N° : NCSIL1314094A 

CALCULATION NOTE  Rev : 0 
Page : 1/5 
   

 
 
 
 
 
 
 
 
RELIABILITY STUDY 
 
SIL EVALUATION 
 
 
 
 
 
 
 
 
 
 
Application field : 
  Final elements of Safety Instrumented System (SIS) as defined in AF13/14094 (SRi reference) 
 
 
Summary : 
  Calculation note for a SIL evaluation. 
 
 
 
 
 
 

This document belongs to SRi and cannot be reproduced without authorization. 
DIFFUSION : 
  Engineering department 
  Customer 
 
\\Bureau_etudes\aqbe\Notes de calcul fiabilité\Affaire\AF13‐14094\NCSIL1314094A.doc 
 
 
 
0  24/01/2014  L. MAURIANGE  C. RANQUET  C. RANQUET 
Rev  Date  Written by  Checked by  Approved by 
 
N° : NCSIL1314094A 
CALCULATION NOTE  Rev : 0 
Page : 2/5 
   

 
Rev  Date  Object  Pages 
0  24/01/2014  Original version  All 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
N° : NCSIL1314094A 
CALCULATION NOTE  Rev : 0 
Page : 3/5 
   

 
SOMMAIRE 
1  OBJECT ..................................................................................................................................................................................... 4 

2  RELATED DOCUMENTS ............................................................................................................................................................ 4 

3  SIS COMPOSITION AND RELIABILITY DATA ............................................................................................................................ 4 
3.1  BALL VALVE (FINAL ELEMENT) ..................................................................................................................................................... 4 
3.2  ACTUATION SYSTEM COMPONENTS .............................................................................................................................................. 4 
4  SIL EVALUATION ...................................................................................................................................................................... 4 
4.1  THEORY .................................................................................................................................................................................. 4 
4.2  APPLICATION ........................................................................................................................................................................... 5 
5  CONCLUSION ........................................................................................................................................................................... 5 
N° : NCSIL1314094A 
CALCULATION NOTE  Rev : 0 
Page : 4/5 
   

1 OBJECT 
This document evaluates the reliability of a final element of a Safety Instrumented System (SIS). 

2 RELATED DOCUMENTS 
1) IEC61508/61511 
2) FSP 12001‐01 Certificate for SRi Engineering ‐ A90RL Ball Valve 
3) BET 090460 C001 EXIDA SIL Certificate ‐  BETTIS CB Series actuators 
4) VER 090434 C003 EXIDA SIL Certificate ‐ VERSA Solenoid valves 
5) VER 1105071 C001, EXIDA SIL Certificate ‐ VERSA Quick Exhaust Valves 
6) 5034544‐001C, Control panel type P1A 

3 SIS COMPOSITION AND RELIABILITY DATA 
3.1 Ball valve (final element) 
The valve's failure rates are defined in Ref[2]. 
 
Normaly open valve closes in response to actuation with PVST : 
λDU, Valve = 1.90E‐7Fail/h
λDD, Valve = 5.09E‐7Fail/h
λSU, Valve = 1.91E‐6Fail/h 
λSD, Valve = 0 

 
3.2 Actuation system components 
The valve is equipped of a BETTIS type CBB actuator with control panel Ref[6]. The parts involved in the 
moving in security position are 1 VERSA CSG 3321 3/2 solenoid valve, 1 VERSA CSP 3301 3/2 pilot valve 
and 1 VERSA Quick Exhaust Valve EQ‐3‐316. The data used for the calculation are defined in Ref[3] and 
Ref[5]. 
 

4 SIL EVALUATION 
4.1 Theory 
In order to estimate the SIL of a SIS, two parameters need to be calculated : the Average Probability of 
Failure on Demand (PFDavg) and the Safe Failure Fraction (SFF). 
Ti = Test Interval = 1 year 
 
N° : NCSIL1314094A 
CALCULATION NOTE  Rev : 0 
Page : 5/5 
   

PFD
 Global  1   1  PFD u 

 u

PFD u  λ DU,u Ti for all the components



PFD Avg  PFD Global
 2  
  λ i,DU 
 
SFF  1  i   100
  λ i,Tot 
 i 
 
4.2 Application 
VERSA  BETTIS 
  SRi closed in  VERSA  VERSA 
Quick Exhaust  Actuator 
security valve  
Pilot valve  Solenoid valve Valve –    CBB 
with PVST 
CSP‐3301  CSG‐3321  QE3‐316  SR with PVST 
λDU  1.90E‐07  4.91E‐07  5.94E‐07  5.00E‐08  1.98E‐07 
λDD  5.09E‐07  0.00E+00  0.00E+00  0.00E+00  2.28E‐07 
λD  6.99E‐07  4.91E‐07  5.94E‐07  5.00E‐08  4.26E‐07 
λSU  1.91E‐06  1.67E‐06  2.35E‐06  2.27E‐07  7.58E‐07 
λSD  0.00E+00  0.00E+00  0.00E+00  0.00E+00  3.73E‐07 
λS  1.91E‐06  1.67E‐06  2.35E‐06  2.27E‐07  1.13E‐06 
λTot  2.61E‐06  2.16E‐06  2.94E‐06  2.77E‐07  1.56E‐06 
DCpvst  72.82%  0.0%  0.0%  0.0%  53.5% 
Ti  8760  8760  8760  8760  8760 
SFF  92.7%  77.3%  79.8%  81.9%  87.3% 
PFD  1.66E‐03  4.30E‐03  5.20E‐03  4.38E‐04  1.73E‐03 

PFDGlobal  1.33E‐02 

PFDAvg  6.64E‐03 

SFF  84.04% 
 
 
 

5 CONCLUSION 
The criteria which must be respected in order to reach SIL2 are: 
o PFDAvg<1E‐2 
o SFF>60%. 
 
 
The criteria are respected. Therefore, the different components, including the SRi ball valve, constitute a 
final element of SIS up to SIL2. 