You are on page 1of 3

PDV/0903/2019

To : PLN

Schedule of Technical Data

Date 15-Aug-19 Rev. 0


FOR APPROVAL
Prepared

Yudi Yasti Putra


Engineer

Checked

Anggono
Supervisior

Approved

Praptono Hadi Prasetyo


Manager
Rev. : 0
NA2XSR(AL)Y
Schedule of Technical Data SPLN 43-5-3 : 1995
12/20 (24) kV

1. Conductor : Compacted Round Stranded Alumunium wire class 2


1
2. Conductor screen : Extruded bonded semi-conductive compound
2 3. Insulation : Extruded XLPE

4. Insulation screen : Extruded strippable semi-conductive compound


3
5. Water Blocking : Helically Overlapped Semiconductive Water Blocking Tape
4 6. Metallic screen : Plain Anneled Copper wire and Tape

7. Water Blocking : Helically Overlapped Semiconductive Water Blocking Tape


5
8. Bedding : Extruded PVC (Black Colour)
6 9. Armour : Aluminium Wire

10. Outer Sheath : Extruded PVC (Red Colour)


7

10
Marking by Embossed (example) :

SPLN 43 JEMBO CABLE NA2XSR(AL)Y 1 x 300 CM/25 12/20 (24) kV "Year" "Length Marking"
Length Marking by Ink Jet Printing with interval every 1 meter

CONSTRUCTION `

Conductor Insulation Inner Sheath Armour Outer Sheath Approx. Approx. Standard

Item Number Nominal Size No.of shape Approx. Thickness Thickness Diameter Thickness OD Cable Length

wire dia. Nominal Nominal Nominal Nominal of Cable Weight per drum

sqmm mm - mm mm mm mm mm mm kg/km m

DNA2XRY00130020S 1 x 300 35 cm 20,28 5,5 1,3 2,50 3,0 51,0 3140 500

cm : Compacted Round Stranded

Tolerance of overall diameter : OD ≤ 20 mm : ± 1.0 mm, OD ≤ 40 mm : ± 2 mm, OD > 40 mm : ± 5%

CHARACTERISTICS

Max. Max. Min. AC Max. Short

Partial
DC Conductor AC Conductor Insulation Voltage circuit current
Item Number Nominal Size Discharge

Resistance at Resistance at
Resistance at 20°C Test at 1.73 Uo at 1 Sec
90°C 20°C

sqmm Ohm/km Ohm/km M Ohm km kV / 5 min. pC kA

DNA2XRY00130020S 1 x 300 0,10 0,1297 5.000 42,0 10 27,49

- Minimum bending radius : 20 x OD cable

- Standard packing : wooden drum

Current carrying capacity

Buried Direct In Ground In single -way ducts In Air

Flat Touching
Trefoil Flat Spaced Trefoil ducts Trefoil Flat Touching Flat Spaced
Ducts

Item Number Size

A A A A A A A

DNA2XRY00130020S 1 x 300 414 419 397 402 577 586 677

Maximum conductor temperature 90 ºC Depth of laying 0.8 m


Ambient air temperature 30 ºC Thermal resistivity of soil 1.5 K.m/W
Ground temperature 20 ºC Thermal resistivity of earthenware ducts 1.2 K.m/W

- Maximum permissible continuous conductor temperature : 90ºC


- Maximum short time over load temperature : 130ºC
- Maximum short circuit conductor temperature : 250ºC
Rev. : 0

NA2XSY
Schedule of Technical Data SPLN 43-5-3 : 1995
12/20 (24) kV

1. Conductor : Compacted Round Stranded Alumunium wire class 2


1 2. Conductor screen : Extruded bonded semi-conductive compound
3. Insulation : Extruded XLPE
2
4. Insulation screen : Extruded strippable semi-conductive compound
3 5. Water Blocking : Helically Overlapped Semiconductive Water Blocking Tape
6. Metallic screen : Plain Anneled Copper wire and Tape
4
7. Water Blocking : Helically Overlapped Semiconductive Water Blocking Tape

5 8. Outer Sheath : Extruded PVC (Red Colour)

7
Marking by Embossed (example) :
8 SPLN 43 JEMBO CABLE NA2XSY 1 x 300 CM/25 12/20 (24) kV "Year" "Length Marking"
Length Marking by Ink Jet Printing with interval every 1 meter

CONSTRUCTION
Conductor Insulation Outer Sheath Approx. Approx. Standard
Nominal Size No.of shape Approx. Thickness Thickness OD Cable Length
Item Number
wire dia. Nominal Nominal of Cable Weight per drum
sqmm mm - mm mm mm mm kg/km m

DN2XTY000130020I 1 x 300 35 cm 20,28 5,5 3,0 43,4 2160 1000

cm : Compacted Round Stranded


Tolerance of overall diameter : OD ≤ 20 mm : ± 1.0 mm, OD ≤ 40 mm : ± 2 mm, OD > 40 mm : ± 5%

CHARACTERISTICS
Max. Max. Min. AC Max. Short
Partial
Nominal Size DC Conductor AC Conductor Insulation Voltage circuit current
Discharge
Item Number
Resistance at Resistance at
Resistance at 20°C Test at 1.73 Uo at 1 Sec
90°C 20°C
sqmm Ohm/km Ohm/km M Ohm km kV / 5 min. pC kA
DN2XTY000130020I 1 x 300 0,1 0,1297 5.000 42,0 10 27,49

- Minimum bending radius : 20 x OD cable


- Standard packing : wooden drum

Current carrying capacity


Buried Direct In Ground In single -way ducts In Air
Flat Touching
Trefoil Flat Spaced Trefoil ducts Trefoil Flat Touching Flat Spaced
Ducts

Item Number Size

A A A A A A A
DN2XTY000130020I 1 x 300 414 419 397 402 577 586 677

Maximum conductor temperature 90 ºC Depth of laying 0.8 m


Ambient air temperature 30 ºC Thermal resistivity of soil 1.5 K.m/W
Ground temperature 20 ºC Thermal resistivity of earthenware ducts 1.2 K.m/W

- Maximum permissible continuous conductor temperature : 90ºC


- Maximum short time over load temperature : 130ºC
- Maximum short circuit conductor temperature : 250ºC

You might also like