIN SQ.FT
CEILING GAIN 1658 SQ.FT
SH PER PERSON 260 BTU/HR
LH PER PERSON 90 BTU/HR
BYPASS FACTOR 0.1
HEAT LOAD ESTIMATE
CONDITIONED AREA 1658 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 11.5 FT. OUTSIDE 95 58 82 45.76 145.7
VOLUME 19033 CU.FT INSIDE 71.6 55 61.07 27.11 63.7
BYPASS FACTOR 0.1
PEOPLE - BASIS 30 x 5 + 0.06 = 249.48 DIFFERENCE 23.4 20.93 18.65 82
FRESH AIR QTY. 0 = 0
AIR CHANGE BASIS 0 x 19033 x 0.0166 = 0
TOTAL VENTILATION CFM 249

NORTH WALL 0 x 0.33 x 17.4 = 0 RETURN AIR


= ((∑WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL 0 x 0.33 x 23.4 = 0 GAIN FOR
EAST WALL 502 x 0.33 x 31.4 = 5199 WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL 0 x 0.33 x 31.4 = 0
SOUTH WALL 329 x 0.33 x 29.4 = 3197 RETURN AIR GAIN ****
SOUTH WEST WALL 0 x 0.33 x 27.4 = 0
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN
WEST WALL 122 x 0.33 x 25.4 = 1026
FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE
NORTH WEST WALL 0 x 0.33 x 19.4 = 0
TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE
NORTH GLASS 0 x 0.56 x 35 = 0
SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND
NORTH EAST GLASS 0 x 0.56 x 11.23 = 0
ADDED TO RETURN AIR GAIN
EAST GLASS 184 x 0.56 x 11.23 = 1157
SOUTH EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH GLASS 0 x 0.56 x 11.23 = 0
SOUTH WEST GLASS 0 x 0.56 x 70.9 = 0 SENSIBLE HEAT RATIO (ESHF) = 0.93
O
WEST GLASS 0 x 0.56 x 159 = 0 APPARATUS DEW POINT F = 54.0
NORTH WEST GLASS 0 x 0.56 x 145.5 = 0 DEHUMIDIFIED CFM CFM = 3299
SKY GLASS 0 x 0.56 x 110 = 0 TOTAL SPACE HEAT BTU/HR = 60737
ALL GLASS 184 x 1.13 x 23.4 = 4865 VENTILATION HEAT BTU/HR = 18843
PARTITION WALL 243 x 0.42 x 18.4 = 1877 RETURN AIR GAIN **** BTU/HR = 2260
FLOOR 0 x 0.32 x 18.4 = 0 REFRIGERATION SUB TOTAL BTU/HR = 81840
CEILING 1658 x 0.31 x 18.4 = 9457 SAFETY (PUMP GAIN ETC.,) 5% BTU/HR = 4092
ROOF 0 x 0.12 x 43.4 = 0 REFRIGERATION TOTAL BTU/HR = 85932
VENTILATION 249 x 23.4 x 0.108 = 630 REFRIGERATION LOAD TR = 7.16
PEOPLE 30 x 260 x 1 = 7800
LIGHTS 1824 x 1.5 x 3.41 = 9328 CONCLUDED PARAMETERS FOR AHU
EQUIPMENT 2 x 1 x 3410 = 5654 DEHUMIDIFIED CFM CFM
MISCELLANEOUS 0 x 1 x 1 = 0 SPACE SENSIBLE HEAT BTU/HR
SPACE SENSIBLE SUB TOTAL = 50189 REFRIGERATION LOAD TR
DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE 12.5 = 6274 AHU MAKE
TOTAL SPACE SENSIBLE HEAT = 56463 AHU MODEL NO:
VENTILATION 249 x 82 x 0.067 = 1371 FAN MAKE
PEOPLE 30 x 90 x 1 = 2700 FAN MODEL NO:
MISCELLANEOUS 0 x 1 x 1 0 COOLING COIL FACE AREA SQ.FT
O
SPACE LATENT SUB TOTAL = 4071 CH. WATER INLET TEMP. F
O
SAFETY PERCENTAGE 5 = 204 CH. WATER OUTLET TEMP. F
TOTAL SPACE LATENT HEAT = 4274 CHILLED WATER FLOW RATE USGPM
TOTAL SPACE SENSIBLE HEAT = 56463 FAN STATIC PRESSURE INCH WC
TOTAL SPACE HEAT = 60737 MOTOR RATING HP
JOB NO: C10-46042
INPUT DATA
CUSTMOR NAME INKEL
FLOOR SECOND FLOOR DATE: 8/28/2019
AREA CORRIDOR TIME OF PEAK 1600 HRS LATITUDE 11.2 DEG N
MONTH OF PEAK MAY ALTITUDE 1 MTRS ABOVE MSL
CONDITIONED AREA 1810 SQ.FT DAILY RANGE 10
TOTAL WALL HEIGHT 13.8 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 11.5 FT. CONDITIONS CONDITIONS
O O
EXPOSURE N N-E E S-E S S-W W N-W DB - F 95 DB - F 71.6
GLASS AREA -SQ.FT 68 89 RH - % 58 RH - % 55
O O
WALL AREA- SQ.FT ** 249 90 339 WB - F 82 WB - F 61.07
PARTITION AREA 1717 SQ.FT TH - BTU/LB 45.76 TH - BTU/LB 27.11
SKY GLASS AREA SQ.FT ** WALL AREA FIGURES GRAINS/LB 145.7 GRAINS/LB 63.7
NO OF AIR CHANGES PER HOUR ARE FOR THE HEIGHT
NO. OF PEOPLE 20 OF WALL UP TO FALSE FACTORS ADP/SHR VALUES FOR INSIDE DESIGN
CFM/PERSON 5.0 CEILING AND BALANCE WALL 0.33 DB 71.6 RH 55
CFM/SQFT 0.06 HEIGHT WILL BE TO GLASS 0.56
FRESH AIR QTY CFM RETURN AIR GAIN ALL GLASS 1.13 SHR ADP
LIGHTING LOAD 1.1 WATT/SQ.FT PARTITION 0.42 1 54.9
EQUIPMENT LOAD 1.8 KW CEILING 0.31 0.93 54
MISCELLANEOUS-SENS BTU/HR FLOOR 0.32 0.83 52
MISCELLANEOUS-LATE BTU/HR ROOF 0.12 0.77 50
EXPOSED FLOOR SQ.FT SKY GLASS 0.56
ROOF GAIN SQ.FT
CEILING GAIN 1810 SQ.FT
SH PER PERSON 285 BTU/HR
LH PER PERSON 165 BTU/HR
BYPASS FACTOR 0.1
HEAT LOAD ESTIMATE
CONDITIONED AREA 1810 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 11.5 FT. OUTSIDE 95 58 82 45.76 145.7
VOLUME 20783 CU.FT INSIDE 71.6 55 61.07 27.11 63.7
BYPASS FACTOR 0.1
PEOPLE - BASIS 20 x 5 + 0.06 = 208.62 DIFFERENCE 23.4 20.93 18.65 82
FRESH AIR QTY. 0 = 0
AIR CHANGE BASIS 0 x 20783 x 0.0166 = 0
TOTAL VENTILATION CFM 209

NORTH WALL 249 x 0.33 x 17.4 = 1427 RETURN AIR


= ((∑WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL 0 x 0.33 x 23.4 = 0 GAIN FOR
EAST WALL 90 x 0.33 x 31.4 = 936 WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL 0 x 0.33 x 31.4 = 0
SOUTH WALL 339 x 0.33 x 29.4 = 3285 RETURN AIR GAIN ****
SOUTH WEST WALL 0 x 0.33 x 27.4 = 0
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN
WEST WALL 0 x 0.33 x 25.4 = 0
FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE
NORTH WEST WALL 0 x 0.33 x 19.4 = 0
TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE
NORTH GLASS 68 x 0.56 x 35 = 1329
SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND
NORTH EAST GLASS 0 x 0.56 x 11.23 = 0
ADDED TO RETURN AIR GAIN
EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH GLASS 89 x 0.56 x 11.23 = 558
SOUTH WEST GLASS 0 x 0.56 x 70.9 = 0 SENSIBLE HEAT RATIO (ESHF) = 0.93
O
WEST GLASS 0 x 0.56 x 159 = 0 APPARATUS DEW POINT F = 54.0
NORTH WEST GLASS 0 x 0.56 x 145.5 = 0 DEHUMIDIFIED CFM CFM = 3813
SKY GLASS 0 x 0.56 x 110 = 0 TOTAL SPACE HEAT BTU/HR = 69758
ALL GLASS 157 x 1.13 x 23.4 = 4140 VENTILATION HEAT BTU/HR = 15758
PARTITION WALL 1717 x 0.42 x 18.4 = 13269 RETURN AIR GAIN **** BTU/HR = 3784
FLOOR 0 x 0.32 x 18.4 = 0 REFRIGERATION SUB TOTAL BTU/HR = 89300
CEILING 1810 x 0.31 x 18.4 = 10326 SAFETY (PUMP GAIN ETC.,) 5% BTU/HR = 4465
ROOF 0 x 0.12 x 43.4 = 0 REFRIGERATION TOTAL BTU/HR = 93765
VENTILATION 209 x 23.4 x 0.108 = 527 REFRIGERATION LOAD TR = 7.81
PEOPLE 20 x 285 x 1 = 5700
LIGHTS 1991 x 1.5 x 3.41 = 10186 CONCLUDED PARAMETERS FOR AHU
EQUIPMENT 2 x 1 x 3410 = 6173 DEHUMIDIFIED CFM CFM
MISCELLANEOUS 0 x 1 x 1 = 0 SPACE SENSIBLE HEAT BTU/HR
SPACE SENSIBLE SUB TOTAL = 57858 REFRIGERATION LOAD TR
DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE 12.5 = 7232 AHU MAKE
TOTAL SPACE SENSIBLE HEAT = 65090 AHU MODEL NO:
VENTILATION 209 x 82 x 0.067 = 1146 FAN MAKE
PEOPLE 20 x 165 x 1 = 3300 FAN MODEL NO:
MISCELLANEOUS 0 x 1 x 1 0 COOLING COIL FACE AREA SQ.FT
O
SPACE LATENT SUB TOTAL = 4446 CH. WATER INLET TEMP. F
O
SAFETY PERCENTAGE 5 = 222 CH. WATER OUTLET TEMP. F
TOTAL SPACE LATENT HEAT = 4668 CHILLED WATER FLOW RATE USGPM
TOTAL SPACE SENSIBLE HEAT = 65090 FAN STATIC PRESSURE INCH WC
TOTAL SPACE HEAT = 69758 MOTOR RATING HP
JOB NO: C10-46042
INPUT DATA
CUSTMOR NAME INKEL
FLOOR SECOND FLOOR DATE: 8/28/2019
AREA DOCTORS LOUNGE TIME OF PEAK 1600 HRS LATITUDE 11.2 DEG N
MONTH OF PEAK MAY ALTITUDE 1 MTRS ABOVE MSL
CONDITIONED AREA 66 SQ.FT DAILY RANGE 10
TOTAL WALL HEIGHT 13.8 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 11.5 FT. CONDITIONS CONDITIONS
O O
EXPOSURE N N-E E S-E S S-W W N-W DB - F 95 DB - F 71.6
GLASS AREA -SQ.FT RH - % 58 RH - % 55
O O
WALL AREA- SQ.FT ** WB - F 82 WB - F 61.07
PARTITION AREA 95 SQ.FT TH - BTU/LB 45.76 TH - BTU/LB 27.11
SKY GLASS AREA SQ.FT ** WALL AREA FIGURES GRAINS/LB 145.7 GRAINS/LB 63.7
NO OF AIR CHANGES PER HOUR ARE FOR THE HEIGHT
NO. OF PEOPLE 3 OF WALL UP TO FALSE FACTORS ADP/SHR VALUES FOR INSIDE DESIGN
CFM/PERSON 5.0 CEILING AND BALANCE WALL 0.33 DB 71.6 RH 55
CFM/SQFT 0.06 HEIGHT WILL BE TO GLASS 0.56
FRESH AIR QTY CFM RETURN AIR GAIN ALL GLASS 1.13 SHR ADP
LIGHTING LOAD 1.1 WATT/SQ.FT PARTITION 0.42 1 54.9
EQUIPMENT LOAD 0.25 KW CEILING 0.31 0.93 54
MISCELLANEOUS-SENS BTU/HR FLOOR 0.32 0.83 52
MISCELLANEOUS-LATE BTU/HR ROOF 0.12 0.77 50
EXPOSED FLOOR SQ.FT SKY GLASS 0.56
ROOF GAIN SQ.FT
CEILING GAIN 66 SQ.FT
SH PER PERSON 285 BTU/HR
LH PER PERSON 165 BTU/HR
BYPASS FACTOR 0.1
HEAT LOAD ESTIMATE
CONDITIONED AREA 66 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 11.5 FT. OUTSIDE 95 58 82 45.76 145.7
VOLUME 759 CU.FT INSIDE 71.6 55 61.07 27.11 63.7
BYPASS FACTOR 0.1
PEOPLE - BASIS 3 x 5 + 0.06 = 18.969 DIFFERENCE 23.4 20.93 18.65 82
FRESH AIR QTY. 0 = 0
AIR CHANGE BASIS 0 x 759 x 0.0166 = 0
TOTAL VENTILATION CFM 19

NORTH WALL 0 x 0.33 x 17.4 = 0 RETURN AIR


= ((∑WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL 0 x 0.33 x 23.4 = 0 GAIN FOR
EAST WALL 0 x 0.33 x 31.4 = 0 WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL 0 x 0.33 x 31.4 = 0
SOUTH WALL 0 x 0.33 x 29.4 = 0 RETURN AIR GAIN ****
SOUTH WEST WALL 0 x 0.33 x 27.4 = 0
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN
WEST WALL 0 x 0.33 x 25.4 = 0
FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE
NORTH WEST WALL 0 x 0.33 x 19.4 = 0
TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE
NORTH GLASS 0 x 0.56 x 35 = 0
SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND
NORTH EAST GLASS 0 x 0.56 x 11.23 = 0
ADDED TO RETURN AIR GAIN
EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH EAST GLASS 0 x 0.56 x 11.23 = 0
SOUTH GLASS 0 x 0.56 x 11.23 = 0
SOUTH WEST GLASS 0 x 0.56 x 70.9 = 0 SENSIBLE HEAT RATIO (ESHF) = 0.85
O
WEST GLASS 0 x 0.56 x 159 = 0 APPARATUS DEW POINT F = 52.5
NORTH WEST GLASS 0 x 0.56 x 145.5 = 0 DEHUMIDIFIED CFM CFM = 196
SKY GLASS 0 x 0.56 x 110 = 0 TOTAL SPACE HEAT BTU/HR = 4276
ALL GLASS 0 x 1.13 x 23.4 = 0 VENTILATION HEAT BTU/HR = 1433
PARTITION WALL 95 x 0.42 x 18.4 = 736 RETURN AIR GAIN **** BTU/HR = 147
FLOOR 0 x 0.32 x 18.4 = 0 REFRIGERATION SUB TOTAL BTU/HR = 5856
CEILING 66 x 0.31 x 18.4 = 377 SAFETY (PUMP GAIN ETC.,) 5% BTU/HR = 293
ROOF 0 x 0.12 x 43.4 = 0 REFRIGERATION TOTAL BTU/HR = 6148
VENTILATION 19 x 23.4 x 0.108 = 48 REFRIGERATION LOAD TR = 0.51
PEOPLE 3 x 285 x 1 = 855
LIGHTS 73 x 1.5 x 3.41 = 372 CONCLUDED PARAMETERS FOR AHU
EQUIPMENT 0 x 1 x 3410 = 853 DEHUMIDIFIED CFM CFM
MISCELLANEOUS 0 x 1 x 1 = 0 SPACE SENSIBLE HEAT BTU/HR
SPACE SENSIBLE SUB TOTAL = 3241 REFRIGERATION LOAD TR
DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE 12.5 = 405 AHU MAKE
TOTAL SPACE SENSIBLE HEAT = 3646 AHU MODEL NO:
VENTILATION 19 x 82 x 0.067 = 104 FAN MAKE
PEOPLE 3 x 165 x 1 = 495 FAN MODEL NO:
MISCELLANEOUS 0 x 1 x 1 0 COOLING COIL FACE AREA SQ.FT
O
SPACE LATENT SUB TOTAL = 599 CH. WATER INLET TEMP. F
O
SAFETY PERCENTAGE 5 = 30 CH. WATER OUTLET TEMP. F
TOTAL SPACE LATENT HEAT = 629 CHILLED WATER FLOW RATE USGPM
TOTAL SPACE SENSIBLE HEAT = 3646 FAN STATIC PRESSURE INCH WC
TOTAL SPACE HEAT = 4276 MOTOR RATING HP