Professional Documents
Culture Documents
FULL ENERGY
Power supplies for machines and plants.
Powerful + reliable + efficient.
wipos PB1 24-1
wipos PB1 24-1
Switching power supply
24 V DC/1 A
81.000.6310.0
Block diagram
Dimensional diagram
Technical Data
wipos PB1 24-1 Part number: 81.000.6310.0
Fig. 1 Derating
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos PB1 24-1
www.wieland-electric.com Revision: Rev. B, date: 03/2015 – Page 1 of 2
wipos PB1 24-1
Technical Data
wipos PB1 24-1 Part number: 81.000.6310.0
Rated input voltage AC [UIN_AC] 100 - 240 V AC
Line frequency AC 47 - 63 Hz
Power factor correction filter (PFC) not necessary
Input voltage range AC [UI_AC] 90 ... 264 V AC
Input voltage range DC [UI_DC] 120 ... 375 V DC
Rated input current (UI_AC = 115 V, ION) 0.68 A typ./0.9 A max.
Inrush current (UI = 115/230 V AC, ION) max. 25 A/max. 50 A
Input fuse T 2A/250 V AC (internal)
Hold up time (UI = 115/230 V AC, I0N) > 20 ms/> 100 ms
Input surge voltage protection Varistor
MTBF 832,000 h
Dimensions (W x H x D) 35 x 91 x 57 mm
Weight ca. 0.13 kg
Housing material Plastic
Control elements
Vout Adjust Trim potentiometer for UOut adjustment
Terminal connections
- 2 x output voltage 24 V DC, negative output
(internally connected)
+ 2 x output voltage 24 V DC, positive output
(internally connected)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos PB1 24-1
www.wieland-electric.com Revision: Rev. B, date: 03/2015 – Page 2 of 2
wipos PB1 24-1.5
wipos PB1 24-1.5
Switching power supply
24 V DC/1.5 A
81.000.6320.0
Block diagram
Dimensional diagram
Technical Data
wipos PB1 24-1.5 Part number: 81.000.6320.0
Fig. 1 Derating
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos PB1 24-1.5
www.wieland-electric.com Revision: Rev. B, date 03/2015 – Page 1 of 2
wipos PB1 24-1.5
Technical Data
wipos PB1 24-1.5 Part number: 81.000.6320.0
Rated input voltage AC [UIN_AC] 100 - 240 V AC
Line frequency AC 47 - 63 Hz
Power factor correction filter (PFC) not necessary
Input voltage range AC [UI_AC] 90 ... 264 V AC
Input voltage range DC [UI_DC] 120 ... 375 V DC
Rated input current (UI_AC = 115 V, ION) 0.68 A typ./0.9 A max.
Inrush current (UI = 115/230 V AC, ION) max. 25 A/max. 50 A
Input fuse T 2A/250 V AC (internal)
Hold up time (UI = 115/230 V AC, ION) > 20 ms/> 100 ms
Input surge voltage protection Varistor
MTBF 732,000 h
Dimensions (W x H x D) 53 x 91 x 57 mm
Weight ca. 0.19 kg
Housing material Plastic
Control elements
Vout Adjust Trim potentiometer for UOut adjustment
Terminal connections
- 2 x output voltage 24 V DC, negative output
(internally connected)
+ 2 x output voltage 24 V DC, positive output
(internally connected)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos PB1 24-1.5
www.wieland-electric.com Revision: Rev. B, date 03/2015 – Page 2 of 2
wipos PB1 24-2.5
wipos PB1 24-2.5
Switching power supply
24 V DC/2.5 A
81.000.6330.0
Block diagram
Dimensional diagram
Technical Data
wipos PB1 24-2.5 Part number: 81.000.6330.0
Fig. 1 Derating
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos PB1 24-2.5
www.wieland-electric.com Revision Rev. B, date: 03/2015 – Page 1 of 2
wipos PB1 24-2.5
Technical Data
wipos PB1 24-2.5 Part number: 81.000.6330.0
Rated input voltage AC [UIN_AC] 100 - 240 V AC
Line frequency AC 47 - 63 Hz
Power factor correction filter (PFC) not necessary
Input voltage range AC [UI_AC] 90 ... 264 V AC
Input voltage range DC [UI_DC] 120 ... 375 V DC
Rated input current (UI_AC = 115 V, ION) 1.1 A typ./1.5 A max.
Inrush current (UI = 115/230 V AC, ION) max. 30 A/max. 60 A
Input fuse T 2A/250 V AC (internal)
Hold up time (UI = 115/230 V AC, ION) > 12 ms/> 60 ms
Input surge voltage protection Varistor
MTBF 608,000 h
Dimensions (W x H x D) 71 x 91 x 57 mm
Weight ca. 0.25 kg
Housing material Plastic
Control elements
Vout Adjust Trim potentiometer for UOut adjustment
Terminal connections
- 2 x output voltage 24 V DC, negative output
(internally connected)
+ 2 x output voltage 24 V DC, positive output
(internally connected)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos PB1 24-2.5
www.wieland-electric.com Revision Rev. B, date: 03/2015 – Page 2 of 2
wipos P1 24-1.25
wipos P1 24-1.25
Switching power supply
24 V DC / 1.25 A
81.000.6110.0
Block diagram
Dimensional diagram
Technical data
wipos P1 24-1.25 Part number: 81.000.6110.0
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 24-1.25
www.wieland-electric.com Rev.: 12/2014 –
Page 1 of 2
wipos P1 24-1.25
Technical data
wipos P1 24-1.25 Part number: 81.000.6110.0
Rated input voltage AC [UIN_AC] 100 - 240 V AC (85 ... 264 V AC)
Line frequency AC 47 – 63 Hz
Power factor correction filter (PFC) not necessary
Rated input voltage DC [UIN_DC] 90 – 375 V DC
Rated input current 0.8 A
Inrush current 115 V AC / 230 V AC 20 A / 40 A max.
Input fuse T2 A / 250 V (internal)
Hold up time (at ION) UI_AC = 115 V > 20 ms
UI_AC = 230 V > 30 ms
Operating ambient temperature [TU] -40 °C ... +71 °C (UL: max. 50 °C)
Humidity in operation 20 – 95 % RH
Storage temperature [TU] -40 °C ... +85 °C
Terminal connections
- 2 x output voltage 24 V, negative output
terminal (internally connected)
+ 2 x output voltage 24 V, positive output
terminal (internally connected)
OK DC OK output (open collector output)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
g (PE) PE (Ground), always connect
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 24-1.25
www.wieland-electric.com Rev.: 12/2014 –
Page 2 of 2
wipos P1 24-2.5
wipos P1 24-2.5
Switching power supply
24 V DC / 2.5 A
81.000.6120.0
Block diagram
Dimensional diagram
Technical data
wipos P1 24-2.5 Part number: 81.000.6120.0
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 24-2.5
www.wieland-electric.com Rev.: 12/2014 – Page 1 of 2
wipos P1 24-2.5
Technical data
wipos P1 24-2.5 Part number: 81.000.6120.0
Rated input voltage AC [UIN_AC] 100 - 240 V AC (85 ... 264 V AC)
Line frequency AC 47 – 63 Hz
Power factor correction filter (PFC) not necessary
Rated input voltage DC [UIN_DC] 90 – 375 V DC
Rated input current 1.5 A
Inrush current 115 V AC / 230 V AC 30 A / 60 A max.
Input fuse T2 A / 250 V (internal)
Hold up time (at ION) UI_AC = 115 V > 20 ms
UI_AC = 230 V > 30 ms
Operating ambient temperature [TU] -40 °C ... +71 °C (UL: max. 50 °C)
Humidity in operation 20 – 95 % RH
Storage temperature [TU] -40 °C ... +85 °C
Terminal connections
- 2 x output voltage 24 V, negative output
terminal (internally connected)
+ 2 x output voltage 24 V, positive output
terminal (internally connected)
OK DC OK output (open collector output)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
g (PE) PE (Ground), always connect
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 24-2.5
www.wieland-electric.com Rev.: 12/2014 – Page 2 of 2
wipos P1 24-5
wipos P1 24-5
Switching power supply
24 V DC / 5 A
81.000.6130.0
Block diagram
Dimensional diagram
Technical data
wipos P1 24-5 Part number: 81.000.6130.0
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Typ: wipos P1 24-5
www.wieland-electric.com Rev.: 12/2014 – Page 1 of 2
wipos P1 24-5
Technical data
wipos P1 24-5 Part number: 81.000.6130.0
Rated input voltage AC [UIN_AC] 115 V AC (90 ... 132 V) auto select
230 V AC (180 ... 264 V) auto select
Line frequency AC 47 – 63 Hz
Power factor correction filter (PFC) yes (0.7)
Rated input voltage DC [UIN_DC] 210 – 375 V DC
Rated input current 115 V / 230 V 2.8 A / 1.4 A
Inrush current 115 V AC / 230 V AC 24 A / 48 A max.
Input fuse T3.15 A / 250 V (internal)
Hold up time (at ION) UI_AC = 115 V > 25 ms
UI_AC = 230 V > 30 ms
Operating ambient temperature [TU] -35 °C ... +71 °C (UL: max. 50 °C)
Humidity in operation 20 – 95 % RH
Storage temperature [TU] -35 °C ... +85 °C
Terminal connections
- 2 x output voltage 24 V, negative output
terminal (internally connected)
+ 2 x output voltage 24 V, positive output
terminal (internally connected)
OK 2 x relay (normally closed)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
g (PE) PE (Ground), always connect
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Typ: wipos P1 24-5
www.wieland-electric.com Rev.: 12/2014 – Page 2 of 2
wipos P1 24-10
wipos P1 24-10
Switching power supply
24 V DC / 10 A
81.000.6140.0
Block diagram
Dimensional diagram
Technical data
wipos P1 24-10 Part number: 81.000.6140.0
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 24-10
www.wieland-electric.com Rev.: 12/2014 – Page 1 of 2
wipos P1 24-10
Technical data
wipos P1 24-10 Part number: 81.000.6140.0
Operating ambient temperature [TU] -40 °C ... +71 °C (UL: max. 50 °C)
Humidity in operation 20 – 95 % RH
Storage temperature [TU] -40 °C ... +85 °C
Terminal connections
- 2 x output voltage 24 V, negative output
terminal (internally connected)
+ 2 x output voltage 24 V, positive output
terminal (internally connected)
OK 2 x relay (normally closed)
L AC: phase conductor, DC: no polarity
N AC: neutral conductor, DC: no polarity
g (PE) PE (Ground), always connect
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 24-10
www.wieland-electric.com Rev.: 12/2014 – Page 2 of 2