Professional Documents
Culture Documents
Voltage Stability Monitoring
Voltage Stability Monitoring
Abstract: This study focuses on a method to monitor voltage stability in sub-transmission grids with a real-time calculation
of the Thevenin impedance seen from the concerned bus requiring only information of the system topology, phasor
measurement units (PMU) and SCADA data. The voltage stability status is assessed by an impedance stability index
and a power stability index based on the maximum power transfer to the load according to the Thevenin theorem. Due
the influence of the non-linear behaviour of generation units, especially synchronous generators, it is necessary to
adjust the magnitude of the calculated Thevenin impedance according to their operational status. This problem is
approached by adding an additional impedance at the generator bus, whereby its magnitude is calculated with two
algorithms. The validation and a comparison of these algorithms are achieved by simulations with IEEE-9-bus-network
topology.
1 Introduction paper, this approach is traced further and compared with a second
algorithm described below.
The increasing amount of generation power, mainly renewable In Section 2, the basic idea behind the Thevenin-based approaches
sources, connected at distribution grid level and the slow network and the existing algorithm from [7] is summarised and the new
development, which cannot keep pace with the installed capacity, algorithm is proposed. Section 3 focuses on the implementation of
requires a change in the operation of distribution grids. The grid the results of the algorithms into the network topology. The
operators must become more informed about the system status to analysis and results comparing both algorithms are shown in
react flexible on load flow situations pushing the system to its Section 4. The paper finishes with the conclusion in Section 5.
limits and to maintain a sufficient security of supply. It is therefore
indispensable to use the possibilities of acquiring real-time data, so
far mostly used in high voltage and super grids, in all voltage 2 Method description
levels to identify the operation limits and operation margins in real
time. 2.1 Recapitulation of online voltage stability monitoring
Voltage stability becomes also a more and more a limiting factor based on the Thevenin impedance
in distribution grids, due the increasing share of power controlled
load and in general higher loaded lines. So far research addressing The basic idea of the Thevenin-based methods is to use data of the
voltage stability mainly focused on using offline data, power flow network topology, SCADA systems and online measurements
results and simulated active power – voltage curves (PV) curves from PMUs to estimate the accurate equivalent Thevenin
for load buses. As shown in [1], a static relationship explorer and impedance of the network seen from the concerned load bus.
historical data can be used to estimate a transmission margin of According to circuit theory, any network connected to an arbitrary
active power correlating to the operation state of the instability bus can be reduced to an equivalent voltage source ETh and the
point. Other approaches are based on neural networks providing a equivalent impedance ZTh seen from the bus. Assuming a load ZL
forecast of the loadability [2, 3]. The needed training cases must at the concerned bus, the maximum loadability at the bus is
be provided by offline load flow calculations with different reached when the magnitudes of load and Thevenin impedance are
switching status and load distribution. The accuracy of the equal as
obtained forecast is depending on the number of samples. In
addition to monitoring voltage stability, [4] offers a risk-based
Z = Z (1)
monitoring and preventive control method combining offline PV L Th
curves of critical buses and (n − 1) line contingencies with online
data from PMUs. The load impedance can be determined by the ratio of load voltage
A different approach for online voltage stability monitoring VL and the load current IL. The resulting representative network is
without any offline calculation and historical data is to calculate shown in Fig. 1.
the Thevenin impedance of the concerned load bus [5, 6] by using Considering the Thevenin condition for maximum loadability (1)
PMU and SCADA data and the system topology. However, there an impedance stability index (ISI) is established in [8] as
is still a lack of analyses related to performance and validity of the
Thevenin impedance based methods. It was already demonstrated Z
in [7] that the Thevenin impedance actually seen from the load ISI = L
(2)
bus is not the equivalent impedance for short circuit calculations, ZTh
since the latter does not take operational limits of generation units
into account. In the same paper, an algorithm was proposed that The value of the ISI reaches 1 for the maximum loadability and drops
improves the performance of the Thevenin-based methods. In this below 1 for further increasing load. Depending on the composition
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1535–1539
This is an open access article published by the IET under the Creative Commons 1535
Attribution License (http://creativecommons.org/licenses/by/3.0/)
A more detailed description is given in [7], resulting in four
different magnitudes of Z′ depending on the operational state of
the generator
⎧
⎪
⎪
0 no limits reached
⎪
⎪ Vrated
2
⎪
⎪
⎪
⎪ active power dispatch
⎪
⎨ 4PG, max
|Z ′ | = 4Vrated (3)
⎪
⎪ over excitation limit
⎪
⎪ IG
⎪
⎪
⎪
⎪ 4V
⎪
⎩ rated armature current limit
IG,rated
Fig. 1 Thevenin equivalent circuit
The impedance angle of Z′ can be chosen freely, but for obtaining
reasonable results it was chosen in the previous work near the
of the load, a voltage collapse can occur in this situation for constant angle of the main transmission elements or pure inductive.
power or constant current loads.
However, these relations are only valid, if all generators are
assumed as ideal sources supplying infinite active and reactive 2.3 Virtual generator bus
power to the system. If any generator reaches its capability border,
the load contribution no longer depends simply on the grid This algorithm for calculating the adjustment impedance focuses on
topology. Therefore, the Thevenin-based instability monitoring the idea that the generator bus voltage is hold at its rated value as
obtains wrong results if no adjustment impedance Z′ is introduced long as the feeding generator does not reach any limitation. After
between the source representing the generator and the generator reaching a limit the voltage at the generator bus changes in general
bus. The magnitude of the adjustment impedance can be and the generator cannot be assumed as an ideal source anymore.
calculated using two different algorithms, which are described in The proposed approach to implement this behaviour is to
the two following sub items. introduce a virtual generator bus, at which the ideal voltage source
representing the unlimited generator is connected. Therefore, the
magnitude of the voltage at the virtual bus VG,virtual can be
2.2 Generator parameter-based adjustment assumed as the rated voltage VG,rated at any time. The actual
physical generator bus is connected to the virtual one by the
This approach takes a closer look onto the generator parameters adjustment impedance Z′ as shown in Fig. 3. This impedance can
defining the capability border for an over-excited synchronous be calculated with the PMU measured parameters bus voltage VG
generator and therefore limiting the reactive power supplied by and generator stator current IG
the generator. The concerning parameters are the maximum
exciter current If, the maximum stator current IG and the available VG,virtual − VG
turbine power Pt. The turbine power must be taken into account, Z′ = (4)
IG
although it is not limiting the reactive power of the generator, but
leads to a change of the active power distribution between the
generators connected to the system and therewith influences the
voltage profile of the load buses. In Fig. 2, the section of the
capability diagram defined by the mentioned parameters is
presented.
The basic concept of the parameter-based algorithm is to assume
the generator as an ideal source behind Z′ feeding a single load ZG
directly connected to the generator bus, whereby Z′ must be
chosen in a way, that at the instant of maximum loadability the
maximum value for the considered limiting parameter is reached.
The magnitude of Z′ is then calculated by expressing it as a
function of the rated generator bus voltage Vrated and the
concerned parameter under the condition of maximum loadability.
Fig. 2 Generator capability diagram Fig. 4 Relation between measured phasors, VG,virtual and Z′
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1535–1539
1536 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
The weakness of this simple equation is that the phasor angle of to estimated maximum apparent load power at any instant (11),
VG,virtual is unknown. This obstacle can be overcome by assuming [9, 10]
the phasor angle jZ′ of Z′ as given parameter. Fig. 4 shows the
relation between the measured phasors VG, IG, the voltage VG,virtual ETh = VL,k + ZTh,k · IL,k (10)
and the impedance Z′ .
To derive the magnitude of Z′ (5) has to be squared and written by 2
E Z − imag Z sin d + real Z cos d
separated real and complex part resulting in (6) with the magnitude Th Th Th Th
Smax
2 (11)
of Z′ as only unknown variable 2 imag ZTh cos d − real ZTh sin d
VG,rated = VG + Z ′ · IG (5) A power-based stability index (SSI) can be introduced with the
2 estimated maximum apparent load power Smax
2
VG,rated = VG cos wVG + Z ′ IG cos wIG + wZ ′
(6) S
2 SSI = max (12)
′ SL
+ VG sin wVG + Z IG sin wIG + wZ ′
By solving (6), the phasor Z′ can be calculated as shown in (7) and The SSI is in general more robust to errors in the estimation of the
(8), whereby the phasor angle jZ′ is a free parameter, which Thevenin impedance. This can be proven by calculating the error
restrictions are discussed below. It must be noted that negative propagation for the estimated maximal apparent load power
results of the equation are not reasonable corresponding to the magnitude error ΔZTh. The resulting
deviation is used to calculate the relative error in Smax. The SSI
is more accurate than the ISI as long as (13) is fulfilled
−VG · a + VG2 (a2 − 1) + VG,rated
2
′
Z = ewZ ′ ·i (7) 2
IG 1 − ZTh
2
/ ZTh + DZTh
,1 (13)
a = cos wVG − wIG − wZ ′ (8) 2 1 + cos (wZTh − d)
Due to the significant impact of the angle jZ′ on the phasor Z′ and The condition is always valid, since the term including the
therefore on the calculated Thevenin impedance, it becomes Thevenin impedance and the magnitude error is in any case
crucial to find a proper rule to choose it. positive and the trigonometric part has also only positive values
The approach used in this paper is based on the idea that the for the reasonable angle differences.
voltage drop at the generator bus is caused by a limitation of the
reactive power of the generator. This reactive power limitation is
also valid for the generated reactive power of the virtual source 4 Analysis of the Thevenin impedance
and it should therefore always equal the reactive power delivered
from the generator bus to the network. To fulfil these limiting The accuracy of the algorithms described above is tested in the 9-bus
conditions, the additional impedance Z′ is assumed to be purely network shown in Fig. 6. The limiting parameters of the generators
resistive. SG1 and SG2 and the line impedances are given in Tables 1 and 2.
The generator SGref represents the connection to the transmission
grid and its parameters are chosen in such a way that it is working
3 Implementation as slack node.
ZL,k · Z(k, k)
ZTh,k = (9)
ZL,k − Z(k, k)
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1535–1539
This is an open access article published by the IET under the Creative Commons 1537
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Table 2 Line impedances (based on 110 kV)
Line impedances R, Ω X, Ω
5 Conclusion
This paper proves on the one hand, that the parameter-based method
to estimate the Thevenin impedance is also working for meshed
topologies. On the other hand, it was shown that the virtual bus
Fig. 7 Time course of impedances at load bus 4, estimated max. load power method provides also a useable estimation of the Thevenin
and actual load power. The dashed lines indicate the instant of ISI = 1, red impedance with the advantage, that it is not necessary to know
for the parameter-based method, green for the virtual generator bus method any generator parameters at all and it is also suitable for any kind
of energy source connected to the network.
However, the magnitude and power factor of neighbouring loads
cause a rather high error in the estimation of the Thevenin
impedance, so that the actual calculated ISI is not accurate enough
to be used in a voltage stability monitoring. Therefore, it was
shown that the SSI and its error propagation regarding the
Thevenin impedance provide a reasonable benchmark to detect an
approaching voltage instability.
Summing up, the virtual bus method is able to provide an online
voltage stability monitoring system based on PMU measurements
and system topology. Its slightly worse accuracy compared with
the parameter-based method is outweighed by the easier available
Fig. 8 ISI of load bus 4 at the instant of maximum apparent load power as information and its usability for all kind of sources without the
function of apparent power of loads 6 and 7 at a power factor of cos j = 0.7 need of adjusting the algorithm.
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1535–1539
1538 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
6 References 6 Duong, D.T., Uhlen, K.: ‘Online voltage stability monitoring based on PMU
measurements and system topology’. 2013 3rd Int. Conf. Electric Power and
Energy Conversion Systems 2013, 2013, pp. 4–9
1 Fan, Y., Liu, S., Qin, L., et al.: ‘A novel online estimation scheme for static voltage
7 Polster, S., Duong, D.T., Renner, H., et al.: ‘Voltage stability monitoring using
stability margin based on relationships exploration in a large data set’, IEEE Trans. a modified Thevenin impedance’. PowerTech Manchester 2017, forthcomming
Power Syst., 2015, 30, (3), pp. 1380–1393 2017
2 Liu, S., Xu, Z., Tang, G., et al.: ‘A SIPSS-Lasso-BPNN scheme for online voltage 8 Begovic, M., Milosevic, B., Novosel, D.: ‘A novel method for voltage instability
stability assessment’. IEEE Power & Energy Society General Meeting, 2014, 2014 protection’. Proc. Annual Hawaii Int. Conf. System Sciences, 2002, 2002
October, pp. 1–5 January, pp. 802–811
3 Zhao, J., Zeng, Y., Wei, W., et al.: ‘Fast assessment of regional voltage stability 9 Duong, D.T., Uhlen, K., Løvlund, S.: ‘A method for real time voltage stability
based on WAMS’. IEEE Asia-Pacific Conf. Circuits Syst. Proc., APCCAS, monitoring in sub-transmission networks’. Proc. 2014 Power Systems
2008, no. 1, pp. 635–638 Computation Conf., PSCC 2014, 2014
4 Putranto, L.M., Hara, R., Kita, H., et al.: ‘Risk-based voltage stability monitoring 10 Wang, Y., Pordanjani, I., Li, W., et al.: ‘Voltage stability monitoring based on the
and preventive control using wide area monitoring system’. 2015 IEEE Eindhoven concept of coupled single-port circuit’, IEEE Trans. Power Syst., 2011, 26, (4),
PowerTech, PowerTech 2015, 2015 pp. 2154–2163
5 Maharjan, R., Kamalasadan, S.: ‘Voltage stability index for online voltage stability 11 Machowski, J., Bialek, J.W., Bumby, J.R.: ‘Power system dynamics: stability and
assessment’. North American Power Symp., 2015 control’ (2nd ed. Re. Chichester: John Wiley & Sons Ltd, 2008)
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1535–1539
This is an open access article published by the IET under the Creative Commons 1539
Attribution License (http://creativecommons.org/licenses/by/3.0/)