You are on page 1of 2

Area Replacement Calculations

per ASME B31.3, paragraph 304.3.3

By: G. Woods

Temperature: 400 ssure psig: 600 corrosion: 0.1 % mill tol.: 12.5
Materal:
Header: A240-304 S: 20000 Eh: 0.85 Angle B: 90
Branch: A312-TP304 S: 20000 Eb: 1
OD Nom. Wall
Header: 8.625 0.322 Pad OD: 6.500 y: 0.4
Branch: 4.5 0.237 Pad, Tr: 0.322
th tb
Min. wall: 0.150 0.067

Dim. d1: 4.285 A1: 0.643 d2a: 2.432


Dim. d2: 4.285
A2: 0.136 L4a: 0.454
L4: 0.454 L4b: 0.590 Tb
A3: 0.037 tb
A4: 0.638
A2+A3+A4: 0.811 mill tol.
% Replaced: 126.102 c

UFT A3 Pad reinforced intersection


Pad OD Tr
A2 A1 Th
mill tol. L4 A4 th

c d1
d2 d2

B
C Header
0.893997
0.850904

% Replaced must be at least 100