Professional Documents
Culture Documents
dseGenset
dse6110/20
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO START & AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
CONTROL MODULES EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
6 4 3
DEUTZ
DSE6110/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) DC OUTPUTS GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING ALTERNATOR OUTPUTS ENGINES OR
DSE6120 ONLY (Flexible with CAN) MAGNETIC PICK-UP
ISSUE 2
®
DSEGenset
DSE6110/20
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
2 A DC at supply voltage
OUTPUT B (START)
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
KEY FEATURES • Current Monitoring and protection • Multiple engine parameters are MAGNETIC PICK UP
• Back-lit text LCD display • 3 Phase Mains (Utility) monitored simultaneously VOLTAGE RANGE
+/- 0.5 V to 70 V
• Front panel editing monitoring (DSE6120 only) • Module can be configured to
• LED and LCD alarm indication • Test button (DSE6120 only) suit individual applications FREQUENCY RANGE
• Power Save mode • Battery voltage monitoring • Compatible with a wide range 10,000 Hz (max)
• CAN and Magnetic Pick-up/Alt. • Engine pre-heat of CAN engines DIMENSIONS
versions available (specify on • Hours counter • Tier 4 engine support OVERALL
ordering) • Comprehensive shutdown or • Uses DSE Configuration Suite 215 mm x 158 mm x 42 mm
8.5” x 6.2” x 1.6”
• PC and front panel warning on fault condition PC software for simplified
configuration configuration PANEL CUT-OUT
• 6 Digital inputs KEY BENEFITS • IP65 rating (with optional 182 mm x 137 mm
7.2” x 5.4”
• 3 Analogue inputs • Automatically transfers between gasket) offers increased
• 6 Outputs (4 configurable on mains (utility) and generator resistance to water ingress MAXIMUM PANEL THICKNESS
Magnetic Pick-up/Alt., 6 power (DSE6120 only) • Licence-free PC software 8 mm
0.3”
configurable on CAN version) • Hours counter provides accurate
• Configurable timers and alarms information for monitoring and STORAGE TEMPERATURE RANGE
• Alternative configuration maintenance periods -40 oC to +85 oC
• Event Log (10) • User-friendly set-up and button
• Remote Start input layout
• 3 Phase generator monitoring
RELATED MATERIALS
TITLE PART NO’S
DSE6110 Installation Instructions 053-059
DSE6120 Installation Instructions 053-060
DSE6100 Quick Start Guide 057-102
DSE6100 Operator Manual 057-095
DSE6100 Configuration Suite PC Manual 057-096
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-069/01/16 (5)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457