3. Concrete mix with 10mm nominal size aggregate shall be used in congested
areas at the direction of the Engineer.
4. All exterior exposed beams &Columns and slab to seawater spray concrete to
be covered with suitable protection like EIFS and/ or suitable paint too proof
below concrete.
TABLE 2
GENERAL REQUIREMENTS OF CONCRETE
9 Rapid Chloride Penetration (RCP) ASTM C1202 Low to very low for sub-
Max Charge Pass at 56 days structure and Moderate
for superstructure
10 Initial surface absorption test (ISAT) BS 1881 Part 208 OPC: 0.30
Max at 56 days: 10minute test (ml/m2/s) OPC+GGBS: 0.15
12 Chlorides (as Cl) by weight of BS1881: Part 124 For reinforced concrete
cementitious material only
If made with OPC/MSRPC 0.10% Max.
If made with SRPC 0.06% Max.
Notes
1. For concrete grade C20, only requirements of No. 2, 4, and 5 shall apply, unless otherwise
directed by the Engineer.