From the Table 4-2: Quantity of Sewage Flow in Plumbing Design and Estimate by Max
B. Fajardo Jr.
60 gallons per day per person – for Multiple Family dwellings (Apartment)
We adjust the number of occupants and added two more for visitor.
𝑔𝑎𝑙𝑙𝑜𝑛𝑠
Where :Q = daily sewage flow in gallons = 60 (30 person) = 1800 gallons
𝑝𝑒𝑟𝑠𝑜𝑛
1𝑚3
By conversion : (1m3 = 264 gallons) ; V = 1441.125 gallons ( 264 𝑔𝑎𝑙𝑙𝑜𝑛𝑠 ) = 5.45 m3
𝑉 5.45𝑚3
V = ( L )( W )( H ) ; L = = = 2.42 m
𝑊(𝐻) 1.5𝑚(1.5𝑚)
Specification:
L fy 2400mm 276MPa
t = 20 [0.4 + 700] = [0.4 + ] = 95.31 mm say 100mm
20 700
Computation of loads ;
Live load (WLL) ∶ WLL = (LiveLoad)(1m) = (2.4 KN⁄m2 )(1m) = 2.4 KN⁄m
Wu L² 6.185kN/m (2.4m)²
Ultimate Moment : Mu = = = 4.45 kN-m
8 8
1
d = t − cover − (ɸBAR ) = 100mm − 20mm − 6mm = 74mm
2
Design of Reinforcement
Mu (4.45x106 )N. mm
R𝑛 = = = 0.903 MPa
ɸbd2 (0.90)(1000mm)(74𝑚𝑚)2
1.4 1.4
ρmin = = = 0.00507 ; ρ < ρmin = thus use ρmin
fy 276
AS 375.18mm2
N = = 113.10mm2 = 3.317 say 4pcs
Ab
Ab 113.10mm2
Spacing of bars (S) ; S = (1000mm) = (1000mm)
AS 375.18mm2
AS 200mm2
Required no. of bars (N) ; N = = = 2.546 say 3pcs.
Ab 78.54mm2
Ab 78.54mm2
Spacing of bars : S = (1000mm) = (1000mm)
AS 200mm2
a. 3h = 3 (100mm) = 300mm