1. IL-NT-232
2. IL-NT-RS232-485
3. IL-NT-S-USB (USB easy removable service module)
The RS232 or USB interface uses COM1 port of the controller. The RS485 uses COM2.
PC software – LiteEdit
On the PC (for direct or modem connection) has to be installed the ComAp’s software package
LiteEdit. (based on Windows 95 or newer platform)
LiteEdit enables:
read the quantities
adjust all set points
control the engine
configure the controller
select software configuration
modify alarm inputs and outputs
modify password, commands protections
direct, modem or Internet communication
Modbus protocol
The selection of the function of iL serial port is done via the setpoint COMx Mode in Basic settings
The complete description of Modbus communication protocol can be found in Modbus Protocol
Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are
available from web site at http://www.modicon.com/openmbus/ .
Hint:
To obtain communication object numbers it is possible to download the actual controller description
on-line from controller or from (ail) archive and use “export data” function from LiteEdit software.
Setpoints of AMF25:
Name Firmware ver. Application Date App. ver. Ser. num. Filename
IL-NT-AMF25-
IL-NT IL-NT-1.5 R:22.10.2009 AMF25 22.10.2009 1,5 12345678 1.5.AIL
Group Name Value Dimension Password Com. obj. Low limit High limit Data type
Basic Settings Nominal RPM 1500 RPM No 8253 100 4000 Unsigned 16
Engine Params Starting Oil P 4,5 Bar No 9681 0,0 10,0 Integer 16
Engine Protect AI1 Wrn 2,0 Bar No 8369 -10,0 1000,0 Integer 16
Gener Protect Short Crct Del 0,00 s No 9991 0,00 10,00 Unsigned 16
Gener Protect Amps IDMT Del 4,0 s No 8283 1,0 60,0 Unsigned 16
Gener Protect Amps Unbal Del 5,0 s No 8285 0,0 600,0 Unsigned 16
Gener Protect Volt Unbal Del 3,0 s No 8289 0,0 600,0 Unsigned 16
Gener Protect Gen Freq Del 3,0 s No 8297 0,0 600,0 Unsigned 16
AMF Settings MCB Close Del 1,0 s No 8389 0,0 60,0 Unsigned 16
AMF Settings Mains VUnb Del 2,0 s No 8447 0,0 60,0 Unsigned 16
AMF Settings Mains Freq Del 0,5 s No 8311 0,0 60,0 Unsigned 16
Values of AMF25:
Name Firmware ver. Application Date App. ver. Ser. num. Filename