You are on page 1of 34

Precision Cooling

For Business-Critical Continuity™

Liebert® DM Series Air Conditioner


Technical Manual
Liebert_DM Series Air Conditioner
Technical Manual

Version V1.0
Revision date
BOM

Emerson Network Power provides customers with technical support. Users may contact the
nearest Emerson local sales office or service center and company headquarters.

Copyright © 2012 by Emerson Network Power Co., Ltd.


All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd.


Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen
China
Postcode: 518057
Customer Service Hotline: 4008876510
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn
Contents

Chapter 1 Preface ............................................................................................................................................................... 1


1.1 Special Requirements On The Equipment Room Environment ............................................................................ 1
1.2 Liebert_DM Series AC – Designed For Equipment Room .................................................................................... 1
Chapter 2 Overview ............................................................................................................................................................ 3
2.1 Appearance .......................................................................................................................................................... 3
2.2 Model Description ................................................................................................................................................. 3
2.3 Product Introduction .............................................................................................................................................. 3
2.4 Main Components ................................................................................................................................................. 4
2.4.1 Indoor Unit ................................................................................................................................................. 4
2.4.2 Outdoor Unit .............................................................................................................................................. 4
2.5 Options ................................................................................................................................................................. 5
2.5.1 Humidifier .................................................................................................................................................. 5
2.5.2 Heater ........................................................................................................................................................ 5
2.5.3 Remote Monitor ......................................................................................................................................... 5
2.5.4 Energy-Saving Card .................................................................................................................................. 5
2.5.5 Power SPD ................................................................................................................................................ 5
Chapter 3 Technical Parameter .......................................................................................................................................... 6
3.1 Technical Parameter Of The Indoor Unit .............................................................................................................. 6
3.2 Technical Parameter Of The Outdoor Unit............................................................................................................ 7
3.3 Mechanical Parameter .......................................................................................................................................... 7
3.3.1 Indoor Unit ................................................................................................................................................. 7
3.4 Outdoor Unit.......................................................................................................................................................... 8
3.5 Operation Environment ......................................................................................................................................... 9
Chapter 4 Application Guidline .......................................................................................................................................... 10
4.1 General Arrangement ......................................................................................................................................... 10
4.2 General Principles............................................................................................................................................... 10
4.3 Piping .................................................................................................................................................................. 11
4.4 Model Configuration ............................................................................................................................................ 12
4.5 Cooling Circulation .............................................................................................................................................. 12
Chapter 5 Micro-Processing controller .............................................................................................................................. 13
5.1 Appearance ........................................................................................................................................................ 13
5.2 LCD Screen ........................................................................................................................................................ 13
5.3 Control Buttons ................................................................................................................................................... 13
5.3.1 Function Description ................................................................................................................................ 13
5.3.2 Operation Example .................................................................................................................................. 14
5.4 Control Screen .................................................................................................................................................... 14
5.4.1 ON Screen ............................................................................................................................................... 14
5.4.2 Normal Screen......................................................................................................................................... 14
5.4.3 Password Screen .................................................................................................................................... 15
5.5 Control Logic ....................................................................................................................................................... 15
5.5.1 Cooling logic ............................................................................................................................................ 15
5.5.2 Heating Logic........................................................................................................................................... 16
5.5.3 Dehumidifying Logic ................................................................................................................................ 16
5.5.4 Humidifying Logic .................................................................................................................................... 18
5.5.5 Outdoor Fan Control ................................................................................................................................ 18
5.5.6 Economy Mode Control ........................................................................................................................... 19
5.5.7 Sleep Mode Control ................................................................................................................................. 19
5.5.8 Host/Standby Unit Control ....................................................................................................................... 19
5.6 Alarm Function .................................................................................................................................................... 20
5.6.1 Alarm Category........................................................................................................................................ 20
5.6.2 Alarm State And History .......................................................................................................................... 20
5.6.3 Alarm Prerequisites And Handling Methods ............................................................................................ 20
5.7 Other Functions .................................................................................................................................................. 23
5.7.1 Real-Time Clock ...................................................................................................................................... 23
5.7.2 Operating Record .................................................................................................................................... 23
5.7.3 Parameter Protection ............................................................................................................................... 23
5.7.4 Password Protection ................................................................................................................................ 23
5.7.5 Shutdown Mode ....................................................................................................................................... 23
5.7.6 Diagnosis Output ..................................................................................................................................... 24
5.7.7 Sensor Calibration ................................................................................................................................... 24
5.7.8 Deployment Management........................................................................................................................ 24
Appendix 1 Menu Structure ............................................................................................................................................... 25
Appendix 2 Wiring Diagram............................................................................................................................................... 26
Appendix 3 Glossary ......................................................................................................................................................... 28
Chapter 1 Preface 1

Chapter 1 Preface

This chapter mainly introduces the special requirements on the equipment room environment and the features and
advantages of Liebert_DM series air conditioners (AC for short).

1.1 Special Requirements For The Equipment Room Environment


The precise environment control is very important for the operation of the computers , therefore, the computers have
strict requirements for the equipment room environment, which cannot be achieved by the commercial air conditioners
designed for comfort. The relevant requirements mainly include the following four aspects.
Temperature control: Huge amount of sensible heat is generated when computers and exchanges are operating in
the equipment room, whose density is 6 to 10 times of that of the general offices. To ensure that the computers and the
devices exert their optimal effect, the temperature of the equipment room is best controlled within 24°C±1°C; This
requires that the AC units have sufficient cooling capacity and timely response regulatory capacity to cope with drastic
changes in temperature, which cannot be implemented by the commercial air conditioners.
Humidity control: In computer room, ultra-high or ultra-low humidity will damage the computers. The ultra-high
humidity makes the air moisture condense to form condensation water in the computers, resulting in short-circuit or
damage of the host hardware. The ultra-low humidity will make the static electricity generate in the computer room,
making the computers unable to operate or even crash. The commercial air conditioners cannot control the humidity
within the required range.
Airflow / cleanliness control: Computers and exchanges will produce huge sensible heat during the operation. To
eliminate the heat rapidly, The ACs are required to have large enough large cooling cycle airflow and long blowing
distance. Besides, because of the strict requirement of air cleanliness, the AC should provide an airflow equivalent to
the ventilating rate of 30 times per hour, so as to filter the air. The commercial ACs cannot achieve these.
All-year-round running: The commercial ACs (cooling operation) are only used in summer and they only run for 8 ~
10 hours each day. In the equipment room, however, the ACs are required to work all year round even in winter when
the temperature reached -34°C outdoors.

1.2 Liebert_DM Series AC – Designed For Equipment Room


The Liebert_DM series AC includes units with a cooling capacity of 7.5kW and 12.5kW. You can configure them freely
to meet different requirements of large-, medium-, and small-sized equipment rooms and base stations. Besides, the
AC has precise temperature/ humidity control and reliability design, fully meeting the special use environment
requirement of the equipment rooms.
Special development: As a part of the integration solution to equipment room, the Liebert_DM series ACs are
specially designed for the electrical devices and provides a proper environment for the running of the precise devices,
such as sensitive devices, industry process devices, communication devices and computers.
Considerate design: Being concerned about inter-device practical applications, the Liebert_DM series ACs are
designed to keep the overall layout between devices and ensure onsite installation and maintenance.
2 2
Saving space: The Liebert_DM series AC occupies 0.3 m and a total of 1 m area is required plus the maintenance
space.
Precise control: The precise control system of the Liebert_DM series ACs implement precision control over indoor
environment, guaranteeing the safe working and stable running of devices to a maximum degree. For the indoor unit
control panel, see Figure 1-1.

Liebert DM Series Air Conditioner Technical Manual


2 Chapter 1 Preface

J13 Board power


supply input J34 Temp/Hum detection board J23 Pressure sensor

J14 Monitoring

ON
J12 Display board power supply
J18 SCR output J39 Display board data line
to contactor J21 Switch input, such as high
pressure switch
J31 DI input power supply

J28 Output, such as J19 Remote switch


electric heater output
Figure 1-1 Control board of the indoor unit

Outstanding man-machine interface: The Liebert_DM series ACs provide a large Chinese/English LCD, a
user-friendly man-machine interface and an expert diagnosis system, as well as implement multi-level password
protection (avoid misoperation) and intelligent display of running states.
High reliability: Relying on the excellent quality and considerate services of Emerson, the Liebert_DM series ACs
ensure 24-hour reliable running all year round.
Strong adaptability to power grid: The Liebert_DM series ACs allow a wide range of voltage and provide the
following distinctive functions: unique phase loss protection, phase-sequence detection and protection, automatic
high-voltage & low-voltage detection and protection, self-recovery upon power failure.
All-weather operation: According to the distinct heating load feature of equipment rooms, the Liebert_DM series ACs
implement 24-hour running all year round in temperature ranging from -15°C to +45°C. If a Lee-Temp outdoor unit is
configured, the allowed running temperature ranges from -34°C to +45°C.
Strong network management: Being configured with a standard RS485 monitor interface, the Liebert_DM series
ACs implement flexible automatic switchover between active and standby devices, work shift, remote turn-off and
turn-on, remote alarm, and fault query and troubleshooting over standard telecommunication protocols.
Easy maintenance: The Liebert_DM series ACs provide a full front maintenance structure, facilitating maintenance.
Table 1-1 describes the differences between the Liebert_DM series ACs and commercial ACs.
Table 1-1 Differences between the Liebert_DM series ACs and commercial ACs
Design focus Liebert_DM series AC Commercial AC
Precision ±1°C; ±1%RH Generally ±3°C
Temperature control Humidifying and dehumidifying control None in general
Monitoring Local and romote monitoring None
All-rear-round continually operating All-year-around cooling No cooling needed in winter
Testing before delivery Strict requirement Simple testing
Control design Precise control CPU
Cleanliness High Low

Liebert DM Series Air Conditioner Technical Manual


Chapter 2 Overview 3

Chapter 2 Overview

This chapter expounds the appearance, model description, product introduction, components and variety of accessory
options.

2.1 Appearance
Taking the indoor unit of the Liebert_DM series air conditioner as an example, the appearance as shown in Figure 2-1.

Figure 2-1 Indoor unit of the air conditioner

2.2 Model Description


The model description of the air conditioner is shown in Figure 2-2.

DM E 07 M C T 1
1: Standard; 2: High efficiency
Version code
C: cooling only; O: with heater; H: with heater and humidifier
Input power supply. M: 380V-3-ph-50Hz
Cooling capacity. 07: 7.5kW ; 12: 12.5kW
E: indoor unit; C: outdoor unit; L: Lee-Temp outdoor unit
Liebert_D series air conditioner

Figure 2-2 Model description

2.3 Product Introduction


The Liebert_DM AC is a small precise environment control system, specially designed for cooling the electrical
devices. It is applicable to environment control in equipement room and computer room. Featuring high reliability, it
can maintain a favorable environment for precise devices such as sensitive devices, industry process devices,
communication devices and computers.
The cooling kit is provided as standard and it can precisely control the ambient temperature. The heater and humidifier
are provided as options and they can precisely control the ambient humidity. If the AC unit is only available for cooling,
the options are not needed.

Liebert DM Series Air Conditioner Technical Manual


4 Chapter 2 Overview

The Liebert_DM AC provides a micro-processing controller that can automatically switch over to the required function
(cooling or heating, dehumidifying or humidifying), based on the programmed setpoints and room ambient conditions.
Each Liebert_DM AC consists of an indoor unit and an outdoor unit. Both units are installed on the floor separately.
Indoor unit
The Liebert_DM AC includes units with a cooling capacity of 7.5kW and 12.5kW, which are applicable to power supply
of 380V, 3-ph. You can select them according to the actual equipment room conditions.
Outdoor unit
The outdoor unit adopts air cooled mode. It is classified into two models: standard model and Lee-Temp model. The
Lee-Temp model can be used at lower temperature (see Table 1-1) than the standard model.

2.4 Main Components

2.4.1 Indoor Unit


The indoor unit consists of evaporator, compressor, fan, micro-processing controller, thermal expansion valve, strainer,
filter, heater (optional), humidifier (optional) and surge protective devices (SPD, optional). For option introduction, refer
to 2.5 Options.
Evaporator
Adopt a fin-tube heat exchanger with high efficiency. The distributor is designed and verified according to individual
model to ensure that the refrigerant is distributed evenly in each loop, improving the efficiency of the heat exchanger to
a great extent.
Compressor
Adopt a compressor with high efficiency ratio. It features low vibration, low noise and high reliability.
Fan
Adopt a centrifugal fan with high efficiency and high reliability. It features large airflow, long blowing distance, direct
driving and easy maintenance.
Micro-processing controller
Provide a simple-operation user interface with multi-level password protection, self-recovery upon power failure,
high-voltage & low-voltage protection, phase loss protection, automatic phase-sequence switching upon anti-phase
and rotate speed control of the outdoor fan. The expert-level fault diagnose system can automatically display current
fault information to facilitate equipment maintenance by maintenance personnel.
Thermal expansion valve
Adopt a thermal expansion valve with external equalizer type. It collects temperature and pressure signals at the same
time to accurately regulate the refrigerant flow.
Strainer
Filtrate the impurities generated during long-term system operation and ensure normal system operation.
Filter
Adopt nylon filter material with big mesh for Liebert_DM AC. The filter features compact structure and easy
maintenance. It can be washed repeatedly.

2.4.2 Outdoor Unit


The outdoor unit consists of fan and condenser. Other than the above components, the Lee-Temp model also includes
a low-temperature unit.
Fan
Adopt axial flow blades with low noise. The single-phase motor with high performance is customized based on the
power grid of base stations, so it can work over a wide voltage range with high reliability.

Liebert DM Series Air Conditioner Technical Manual


Chapter 2 Overview 5

Condenser
Adopt a fin-tube heat exchanger with high heat dissipation and wavy fins. It is free of dust accumulation, and can be
easily cleaned and maintained.
Low-temperature unit
Make the AC unit operate in cooling mode normally at the lowest outdoor temperature of -34°C.

2.5 Options

2.5.1 Humidifier
The humidifier can add pure water vapor (up to 2.5kg/hour) into the room to control the indoor humidity within ranges
required by devices and computer.
The humidifier consists of a steam canister with automatic flushing control function, inlet tube, drain tube, solenoid
valve and steam distributor.

 Note
1. The electrode humidifier should be installed and tested in factory.
2. The Liebert_DM AC can control the ambient humidity only after a humidifier is installed.

2.5.2 Heater
A ceramic heater with positive temperature coefficient can be selected. It is safe and reliable. When the surface
temperature is too high, it will reduce the heating power to avoid danger caused by over-temperature. A temperature
switch is provided on the surface of the heater, and it will cut off the power of the heater when the surface temperature
is too high. When the surface temperature decreases to normal, the temperature switch will restore the operation of
the heater automatically.

2.5.3 Remote Monitor


The Liebert_DM AC communicates with the host computer through a configured RS485 port and receives the control
of the host software. You can also select and configure a monitoring card to realize different monitoring functions. For
the descriptions of the host monitoring software SiteMonitor developed by Emerson, refer to
Appendix 3 SiteMonitor Software Introduction.

2.5.4 Energy-Saving Card


The Liebert_DM AC can monitor the maximum room temperature with the energy-saving card located outside the unit
cabinet. The card is placed in position with high heat load and temperature. Up to four cards can be used for an AC
unit. When the temperatures measured by all energy-saving cards are lower than the setpoint in ‘Sleep Mod’ and only
indoor fan is running, if the ‘Sleep Mod’ is set to ‘ENAB’, the AC unit will turn off the indoor fan and enter the sleep
mode for saving the energy.

2.5.5 Power SPD


The power SPD is used for second level (C level) lightning over-voltage protection of the AC power. It can be
maintained easily and provides status indicating and alarm function.

 Note
The power SPD should be installed in factory.

Liebert DM Series Air Conditioner Technical Manual


6 Chapter 3 Technical Parameter

Chapter 3 Technical Parameter

This chapter expounds the technical parameter, mechanical parameter and operating environment of the
indoor/outdoor unit of the Liebert_DM series AC.

3.1 Technical Parameter Of The Indoor Unit

Table 3-1 Technical parameter of DME07 series indoor unit


Model
Type DME07 DME07 DME07 DME07 DME07 DME07
MCT1 MOT1 MHT1 MCP1 MOP1 MHP1
Cooling Cooling
24°CdB 7500 7500 7500 7500 7500 7500
capacity and capacity
sensible Sensible
cooling 50%RH cooling 6500 6500 6500 6500 6500 6500
capacity (kW) capacity
Standard airflow (m3/h) 1800 1800 1800 1800 1800 1800
Number 1 1 1 1 1 1
Fan
Static pressure outside
0 0 0 0 0 0
the fan (Pa)
Compressor Number 1 1 1 1 1 1
Front face area (m2) 0.25 0.25 0.25 0.25 0.25 0.25
Evaporator coil
Face air velocity (m/s) 2 2 2 2 2 2
Electric heater Power (kW) - 3.2 3.2 - 3.2 3.2
Electrode Humidifier water rate
- - 1.5 - - 1.5
humidifier (kg/h)
Front filter size (mm, 1 485 × 845 485 × 845 485 × 845 485 × 845 485 × 845 485 × 845
pcs) ×8 ×8 ×8 ×8 ×8 ×8
Filter Side filter size (mm, 1 312 × 317 312 × 317 312 × 317 312 × 317 312 × 317 312 × 317
pcs) ×8 ×8 ×8 ×8 ×8 ×8
Number 3 3 3 3 3 3
Liquid return pipe ID
9.52 9.52 9.52 9.52 9.52 9.52
(mm)
Discharge pipe ID (mm) 12.7 12.7 12.7 12.7 12.7 12.7
Port size Humidifier
- - 19 - - 19
Charging pipe OD (mm)
Condensed water drain
20 20 20 20 20 20
pipe OD (mm)
Net weight (kg) 90 92 95 90 92 95
Electrical Max. current (A) 6 8 20 6 8 20
parameter Air breaker 32 32 32 32 32 32
Note: all the cooling capacity is nominal, ±5% error exists in the actual capacity

Table 3-2 Technical parameter of DME12 series indoor unit


Model
Type DME12 DME12 DME12 DME12 DME12 DME12
MCT1 MOT1 MHT1 MCP1 MOP1 MHP1
Cooling Cooling
24°CdB 12500 12500 12500 12500 12500 12500
capacity and capacity
sensible Sensible
cooling 50%RH cooling 10200 10200 10200 10200 10200 10200
capacity (kW) capacity
Standard airflow (m3/h) 2800 2800 2800 2800 2800 2800
Number 1 1 1 1 1 1
Fan
Static pressure outside
0 0 0 0 0 0
the fan (Pa)

Liebert DM Series Air Conditioner Technical Manual


Chapter 3 Technical Parameter 7

Compressor Number 1 1 1 1 1 1
Front face area (m2) 0.37 0.37 0.37 0.37 0.37 0.37
Evaporator coil
Face air velocity (m/s) 2.1 2.1 2.1 21 2.1 2.1
Electric heater Power (kW) - 3.2 3.2 - 3.2 3.2
Electrode Humidifier water rate
- - 2.5 - - 2.5
humidifier (kg/h)
Front filter size (mm, 1 578 × 914 578 × 914 578 × 914 578 × 914 578 × 914 578 × 914
pcs) ×8 ×8 ×8 ×8 ×8 ×8
Filter Side filter size (mm, 1 376 × 427 376 × 427 376 × 427 376 × 427 376 × 427 376 × 427
pcs) ×8 ×8 ×8 ×8 ×8 ×8
Number 3 3 3 3 3 3
Liquid return pipe ID
12.7 12.7 12.7 12.7 12.7 12.7
(mm)
Discharge pipe ID (mm) 16 16 16 16 16 16
Port size Humidifier
- - 19 - - 19
Charging pipe OD (mm)
Condensed water drain
20 20 20 20 20 20
pipe OD (mm)
Net weight (kg) 140 142 145 140 142 145
Electrical Max. current (A) 10.5 10.5 22 10.5 10.5 22
parameter Air breaker 32 32 32 32 32 32
Note: all the cooling capacity is nominal, ±5% error exists in the actual capacity

3.2 Technical Parameter Of The Outdoor Unit


Table 3-3 Technical parameter of the standard outdoor unit
Model
Item
DMC07WT1 DMC12WT1
Airflow (CMH) 3800 7300
Condenser coil CSA (m2) 0.73 1.1
Number of the condenser coil row 2 2
Motor power (W) 170 340
Operating temperature range (°C) -15°C ~ +45°C -15°C ~ +45°C
Refrigerant charge quantity (g) 500 1000
Size of the liquid pipe (mm) 9.52 12.7
Size of the discharge pipe (mm) 12.7 16

Table 3-4 Technical parameter of the Lee-Temp outdoor unit


Model
Item
DML07W1 DML12W1
Airflow (CMH) 3800 7300
Condenser coil CSA (m2) 0.49 0.98
Number of the condenser coil row 2 2
Motor power (W) 150 300
Operating temperature range (°C) -34°C ~ +45°C -34°C ~ +45°C
Refrigerant charge quantity (g) 4870 7150
Size of the liquid pipe (mm) 9.52 12.7
Size of the discharge pipe (mm) 12.7 16

3.3 Mechanical Parameter

3.3.1 Indoor Unit


The mechanical parameters of the indoor unit are listed in Figure 3-1 and Table 3-6.

Liebert DM Series Air Conditioner Technical Manual


8 Chapter 3 Technical Parameter

600 50
510 38 0
5

1850
1750

510 600
510
600
DME07kW DME12kW
Figure 3-1 Dimensions of the indoor unit (unit: mm)

The shadows in Figure 3-1 indicate a reasonable installation and service space. For 7.5kW units, 510mm must be
reserved to facilitate maintenance; For 12.5kW unit, 600mm must be reserved to facilitate maintenance.
The AC unit equipped with a heater should be kept a distance of minimum 150mm from combustible substance. When
testing the AC unit, keep the external static pressure below 150Pa lest the air volume becomes too low and the heater
becomes too hot.

3.4 Outdoor Unit


The mechanical parameters of the outdoor unit are shown in Figure 3-2, Figure 3-3 and Table 3-6.

352 787

352 787
1240
829

Figure 3-2 Dimensions of standard outdoor unit (unit: mm)

Liebert DM Series Air Conditioner Technical Manual


Chapter 3 Technical Parameter 9

352 103
7

352 103
7

1240
829

575

575
Figure 3-3 Dimensions of Lee-Temp outdoor unit (unit: mm)
Table 3-5 Mechanical parameters of indoor unit and outdoor unit
Model Cooling capacity (kW) Dimensions (W × D × H, mm) Net weight (kg)
DME07*** 7.5 510 × 385 × 1750 90
Indoor unit
DME12*** 12.5 600 × 500 × 1850 145
DMC07WT1 - 787 × 352 × 829 40
DMC12WT1 - 787 × 352 × 1240 60
Outdoor unit
DML07W1 - 1037 × 352 × 829 53
DML12W1 - 1037 × 352 × 1240 95

3.5 Operation Environment


The operation environment requirements are listed in Table 3-7.
Table 3-6 Operation environment requirements
Item Requirements
The maximum equivalent horizontal distance between the indoor unit and outdoor unit[1]: 50m;
Installation position
Vertical distance ΔH[2]: -5m ≤ ΔH ≤ 20m
Indoor unit: vertical mode; mounting base ≥ 150mm;
Installation mode
outdoor unit: horizontal airflow mode
Indoor: 0°C ~ 40°C
Ambient temperature
Outdoor: standard model, -15°C ~ +45°C; Lee-Temp model, -34°C ~ +45°C
Ambient humidity 30%RH ~ 80%RH
Protection level Outdoor unit: IPX4
Altitude < 1000m. Derating is required when the altitude exceeds 1000m
Operation voltage range 380V (-15% ~ +15%), settable according to different environments, the error is 3%
Note:
[1]: The value is positive if the outdoor unit is installed above the indoor unit; negative if the indoor unit is installed above the
outdoor unit.
[2]: ΔH = Altitude of the outdoor unit - Altitude of the indoor unit
[3]:Total transportation and storage time should not exceed six months. Otherwise, the performance needs to be re-calibrated

Liebert DM Series Air Conditioner Technical Manual


10 Chapter 4 Application Guidline

Chapter 4 Application Guidline

This chapter mainly introduces the general arrangement, general principle, piping, model configuration and cooling
cycle.

4.1 General Arrangement


The general system arrangement diagram is shown in Figure 4-1. The standard pipe sizes are shown in Table 4-1.

Figure 4-1 General arrangement diagram

 Note
1. : Factory piping.
2. : Field piping (by technicians).
3. *: Check valve and traps are optional and not supplied by Emerson. But they are recommended for normal system operation
and easy maintenance. They should be installed on site by technicians.
4. +: Solenoid valve is a part of extended piping kit.

Table 4-1 Standard pipe sizes


Actual cooling capacity Pipe length (m) Discharge pipe OD Liquid pipe OD
7.5kW unit 5 1/2” (12mm) 3/8” (10mm)
Liebert_DM series
12.5kW unit 5 5/8” (16mm) 1/2” (12mm)

4.2 General Principles


1. Use copper pipes with quick thread connector to connect the indoor unit and the outdoor unit. If the pipe length
exceeds the standard pipe length (see Table 4-1) and straight copper pipe is used, piping joints must be brazed.
2. Follow standard industry procedures in selection and placement of pipe, system evacuation and charging with
refrigerant (only when pipeline is too long). The standard refrigerant of the AC unit is R22.
3. Give considerations to pipeline pressure drop, oil return to the compressor, to avoid oil leakage and clogging in parts
of the system and minimize noise and vibration to the greatest extend.
4. Consult Emerson before installation on whether measures such as using extended piping kit are needed, if the
equivalent length exceeds 50m, or if the vertical distance between the indoor unit and the outdoor unit exceeds the
values in Table 4-2.

Liebert DM Series Air Conditioner Technical Manual


Chapter 4 Application Guidline 11

Table 4-2 Vertical distance between indoor unit and outdoor unit
Relative position Value
Outdoor unit installed higher than indoor unit Maximum: 20m
Outdoor unit installed lower than indoor unit Maximum: 5m

5. The equivalent length of each part is given in Table 4-3. The resistance loss caused by elbows and valves has been
taken into consideration. The installer should confirm if these values are appropriate for site conditions.
Table 4-3 Equivalent length of each part
Equivalent length (m)
Liquid pipe OD (inch)
90° elbow 45° elbow T-type three way
3/8 0.21 0.10 0.76
1/2 0.24 0.12 0.76
5/8 0.27 0.15 0.76
3/4 0.3 0.18 0.76
7/8 0.44 0.24 1.1
1-1/8 0.56 0.3 1.4

4.3 Piping
All equipment must be installed vertically. The Liebert_DM AC is available in two installation modes: outdoor unit
installed higher than indoor unit and indoor unit installed higher than outdoor unit. See Figure 4-2 and Figure 4-3 for
details.
Outdoor unit

Liquid pipe (not be exposed to sun)

Indoor unit
Max. 20m

Trap

Protection Isolataion Humidifier canister water


7.5m

tube floor supply pipe (to water tap)

Sealed Discharge pipe (slope) Insulation Floor Condensation water


1:200 material drain pipe (to outdoor)
1:200
Figure 4-2 Outdoor unit above indoor unit

Liebert DM Series Air Conditioner Technical Manual


12 Chapter 4 Application Guidline

Indoor unit

Protection tube

Discharge pipe (slope)


1:200 Humidifier canister water
Sealed Isolation floor supply pipe (to water tap)

Liquid pipe (not be


exposed to sun)

Min. 5m
Outdoor unit

Insulation Floor Condensation water


material drain pipe (to outdoor)
1:200

Figure 4-3 Indoor unit above outdoor unit

4.4 Model Configuration


Table 4-4 Configuration of the indoor unit and the outdoor unit
Indoor unit Outdoor unit
Cooling
Main power With electric With humidifying Standard Lee-Temp
capacity Single cooling
heating and heating model model
7.5kW DME07MCT(P)1 DME07MOT(P)1 DME07MHT(P)1 DMC07WT1 DML07W1
380V/3P/50Hz
12.5kW DME12MCT(P)1 DME12MOT(P)1 DME12MHT(P)1 DMC12WT1 DML12W1

4.5 Cooling Circulation


As shown in Figure 4-4, the compressor (1) presses the high-temperature gaseous refrigerant into the air-cooled
condenser (2). The refrigerant is condensed as fluid in the condenser and sent to the evaporator (4) after being
throttled by the thermostatic expansion valve (3). In the evaporator (4), the refrigerant performs heat exchange with
the indoor air that is driven and circulated by the indoor fan (5) and then evaporates. The refrigerant is sent back to the
compressor (1) to start a new circulation. The system adjusts the rotation speed of the outdoor fan (6) to retain the
discharge pressure normal.
The compressor (1) is configured with a crankcase heating strip to prevent the refrigerant from flowing back from the
condenser in summer. This can protect the compressor from liquid strike during startup.

Figure 4-4 Schematic diagram of the system

Liebert DM Series Air Conditioner Technical Manual


Chapter 5 Micro-Processing Controller 13

Chapter 5 Micro-Processing controller

This chapter gives a detailed description on appearance, LCD screen, control buttons, control screen, control logic,
alarm function of the micro-processing controller of the Liebert_DM AC.

5.1 Appearance
The micro-processing controller panel is shown in Figure 5-1.

Figure 5-1 Micro-processing controller panel

5.2 LCD Screen


The LCD screen displays English menus with white backlight. When the system is operating normally, it displays the
current temperature & humidity (whether to display humidity is optional. Only the unit configured with a humidifier can
display humidity), unit output status (cooling, heating, dehumidifying and humidifying), unit status (single, host,
standby), unit operation status (running, standby, locked), alarm information and current date & time, as shown in
Figure 5-2.

21°C Heat SIG


50%rh Hum RUN
High Hum 1/4
2012/01/01 00:00

Figure 5-2 LCD screen

More detailed operating status of certain component and alarm information are available from the Main Menu screen.
The selected menu item will be highlighted while browsing. The digit to be changed will be highlighted while you are
changing setting.

5.3 Control Buttons

5.3.1 Function Description


The micro-processing controller provides five control buttons, as shown in Figure 5-3.

ON/OFF button
Up button

Enter button

Down button
Esc button

Figure 5-3 Control keypad

The functions of the control buttons are described in Table 5-1.


Table 5-1 Function descriptions of control buttons
Control button Function descriptions

Liebert DM Series Air Conditioner Technical Manual


14 Chapter 5 Micro-Processing Controller

ON/OFF button Press this button for 3s to turn on or off the unit
Enter button (ENT) Enter the selected menu screen. Validate the parameter setting value
Exit the current menu and return to the Normal screen or previous menu screen. Abort parameter change;
Esc button (ESC)
silence the audible alarm
Move the cursor up or increase the parameter value. For a toggle selection: scroll through the options. For a
Up button
multi-screen menu: scroll up the screen
Move the cursor down or decrease the parameter value. For a toggle selection: scroll through the options.
Down button
For a multi-screen menu: scroll down the screen

5.3.2 Operation Example


Example 1: Inputting password to enter the Main Menu
After the unit is started up, you can enter the Main Menu through conducting the following operations on the Normal
screen.
1. Press the Enter button to enter the Password screen.
2. Press the Enter button to highlight the input data field in the Password screen.
3. Press the Up or Down button to change the current password number.
4. Press the Enter button to confirm the password and enter the Main Menu screen.
Example 2: changing parameters
Taking Hi Temp in Alarm Output screen as an example, the procedures are as follows:
1. Press the Up or Down button to move the cursor on the Alarm Menu in the Main Menu screen.
2. Press the Enter button to enter the Alarm Menu.
3. Press the Up or Down button to move the cursor on Alarm Output in the Alarm Menu screen.
4. Press the Enter button to enter the Alarm Output screen.
5. Press the Up or Down button to move the cursor on Hi Temp.
6. Press the Enter button to highlight the parameter field of Hi Temp.
7. Press the Up or Down button to select the parameter option.
8. After selecting, press the Enter button to confirm. The parameter will take effect.
9. Press the Esc button to return to the previous menu screen.

 Note
After changing the parameter, if you do not press the Enter button to validate the changed parameter, the change will be invalid.

5.4 Control Screen

5.4.1 ON Screen
After the AC unit is powered on, the LCD screen will display the ON screen, as shown in Figure 5-4.

Connecting
Please wait...

Figure 5-4 ON screen

5.4.2 Normal Screen


After the AC unit is powered on, the Normal screen will be displayed after 10 seconds (default) for heat startup delay or
through pressing the Enter button directly, as shown in Figure 5-5. The Normal screen displays the following
information: the current temperature and humidity, unit operation state (cooling, heating, dehumidifying, humidifying),
unit mode (single, host, standby), unit operation status (running, standby, locked, off, sleep), alarm information and
current date & time.

Liebert DM Series Air Conditioner Technical Manual


Chapter 5 Micro-Processing Controller 15

21°C Heat SIG


50%rh Hum RUN
No alarm 0
2012/01/01 00:00

Figure 5-5 Normal screen

5.4.3 Password Screen


Press the Enter button on the Normal screen, and the Password screen will appear, as shown in Figure 5-6.

Password: 1***

Figure 5-6 Password screen

Three levels of passwords are provided for accessing the menus. The detailed descriptions are listed in Table 5-2.
Table 5-2 Password level
Password level User Initial password Remark
Browse all menu information. Only set temperature and
Level 1 General operator 0001 humidity setpoints (see Figure 5-12) and cannot change any
values and settings
Level 2 Maintenance personnel - Set all parameters
Level 3 Factory technician - -

For detailed operation on entering the password, refer to 5.3.2 Operation Example. If entering a wrong password, you
can only view the menu, but cannot change the settings. In this case, you can press the Esc button to return to the
Normal screen, and then press the Enter button to enter the Password screen again.

 Note
If pressing the Enter button in the Password screen instead of inputting any password, you can only view the menu settings but
cannot change any parameters.

5.5 Control Logic

5.5.1 Cooling logic


When the actual temperature = set temperature + temperature precision value, the cooling requirement reaches
100%.
When the actual temperature = set temperature, the cooling requirement is 0%.
When the actual temperature rises to the degree corresponding to the 100% cooling requirement, cooling starts; when
the actual temperature drops to the degree corresponding to the 0% cooling requirement, cooling stops (the
compressor is turned off).
Figure 5-7 shows the cooling logic diagram.

Liebert DM Series Air Conditioner Technical Manual


16 Chapter 5 Micro-Processing Controller

The compressor is The compressor


turned off is turned on

Indoor temperature
0% +100%
Set point

Figure 5-7 Cooling logic

5.5.2 Heating Logic


When the actual temperature = set temperature - temperature precision value, the heating requirement reaches 100%.
When the actual temperature = set temperature, the heating requirement is 0%.
When the actual temperature drops to the degree corresponding to the 100% heating requirement, heating starts;
when the actual temperature rises to the degree corresponding to the 0% heating requirement, heating stops (the
electronic heater is turned off).
Figure 5-8 shows the heating logic diagram.

Electric heater Electric heater


is turned on is turned off

Indoor temperature
-100% 0%
Set point

Figure 5-8 Heating logic

5.5.3 Dehumidifying Logic


1. Relative humidity control logic
Dehumidifying is activated when the cooling requirement is smaller than 125% and the dehumidifying requirement is
larger than 100%.
Dehumidifying is deactivated when the dehumidification requirement is no larger than 50%.
Figure 5-9 shows the dehumidifying activation and deactivation requirements.

Exit
Enter dehumidifying
dehumidify-
mode
ing mode

Indoor humidity
+50% +100%
Set point

Figure 5-9 Dehumidifying activation and deactivation requirements

Liebert DM Series Air Conditioner Technical Manual


Chapter 5 Micro-Processing Controller 17

In the dehumidifying mode, the fan switches to high gear immediately when the cooling requirement is larger than
125%. The fan switches back to low gear when the temperature drops normal.
Figure 5-10 shows the high/low gear switch diagram of the fan in the dehumidifying mode.

Switch to
Switch to low gear
high gear

Indoor
temperature
Set point +125%

Figure 5-10 High/low gear switch diagram of the fan in the dehumidifying mode

In the temperature compensation mode, the compressor is turned on when the cooling requirement is larger than 0%
and it is turned off when the cooling requirement is smaller than -100%; the electronic heater is turned on when the
cooling requirement is smaller than 0% and it is turned off when the cooling requirement is larger than 25%.
Figure 5-11 shows the control logic of the compressor in a) and the control logic of the electronic heater in b).

The
The compressor The electric heater The electric heater
compressor
is turned on is turned on is turned off
is turned off

-100% Indoor +25% Indoor


Set point temperature Set point temperature
a) Control logic of the compressor b) Control logic of the electronic heater
Figure 5-11 Dehumidification logic in the temperature compensation mode

In the non-temperature compensation mode, the compressor is turned on and the electronic heater is turned off when
the cooling requirement is no smaller than 0%; the compressor is turned off and the electronic heater is turned on
when the cooling requirement is smaller than -100%.
Figure 5-12 shows the control logic of the compressor in a) and the control logic of the electronic heater in b).

The The The electric The electric


compressor compressor heater is heater is
is turned off is turned on turned on turned off

-100% Indoor -100% Indoor


Set point temperature Set point temperature
a) Control logic of the compressor b) Control logic of the electronic heater
Figure 5-12 Dehumidifying logic in the non-temperature compensation mode

2. Absolute Humidity Control Logic


If absolute humidity control logic is used, users should calculate the absolute humidity based on the actual
temperature and humidity and perform humidity control by referring to 1. Relative humidity control logic in this section.

Liebert DM Series Air Conditioner Technical Manual


18 Chapter 5 Micro-Processing Controller

5.5.4 Humidifying Logic


1. Relative humidity control logic
When the actual humidity = set humidity - humidity precision value, the humidification requirement reaches 100%.
When the actual humidity = set humidity, the humidification requirement is 00%.
When the actual humidity drops to the value corresponding to the 100% humidification requirement, humidification
starts; when the actual humidity rises to the value corresponding to the 0% humidification requirement, humidification
stops.
Figure 5-13 shows the humidification logic diagram.

The The
humidifier is humidifier is
turned on turned off

0%
-100% Indoor
Set point temperature
Figure 5-13 Humidification logic

2. Absolute humidity control logic


If absolute humidity control logic is used, users should calculate the absolute humidity based on the actual
temperature and humidity and perform humidity control by referring to 1. Relative humidity control logic in this section.

5.5.5 Outdoor Fan Control


1. If the pressure sensor is faulty, the fan operates at full speed.
2. If frequency deviation happens, the fan stops operating.
3. If the compressor is supplied with power and the pressure in the condenser meets requirements for starting the fan,
the fan starts.
4. If the compressor is supplied with power and the pressure in the condenser meets requirements for stopping the fan,
the fan stops. Alternatively, if the compressor is stopped for more than one minute, the fan stops.
5. Figure 5-14 shows the voltage control curve during fan operating, which is on the basis of FSC1P control curve.
V

Vin F E L2
100%

MaxV B
C D

A
Vx
L1 100% output

Condensation pressure point


H G
MinV
Pband Pv100 = (Pset + Pband + 5)
I
Poff Pset Px Pmaxv Pv100 P

Figure 5-14 FSC1P control curve

During fan startup, the voltage is obtained based on the pressure-voltage curve if the pressure is kept within the set
range and the voltage is the value of MaxV if the pressure exceeds the set range. During fan operating, the power
system stops supplying power to the fan if the condensation pressure is smaller than (Pset - 1), namely Poff. The

Liebert DM Series Air Conditioner Technical Manual


Chapter 5 Micro-Processing Controller 19

control process is A -> B -> C -> D -> E -> F -> C -> B -> A -> G -> H -> I (point A corresponds to the pressure ranging
from B to G). In the case of 100% voltage output, the voltage restores to MaxV after the pressure drops by 2 bars to
the point of Pmaxv. Table 5-3 lists the voltage and pressure parameters.
Table 5-3 Voltage and pressure setting table
Parameter Lower limit Upper limit Default
Min. power supply voltage (%) 30 50 30
Max. power supply voltage (%) 60 100 100
Start pressure (Bar) 11 15 13
Pressure bandwidth (Bar) 4 6 5

5.5.6 Economy Mode Control


1. The AC units enter the Economy mode after this mode is enabled.
2. When the system starts to operate in this mode, the temperature control precision is added with the precision
amplification value. When the system exits this mode, the normal precision value recovers.
Table 5-4 lists the parameter setting in the Economy mode.
Table 5-4 Parameter setting in the Economy mode
Parameter Default value Lower limit Upper limit
Economy mode OFF (0) OFF (0) ON (1)
Start At 22: 00 18: 00 3: 00
Start At 7: 00 5: 00 10: 00
Zoom (°C) 2 2 10

5.5.7 Sleep Mode Control


1. The AC units enter the Sleep mode when there is one energy-saving card or more.
2. In this mode, the fan stops operating when the following conditions are met:
1) All the other moving parts do not need to operate except for the indoor fan.
2) The temperature of all energy-saving cards (four at most) is lower than the sleep temperature.
3) The energy-saving cards are kept in the temperature for 600 seconds.
3. The AC units exit the Sleep mode when either of the following conditions is met:
1) The temperature of an energy-saving card exceeds the value of sleep temperature plus 2 and the energy-saving
card is kept in the temperature for 30 seconds.
2) No energy-saving card is available.
Table 5-5 lists the parameter setting in the Sleep mode.
Table 5-5 Parameter setting in the Sleep mode
Parameter Default value Lower limit Upper limit
EngySave Cd Num 0 0 4
Sleep At 27°C 15 40

5.5.8 Host/Standby Unit Control


1. The host unit automatically switches as a standby unit after a rotate cycle ends.
2. The host unit switches as a standby unit and the standby unit switches as an host unit after a fault occurs in the host
unit or standby unit, such as high pressure locking, low pressure locking, or discharge locking.
3. The standby unit works as a host unit after a high temperature alarm is generated by the host unit.
Table 5-6 lists the parameter setting for host/standby unit control.
Table 5-6 Parameter setting for host/standby unit control
Parameter Lower limit Upper limit Default Remark
Unit Status 0 2 0 0: SIG; 1: HST; 2: Standby
Switch Mod 0 1 0 0: Standby; 1: Rotate
The number indicates the interval days
Rt Time By day (1, 2, 3, 4, 5, 6, and 7) 1
between two polling cycles.

Liebert DM Series Air Conditioner Technical Manual


20 Chapter 5 Micro-Processing Controller

Rt At 0: 00 23: 00 12: 00 -

5.6 Alarm Function

5.6.1 Alarm Category


Alarms fall into the following categories: high pressure alarm, low pressure alarm, discharge temperature alarm, high
temperature alarm, low temperature alarm, high humidity alarm, low humidity alarm, humidifier fault, fault of return air
temperature sensor, high pressure locking, low pressure locking, discharge temperature locking, floor wetting, power
loss, over-voltage alarm, under-voltage alarm, frequency deviation, loss phase alarm, negative phase alarm, custom
alarm 1 (lightning protection), energy-saving card fault, air flow loss, pressure sensor fault, humidity sensor fault, air
flow sensor fault, and custom alarm 2.

5.6.2 Alarm State And History


1. Alarm state recording
1) Alarms are recorded based on alarm occurrence time.
2) Both the alarm category and alarm time are recorded.
3) Alarm states are cleared upon power failure.
2. Alarm history recording
1) Historical alarms are recorded based on alarm occurrence time.
2) A maximum of 200 historical alarms are recorded.
3) A historical alarm includes the alarm SN., alarm category, alarm time, and alarm clearance time.
4) Historical alarms are saved upon power failure.
5) Historical alarms can be manually cleared.
6) Two-level password protection is enabled for historical alarms.

5.6.3 Alarm Prerequisites And Handling Methods


Table 5-7 Alarm prerequisites and handling methods
Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
The alarm is
The high pressure switch is Keep the high
High triggered and
kept open-circuited for a pressure switch turned Enabled/
1 pressure the 3
duration of alarm reporting off for a duration of disabled
alarm compressor is
delay alarm reporting delay
forcibly closed
The low pressure switch is
kept open-circuited for a
duration of alarm reporting
The alarm is
delay in the case of Keep the low pressure
Low triggered and
compressor operating. The switch turned off for a Enabled/
2 pressure the 30
state of the low pressure duration of alarm disabled
alarm compressor is
switch is ignored for 180 reporting delay
forcibly closed
seconds. The duration is
configurable, ranging from
30 seconds to 600 seconds
The discharge temperature The alarm is Keep the discharge
Discharge switch is kept turned off for a triggered and temperature switch
Enabled/
3 temperature duration of alarm reporting the turned off for a 3
disabled
alarm delay in the case of compressor is duration of alarm
compressor operating forcibly closed reporting delay
High The fan is enabled for 10 The alarm is Keep the return air Enabled/
4 temperature minutes and the return air triggered and temperature lower 30 disabled/
alarm temperature is kept higher the electronic than the value (current closed

Liebert DM Series Air Conditioner Technical Manual


Chapter 5 Micro-Processing Controller 21

Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
than the high temperature heater is high temperature
threshold for a duration of closed threshold - 2°C) for a
alarm reporting delay while duration of alarm
the return air temperature reporting delay
sensor operates normally
The fan is enabled for 10
Keep the return air
minutes and the return air
The alarm is temperature higher
temperature is kept lower
Low triggered and than the value (current Enabled/d
than the low temperature
5 temperature the cooling low temperature 30 isabled/
threshold for a duration of
alarm system is threshold + 2°C) for a closed
alarm reporting delay while
closed duration of alarm
the return air temperature
reporting delay
sensor operates normally
The fan is enabled for 10
minutes and the return air Keep the return air
humidity is kept higher than The alarm is humidity lower than
High Enabled/
the high humidity threshold triggered and the value (current high
6 humidity 30 disabled/
for a duration of alarm humidification humidity threshold -
alarm closed
reporting delay while the stops 2%) for a duration of
return air humidity sensor alarm reporting delay
operates normally
The fan is enabled for 10
minutes and the return air Keep the return air
humidity is kept lower than The alarm is humidity higher than
Low Enabled/
the low humidity threshold triggered and the value (current low
7 humidity 30 disabled/
for a duration of alarm dehumidificati humidity threshold +
alarm closed
reporting delay while the on stops 2%) for a duration of
return air humidity sensor alarm reporting delay
operates normally
Keep the humidifier
The humidifier switch is kept Enabled/
Humidifier The alarm is switch turned off for a
8 turned off for a duration of 10 disabled/
fault triggered duration of alarm
alarm reporting delay closed
reporting delay
The alarm is Keep the return air
Fault of the The return air temperature is
triggered and temperature within the Enabled/
return air kept out of the allowed range
9 the cooling allowed range for a 10 disabled/
temperature for a duration of alarm
system is duration of alarm closed
sensor reporting delay
forcibly started reporting delay
The high pressure alarm is The alarm is
High reported for three times triggered and
Manually clear the Enabled/
10 pressure within an hour or the alarm is the /
alarm disabled
locking kept uncleared within 10 compressor is
minutes locked
The low pressure alarm is The alarm is
Low reported for three times triggered and
Manually clear the Enabled/
11 pressure within an hour or the alarm is the /
alarm disabled
locking kept uncleared within 10 compressor is
minutes locked
The discharge temperature The alarm is
Discharge alarm is reported for three triggered and
Manually clear the Enabled/
12 temperature times within an hour or the the /
alarm disabled
locking alarm is kept uncleared for compressor is
20 minutes locked
The alarm is Keep the floor wetting
Floor The floor wetting switch is Enabled/
triggered and switch turned off for a
13 wetting kept turned off for a duration 10 disabled/
humidification duration of alarm
alarm of alarm reporting delay closed
stops reporting delay

Liebert DM Series Air Conditioner Technical Manual


22 Chapter 5 Micro-Processing Controller

Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
The alarm is Enabled/
Power loss occurs when the The alarm is
14 Power loss automatically cleared / disabled/
AC units are in operation triggered
one second later closed
The alarm is
Enabled/
Over-voltag The input voltage increases triggered and Restore the input
15 3 disabled/
e alarm by 15% the system is voltage
closed
locked
The alarm is
Enabled/
Under-volta The input voltage decreases triggered and Restore the input
16 3 disabled/
ge alarm by 15% the system is voltage
closed
locked
The alarm is
Enabled/
Frequency The input frequency is triggered and
17 Restore the frequency 3 disabled/
deviation deviated by 5Hz the system is
closed
locked
The alarm is
Enabled/
Open phase triggered and
18 Open phase occurs Manual restoration 3 disabled/
alarm the system is
closed
locked
The alarm is
Enabled/
Negative triggered and
19 Negative phase occurs Manual restoration / disabled/
phase alarm the system is
closed
locked
Custom The set polarities are kept Keep the set polarities
Enabled/
alarm 1 inconsistent with those input The alarm is consistent with those
20 30 disabled/
(lightning for a duration of alarm triggered input for a duration of
closed
protection) reporting delay alarm reporting delay
The alarm is
The number of normally triggered and
online energy-saving cards the dormancy Keep the number of
Energy is less than the set number mode cannot the cards consistent Enabled/
21 saving card or more than one be activated if with the set number 30 disabled/
fault energy-saving card exceed all and keep the cards in closed
the allowed temperature energy-saving normal temperature
range cards are
faulty
The value (temperature
measured by using the
sensor NTC0 - return air
temperature) is kept larger
Keep the value
than the set temperature for The alarm is
(temperature
a duration of alarm reporting triggered and
measured by using the
delay when the fan is in shut down all Enabled/
22 Air flow loss sensor NTC0 - return 10
normal operation. The air the devices disabled
air temperature)
flow detection thermal except for the
smaller than the value
resistor output is closed fan
(set temperature - 2°C)
when the fan is shut down.
This alarm is not reported if
the fan is closed and the
temperature sensor is faulty
Fault of Keep the condensing
The condensing pressure is
pressure pressure within the
kept out of the allowed range The alarm is Enabled/
23 sensor 1 allowed range for a 3
for a duration of alarm triggered disabled
(lightning duration of alarm
reporting delay
protection) reporting delay
24 Humidity The return air humidity is The alarm is Keep the return air 10 Enabled/

Liebert DM Series Air Conditioner Technical Manual


Chapter 5 Micro-Processing Controller 23

Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
sensor fault kept out of the allowed range triggered humidity within the disabled/
for a duration of alarm allowed range for a closed
reporting delay duration of alarm
reporting delay
Keep the temperature
The temperature measured
measured by using the
by using the air flow loss
air flow loss sensor Enabled/
Air flow sensor (NTC0) is kept out of The alarm is
25 (NTC0) within the 10 disabled/
sensor fault the allowed range for a triggered
allowed range for a closed
duration of alarm reporting
duration of alarm
delay
reporting delay
Note:
1. Alarm reporting delay is a fixed configuration.
2. In the case of system locking, the compressor, heater, humidifier, and outdoor fan are locked.

5.7 Other Functions

5.7.1 Real-Time Clock


1. Set and display the system date and time.
2. This function provides the accurate time of data recording.

5.7.2 Operating Record


1. Device startup and stop record
A maximum of 50 records about device startup and stop are recorded, including the fan, compressor, electronic heater,
and humidifier.
2. Operating time record
The operating time of the fan, compressor, electronic heater, and humidifier is recorded by hour.

5.7.3 Parameter Protection


1. All parameters that need to be protected are saved in the internal EEPROM.
2. Default parameter settings can be restored.
3. Two-level password protection is enabled.

5.7.4 Password Protection


1. A password consists of four digits, ranging from 0000 to 9999. Password protection is classified into three levels.
2. Level 1 password is available for ordinary users. They can modify password protection parameters and level 1
password.
3. Level 2 password is available for operators. They can modify password protection parameters and level 1 and level
2 password.
4. Level 3 password is available for maintenance personnel. Except for level 3 password, they can modify password
parameters and level 1 and level 2 password.

5.7.5 Shutdown Mode


1. Shutdown modes fall into local shutdown, monitor shutdown, and remote shutdown.
2. Local shutdown is implemented by pressing the on/off button on the display panel.
3. Monitor shutdown is implemented through the background monitor RS485-1.
4. Remote shutdown has the highest priority and is in serial relationship with the other shutdown modes.

Liebert DM Series Air Conditioner Technical Manual


24 Chapter 5 Micro-Processing Controller

5.7.6 Diagnosis Output


1. In the diagnosis mode, devices such as the primary fan, compressor, electronic heater, and humidifier can be
tested.
2. A tested device can be automatically or manually shut down when it diagnoses another load.
3. If a device is not manually shut down within an hour, the device automatically exits the manual shutdown mode.
4. The fan must be always in operation. If the fan stops operating, the other devices are forcibly shut down. The
system must be protected in the case of major alarms, such as air flow loss, high pressure alarm, low pressure alarm,
discharge alarm and locking, and power fault.

5.7.7 Sensor Calibration


1. The temperature calibration range is ±5°C.
2. The humidity calibration range is ±10%.

5.7.8 Deployment Management


Deployment management is required during initial system operating.

Liebert DM Series Air Conditioner Technical Manual


Appendix 1 Menu Structure 25

Appendix 1 Menu Structure

Main Menu

Alarm Menu Set Points System Status Temp Calib System Menu Help Menu LCD Setting

Temp Stpt Analog Hum Calib Mntr Prtcl


Version Info Contrast
Temp Sens Time/Date NTC0 Calib Mntr Addr
Enab Open Language
Hum Stpt In/Out Status In Fan SS Record Setup Baut Rate
Alarm Hum Sens Run Time Comp SS Record System Over Press
Status
SS Record Heat SS Record Under Press
Alarm
History Hi Temp Hum SS Record Pwr Freq Devia
Alarm Lo Temp Out Fan SS
Min. Volt
Setpoint Record
Hi Hum
Max. Volt
Lo Hum Outdoor
Out Volt
Unit
Air Loss
Start Press
Press BdWdth

Heat Num
Hum Num

Select CostSave Mod


Options EngySave Cd Num
Unit Mode
Switch Mod

Change Password
Factory Reset

Figure 1 Menu structure

Liebert DM Series Air Conditioner Technical Manual


Appendix 2 Wiring Diagram 26

Appendix 2 Wiring Diagram


Black Yellow Fuse

Red Yellow
Transformer T2
Indoor connection
Black Yellow Fuse
terminal TB1
TB1-N
NN Black Yellow
Grounding point of the NN
TB1-N Transformer T1 23 24 Indoor connection
electrical control box NN
TB1-N TB1-N 2122 terminals TB2
NN
TB1-1 TB1-11

TB2-21
TB2-22
1 11
TB1-2
TB1-3
2 12 TB1-13
3 13
J3-1
J3-2

Yellow-green

TB1-4
4 14
TB1-5 TB1-15

KM2-A1
5 15

J28-4
PE Yellow-green
6 16
Black
Black
Black
Black

Black
Black
Black
Black
TB1-7
J28-7 7 17

Black

Black

Black

Black
TB1-8 Standby unit is available
8 18
Black

Black

J28-8
TB1-9
J28-9 9 19
QF-1

QF-3

QF-5

Public alarm
SPD-N
SPD-1 TB1-10

SPD-2

SPD-3
J28-10 1020
PE
N

Black J18-1

J01-1

J01-3

J01-5

J01-7
1 3 5 Power 1 1 2 1 2
N L1 L2 L3 Black J18-2
Black 2 J13 J31
PE1L1N1 PE N MCB ALARM
Power SPD KM1-A1 J18-3
3 J18 1 2 3 4 5 6 7 8
2 4 6 SPD/D
COM NC
4
5
J01 J14 2
1
J14-2
J14-1
DB9
Monitoring
Black
Black
card
Black
Black

Black
Black
Power

J2-2
J2-1
Black J02
J1-N
2 1 2 2
J1 Black J02
J19-2
J19-1

1 J1-L
1
board

TB2-21
To outdoor 380V/50Hz 3N~ J2 GND GND
J18-3

KM1-21
Filter J12 2 12V 12V
4
Display
KM1-1

KM1-3

KM1-5

KM2-1

KM2-3
unit 1 Gray 3
A A
2 J4
J03 J39 2
A1 1 3 5 21 A1 1 3 5 13 board Yellow-green J03
2 J29 1
B B
1 board
1 1 2 3 4 5 6 7 8
KM1 KM2
J3
A2 2 4 6 22 A2 2 4 6 14 5 4 3 2 1
J34
Gray Temp/Hum
KM1-22
KM1-2

KM1-4

KM1-6

J3-4

J3-1
J3-2
detection board
J3-4

J28-3
1 2 3 4 5 6 7 8 1
Brown
Black

J30
Gray

Grounding point 2
KM1-A2 N1 L1 of the electrical J28-3 Black
3 KM2-A2
Brown
Brown Black

White
Black
control box J28-4
Blue
Blue

4 TB2-22

Control board J28 5


T1

T2

T3

6 Black
J28-7
7 TB1-7
J28-8 Black
8 TB1-8
Compr- Electric Indoor J19-1 91
J28-9 Black TB1-9
Yellow-green
SPD-NC 1 J28-10 Black
heater J19-2 TB1-10
SPD-COM 2
essor fan 3
0
1
Black
4 Black High pressure switch
J19
Brown

Brown
J19-5 2
5 Blue
Remote turn on/off J19-6 3
6 Blue Low pressure switch
Electric heater belt J19-7 4 Black
Grounding point of the Grounding point 7 J21 J21-5
Standby unit request 5
of the electrical Start capacitor
J19-8
of the compressor 8 J21-6 Brown Air discharging switch
electrical control box 6
control box J23 J36 7
3 2 1 Floor overflow
8

GND

+5V
VIN
Cable description:

Green
Connection cables between indoor

Black

Red
and outdoor connection terminal
Factory supplied line
Energy- +12V

Field supplied line L L1 Indoor


saving card
GND
CANH
CANL
N N1 connection
Parts supplied line PE1 terminal Pressure sensor
Inserted terminals Outdoor
connection
Connection description: terminal
1. This diagram is only for 7.5kW model.
2. There is no electric heater contactor KM2, electric heater and the corresponding cables in the single cooling unit.
3. There are transformer T2 and connection terminal TB2 Only when the heating function is select; The single cooling model is not equipped with transformer T2 and
connection terminal TB2.
4. The energy-saving card and the monitoring card are options; If you need them, field connection is essential.
5. The power SPD is equipped with T version unit; P version unit does not have power SPD and corresponding cables, J19-1 and J19-2 of the control board is shorted using cable.

Figure 2 DME07 model

Liebert DM Series Air Conditioner Technical Manual


Appendix 2 Wiring Diagram 27
Black Yellow Fuse

Red Yellow
Transformer T2
Indoor connection Black Yellow Fuse
terminal TB1
N N Black Yellow
TB1-N
Grounding point of the
TB1-N
N N
TB1-N Transformer T1 272829303132 Indoor connection
electrical control box N N
TB1-N TB1-N 21 2223242526 terminal TB2
N N
TB1-1 TB1-11
1 11

TB2-28
TB2-21
TB2-22
TB2-23
TB2-24
TB2-25
TB2-26
TB2-31
TB1-2
2 12

J3-1
J3-2
TB1-3 TB1-13
3 13
TB1-4
4 14

PE Yellow-green
TB1-5 TB1-15
5 15
TB1-6

PE Yellow-green
6 16

KM2-A1
KM3-A1

J28-6
KA1-3

TLR
J28-4

G0
G
QF-1 Black

QF-3 Black

QF-5 Black

Black
Black
Black
Black

Black

Black

Black

Black
J28-7 TB1-7 7 17

Black

Black

Blue
TB1-8
8 18 Standby unit is available
J28-8
TB1-9
J28-9 9 19

SPD-N
Public alarm

SPD-1
SPD-2
SPD-3
TB1-10
J28-10 10 20

N
Black J18-1
1 3 5 1

J01-1

J01-3

J01-5

J01-7
1 2 1 2
PE1 L1N1
Power N L1 L2 L3
Power SPD
Black J18-2
2 J13 J31
PE N Black J18-3
MCB ALARM KM1-A1 3 J18 1 2 3 4 5 6 7 8
2 4 6 COM NC SPD/D Black J18-4 J14-2
4
J01 J14 2 J14-1
5 1 DB9 Monitoring card
Power

Black
Black

Black
Black
J02

J2-1
J2-2
KM1-1 Black
Black
Black
KM1-21 Black
Black
2 J1-N J02-2 2

J19-2
J19-1
To outdoor unit 380V/50Hz 3N~ J1 J1-L Black

TB2-28
2 1
board

TB2-21

TB2-22
1 1 GND GND

J18-3
J2 J12 2 4
Display

KM2-1

KM2-3
12V 12V

KA1-4
Gray

KM1-3
KM1-5
1

KM3-1
KM3-3
3
J4
Filter J03 J39 2
1
A
B
A
B
2
1 board
A1 1 3 5 21 A1 1 3 5 13 A1 1 3 5 13 3 6 4 board Yellow-green J03 2
1
J29
1 2 3 4 5 6 7 8
KM1 KM2 KM3 KA1 J3
A2 2 4 6 22 A2 2 4 6 14 A2 2 4 6 14 1 5 2 5 4 3 2 1 J34
Gray Temp/Hum

J3-1
J3-2
detection board

J3-4
KM1-22
KM1-2
KM1-4
KM1-6

KM3-3
KM3-6
J3-4

TLR
J28-3

J28-5
1 2 3 4 5 6 7 8 J28-1 Black
1 +VR
Grounding point J30 J28-2 Brown

Black
Black
Black
2 SET
KM1-A2 N1 L1 of the electrical J28-3 Black

Brown
Brown

White
KM2-A2

Black
3

Blue
J28-4 Black

Blue
Blue
control box

HUM-N
4 TB2-24

HUM-L
Control J28-5 Black KA1-1
J28 5 J28-6
T1
T2
T3
Black TB2-31
6
J28-7 Black
7 TB1-7
8 J28-8 Black TB1-8
Comp- Humidify Indoor J19-1
board J28-9 Black

Yellow-green
SPD-NC 1 9 TB1-9
J19-2 J28-10 Black
SPD-COM 10 TB1-10
ressor -ing tub fan J19-3
2

Black
Black
AL 3
J19-4 1 Black
AL 4 J19 High pressure switch
J19-5 2 Black

Brown

Brown
5 Blue
Remote turn on/off J19-6 3
6 Blue Low pressure switch
J19-7 4
Grounding point Electric heater belt of Electric heater Grounding point 7 Black
of the electrical of the electrical Start capacitance Standby unit request J19-8
8
J21 5
the compressor J23 J36 Brown Air discharging switch
control box control box 6
3 2 1 7
8 Floor overflow

Black GND

Red +5V
Green VIN
KM3-A2 TLR G TB2-23
TB2-25 TLR G0 TB2-26

TAM ON 0 Drain manually


GND
J19-3 AL DR 1 Humidify normally +12V
GND Energy-saving

control board
J19-4 AL CANH

card
Humidifying
CANL
EV2 Outlet solenoid Pressure
G valve sensor
EV1
J28-1 +VR Inlet solenoid
J28-2 SET valve
GND
AB LS Water level
AB LS probe
Cable description: CS Conductivity
Connection cable between the CS probe
Factory supplied line indoor and outdoor terminal
Field supplied line L L1 Indoor
Parts supplied line N N1
PE1
terminal
block
Inserted terminal Outdoor
connection
Connection description: terminal

1. This diagram is only for 12.5kW model.


2. There is no electric heater contactor KM2, electric heater, humidifying contactor KM3, inner fan relay KA1, humidifying control board and the corresponding cables in the single cooling unit.
3. There is no humidifying contactor KM2, inner fan relay KA1, humidifying control board and the corresponding cables in the heating model.
4. Both single cooling model and heating model are not equipped with inner fan relay KA1. The black plug of the inner fan connects J18-4 terminal directly;
after crimped by the closed end connectors, the blue plug connects to the electric control box.
5. There are transformer T2 and connection terminal TB2 Only when the heating and humidifying function are select; The single cooling model is not equipped with transformer T2 and
connection terminal TB2.
6. The energy-saving card and the monitoring card are options; If you need them, field connection is essential.
7. The power SPD is equipped with T version unit; P version unit does not have power SPD and corresponding cables, J19-1 and J19-2 of the control board is shorted using cable.

Figure 3 DME12 model

Liebert DM Series Air Conditioner Technical Manual


Appendix 3 Glossary 28

Appendix 3 Glossary

AC Air conditioner
ID Inside diameter
LCD Liquid crystal display
Lee-Temp Low temperature
OD Outside diameter
SPD Surge protective device
SCR Silicon controlled rectifier

Liebert DM Series Air Conditioner Technical Manual


Emerson Network Power Asia

Australia Pakistan
T: 1800-065345 T: 92-42-36622526 to 28
F: 61-2-97810252 F: 92-42-36622530

Indonesia Philippines
T: 62-21-2513003 T: 63-2-7207400
F: 62-21-2510622 F: 63-2-6203693

Japan Singapore
T: 81-3-54038564 T: 65-64672211
F: 81-3-54032919 F: 65-64670130

Korea Thailand
T: 82-2-34831500 T: 66-2-6178260
F: 82-2-5927886 F: 66-2-6178277 to 78

Malaysia Vietnam
T: 603-78845000 T: 84-4-37628908
F: 603-78845188 F: 84-4-37628909

New Zealand
T: 64-3-3392060
F: 64-3-3392063

While every precaution has been taken to ensure the


accuracy and completeness of this literature, Emerson
Network Power assumes no responsibility and
disclaims all liability for damages resulting from use of
this information or for any errors or omissions.

Emerson, Business-Critical Continuity and Emerson


Network Power are trademarks of Emerson Electric Co.
or one of its affiliated companies.

©2013 Emerson Electric Co.


All rights reserved throughout the world. Specifications
subject to change without notice.

Emerson Network Power.


The global leader in enabling Business-Critical Continuity™. www.EmersonNetworkPower.Asia
AC Power Embedded Computing Infrastructure Management & Monitoring Precision Cooling
Connectivity Embedded Power Outside Plant Racks & Integrated Cabinets
DC Power Industrial Power Power Switching & Controls Services

AP13DPG-LiebertDM_Aircooled-TM

You might also like