Our reply in red MHT reply in blue

For the FSC units, we will be proceeding to submit amendment plans except for the
following :

 #B1-02 Koi (Form 1)


 #B2-K2&K4 Eat & Nam Kee Pau (Form 1 issued 24 July 2019)
 #B2-K3 Hayai (Form 1 to issue pending to RI comment)
 #B2-32 Old Chang Kee (Hard copy CMV/A05686/19 shown tenant is Please find attached
TEN & HAN Trading Pte Ltd, no record of BP / FP NOA, approval requested documents
plans and attendees list with date & time inspected received)
 #B2-13 Bread Club (No record of BP NOA and attendees list with date &
time inspected received ) Please find attached
 #B2-29 Yong Xing Teochew Porridge (Form 1 to issue pending to RI requested documents
comment)
 #B2-11 Song Fish (Form 1 issued 05 August 2019)
 #B2-18 Hanis Café & Bakery (Form 1 issued 05 August 2019)
 #B2-05 YM Bakery (Form 1 issued 24 July 2019)
 #B2-30 Bee Cheng Hiang (Form 2 issued 24 July 2019 – there’s a Okay, noted
relocation of sprinkler required, therefore required re-submission)
 #02-20 Maccha House (Form 2 – Drawing to include the schematic of Okay, noted
the interlocking of the BMG and fire alarm, therefore required re-
submission)

Please find below a compiled list of the comments for the FSC units. (Grey out
comments are those that are rectified, please find the link to the compiled photos/videos
: https://we.tl/t-6T8nIj5IxG)

FSC UNITS

 #01-14 Starbucks - 27 June (MEP)

o (MEP) Prepare for BGM interlocking test


o (MEP) Submit updated EVC layout

 #02-01/02/03/04 Uniqlo - 27 June (MEP)

o (MEP) Prepare for BGM interlocking test


o (MEP) Provide sprinkler in hosereel compartment
o If sprinkler is provided, any re-submission required? Yes, will proceed after obtaining TFP

 #03-08 Paradise Dynasty - 27 June (MEP)

o (MEP) Interlock exhaust, fresh air and gas detector panels


 #B2-09 Fairprice - 27 June (MEP)

o (MEP) To provide sprinkler coverage for perimeter ledge ceilings


o (MEP) To ensure BGM interlocked with PA system
o (MEP) To relocate 2 numbers of strobelights to be displayed more
prominently
o (MEP) To submit latest FP drawings
o (MEP) To provide sprinkler coverage for space above the cold room
compartments
o (MEP) To relocate cold room sprinkler away from blowers and
lighting obstructions

 #02-20 Maccha House - 27 June (MEP)

o (MEP) Prepare for gas and exhaust interlocking test


o If there’s a need to include the schematic of the interlocking of
the BMG and fire alarm in your approved plan, any re-
submission required? Yes, will proceed after obtaining TFP

 #03-13 Elemens - 27 June (MEP)

o (MEP) Prepare for BGM interlocking test


o (MEP) Prepare for gas interlocking test
o (MEP) Prepare for exhaust fan interlocking test
o Refer to RI Form 2 item 3 to 6 Yes, will proceed after obtaining TFP

 #04-11 Kopitiam – 10 July Pre-RI (MEP)

o (MEP) Strobelight is not connected to the alarm system


o (MEP) Shift suspended sprinklers under the ledge
o (MEP) To perforate false ceiling evenly for smoke control(under
book area)
o (MEP) To prepare for gas interlocking test
o (MEP) To shift down sprinkler brackets so deflector is not blocked
o (MEP) To submit updated FP drawings
o (MEP) Gas interlocking with fan not ready for testing
o (MEP) Smoke curtain gap > 40mm at entrance, to rectify
o (MEP) To install gas indicator panel
o (MEP) To confirm that alterations to the smoke control system is
acceptable

 #03-11/12 Hai Di Lao –10 July (MEP)

o (MEP) Provide sprinkler inside hosereel compartment


o (MEP) Shift sprinklers affected by ledge ceilings
o (MEP) Shift down sprinkler point blocked by drop down ceiling
o (MEP) Shift down sprinkler brackets so deflector is not blocked
o (MEP) Label ACMV control panel in English
o (MEP) To submit updated FP drawings

 #05-02 #06-01 Shaw 10 July (MEP)

o (MEP) Sprinkler coverage is affected by tray ceilings


o (MEP) Access panel for raised floors in Hall 1 and IMAX Hall
o (MEP) Sprinklers in toilets are too close
o (MEP) Sprinkler covers are painted over
o (MEP) To submit updated FP drawings

 #04-13 Saizeriya –12 July (MEP)

o (MEP) Remove blue caps from all sprinkler heads


o (MEP) Prepare for BGM interlocking test
o (MEP) Prepare for gas and fan interlocking test

 #04-09 Hot Tomato – 31 July (MEP)

o (MEP) To shift down MV fan control panel from above false ceiling

 #B2-30 Bee Cheng Hiang –12 July (MEP)

o (MEP) To shift above hood sprinkler away from obstruction


o (MEP) To submit COC for flexible duct of exhaust hood

 #B2-18 Hanis Café & Bakery –12 July (MEP)

o (MEP) To remove blue covers from sprinkler points


o (MEP) To clean royal flush sprinkler covers

 #B2-05 YM Bakery –10 July (MEP)

o No Comments

 #B2-02 Old Street Bak Kut Teh – 31 July (MEP)

o (MEP) To install 1 no of sprinkler at hood area


o (MEP) To rectify EAF damper
o (MEP) To add 1 number of EVC speaker at back of house area
 #B2-17 XiXiang Kaya Kopitiam – 12 July (MEP)

o (MEP) To add sprinkler points on ledge ceiling


o Additional sprinkler provided, any re-submission required?
Yes, will proceed after obtaining TFP

 #01-37 Hawker Express – 31 July (MEP)

o (MEP) To install sprinkler points in open ceiling area


o (MEP) To label sprinkler pipe with red bands
o (MEP) To rectify flexible ducting more than 2m
o Additional sprinkler provided, any re-submission required?
Yes, will proceed after obtaining TFP

 #04-12 Sushi Express –12 July (MEP)

o (MEP) To add speaker in room


o Additional speaker provided, any re-submission required?
Yes, will proceed after obtaining TFP

 #B1-02 Koi – 18 July(MEP)

o (MEP) No comment.

 #B2-K2&K4 Eat and Nam Kee Pau – 18 July(MEP)

o (MEP) No comment.

 #B2-K3 Hayai – 18 July(MEP)

o (MEP) To relocate cylinder below exhaust hood (Letter of no


objection provided)

 #04-10 Pizza Hut – 31 July(MEP)

o (MEP) BGM interlocking not working, to rectify


o (MEP) To relocate down the sprinklers at trellis area

 #03-09/10 Tunglok – 31 July(MEP)

o (MEP) To remove obstructions to the fireman exit


 #02-10/11/12 UOB – 31 July(MEP)

o (MEP) To sprinkler protect the cabinets

 #B1-01 Collin’s – 31 July(MEP)

o (MEP) To relocate down sprinklers at trellis area.


o (MEP) BGM interlocking not working, to rectify

 #B2-11 Song Fish – 31 July(MEP)

o (MEP) No comment.

 #B2-29 Yong Xing Teochew Porridge – 31 July(MEP)

o (MEP) To rectify flexible ducting > 2m


o (MEP) To label sprinkler pipes with red bands
o (MEP) To place permanent labels for MV control panels

 #B2-32 Old Chang Kee – 31 July(MEP)

o (MEP) To submit fire suppression form 1

 #B2-K9 Shihlin – 7 August(MEP)

o (MEP) To install exhaust fan/fresh air fan as per submitted MV


plans.

 #01-07 Wine Connection – 7 August(MEP)

o (MEP) No comments

 #01-01 Providore – 7 August(MEP)

o (MEP) BGM interlocking not ready for testing, to conduct when


ready
o (MEP) To add 1 no. of sprinkler (under duct)
o (MEP) To label the sprinkler pipes
 #B2-33 Duckland – 7 August(MEP)

o (MEP) Remove royal flush cover for sprinkler point blocked by the
mesh ceiling
o (MEP) BGM interlocking not ready for testing, to conduct when
ready