Professional Documents
Culture Documents
Keywords: net-zero energy building, U.S. electrical grid, U.S. climate zones, grid-tied
photovoltaic generation, electrical energy storage
2 Methodology 2.1 U.S. Electric Power Demand Curve. U.S. Energy Infor-
To estimate electricity demand profiles and evaluate potential mation Administration (EIA) provides hourly electrical system
aggregate effects of large-scale NZEB implementations nation- operating data from all balancing authorities, including actual
ally, a simplified method is proposed and performed as described electricity demand, day-ahead electricity demand forecast, system
in this section. The detailed steps are depicted in Fig. 1. ENERGY- electricity net-generation, and system total electricity interchange
PLUS prototype office buildings [19], modeled based on ASHRAE (energy flow) [21]. The electrical system operating data (EIA-930
Standard 90.1-2013, are selected and simulated using 14 U.S. Data) is estimated based on the physical flow of electricity
climate weather files to determine electricity consumption of each metered at the grid-tied boundaries between electrical systems in
conventional office building. Then two different strategies are several different sectors (e.g., residential, commercial, industrial,
adopted to enable NZEB balances with a net-metering option to and transportation) [22]. Aggregate hourly electricity demand
the electrical grid, including only PV power generation (case 1), reflects 13 available regions (i.e., Northwest, California, South-
and PV power generation with electrical energy storage (EES) west, Central, Midwest, Texas, Tennessee, Southeast, Florida,
(case 2). Carolinas, Mid-Atlantic, New York, and New England ISO) in the
After reaching NZEB balances, a comparative study is per- U.S. lower 48 states [21,22].
formed to calculate net-purchased electricity from the electrical Figure 2 presents the U.S. hourly electricity demand for each
grid, and net-sold electricity that can be fed back to the electrical representative day on the U.S. electrical grid. Three days in 2017
grid. Finally, the weighted number of national office buildings is (August 22, January 6, and April 28) are selected to represent typ-
calculated based on detailed construction weights by the U.S. ical seasonal conditions (summer, winter, and transition), which
climate zones and building types [20], developed by Pacific are chosen based on the highest daily electricity usage during
Northwest National Laboratory (PNNL). This building number is each seasonal month. These profiles of the actual aggregate U.S.
used in developing a weighted national electricity demand esti- electricity demand are used as a base to calculate the simulated
mate for the potential aggregate impact of wide-scale NZEB U.S. net-electricity demand profiles in terms of NZEB
implementations on the U.S. electrical grid. To reflect the implementations.
adoption of NZEBs in the future, this study also examines three
scenarios with 20%, 50%, and 100% of the U.S. office building 2.2 U.S. Climate Zones and Construction Weights. Office
stock that are composed of NZEBs. The three scenarios are building models are placed in 14 different climate zones repre-
selected to show the contribution of NZEBs to the national elec- senting all the U.S. climates. The climate zones are classified
tricity demand in different NZEB goals by the state and federal from one to eight climates, based on the range of climate parame-
governments. ters, such as heating degree days and cooling degree days [23,24].
In order to compare only electricity demand profiles, in this Then the climate zones are separated into moist (A), dry (B), and
study, the natural gas consumption used to provide central heating marine (C) regions by considering regional weather conditions
in an office building is not considered. Although there are many (e.g., mean temperature of coldest/warmest month and annual
different types of commercial buildings, such as standalone retail, precipitation) [24].
Table 1 Construction weights and the number of medium office buildings in the U.S. climate location
Climate zone City (weather file) Construction weights (%) 100% 50% 20%
For this analysis, specific climate locations (cities) are selected 5.6 106 commercial buildings in the United States surveyed in
as a representative of each climate zone as shown in Table 1. The 2012 [26]. Based on the surveyed number of the U.S. commercial
impact of electric energy savings potential on a national scale is buildings CBECS provides, the weighted number of office build-
estimated using the concept of “construction weights” developed ings is estimated by multiplying construction weights to further
by PNNL [25]. The construction weights are defined by the conduct a comparative analysis in each climate zone.
weighting factors of the total construction floor area assigned by
climate locations for category of building types (e.g., large office
and hospital) in a national scale. National weights for the U.S. 2.3 Net-Zero Energy Building Model. The Department of
commercial building construction are developed based on the U.S. Energy (DOE)’s flagship building energy modeling software,
EIA’s Commercial Building Energy Consumption Survey ENERGYPLUS version 8.6, is used to model office buildings. DOE
(CBECS) and the McGraw-Hill Construction Projects Stars Data- provides three different types of office building models (e.g.,
base (MHC) by mapping MHC data to CBECS building types small, medium, and large office models) in commercial buildings.
[25]. Table 1 lists the construction weights assigned to an office Total U.S. construction weighting factors of 5.61%, 6.04%, and
building in the commercial building stock in all the 14 U.S. 3.33% are used for small, medium, and large office models,
climate zones. Each construction weighting factor varies for office respectively. The prototype medium office models shown in
buildings within the 14 U.S. climate locations. For example, Fig. 3 [19], developed by DOE and PNNL, are used to estimate
the highest weighting factor is 1.19% for Baltimore, MD (climate electrical energy variations of office buildings due to the highest
4A). The lowest weighting factor is 0.03% for Duluth, MN (cli- construction weights within office building types.
mate 7). The prototype medium office models for each of the 14 climate
Table 1 also shows the weighted number of the U.S. office zones comply with the minimum energy code requirements pre-
buildings by three scenarios (i.e., 100%, 50%, and 20% of the scribed in ASHRAE Standard 90.1-2013 [27]. Each office model
U.S. NZEB stocks). U.S. EIA’s Commercial Building Energy has a rectangular floor plan and a total floor area of 4982 m2
Consumption Survey (CBECS) estimated that there were about (53,626 ft2). Each floor has five thermal zones, including four
Fig. 4 PV row spacing calculation for fixed roof-mounted and ground-mounted panels
perimeter zones and one core zone with a 33% window-to-wall frac- back-surface integration modes (e.g., decupled and integrated
tion as shown in Figs. 3(a) and 3(b). Its envelope uses steel-framed surfaces) to determine PV power operating temperature. In this
constructions for exterior walls and insulation entirely above deck study, the integrated surface outside face mode is used to calculate
for a flat roof, as well as the slab-on-grade for floors [28,29]. For a PV cell temperature, reflecting ambient conditions, and PV panel
heating, ventilation, and air conditioning (HVAC) system, a rooftop surfaces [33]. Figure 4 illustrates fixed roof-mounted and ground-
unit system with variable air volume electric reheat coils is used in mounted PV panels.
the office model. This system is the electrical air conditioning sys- Although PV systems require the greatest possible radiation to
tem that varies supply air volume flow rates through an air handing maximize electric power generation through ideal array orienta-
unit with dampers located in a variable air volume terminal box to tion, it is not practical in general to achieve the maximum power
meet the required set-point temperature [30]. generation from PV because of building designs and locations. A
Input values for this building energy modeling are directly fixed tilt angle of 15 deg is used for all simulation models in each
taken from the original version of the prototype office model with- of the 14 different climate zones. For the flat roof instance, 70%
out modifications. Although most of the input values, such as of the roof area is assumed to be available for PV installation
building geometry and internal heat gains, are the same for each [36]. PV spacing between rows of PV modules can be calculated
of the 14 climate zones, some changes occur depending on system based on a site location, PV panel height and tilt angle, and inter
capacities and envelope requirements that vary with climate row spacing while avoiding a shading effect on winter solstice
conditions, including outdoor air ventilation, supply air flow rates, [37]. Figure 4 depicts detailed calculation of the PV row spacing
U-values, and solar heat gain coefficients [19]. between PV panels. The manufactured PV panel, LG230M1C
[38], is used for input parameters of the equivalent one-diode
2.3.1 Distributed Photovoltaic Power Generation. Since a model in ENERGYPLUS listed in Table 2.
solar PV system is one of the most common types of distributed Based on the calculated PV row spacing, the maximum PV area
power systems integrated to buildings [31,32], a PV system is on the roof of the simulated office model is about 1114 m2
used to enable NZEB balances in the U.S. climate zones for this (11,991 ft2), which is about 67% of the entire roof area of 1661 m2
study. In consideration of net-metering available within the elec- (17,879 ft2). Table 3 shows the number of PV panels on the roof
trical grid-level, a PV power generation system in ENERGYPLUS is and parking areas. In order to achieve net-zero performance, the
modeled to allow feeding the excess on-site electricity produced number of PV panels required on roof areas is obtained by match-
by PV power panels [33]. ing the annual electric energy usage to the annual on-site electric-
The equivalent one-diode model that ENERGYPLUS offers is used ity generation. In addition to the PV panels installed on roof areas,
to predict the on-site electricity generation. This model employs additional PV panels are used on parking areas until each simu-
equations for an empirical equivalent circuit model to determine lated NZEB shows satisfactory annual NZEB balances. Table 3
the current–voltage characteristics of a single module [30]. This also presents the total number of PV panels and maximum power
model also uses empirical relationships to predict PV operating output needed to achieve NZEBs for each climate zone.
performance depending on environmental variables, such as PV
cell temperature and shading effects. Since the cell temperature of 2.3.2 Photovoltaic Inverter Systems and the Grid-Connection
PV panels is one of the important factors for performance of elec- Model. The electric power generation of arrayed PV systems to
trical outputs [34,35], ENERGYPLUS provides several options of PV the grid-connection heavily depends on the performance of
Table 3 The number of PV panels and total maximum power outputs of PV systems installed
for NZEBs
Climate zone Roof Parking Total maximum power output (kWp; STC)
With hourly calculated net-electricity difference profiles, the and sold electricity profiles can be reduced, resulting in significant
potential aggregate impact of NZEB implementations on the U.S. changes in the trends of the hourly net-electricity difference pro-
electrical grid is calculated as files between cases 1 and 2. In addition, Fig. 6(b) depicts the status
of hourly charging and discharging electricity through the EES.
EU:S:Net ¼ EU:S:TotalDemand DENet (2) Such trends of net-electricity difference profiles are further con-
sidered in order to estimate hourly variations of net-electricity
where EU:S:TotalDemand is the actual U.S. aggregate electricity demand demand values on a national scale.
for available U.S. regions in terms of all sectors (e.g., residential,
commercial, industrial, and transportation), as shown in Fig. 2.
DENet indicates the net-electricity differences for NZEBs on a 3 Results and Discussion
national scale. This section presents and discusses the simulated results of
Figure 6 also shows variations of hourly net-electricity differ- office NZEB models on a national scale and potential aggregate
ence profiles of two NZEB cases: only PV (case 1) and PV þ EES effects on the U.S. electrical grid. First, the electric energy use
(case2). In this figure, imported (purchased) electricity from the intensities (EUIs) of the prototype office models are compared to
electrical grid is reduced once the electrical output of the PV sys- the published office building EUIs. NZEB performance of each
tems kicks on. It is also seen how, during the daytime, the excess NZEB case in the U.S. climate zones is then explained. Next, net-
generated electricity is fed to the electrical grid when the on-site electricity differences of NZEBs on a national scale in terms of
electricity generation is higher than the electricity needed. When 100% of the U.S. NZEB stock for three representative seasonal
the EES is considered within NZEBs, the peak of the purchased days (i.e., winter, transition, and summer), calculated by Eq. (1),
Fig. 9 Simulated electricity demand profiles on a national scale for the representative
summer day: (a) only PV and (b) PV 1 EES
investigate potential aggregate impacts of NZEBs with the electri- NZEBs is of difference from that of the baseline model. This is
cal grid on a national scale. mainly because the electricity end-use of NZEBs includes elec-
tricity conversion losses through PV inverters and net-metering on
3.3 Net-Difference Electricity Variations of Net-Zero the electrical grid. In addition, when PV systems are added for
Energy Buildings. Combining electric energy consumption used NZEBs, there are several effects on the interior heating load
in buildings and on-site generation produced by PV systems yields caused by shading on building’s roof and added inverters and the
the net-purchased and net-sold electricity demand profiles in terms EES systems that cause thermal losses inside buildings. PV power
of 100% of the U.S. NZEB stock for three seasonal days, as systems produce maximum on-site power generation, about
shown in Figs. 9–11. These figures demonstrate that simulated 70,490 MW at 11:00 a.m. on the representative summer day. As
electricity demand profiles vary by time of day and by NZEB expected, maximum PV generation does not coincide with the
strategies. For example, the range of the simulated peak electricity peak electricity demand used in buildings mainly due to a peak
demand is around 12:00 to 3:00 p.m. on the selected summer day time of solar radiation. Daily national electricity end-use is about
and around 8:00 to 9:00 a.m. on the selected winter day. 630,797 MWh/day, and daily national on-site generation is about
547,008 MWh/day, which covers about 86% of total daily elec-
3.3.1 Simulated Electricity Demand Profiles for the Represen- tricity usage on the summer day under the 100% NZEB stock sce-
tative Summer Day. Figures 9(a) and 9(b) show simulated elec- nario. Total daily net-difference electricity for 100% NZEB stock
tricity demand profiles when PV power systems are added for is about 537,010 MWh/day.
NZEBs with and without the EES, respectively. Electricity end- Unlike NZEBs, all electric energy end-uses employed within
use profiles for both baseline and NZEB models are estimated baseline building models are directly purchased from the electri-
based on all electrical facilities, such as lights, equipment, a cal grid facility since there is no on-site power generation in base-
domestic hot water system, and HVAC (i.e., cooling coil, reheat line buildings. With annual NZEB balances, the net-purchased
coil, and fan) in simulated office buildings. electricity from the electrical grid is estimated based on electricity
With electricity end-use profiles, the peak electricity demand end-use and on-site PV generation as mentioned in Fig. 6. As seen
includes about 47,751 MW and 51,988 MW at 3:00 p.m. for base- in Fig. 9, the net-purchased electricity for NZEBs starts to reduce
line and NZEB models on a national scale as illustrated in Fig. 9. when PV systems produce the on-site electricity after around
As seen in Figs. 9(a) and 9(b), the electric energy end-use of 6:00 a.m. It indicates that the utility purchased peak demand
from the electrical grid is significantly reduced and flattened by zones on a top-floor in the beginning of HVAC system start up for
on-site PV power generation installed in NZEBs. In addition, the a heating day.
excess generated electricity is then fed to the electrical grid PV power systems within NZEBs generate maximum output at
when on-site power generation is higher than the electric energy 12:00 p.m., about 50,826 MW. Daily electricity end-use of the
consumption used within office buildings during daytime. Simu- baseline is about 587,583 MWh/day, and daily on-site PV genera-
lated daily electricity fed back to the electrical grid includes tion is about 298,697 MWh/day, which covers about 50% of total
about 131,450 MWh/day on the representative summer day. As daily electricity usage for the selected winter day. In addition,
expected, net-purchased and net-sold electricity demand profiles Fig. 10(a) represents the simulated net-purchased and net-sold
show flattened patterns by decreasing electrical flows from and to electricity demand profiles. Simulated daily electricity fed back
the electrical grid, when the operation of the EES is considered into the electrical grid is about 81,575 MWh/day. Total daily net-
within NZEBs on the electrical grid as shown in Fig. 9(b). difference electricity is about 294,242 MWh/day during the
Figure 9(b) also represents the status of EES electricity charging selected winter day under 100% NZEB stock. Using the EES, net-
and discharging during the daytime and the evening, respectively. purchased and net-sold electricity demand profiles can be appa-
rently reduced and flattened as shown in Fig. 10(b).
3.3.2 Simulated Electricity Demand Profiles for the Represen-
tative Winter Day. Figures 10(a) and 10(b) show simulated elec- 3.3.3 Simulated Electricity Demand Profiles for the Represen-
tricity demand profiles in case of the selected winter day for the tative Transition Day. Figures 11(a) and 11(b) show each simu-
baseline versus NZEB models with and without the EES, respec- lated electricity demand profile on the transition day, April 28. As
tively. On January 6, the peak electricity end-use includes about seen in this figure, the hourly pattern of electricity end-use is rela-
40,950 MW at 8:00 a.m. in baseline models. However, there is a tively in a slimier fashion of the summer day pattern, but amount
slight difference between baseline and NZEB models, turning out of daily electricity end-use is lower than other two representative
that NZEBs represent the peak electricity end-use which is about days. Daily electricity end-use of the baseline results in about
41,836 MW at 7:00 a.m. This result is mainly expected that most 489,522 MWh/day, including about 35,564 MW at 3:00 p.m. at a
of the roof areas are shaded by PV panels from sunrise, bringing peak point. However, daily on-site PV generation includes about
about increases of heating electric energy consumption for several 538,690 MWh/day, which is a relatively high on-site PV
generation when compared to other two representative days. Daily as well as net-sold electricity from simulated NZEBs to the elec-
on-site PV generation covers about 100% of daily electricity end- trical grid on a national scale.
use for both NZEBs with and without the EES. Total daily net-
difference electricity between baseline and NZEB models under 3.4.1 Potential Aggregate Impacts on the U.S. Electricity
100% NZEB stock is about 534,461 MWh/day in the transition Demand Profiles for the Representative Summer Day. The peak
day. Figure 11(b) also illustrates similarly how the EES can demand of the actual U.S. electricity at about 2:00 p.m. on Aug.
reduce and flatten net-purchased and net-sold electricity demand 22, 2017, appears to be about 670,229 MW, which reflects all sec-
profiles when compared to only PV power generation. These tors (i.e., residential, commercial, industrial, and transportation).
simulated electricity demand profiles, provided in Figs. 9–11, are The actual daily U.S. electricity demand includes about
further employed to estimate the U.S. net-electricity demand val- 13,308,722 MWh/day during the selected summer day as shown
ues and compare to the actual U.S electricity demand values. in Fig. 2. Figure 12 also illustrates simulated net-electricity
demand resulting from three NZEB scenarios. As expected, sig-
nificant penetration of NZEBs could potentially influence U.S.
3.4 Potential Aggregate Impacts on the U.S. Electricity electricity demand patterns by exporting the on-site electricity
Demand Profiles. Since a large introduction of NZEBs increases generation during daytime. The peak electricity demand of the
the on-site electricity generation and influences different electric- U.S. net-electricity includes about 623,256 MW at 5:00 p.m.,
ity trade patterns and prices with a grid-tied electrical system [17], 640,325 MW at 3:00 p.m., and 657,817 MW at 2:00 p.m. for
potential aggregate impacts of extensive NZEBs on a national 100%, 50%, and 20% NZEB stock scenarios, respectively.
electrical gird-level are evaluated and discussed in this section. With a comparison between the actual U.S. electricity and the
Figures 12–14 illustrate the actual U.S. electricity demand pro- simulated net-electricity demand values at a maximum point
files by comparing with the simulated net-electricity demand pro- (11:00 a.m.) on the selected summer day, the percentage differen-
files regarding the adoption of 20%, 50%, and 100% NZEB stock ces show 10.7% (69,190 MW), 5.4% (34,595 MW), and 2.1%
scenarios. Each scenario indicates the different number of office (13,838 MW) for 100%, 50%, and 20% NZEB stocks, respec-
building stocks, expected to be NZEBs when closing to the net- tively. In contrast, for NZEBs with the EES, peak percentage dif-
zero target that EISA 2007 specifies. In these figures, each sce- ferences are flattened throughout daytime. It turns out that the
nario demand line represents the net-electricity demand, equal to peak difference point between the actual U.S. electricity and
total actual U.S. electricity demand minus weighted differences simulated net-electricity is reduced, including 8.6% (57,535 MW),
between simulated electricity end-uses used in conventional office 4.3% (28,767 MW), and 1.7% (11,507 MW) for each NZEB stock,
buildings and simulated net-purchased electricity used in NZEBs, respectively.
3.4.2 Potential Aggregate Impacts on the U.S. Electricity percentage differences peak in the middle of the day when solar
Demand Profiles for the Representative Winter Day. On the repre- radiation is at its highest (11 a.m.), with 15.2% (73,290 MW),
sentative winter day, Fig. 13 shows increasingly curtailed curves 7.6% (36,645 MW), and 3.0% (14,658 MW) for 100%, 50%, and
of simulated U.S. net-electricity demand for each NZEB stock 20% NZEB scenarios, respectively, provided in Fig. 14(a).
when compared to the actual U.S. electricity demand during day- Figure 14(b) illustrates how added EES can shift peak demand
time. As seen in this figure, the actual peak U.S. electricity to flatten curve shapes and reduce curtailment during the daytime.
demand includes about 575,980 MW at 4:00 p.m., and daily U.S. When the EES is added within NZEBs, peak percentage differen-
electricity demand includes about 12,808,651 MWh/day. Compar- ces of the U.S. net-electricity could potentially be shifted to 12:00
ing each simulated net-electricity demand curve on the summer p.m. and reduced to 13.3% (35,461 MW), 6.7% (17,730 MW), and
day, we observe that peak demand is significantly reduced and 2.7% (7,092 MW), respectively, in each U.S. NZEB stock sce-
shifted to the earlier morning and the late afternoon of the day. nario. Using a combination of the EES within NZEBs can effec-
Simulated net-electricity demand curves, provided in Fig. 13, tively reduce significant changes in the U.S. electricity demand
show that the percentage differences of the simulated U.S. net- curves during the daytime and offer appropriate ways to use on-
electricity demand are 9.3% (50,328 MW), 4.7% (25,164 MW), site generated electricity during the evening, thereby decreasing
and 1.9% (10,066 MW) for three NZEB scenarios, respectively, at the surplus electricity to the U.S. electrical grid.
a maximum point (12 p.m.). However, with the EES, the peak dif-
ference point is shifted to 2 p.m., including 6.3% (34,932 MW),
3.1% (17,466 MW), and 1.3% (6,986 MW) for three NZEB stock 4 Conclusion
scenarios, respectively.
This paper evaluates potential aggregate impacts of a large-
3.4.3 Potential Aggregate Impacts on the U.S. Electricity scale implementation of NZEBs on the national electrical grid in a
Demand Profiles for the Representative Transition Day. Figure 14 simulation-based analysis. Simulated NZEB models are enabled
shows the simulated U.S. net-electricity demand curves on the using on-site PV power generation that equals to annual electricity
representative transition day, April 28. It indicates that the actual consumption used in office buildings. To allow feeding the excess
daily U.S. electricity demand is about 10,400,551 MWh/day, PV power generation from NZEBs to the electrical grid,
which is the lowest value when compared to the summer and the net-metering operation is available with and without the EES.
winter days. From the compared results of peak percentage differ- With the weighted number of national office buildings, aggregate
ences between the actual U.S. electricity and the simulated net- U.S. net-electricity demand profiles are estimated and compared
electricity demand on a national scale, it is observed that to the actual U.S. electricity demand profiles on three seasonal
representative days in terms of three scenarios. We assume that building stock is expected to be NZEBs. Daily on-site PV
20%, 50%, and 100% of the U.S. office building stock is expected power generation could cover around 50–100% of total daily
to be NZEBs for three scenarios in coming decades. Results from electricity usages consumed in office buildings depending on
this study indicate that an implementation of NZEBs could poten- weather conditions. The PV power generation within NZEBs
tially affect the current U.S. electricity demand patterns in the could significantly increase changes in imported and
middle of the day in two ways: (1) lower purchased electricity exported electricity from and to the electrical grid during
from the electrical grid and (2) increased surplus power generation daytime. However, the EES with distributed PV systems
by PV systems from office NZEBs to the electrical grid. The key could help reduce the peak net-electricity difference during
findings from this study are as follows: the daytime and use stored electricity later in the evening.
Peak percentage differences of national electricity demand
Simulated NZEB models show around 94–132 kWh/m2 yr of between the actual U.S. electricity demand and the simulated
annual electricity usages, which is lower than the median net-electricity demand vary depending on the NZEB stock
value of the actual building EUI data throughout U.S. climate scenarios and time of the selected day. On the representative
locations. Simulated results also indicate that the use of summer day, the peak differences from the actual U.S. elec-
the EES within NZEB models shows the relatively high tricity demand profile show 10.7%, 5.4%, and 2.1% at 11:00
power conversion losses, mainly due to the flow net- a.m. for 100%, 50%, and 20% of the U.S. NZEB stocks,
efficiency of the EES model during EES operation. Annual respectively. In consideration of the EES within NZEBs, the
PV power conversion losses without the EES include about peak differences are reduced and shifted to 1:00 p.m., includ-
37,227–48,983 kWh/yr, which varies according to the ing 8.6%, 4.3%, and 1.7% for each U.S. NZEB stock,
amount of PV power generation through inverters and net- respectively.
metering. When the impact of the EES with NZEBs on the On the representative winter day, the peak point of the actual
electrical grid is considered, annual power conversion losses U.S. electricity demand is reduced and shifted to the begin-
increase around 30–38% when compared to NZEBs without ning and late afternoon. NZEBs tend to create the significant
the EES. curtailment of the actual U.S. electricity demand profile, typ-
On a national scale, simulated daily electricity usages ically during the middle of the winter day. The percentage
include about 630,797 MWh/day, 587,583 MWh/day, and differences at a maximum point (12:00 p.m.) are 9.3%, 4.7%,
489,522 MWh/day for representative summer, winter, and and 1.9% for three U.S. NZEB stock scenarios, respectively.
transition days, respectively, when 100% of the U.S. office As expected, using the EES on the winter day could reduce