You are on page 1of 4

Mccb utama

KHA ?

Mccb 1 mccb 2

KHA ? KHA ?

KHA ? KHA ?

Auto Star Lilit


trafo delta

75 HP 125 HP 150 HP

V = 0,7 KV V= 0,7 KV V= 0,7 KV

EFF = 80% EFF = 80% EFF = 80%

COS= 0.85 COS= 0.85 COS= 0.85

Hitunglah : KHA pada MCCB utama ?

Keterangan 1 HP = 746
Penyelesaian :

MCCB 1 :

a. Motor autotrafo

Eff = Pout / Pin

Pin = Pout / eff


= 55.950 / 0.8 = 69.937,5 kW
 69.937,5 / 0.85 = 82.279 kVA

IFL = 82.279 / 3 x 0.7 = 67.862,5 A

Fn = 200% x IFL

= 200% x 67.862,5

= 135.725 A

MCCB yang digunakan 1600 A

Dengan setting = 135.725 A /160 = 0.84

KHA = 125% x IFL

= 125% x 67.862,5 A = 84.828 A

Luas penampang : 6 mm2 NYY

b. Motor star-delta

Eff = Pout / Pin

Pin = Pout / eff


= 93.250 / 0.8 = 116.562,5 kW
 116.562,5 / 0.85 = 137.132 kVA

IFL = 137.132 / 3 x 0.7 = 113.104,5 A

Fn = 250% x IFL

= 250% x 113.104,5

= 282.761 A

MCCB yang digunakan 300 A

Dengan setting = 282.761 /300 = 0.94


KHA = 125% x IFL

= 125% x 113.104,5 = 141.380 A

Luas penampang : 16 mm2 NYY

Jadi :

MCCB 1 = MCCB terbesar + IFL lainnya

= 300 + 67.862,5

= 367.862,5

 Maka MCCB yang digunakan 400 A

KHA 1 = KHA terbesar + IFL lainnya

= 141.380 + 67.862,5

= 209.242,5

 Luas penampangnya 35 mm2

MCCB 2 :

Motor lilit

Eff = Pout / Pin

Pin = Pout / eff


= 111.900 / 0.8 = 139.875kW
 139.875 / 0.85 = 164.558 kVA

IFL = 164.558 / 3 x 0.7 = 135.725 A

Fn = 150% x IFL

= 150% x 135.725

= 203.588 A

MCCB yang digunakan 250 A

Dengan setting = 203.558 A /250 = 0.81

KHA = 125% x IFL

= 125% x 135.725 A = 169.656 A


Luas penampang : 25 mm2 NYY

MCCB utama :
 MCCB utama = mccb terbesar + IFL lainnya
= 400 A + 135.725
= 535.725 A

MCCB yang digunakan : 630 A

 KHA MCCB utama = KHA terbesar + IFL lainnya


= 209.242,5 + 135.725
= 344.967,5
Luas penampangnya : 70 mm2 NYY

You might also like