Professional Documents
Culture Documents
ACE Power System
ACE Power System
Pi <20MW
So P, = 20 MW ; P.= 30 MW
Example 6.10:
‘The Fuel inputs of plant 1 & 2 are given as
F, =0.2 Py’ +40P, +120 Rs/hr
F, = 0.25 P;’ + 30P, + 150 Rs/hr
‘The minimum & max load on each plant is
25 P,< 100 Where i= 1,2.
Determine the economical operating schedule and
corresponding cost of generation for a total
demand of 180 MW.
IC = 0.4 P; +40 R/MWhr
IC2=0.5 P2 +30 R/MWhr
25SP) & Pps 120MW 5
Pp= 180 MW
JC, =IC, = 0.4 P; -0.5 P= 10~
P, +P. = 180
Solving i & ii
P)= 1111 MW
Engineering
lead
Economics of Power Generation
P)= 68.89 MW
Fr=F) (111-11) + F2 (68.89)
= 0.2 (I111N)2 + 40 (111.11) +120 +
0.25 (68.89)° + 30 (68.89) + 150
= 10,436.64 Ryhr
6.1.2. Economic Dispateh with power loss:
Objective:
To minimize
generating units.
the total fuel cost of thermal
Let us assume that total number of units are 4
The total fuel cost is given by
Saw
Such that,
2
Where,
Py. is the power loss in ‘MW’ and it is
expressed as
’» + P, (Equality constraint)
A= Lear MW
For N = 2, the power loss formulae expressed as
PAB R + BaP 2B RE MI
And
Pisin S Pi S Pinax (Inequality constraint) Using
Lagrangian method, the augmented cost function F
can be written as
)
F=6, o(Sa-n-n]
aa
Where, 4. is a Lagrangian multiplier
Minimization can be achieved by the condition
Fog
oF,
By solving the above equation,Powe
Case 2: If load is located at plant -2
oF, G &
2. is the incremental transmission loss the i unit © re
ar
and it is expressed as, Py
Ri 0;R;
By x (Ry +R:)=> Bu ¥0
Byz oc (Ret Rs) => Bro =0
(Biz=Bz) a Rs => Bn =0
6.1.3 Special eases
Case : 1 if the load is located at plant - 1
G
Po
Ri=0 Rr#0Rs=0
By oc (Rr +R3)=> Bu =0
Ba x (Ro +Rs) > Ba #0
(B= Bx) aRs => B= 0
PL=By PP + By Pp +2.By Py P2 MW Example 6.11:
PL=By Py ‘The penalty factor of the system shown below is
sen
Py=4s MW
Penalty Factor,
Fld
1-ITL 1-01
SS eT rand | New Dei | engtorn]| Bhabaeswar | Vinywad | Viakbapaaen | Tropa | Pane | ObesCe
2113: Economics of Power Generation
Example 6.12:
‘A two bus power system is shown below. The
incremental fuel cost of the two plants are
OF ne
Te; = 0.35 P; +41 R/MWhr
Te. =0.35 P2 +41 R, MWh
‘The loss expression is P= 0,001 (P;~ 70° MW
‘The total incremental cost of the system is 117.6
Rsy/MWhr
(@ Calculate the: optimal scheduling of generators
(Gi) Calculate the total power loss.
Sol: (i) From co-ordination equation
A=LIQ=L IG -
P, = 0.001 (P= 70" MW
(0.35 P, +41) = 117.6
P, = 218.85 MW
LAG=%
te _ ((0.35P, +41)=117.6
114=0.002P,
P, = 159,029 MW
(i) PL=0.001(P2-70)"
(001(159.029-70)"
92 MW
1, Py, = 369.966 MW
ESRI ser We Dati | Benes | bance | Visyorach | ViaRapatue | Tropa | Pane | ChennaiCircuit Breakers
7.1 Introduction
‘The protective switch gear is designed based on
fault Analysis
* Circuit breaker is designed based on most
severe fault at its location. (3 - § Fault).
© If there is a fault on any part of the power
system, the magnitude of fault current is
very high. (Approximately 2 to 10 times the
full load current).
The fault current is not just limited to faulty
section of the system but even extended to
each and every healthy sections of the
system.
© The relay is a device which senses the
abnormal operation of power system and
issue signal to corresponding circuit breaker
and cicuit breaker disconnect faulty section
from healthy system.
7.2 Types of protective switches used in the
system
i). Fuse
ii). Load interrupter
iii). Line isolator
iv). Circuit breaker
@ Fuse
Operates only under abnormal conditions
Whenever heat energy developed by the fuse
is more than its thermal limit, then the fuse
will melt down or blown out, fault element
can be disconnected,
* Fuse is a primary protective device in the
distribution system
* In substation, fuse is a backup protective
device.
* The fusing current, Je d%,
diameter of the wire.
* The fuse element is generally made up
‘material having the following characteristic.
(@) Low melting point
Eg: tin, lead, zine
is the
(b) Free from deterioration due to oxidation,
(c) low cost
Gi) Load interrupter
* This will be operated only at full load
conditions.
* Fuse is operates at abnormal conditions
(itself),
© Load interrupter is used for energy
management, load shedding/curtailment
‘* Breaking capacity of load interrupter = full
load capacity.
[> 100 MW (feeder-1)
[> 250 MW (feeder-2)
©—— 150 Mw (feeder)
Rating 50 MW (feeder-4
sow t= (feeder-4)
“> 50 MW (feeder-5)
= Total load = 600 MW
The above diagram represents over load on the
system e100 MW. The load interrupter operates
and disconnects feeder-4 and feeder-5
(ii) Line Isolator
© It will be operated only under no-load
condition,
* The necessity of Line Isolator is to provide
‘more clearance.
* Sequence of operation is: First load
interrupter has to operate and next Line
Isolater.
* Breaking capacity of Line Isolator is zero
cp Bator
Ge Mecof
space
Hyderabad | New Dali | Bexgalura | Bhulanesvar | Vipyavada | Viakapamam | Tirupati | Paoe | Gbeanaieee
Circuit Breaker
(iv) Circuit breaker
# It will be operates under all conditions i.e.,
at no-load or at fulf load or at abnormal
condition,
Fuse and load interrupter can be replaced by
cireuit breaker.
* Breaking capacity of C.B is three phase
short circuit MVA at breaker location.
* CB is a protective switch and which wil
make the circuit and break the circuit during
normal and abnormal conditions
respectively.
7.3 Purpose of cireuit breakers
‘The main purpose of circuit breakers is to:
* Switch load currents
© Make on to a fault
© Break normal and fault current
© Cary fault current with out damage till the
interruption.
The important characteristics from protection
point of view are:
* It should open main contact as quickly as
possible once it receives trip signal from
relay
© The capacity of circuit that-the main contact
is capable of interrupting
The first characteristics referred to as. the
tripping time of circuit breaker (CB open time),
which is expressed in cycles.
The opening time of modem high-speed cireuit
breaker is 4 cycle to 8 cycles.
Opening time:
It is the time between the instant of application of
tripping power to the instant of separation of main
contacts,
Areing time:
It is the time between the instant of separation of
main CB contacts to the instant of Arc extinction,
CB operating time = opening time + Arcing time
| 7.4 Are phenomenon Circuit breaker
7.4.1 ARC Initiation
AC t= 0: There is No trip signal to C.B From
relaying system.
ref | \uc
WY
Att= 0: There isa trip signal to C.B from
Relaying system & CB contacts are started
separating.
FC f | \ MC
fu,
Att=0° CB contacts little separated.
FC Mc
Ie
a
Ave
Ex: 132 kV CB
Ax- Distance between fixed contact and moving
contact (which is very less Ax = 0.1 wm)
AV- Voltage across contact spacing (which is
very less compared to operating voltage AV =
100 V)
Electric field intensity between the contacts,
AF p= tO _ to00ev fem
O.1nm
“Bis very high and it is definitely greater than the
breakdown strength of the medium between
contacts. So gap breakdowns and are is initiated.
E=
‘ar
Conclusion: arc is initiated at the instant of contact
separation due to high field gradient (or) field
ionization,
(EGRET stad New Dai | Berwatrw | Bhubaneswar | Vivavads | Veakapatnam | Tropa | Pune | Channa® rnsab Beste
7.4.2 ARC Maintenance
EX: | ; cycle C-B; Open time = 30 ms.
Att = 30 ms: Contacts are fully separated.
FC MC
Vince
X ~ Contacts Spacing (itis in c.m)
=1om
Vac~Are voltage (it is 2 to 5% of system
voltage)
Vex _0.03X132KV 1
x iB Jem
= 2.286 kV/em.
So field gradient is very’ less compare to the
dielectric strength of the medium between the
contacts.
Conclusion:
* The Arc is maintained not because. of field
grailient
* It is maintained because of thermal ionization
due to high amount of heat produced during
Arcing process.
7.4.3 Properties of the Arc:
Arc is column of ionized gasses.
Conductance of their Arc
Number of free e generated during
ionization.
e< Cross section areas of the Arc
et
lengthoftheAre
* The path of the Arc is purely resistive and it is
negative temperature coefficient Temperature
increases=Rye decreases
[EGS ata |New Dat engine | Banewvar | Viavads | Viskapatan | Tropa | Poe | Cheat]
2116:
Power Systems
= Conductance of the Arc increases.
* The resistance of the Arc is highly non-linear.
7.5 ARC interruption
‘There are two methods of arc interruption:
(i) High Resistance method
ii) Current zero interruption method.
7.5.1 High Resistance Method
In this method, ARC resistance is increased so as to
reduce the current to a value which is insufficient to
‘maintain the Arc.
Heat energy = I Rare t
— Yaw
Re
2
Heat energy = —“= xt
1
Heat energy & <—
p= Resistivity of the Arc
I= Length of the Are
A= Cross section area of the Arc
The Arc resistance can be increased.
(Lengthening the Are
Gi) Constraining the Are
Git)" Cooling the Are
(iv) Reducing cross section area of the Arc.
© When current is interrupted the energy
associated with its magnetic field appears in the
form of electro static energy. So a high voltage
appears across the breaker contacts.
If the voltage across the breaker contact is very
high and it is greater than the with stand
capacity of the gap then gap will breakdown and
Are will restrike.
* Therefore this method of Are interruption is not
suitable for high current interruption.
* This method is employed for how power A.C &
D.C circuit breakers.M7:
7.8.2 Current zero interruption
* This method is applicable only in case of A.C
circuit breakers
+ For a SOHz system, the current wave passes
through natural ze10 100 times per second. This
feature of Arc is utilized for A.C interruption.
* In this method the current is not allowed to rise
again after zero current occurs.
© The current is not interrupted other than zero
current instant, a high transient voltage
appearing across the breaker contacts which
restrike the Are again.
‘There are two theories which are explaining current
zero interruption method
(i) Recovery rate theory. (Slepain’s theory)
Gi) Energy balance theory. (Cassies theory).
Recovery rate theory (Voltage race theory)
* Arcis a column of ionized gasses.
¢ The ionization is minimum at current zero
instant. So to extinguish the arc, ions and
electrons removed from the gap immediately
after the current reaches to a natural zero,
© Tons and electrons can be removed either by
recombining them into neutral molecule or by
sweeping them by inserting an_ insulating
medium between the contacts.
* The Arc is interrupted if rate of removal of ions
from the gap is greater than that of rate of
ionization.
* Rate of ionization is depends on restr
voltage.
* So in this method, the rate at which dielectric
strength recovered is compared with rate of rise
of restriking voltage,
ing,
© If dielectric strength increases more rapidly than
restriking voltage the arc is extinguished.
© If restriking voltage raises more rapidly than the
dielectric strength, the ionization persist and
breakdown of the gap occurs, resulting in an are
for another half cycle,
Circuit Breakers
Voltage Restiking Volz Dielectric
voltage Strength
Dielectric
Restikin
Strength \ a
voltage
Time
‘Are not extinguished
Tine
‘Are extinguished
Fig. 7.1: Recovery rate theory
Energy balance theory
© The C.B contacts are about to open its resistance
is zero and heat generation is zero.
* When contacts are fully opened and are is
extinguished resistance is infinity and heat
generation is again zero.
* Between these two instant heat generation goes
to amaximum value.
Heat generation
R=O Rem
Fig.7.2 Energy batance theory
+ The circuit breaker is designed to remove this
generated heat as early as possible by cooling
the gap, giving a blast of air or flow of oil at
high velocity and pressure.
‘© If the rate of heat generation is less than the rate
of heat dissipation, the arc is extinguished.
* If the rate of heat generation is more than the
rate of heat dissipation, The space break down
and resulting in an arc for another half cycle.
7.6 Terms regarding Arc phenomena
(i Are voltage (Vare)
Voltage across circuit breaker during arcing
period is known as are voltage
[EN Dats enc [Wher | iby | Voalapaam | oat | Poe | Chena118
ve vat
ee RY
Mc
The
© Are will be modeled as a non linear resistor,
where Rye is variable according to
temperature.
Vare = TarcRare
As Jue increases, temperature imereases and
Rare decrease, So Vare ~ constant
# Vaz Tag are in phase
© Are power factor is unity but fault power
factor is almost zero lagging.
Recovery
voltage
Axe Phenomenon
Fig. 73:
(ii) Active Recovery Voltage
The instantaneous voltage at the instant of Arc
extinction is called active recovery voltage.
Active recovery voltage depends on
following factors
(The power factor of the fault current.
(ii) The Armature reactions _ synchronous
machine
(ii)The circuit conditions [ype of fault,
System grounding]
© If operating voltage of the system is132 kV
and all factors are neglected then
Vow = Maximum value of phase voltage of
system (Vin)
* To account for power factor of the fault
“Vmn’ should multiplied by a factor sing
Where ‘$’ is the power factor angle of fault
current.
© To account for effect of armature reaction
‘Vn’ should be multiplied by a factor K,
Kish.
© To account for circuit conditions *V,’
should be multiplied by a factor ‘K2”
Kz is called first pole clearing factor
Ky = _Vitageactoss first pole which iscloared the fault
VoltegeacrossC Batterallpolesarecleared the fault
Type of
| Rand
ve | uw | ue | un | ute
rowing
Grounded . = et | Kels =
womided sat | eis | ket | Kel | Kind
‘Ungrounded orl lete ee
ones Keets [kets | kes | emus
Varv= Ki KV q sing
Note:
To calculate line value of active recovery voltage
the above expression should be multiplied by a
factor V3
Ex: Fora 132 KV system
Van BAY 3
v3
RAN cates | Now Det | Benzaura | Bhubaneswar | Vinyavare | ViaKiapataim | Tirupal | Pane | Chena19: Circuit Breakers
‘The transient voltage across breaker contacts at the
instant of arc extinction is known as restriking
voltage.
‘ault on terminals of a circuit breaker
Where E is the system voltage at the instant of are
interruption (also called active recovery voltage).
As the transient oscillation is a fast phenomenon, E
can be regarded as a constant for a short duration.
Restriking voltage = Voltage across the Circuit
breaker at the instant of are
extinction
= Voltage across the Capeitor
at the instant of are
extinction
‘Substituting these values in the equation given
above, we get
tee yy. =E
dt
Taking Laplace Transform on both sides of the
equation, we get
E
LC8'Ve(3) +Ve(8)
| Where ve(S) is the Laplace Transform of v.
Other terms are zero as initially q= 0 at t= 0,
of Ve(s)[LC3? +1)
E
V-(s)=——=,— =
SA oeriLcaen
tof
; therefore,
‘Taking the inverse Laplace, we get
OE
s(s? +02)
+0,
or V()=
V.0)=0,£ {sino
=o
As Ve(t) = Oat t= 0, constant = 0.
Veit) = B(1 cos eyt )
Restriking voltage
‘The maximum value of restriking voltage
= 2 Epc
=2 x peak value of the system voltage
+ The Rate of Rise of Restriking
Voltage(RRRV)
da
“econ
“te0-so,}
=0,Esino,t
‘The maximum value of RRRV = «,E.
= OE yeax
Frequency of natural oscillation,
rad/sec
Hz
* Ome
ER) raid | Ne Dat | Benga | Bhanesnar | Vita | VisRtapaam | Tapa | Pane | Chena7.7 Current chopping
When interrupting a low inductive current (shunt
reactor or magnetizing current of transformer), the
current become abruptly zero well before natural
zero instant. This phenomenon known as current
chopping.
Due to current chopping the voltage across circuit
breaker under goes to huge oscillation and may
results in restrike.
During current chopping,
Apel
2
<
2
Prospective voltage v
* A current chopping phenomenon is very severe
during the interruption of low magnetizing
current.
* A current chopping phenomenon is very severe
in air blast circuit breaker.
System voltage |
With standing Vs
capacity of CB Va |
vi
Fig. 7.6: Current Chopping
© If prospective voltage > with standing capacity
of circuit breaker then gap will restrike.
© Arc restriking is successfully done up to the
point where the prospective voltage become less
than withstinding capacity of circuit breaker.
2120:
Power Systems
78 Resistance Switehing
The resistance switching is employed to reduce the
effect of restriking voltage and current chopping.
PT
1 ite
Fig. 7.
Circuit for analysis of
resistance switching
‘The voltage equation is given by
div
Lo4—ficdt=B and i=ic tig
at ol : :
Therefore, the above equation become
ilctil yap
a
dic | di
racy tingy,
aa NC
Or ig =f = KC¥e)
a dt
ic _ d(CVe) _o4?Ve
Therefore, Se LC cA
a at &
dig 8Ve/R)_ 1 We
a at R
Substituting these values in the main equation, We
get
Taking Laplace Transform, we get
oP Ve(6)+E8Ve(8)4Ve@)==
uc Vesta Ve (s)+Ve(s): 5
Other terms are zero, as Ve= 0 at t=
ims
nyt
cVelo|et+ ae
or Lc cto +e +l
or Ve(s)
Tiydrabed | New Dali | Benn | Bakanenar | Vinjwada | Viaapatam | Tira | Pune | Cheon2131
Circuit Breakers
For no transient oscillation, all the roots of the
equation should be real. One root is zero, i.e. s = 0
which is real. For the other two roots to be real, the
roots of the quadratic equation in the denominator
should be real. For this, the following condition
should be satisfied,
2
: ) -L] 20 or —L
2RC} LC 4R*C?
‘Therefore, if the value of the resistance connected
across the contacts of the circuit breaker is equal to
or less than [E » there will be no oscillations
‘The frequency of damped oscillation is given by
ere
2«VLC aR?
7.9 Ratings of cireuit breakers
1, Breaking capacity of circuit breaker
2. Making capacity of circuit breaker
3. Short time current rating:
This is based on thermal and mechanical
considerations. The circuit breaker must be
capable of carrying short circuit current for a
short period without damaging its contacts,
Rated voltage > L - L rms voltage, generally
‘more than the nominal system voltage.
5. Rated current or continuous current rating: It is
ms value of current caried by CB under
normal operating condition
=
6. Rated frequency -> System frequency
Lc System | Vstue of R | Envelope of Restriking || 7. No. of operation, : :
damping Voltage No, of operation is specified on name plate of
CB after which the CB requires maintenance.
. ‘One operation = One break + one make
ae 8. Operating duty
| i) Cireuit breaker not used for auto reclosing.
B-3~MB-3-MB
Where, B ~ breaking operation,
3 — Duration in minute
Over ,
damping ‘Mi — Making operation
Gi) Circuit breaker with auto reclosures
L_ B—D,~MB
| Where, D, - Det time of circuit breaker in
cycles (approximately 300 ms).
Under
damping Ex: Fault on power system
G
i © isa BE 7 | No ead
Un. Rew \ R ‘ L 0"
damping | _
_ Mo Irault
Hyderabad | New Delhi | Bengalura | Biabanswar | Viayavada | Veakhapamam | Tirupal | Pune | heal2122:
Power Systems
LA
= sin( or a9)
Z|
Transient
period
‘Steady state period
(08) symmetrical period
7.9.1 Symmetrical breaking capacity
It is the rms value of the ac component of the fault
current that the circuit breaker is capable of
breaking,
oA
v2
* Lys the fault current comesponds to 3-6 fault at
breaker terminal
+ Symmetrical breaking current, Iyy =
ly= 3
2
© Symmetrical breaking capacity
V3 xrated system voltage
symmetrical breaking current
= 1,,(psu.)x Base MVA
= [SOMA ur
7.9.2 Asymmetrical breaking capacity
It is the rms value of the total current comprising of
both ac and de components of the fault current that
the circuit breaker can break.
Asymmetrical current (For First cycle)
[RGR ected Nev ba | Haste | keno | Viren | Vinton [Tepe [Pee Ge]
foo
= xxly
x= 1.6 for first cycle
Asymmetrical breaking capacity:
_ VB xrated systemvoltage
x Asymmetrical breaking current
xxsymmetrical breaking capacity
Note: Default is always symmetrical breaking
capacity.
7.9.3 Making Capacity
The possibility of a circuit breaker to be closed on
short circuit is also considered. The rated making
current is defined as the peak value of the current
(including the de component) in the first cycle at
which a circuit breaker can be closed onto a short
circuit.
© The capacity of a circuit breaker to be closed
onto a short circuit depends upon its ability to
withstand the effects of electromagnetic forces.
‘Making current = the peak value of fault
current corresponds to first
cycle
= oc
-J2 1.8% symmetrical breaking current
2.55 x symmetrical breaking current
Making capacity
= 2.55 x symmetrical breaking capacity
7.10. Classification of Circuit Breakers
Classification is based on Arc quenching medium
(or) insulating medium used between contacts
i) Air break circuit breaker
ii) Air blast circuit breaker
Oil circuit breaker
iv) SF gas circuit breaker
v), Vacuum circuit breaker
In circuit breakers, the solid insulating materials
will not be used for are quenching purpose®
7.10.1. Air break circuit breaker
‘+ Also called AB switch.
© Atmospheric air available at room temperature
and normal pressure will be used as Arc
quenching medium
* Dielectric strength of air = 30 kV/em (peak)
© There is no external action taken for the Are
interruption in the air break circuit breaker. So
Are interruption process is poor
* This circuit breaker used for operating voltages
(400 V to 1900 V)
7.10.2. Air blast circuit breaker
High pressure air will be used as arc quenching
medium
+ High pressure air will be blasted into the Arcing
chamber for Arc interruption.
* High pressure air will have good cooling
properties
‘© The high pressure ait will be maintained up-to
condensation point where the gaseous material
will be converted into liquid material.
© Air pressure is maintained at 20 — 30 kg/em?
© Operating voltage levels:of Air blast circuit
breakers is12 kV to 525 kV
* According to blasting direction of air there are
three types of Air blast circuit breakers.
i) Axial blast
ii) Cross blast
ii) radial blast
(i Axial blast circuit breaker:
ON
High pressufe—,
Air FC Mc
are
Noe
© High pressure ait will be exested on to the are
axially
ERS od New Dai | Benes | Wher | Vioranod| Viana | Trpal| Pae| Chal
ii) Cross blast circuit breaker:
are
FC Mc
eee
(01) forced cool air
‘+ High pressure air will be exerted on to the are
perpendicularly. So arc resistance will increase
and heat energy developed by the arc will
reduce. So it will reduce the thermal ionization
process.
(Gil) Radial blast circuit breaker
ee sir
FCF*S5|MC Double blast CB
aie
High pressure Air
© High pressure air will be exerted on to the arc
perpendicularly and It will leave arcing chamber
axially.
© This method is: used for modem extra high
voltage circuit breakers.
7.103 Oil Circuit breaker
+ Insulating oil or transformer oil is used for Arc
quenching medium,
+ AE ihe contacts are separated there is an are
struck between the contacts.
‘The heat of the are evaporates the oil and it is
decomposed into hydrogen gas at high
pressure.
+ The volume of gas produced is one thousand
times that of oil decomposed.
+ An are energy decomposes oil into 70 %
hydrogen, 5 % methane, 22 % acetylene and
3% ethylene
+ Arc is in a bubble of gas and surrounded by
the oil.
The are extinction is facilitates mainly by two
process.124: Power Systems
(i) Hydrogen gas cools the arc.
(ii) Hydrogen gas pushes the oif in between the
contacts and then removes the arcing
products from the Arc.
Advantages:
+ Itabsorbs the are energy to decompose the oil
into gases which is an excellent cooling
property
+ It acts as an Insulator and permits smaller
clearance between live conductors and earthed
components.
Disadvantages:
+ Itis inflammable and there is a risk of Fire.
+ Possible to form an explosive mixture with ar.
+ Arcing products (carbon particles) remains in
the oil. These carbon particles increases with
number of operation which will deteriorate the
oil, so frequent maintenance of oil is required.
According to the amount of oil used in oil
circuit breaker there are two types of circuit
breaker.
1. Bulk oil circuit breaker
2. Minimum oil circuit breaker
Purpose | Bulk | Minimum oit
rp oil CB CB
‘Are quenching | Oil Oil
Insulation | Solid
provision with ingulatin
respective to | Oil r
live parts in aN
‘the system. (osrceai)
: - Gaseous
Cooling the arc | Oil coolant
* In bulk oil circuit breaker, the contacts are
placed inside a rigid mechanical chamber
* Whenever, the contacts are about to separate, a
small amount of oil will be sent to the space of
contacts, so that, the oil will be converted into
25 which will form a gas bubble around the
Are to cool the Arc, or for heat dissipation,
gaseous coolant will be sent on to gas bubble
(SRR) ati | New Dah | Benin | Bhubaneswar | Vieanada | Vieapatam | Tirupati | Pane | Cheol
7.10.4, SF gas cireuit breaker :
© SF6 gas is used as are quenching medium
* Dielectric strength of SF gas is 2 —3 times of
air dielectric strength,
Dielectric strength of SF gas = 80 kV/em
= 10
Fs gas is « good coolant and it is having
electroregative property.
* Electronegative property is a property of
material which will attract electrons or electron
density under the presence of SFs gas. The
electrons from the arc will be removed so that
the arc strength gets reduced
* By using cooling property of SF¢ gas, the heat
will be dissipated
+ Atcurrent zero point, a turbulence force, will be
created, inside the circuit breaker chamber, such
that the heat dissipation will become more
effective, there by the arc will be interrupted at
current zero point,
© Operating voltage levels 6.6 KV to 800 kV
+ For all voltage levels, this SFs gas circuit
breaker will be used
7.10.5. Vacuum circuit breaker
© Ideally vacuum means zero pressure (or) ‘0” torr
(or) ‘0° mm of Hg pressure
Practically high vacuum is created at 10° torr
Dielectric strength of vacuum = 107 Vem
= 10000 kV/em
«As a dielectric’strength of vacuum is very very
high
‘The spacing require between the contacts is very
Jow and it is about mm.
‘* There is no gaseous atoms or molecules presents
in vacuum,
* When ever the contacts are about to separate a
small amount of metal vapour will be released
from contact bodies, due to mechaaical friction
between the contacts
‘© On the metal vapour there are two forces
(i electromagnetic forces due to current flow
through contacts
Gravitational force (mg)Circuit Breakers
| Atcontact separation time, the electromagnetic Voltage
‘Are
forces will dominate the gravitational force, Range and
Type Quenching
such that the metal vapour will be stayed Breaking
Medium
between the contacts and it forms a conducting Capacity
path between the contacts. This conducting path Miniature ‘Airat ——] 400-600V; for |
is called as plasma. Circuit atmospheric | Small current
|» At current zero point, the electromagnetic farces Breakers Pressure taking rating
| 7 ‘Air Break ‘Air at
become zero and the metal vapour will reach to i Bes | soveitk
circuit . revi atmosphere
the bottom of circuit breaker chamber due to pl eA
gravitational forces. There is no a gaseous atom Breakers
or metal vapour are available for arc restriking. || Minimum Oil S.34N - 220
. ‘Transformer
So arc will be interrupted at first current zero Circuit = KV; 150-
itself Breakers 25000 MVA
| Operating voltage levels up to 66 KV. For Vaca a eT
above 66 KV levels the creation of vacuum is Cu pee | eee
difficult as well as itis costly. rceeees |
sr, SFeats | 3376S kV;
cireuit
7.11. Comparison Of circuit Breaker: eee kg/om? 1000-50,000
ke
1. Insulating Methods. Breakers pressure MVA
iE zi ~ Compressed
Property Breakers Oil | SF6 Vacuum: Air Blast 66 kV — 1100
Nese air at high
Nees Medium | Low | Medium | High Cireuit KV; 2500-
|_ operations | pressure (20-
‘soft’ break | Gooa | Good | Good |) Fair Breakers >, | 60,000 MVA ;
ability i 30 kg/m?)
Monitoring of Manual Not |
Medium NA | “rest_| Automatic | possible _
Fire hazard Choice of
' xowe | High | None | None
it ua Rated Voltage circuit Remark
a
ett | None | Low | tow | None ben a
Economical | Uptol [33-22 | 33 33-36 ir Oreak © | Vacuum is
voltage | kV | kv | gooey | ev Below 1kV | vacuum CB, | TAs
: SFCB, |?
Minimum oil 5
132KV-220KV | CBSF6CB) St
| airblastC.B, | PS
SF, C.B., ait SFe is
400 KV- 760KV | Blast CB preferred.
(Ea rtd | Nev Dati | era | Btneswar | Viyawada | Vsaapawaca | Tira | Pane | Ghana2196: Power Systems
2. Features of CB:
__Factor Gil Breakers Air Breakers VaccumiSK6
Safety Risk of explosion and Fire due to | Emission of hot air and | No risk of explosion
increase in pressure during multiple | ionized gas to the
operations surroundings
Size Quite large Medium Smaller
Maintenance | Regular oil replacement Replacement of arcing | Minimum lubrication
- contacts for control devices
Environmental | Humidity and dust in the atmosphere Since sealed , no
Factors can change the internal properties effect due to
and affect the dielectric environment
Endurance Below Average ‘Average Excellent
Example 7.1: Solution:
‘An LL fault occurs at the terminals of a 34, (i) Symmetrical breaking capacity (SBC) =
KV synchronous generator which is solidly 2000 MVA
grounded. The fault current lags the system 7
voltage by 60° and voltage of the system is Vit = 33 KV
decreased by 5% due to demagnetizing effect of SB.C= V3x¥,,x1,
synchronous machine. Calculate active recovery
voltage. = 2000510"
Solution: ra
‘Vary = K; Kp Vm sing =35KA
(ii) Making current = 2.55 x symmetrical
60° breaking current
= 2.55 x 35 kA,
= 89.22 kA
(Due to demagnetizing voltage is decreased by
5%)
K
5 (LL fault)
Vary = K, KV sing
951.5 Hk,
v3
= 1LO8KV.
Example 7.2: Seo
A3+p, 33 KV oll circuit breaker is rated for 120A
200 MVA and 4 see
(The symmetrical breaking current is
Gi) Us making current will be
pp Hydcabad | New Dali] Benge | Dharwar | Vinvavodh | VinKipatam | Tinga | Pane | Chena
Example 7.3:
A344 fault on a 33 kV, SOHz system will give a
steady state fault current of 20004. A 33 kV C.B
4s placed for this interruption. The phase ground
‘capacitance and inductance up to C.B location is
0.01 UF and 5:mH respectively. If arc is chopped
at peak value of fault current then voltage across
CB contacts is
Solution:
fault current = 2000 A
‘Maximum value of fault current = 2000 x J2
iE
“Ne
z
= 2000 x Jef SA = 2 Mv
donoExample 7.4:
In 2.220 KV system, the reactance and capacitance
up to the location of cireuit breaker is 8Q and 0.025
AF, respectively. A resistance of 600 ohms is
connected across the contacts of the circuit beaker.
Determine the following.
Natural Frequency of oscillation,
Damped Frequency of oscillation.
ii) Critical value of resistance which will give no
transient oscillation,
(iv) ‘The value of resistance which will give
damped frequency of oscillation, one fourth of the
natural frequency of oscillation.
‘Sobution:
= _ 8 _oonssan
2n50 100%
() Natura Frequeney of oscilation = L [
aces IVC
a = 6.304 kHz
~ 2 V0.02544% 0.02510
(ii) Frequency of damped oscillation is given by
1fi_ i
ax lOmsian0oasAI0* aoonsai0*F lon}
1 [10 10"
2m V636 9
(iii) The value of critical resistance
1 2544
Le If
2VC 2\0.025xi0*
(iv) The damped frequency of oscillation is
6.304 kHz = 1576 Hz
413KHz.
= 504.352,
ist6=
2a
2a [aaseaxaoDRI0" solomasci0*P aR
or 1576 = 28 =10"25R
2nV6.36
Circuit Breakers
2 R=5208Q
Example 7.5:
For a 132 kV system, the reactance and
capacitance up to the location of the circuit
breaker is 3 ohms and 0.015 pF, respectively.
Calculate the following.
@ The frequency of transient oscillation,
Gi) The maximum value of restriking voltage
across the contacts of the circuit breaker.
(ii) The maximum value of RRRV
Solution:
(The frequency of transient oscillation,
L= et = 50, the system frequency
.00954H
© Ynef0.0095430.015%10
3 :
uo tO = 13,201kH
2mxi.1962 7.524]
(i The restriking Voltage
= Ef cost]
The maximum value of the restriking
voltige = 2 Epeak
2132 V5 -215.56kV
F
(iii)The maximum value of RRRV = ©y Eyeat
= 20,
132 RV Is
a
=9.0104547 / ps
SERRE I si | New Det eg | lca | Vind | Venap | Twa [Fe | hssProtective Relays
8.1 Introduction:
* An clectrical power system consists of
generators, Transformers, transmission and
distribution line. The system equipments are
likely to damage during fault or abnormal
condition in any part of the power system, if
proper protection system is not provided.
‘© Ifa fault occurs in any part of the power system,
an automatic protective device is needed to
isolate the faulty element as quickly as possible.
* A protective system includes, circuit breakers
and protective relays to isolate the faulty section
of the system from healthy sections.
* The function of a protective relay is to detect an
abnormal condition in the power system and
issue trip signal tothe circuit breaker to
disconnect the faulty element
* The basic electrical quantities likely to change
during abnormal condition are voltage, current,
frequency and phase angle (Direction)
* The protective relays utilize one or more of
these quantities to detect abnormal conditions in
a power system.
Back-up Relay: a back up celay operates after a
slight delay, if the main relay fails to operate.
Back up protection: The back up protection is
designed to clear the fault if the primary protection
fails. It acts as a second line of defense.
Primary protection: If a fault occurs, itis duyy of
the primary protective scheme to clear the fault and
it acts as a first line of defense. If it fails, the back —
up protection clears the fault
Stability: This is the ability of the protective
system to remain inoperative under all load
conditions, and also in case of external faults. The
relay should remain stable when a heavy current
due to an extemal fault is flowing through it.
Pick up level: The value of actuating quantity
above which relay operates,
Reset level: ‘The value of actuating quantity below
which the relay is de-energized and retums to its
original position,
Relay: Relay is a sensing devices, this will sense
the abnormal condition such as short cireuit fault in
the system and gives tip signal for circuit breaker
Operating Time: The time which elapses between
the instant when the actuating quantity exceeds the
pickup value to the instant when the relay contacts
get closed,
Reset Time: The time which elapses between the
instant when the actuating quantity becomes. less
than the reset value to the instant when the relay
contact returns to its normal position,
Primary Relays: The relays which are connected
directly in the circuit to be protected.
Secondary Relays: The relays which are connected
in the circuit to be protected through current and
potential transformers.
Auxiliary Relays: Relays which operate in
response to the opening or closing of its operating
circuit to assist another relay in the performance of
its function, This relay may be instantaneous or
may have a time delay.
8.2 Basic objectives of system protection
The fundamental objective of system protection is
to provide isolation of a problem area in the power
system quickly, so that the damage to the rest of the
system is minimized and as much as possible is left
intact.
Thus protection does not mean prevention, but
rather, minimizing the duration of the trouble and
limiting the damage, outage time, and related
problems that may result otherwise.
The basic objectives of system protection are
(i) Speed of operation
Gi) Sensitivity
ii) Selectivity
(iv) Reliability
EE) | New Deli | Benglura | Bhubaneswar | Viayarad | Visakhapatnam | Tropa | Pane | Cbenah129
Protective Relays
(®) Simplicity
(vi) Stabitity
(vii) Economies
Speed of operation
‘The protection system should ensure minimum fault
duration, consequent minimum damage 10
equipment and system stability.
If the fault clearing is delayed, the healthy
equipments of the system will damage due to
excessive thermal and mechanical stress. So the
protection system should isotate faulty section from
healthy system as quickly as possible.
Sensitivity
The protection system should able to detect
minimum possible value of foult current and issue
trip signal to circuit breaker.
Selectivity (Discrimination)
The protection system should ensure maximum,
continuity of service’ and minimum. system
interruption
The relay should able to discriminate the fault in its
‘own zone of protection or outside the zone of
protection.
Reliability
It is the assurance that the protection gystem will
perform 100% correctly
thas two aspects
1. Dependability
2, Security
Dependability: It should operate when itis required
Security: It should not operate when it is not
required
Simplicity
The protection system should have minimum
number of equipment and associated circuitry 10
achieve the protection objectives
Stability
Relay operation must be in stable mode even it is
carrying the fault current
The relay should able to carry the fault current with
out damaging it self till the point of interruption.
Economics
Protection should provide maximum protection at
minimal total cost.
83 Classification of relays
‘* Classification based on technology
Electromechanical Relays: These relays were
the earliest forms of relay used for protection of
power system, They work on principle of
‘mechanical force causing an operation of relay.
Static Relays: These relays don’t have moving
parts. The design of static relays is based on the
use of Analog electronics instead of coils and
magnets to create relay characteristics
Digital Relays: To “implement the relay
functions, Analog circuits used in static relays
axe teplaced with microprocessors and micro
controlters in digital relays
‘Numerical Relays: These relays can be viewed
as natural developments of digital relays as a
result of advances in technology. These relays
use DSP processor as a computational hardware,
together with the associated software tools.
‘© Classification based on application
1. over current relays
2. Directional relays
3. Distance relays:
4, Differential relays
84. Operating principle of Electro
mechanical Relays
Basically there are two different operating
principles of relays
(@ electro magnetic attraction
(ii) electro magnetic induction
FER Ne Ba Tce | anwar | Vga | Vea | Tea Pe | Clea]Power Systems
Fig. 8.1: Attracted armature Relay
‘A rrestraining force has to be produced exactly in
opposite direction of operating force to restrict
relay operation under normal condition.
‘+ Field energy stored in electro magnetic circuit is
function of air gap length (x)
w=?
2
p= asa
T
I= length of magnetic path
Jo. of tus of coil
a= area of cross section of coil
© The inductance ‘L’ changes with respect to
contact gap
= WO)
$10) ?
‘© Torque produced by electro magnetic circuit,
a 1 : yp dL
lasinot, Fo= —(1,, sina)’
sino Fo= 3 (fy sinax)
Jak & sin? ot
2dx
1h (Loastot)
2a" 2
aL
Fora constant ‘x’, “is constant
ix
Tope T°
Tres = Ki?
Resultant torque, T= Top ~ Tres
=KP-K
Where K is the torque produced by spring
‘© This type of relay will be used for both AC and
DC relaying purposes.
84,2. Induction type relays:
Applicable only for AC relaying purpose. There are
‘Wo types of induction relays
1. Induction dise type element
(j) Shaded pote structure
ii) Watt hour meter/energy meter structure
2. Induction cup type element
Shaded pole induction disc type
Shaded pole Induction Relay
For the relay application, continuous rotation of dise
is not required. To restrict the rotation of disk
during normal operation, a restraining torque is
ET csi [Rew Daa | Hei | haber | nana | Vicky | Toa | Pane | CheaACE
84 Engineering Academy
18h:
Protective Relays
produced by using spring. To damp out oscillations}
made by disc a permanent magnet (PM) is provided.
Tox pypsina.
T=Fsina
T=KiP — K=constant
Watt-hour meter (energy meter) disc type
element
fer magnet ef
220;
Fig. 83: Watt-hour meter type Induction Relay
Upper magnet coil Lower magnet coil
V2 20" V2Z0°
+ +
v.20 + _ v.20
"2,28;
+
12-0; = he
+ ¥
6 2-8) hp ZO
Torque produced on Aluminum dise
Tc dy.gasin(®; ~ 02)
© If; — 82 =0 (or) 6; = 6, then torque produced
by Aluminum disc is zero and disc will not
rotate.
© To get rotation Aluminum disc 0; # 2 ot x
ratios of upper coil and lower coil maintained
different
Induction cup type relay:
© Operated based on induction motor principle,
ive, the torque produced is due to interaction of
two rotating magnetic fields.
© Rotating body is a hollow Aluminum cup
* This is constructed either for 4 pole or 8 pole.
Zi
Rotating Al cup
‘Stationary iron core
Contact to tip
r
Fig. 83: Watt-hour meter type Induction Relay
© Size of cup is very small and it’s weight and
inertia is very less
* Torquehveight rat
‘very high,
* Typical operating time = 0.01 sec
* This is high speed relay
* Sensitivity of relay is very high and the ratio
between reset level to pickup level is around
0.9,
* Cup type relays are used in high speed
relaying applications
Applications of induction type elements:
1. All the three elements will be used as
inverse time over current relays.
2, Watt-hour meter and cup type elements will
be used as directional relays
3. In the distance relay both operating forces
and restraining forces will be produced by
system quantities by reconnecting the coils.
PG tas [Ne Dati | Wears | Bhbanevar | Vinvavada | Vayama | Tre | Pane | Chena® vest Tian
2182:
Power Systems
8.4.3. Thermal relay:
Thermal relay used to protect the rotating machines
ftom over heating. (Cause for the over heating is
over load on the system)
‘Types of thermal relays
1, Thermo couple/Thermistor
2, RTD (Resistance temperature detector)
3. Bimetallic strip
Universal Torque Equation
TKDE 4 KV? + KV c0x0-1)+K
yoy 4 4
Current Voltage Directional Spring
unit unit unit torque
8.5. Over current Relays
From universal torque equation
T=K, 0 + Kz V? + Ky VI.cos(6 -1) +K
Ky =#ve, K; = 0,K3=0, K=-ve
T=KiP-K
Under threshold
T=05 Top =
K\P-K=0
Ki P=K
During Operation
T>0; Top > Tres
Ki P-K>0
KiP>K
i Je
K
ee
. If cmment flowing through the relay
operating coil is greater than the pick up value
of current Relay operates.
SRN) certs [New Dot | Benes | Bicone | Viana | Vieapaam [Ti
1> 1 pictap > Relay operates
1