The TAL alternator range is designed to meet the needs of general
applications such as prime power and stand-by.
Electrical design
● Class H insulation
● Low voltage winding:
Three phase 50 Hz: 380V - 400V - 415V - 440V / 220V - 230V - 240V
60 Hz: 380V - 416V - 440V - 480V / 220V - 208V - 240V
Single phase 50 Hz: 115V - 230V
60 Hz: 120V - 240V
● 4-terminal plates in base version (12 wire option)
● Optimized performance
Robust design
● Compact and rugged assembly to withstand engine vibrations
● Steel frame
● Aluminum flanges and shields
● Single bearing design compatible with most diesel engines
● Sealed for life single bearing
● Direction of rotation: clockwise
Available options
● 12 wires connection
● AREP & PMG (PMG not available in TAL 040)
● ULc/us
● Customized painting (machine not painted as standard)
● Space heaters
● Flying leads
● Droop kit for alternator paralleling (TAL 044 only)
● Dedicated single-phase
● Stator sensors (TAL 044 only)
● Winding 8 for 380V / 416V - 60Hz
● Winding protection for harsh environments and relative humidity greater than 95% (system 2 - 4):
derating according to the following table
50 Hz 60 Hz
Type 380 V 400 V 415 V All voltages
TAL 040 1 1 1 1
TAL 042 0.97 1 except 0.97 for TAL 042 G & H 1 except 0.97 for TAL 042 G & H 1 except 0.97 for TAL 042 G & H
TAL 044 1 except 0.97 for TAL 044 K 1 except 0.97 for TAL 044 K 1 except 0.97 for TAL 044 K 1 except 0.97 for TAL 044 K
General characteristics
Insulation class H Excitation system 6 wires SHUNT AREP
Winding pitch 2/3 AVR type R120 R180
Number of wires 6 (12 option) Excitation system 12 wires (option) SHUNT AREP
Protection IP 23 AVR type R120 (*) R180 (*)
Altitude ≤ 1000 m Voltage regulation (**) ±1%
Overspeed 2250 R.P.M. Total Harmonic Distortion THD (***) in no-load < 3.5 %
Air flow 50 Hz (m3/s) 0.06 Total Harmonic Distortion THD (***) in linear load <5%
Air flow 60 Hz (m3/s) 0.07 Waveform: NEMA = TIF (***) < 50
AREP Short-circuit current = 2.7 In: 5 second Waveform: I.E.C. = FHT (***) < 2%
(*) SHUNT: R220 - AREP: R438, R450 if ULc/us (**) Steady state (***) Total harmonic distortion between phases, no-load or on-load (non-distorting)
95.0
TAL 040 B TAL 040 E
95.0
77.4
75.0 75.0
0 2 4 6 8 10 12 2 4 6 8 10 12 14 16 18 20
95.0
TAL 040 C TAL 040 F
95.0
91.3 91.3 91.2
90.2
90.0 88.9 88.5 90.0
88.1 88.1
85.1 87.8
85.0 87.4 87.1
85.0 86.7
82.8
83.8 83.5 83.1
80.0 82.1
81.4 80.0
79.9
75.0 75.0
0 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16 18 20 22 24
95.0
TAL 040 D
85.0 83.5
85.7 86.1
85.3 84.8
80.0 81.2
75.0
2 4 6 8 10 12 14 16 18
B C D E F
30%
25%
20%
Voltage drop
15%
10%
5%
0%
0 10 20 30 40 50
Phase loading (SHUNT/AREP) - kVA at P.F. = 0.8
B C D E F
30%
25%
20%
Voltage rise
15%
10%
5%
0%
0 10 20 30 40 50
Load shedding (SHUNT/AREP) - kVA at P.F. = 0.8
B C D E F
30%
25%
20%
Voltage drop
15%
10%
5%
0%
0 10 20 30 40 50
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
76.6
75.0 75.0
0 2 4 6 8 10 12 14 16 0 5 10 15 20 25
95.0
TAL 040 D
80.0
80.6
75.0
2 4 6 8 10 12 14 16 18 20 22
B C D E F
30%
25%
20%
Voltage drop
15%
10%
5%
0%
0 10 20 30 40 50 60
B C D E F
30%
25%
20%
Voltage rise
15%
10%
5%
0%
0 10 20 30 40 50 60
B C D E F
30%
25%
20%
Voltage drop
15%
10%
5%
0%
0 10 20 30 40 50 60
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
1000
TAL 040 B
100
Symmetrical --------
SHUNT
Asymmetrical - - -
In In
10
Current (A)
AREP
1
1 10 100 1000
Time (ms)
1000
100
TAL 040 C
SHUNT
Symmetrical --------
Asymmetrical - - - In In
10
Current (A)
AREP
1
1 10 100 1000
Time (ms)
1000
100
TAL 040 D
SHUNT
Symmetrical --------
In In
Asymmetrical - - -
10
Current (A)
AREP
1
1 10 100 1000
Time (ms)
1000
TAL 040 E
100
10
Current (A)
AREP
1
1 10 100 1000
Time (ms)
1000
100
TAL 040 F SHUNT
Symmetrical -------- In In
Asymmetrical - - -
10
Current (A)
AREP
1
1 10 100 1000
Time (ms)
General characteristics
Insulation class H Excitation system SHUNT
Winding pitch 2/3 AVR type R121
Number of wires 4 Voltage regulation (*) ±2%
Protection IP 23 Total Harmonic Distortion THD (**) in no-load ....: < 3.5 %
Altitude ≤ 1000 m Total Harmonic Distortion THD (**) in linear load: <5%
Overspeed 2250 R.P.M. Waveform: NEMA = TIF (**) < 100
Air flow (m /s)
3 50 Hz: 0.06 - 60 Hz: 0.07 Waveform: I.E.C. = FHT (**) <2%
(*) Steady state (**) Total harmonic distortion between phases, no-load or on-load (non-distorting)
Cable
outlet
213
Ø N - 0,127
- 0,050
Ø BX - 0,100
Ø N - 0,127
- 0,050
Ø BX - 0,100
130
Ø 53
+0
+0
373
ØP
ØP
+1
H -3
X Ø Y holes
equid over Ø U
4
80 Optional
AIR H = 180
AIR OUTLET AIR OUTLET
13
98 87,5 INLET A2
3 3 13 C2 123,5 A1
5,5 203 5,5 C 51 282
Torsional data Xr
Ø 18
Ø 25
Ø 50
Ø 52
Ø 41
Ø 55
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flex plate S.A.E. 6 1/2 Flex plate S.A.E. 7 1/2 Flex plate S.A.E. 8 Flex plate S.A.E. 10
Type Xr Lr M J Xr Lr M J Xr Lr M J Xr Lr M J
TAL 040 B 211.7 428 25.54 0.0779 211.7 428 25.7 0.0802 243.5 428 26 0.0847 238.3 428 26.5 0.0964
TAL 040 C 211.7 428 25.54 0.0779 211.7 428 25.7 0.0802 243.5 428 26 0.0847 238.3 428 26.5 0.0964
TAL 040 C1 221.7 428 27.95 0.0867 221.7 428 28.11 0.0890 253.5 428 28.41 0.0935 248.3 428 28.91 0.1052
TAL 040 D 229.2 458 30.32 0.0936 229.2 458 30.48 0.0959 261 458 30.78 0.1004 255.8 458 31.28 0.1121
TAL 040 E 236.7 458 32.23 0.1004 236.7 458 32.39 0.1027 268.5 458 32.69 0.1072 263.3 458 33.19 0.1189
TAL 040 F 246.7 478 35.26 0.1102 246.7 478 35.42 0.1125 278.5 478 35.72 0.1170 273.3 478 36.22 0.1287
NOTE : Dimensions are for information only and may be subject to modifications. The torsional analysis of the transmission is imperative. All values are available
upon request.
General characteristics
Insulation class H Excitation system 6 wires SHUNT AREP
Winding pitch 2/3 AVR type R120 R180
Number of wires 6 (12 option) Excitation system 12 wires (option) SHUNT AREP
Protection IP 23 AVR type R120 (*) R180 (*)
Altitude ≤ 1000 m Voltage regulation (**) ±1%
Overspeed 2250 R.P.M. Total Harmonic Distortion THD (***) in no-load <2%
Air flow 50 Hz (m3/s) 0.10 Total Harmonic Distortion THD (***) in linear load <5%
Air flow 60 Hz (m3/s) 0.13 Waveform: NEMA = TIF (***) < 50
AREP Short-circuit current = 2.7 In: 5 second Waveform: I.E.C. = FHT (***) < 2%
(*) SHUNT: R220 - AREP: R438, R450 if ULc/us (**) Steady state (***) Total harmonic distortion between phases, no-load or on-load (non-distorting)
95.0
91.7 95.0
91.1 91.3 91.0 93.2
92.9 92.7 92.5
90.0
87.0 89.8
88.1 87.8 90.0
86.7 90.5 90.1
85.0 86.0
85.0 88.9
88.2 88.4
80.0 85.0
0 5 10 15 20 25 30 0 5 10 15 20 25 30 35 40 45 50
100.0
TAL 042 B 100.0
TAL 042 F
95.0 95.0
93.3 93.4 92.9
91.5 92.0 91.5 92.6
91.2 90.6
90.0 90.0 91.0
90.4
87.9 89.3
88.6 89.0 88.7
88.3
85.9 86.4
87.0
85.0 85.0
0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 40 45 50 55
100.0
TAL 042 C 100.0
TAL 042 G
95.0 95.0
93.2 93.5 93.1
92.1 92.4 91.9 92.8
91.6
90.2
90.0 88.8 90.0 90.9 90.5
89.4 89.4 88.9
88.9 88.7
87.6 87.0
87.0
85.0 85.0
0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40 45 50 55 60
100.0
TAL 042 D 100.0
TAL 042 H
A B C D E F G H A B C D E F G H
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP) - kVA at P.F. = 0.8
A B C D E F G H A B C DE F G H
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP) - kVA at P.F. = 0.8
A B C DE F G H A B C DE F G H
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
80.0 80.0
0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40 45 50 55 60
95.0
TAL 042 B 95.0
TAL 042 F
93.0 93.4 93.1
91.9 91.7 92.9
91.2 91.5
80.0 80.0
0 5 10 15 20 25 30 35 40 0 10 20 30 40 50 60 70
95.0
TAL 042 C 95.0
TAL 042 G
93.5 93.3
92.4 92.9 93.1
91.8 92.2 92.0
80.0 80.0
0 5 10 15 20 25 30 35 40 45 50 0 10 20 30 40 50 60 70 80
95.0
TAL 042 D 95.0
TAL 042 H
93.1 93.1 93.4 93.8 93.6
92.1 93.0 93.4
90.2
90.0 90.0 91.5 91.3
90.2 90.6 90.1 90.5
89.7 90.0
87.8 89.0
80.0 80.0
0 5 10 15 20 25 30 35 40 45 50 55 0 10 20 30 40 50 60 70 80 90
A B C D E F G H A B C D E F G H
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP) - kVA at P.F. = 0.8
A B C DE F G H AB C D E F G H
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP) - kVA at P.F. = 0.8
A B C D E F G H A B C D E F G H
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
1000
TAL 042 A
Symmetrical --------
100 SHUNT
Asymmetrical - - - In In
Current (A)
10
AREP
1
1 10 100 1000
Time (ms)
1000
TAL 042 B
Symmetrical --------
100 SHUNT
Asymmetrical - - - In In
Current (A)
10
AREP
1
1 10 100 1000
Time (ms)
1000
Symmetrical --------
Asymmetrical - - -
Current (A)
10
AREP
1
1 10 100 1000
Time (ms)
10000
10
AREP
1
1 10 100 1000
Time (ms)
10000
TAL 042 E
1000
Symmetrical --------
Asymmetrical - - - 100 SHUNT
Current (A) In In
10
AREP
1
1 10 100 1000
Time (ms)
10000
TAL 042 F
1000
Symmetrical --------
Asymmetrical - - - 100
SHUNT
In In
Current (A)
10
AREP
1
1 10 100 1000
Time (ms)
10000
1000
TAL 042 G
SHUNT
Symmetrical -------- 100
In In
Asymmetrical - - -
Current (A)
10
AREP
1
1 10 100 1000
Time (ms)
10000
10
AREP
1
1 10 100 1000
Time (ms)
General characteristics
Insulation class H Excitation system SHUNT
Winding pitch 2/3 AVR type R121
Number of wires 4 Voltage regulation (*) ±1%
Protection IP 23 Total Harmonic Distortion THD (**) in no-load ....: < 3.5 %
Altitude ≤ 1000 m Total Harmonic Distortion THD (**) in linear load: <5%
Overspeed 2250 R.P.M. Waveform: NEMA = TIF (**) < 100
Air flow (m3/s) 50 Hz: 0.10 - 60 Hz: 0.13 Waveform: I.E.C. = FHT (**) <2%
(*) Steady state (**) Total harmonic distortion between phases, no-load or on-load (non-distorting)
Cable
outlet
264
103 52
Ø 64
Ø N - 0.127
- 0.050
Ø BX - 0.100
Ø N - 0.127
- 0.050
Ø BX - 0.100
+0
Ø 455
+0
ØP
X Ø Y holes
equid. over
ØU
+1
H -3
78.5 Optional
AIR OUTLET AIR OUTLET INLET H = 225 A2
5
LA 137
LA A1
T C
14
T C B
Xr
Torsional data
Ø 18
Ø 41
Ø 30
Ø 60
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flex plate S.A.E. 7 1/2 Flex plate S.A.E. 8 Flex plate S.A.E. 10 Flex plate S.A.E. 11 1/2
Type Xr Lr M J Xr Lr M J Xr Lr M J Xr Lr M J
TAL 042 A 279 526.2 45.36 0.2209 277 558 45.68 0.2246 274 549.8 46.13 0.2363 272 535.6 46.62 0.2843
TAL 042 B 282 526.2 47.36 0.2337 280 558 47.68 0.2374 277 549.8 48.13 0.2491 274 535.6 48.62 0.2611
TAL 042 C 287 526.2 51.41 0.2592 286 558 51.73 0.2629 283 549.8 52.18 0.2746 281 535.6 52.67 0.2866
TAL 042 D 310 571.2 61.49 0.317 308 603 61.81 0.3207 306 594.8 62.26 0.3324 304 580.6 62.75 0.3444
TAL 042 E 310 571.2 61.49 0.317 308 603 61.81 0.3207 306 594.8 62.26 0.3324 304 580.6 62.75 0.3444
TAL 042 F 325 611.2 67.41 0.3491 323 643 67.73 0.3528 321 634.8 68.18 0.3645 319 620.6 68.67 0.3765
TAL 042 G 330 611.2 70.42 0.3683 328 643 70.74 0.372 326 634.8 71.18 0.3837 324 620.6 71.68 0.3957
TAL 042 H 344 641.2 77.49 0.4141 342 673 77.81 0.4178 340 664.8 78.25 0.4295 338 650.6 78.75 0.4415
NOTE : Dimensions are for information only and may be subject to modifications. The torsional analysis of the transmission is imperative. All values are available
upon request.
General characteristics
Insulation class H Excitation system 6 wires SHUNT AREP
Winding pitch 2/3 AVR type R120 R180
Number of wires 6 (12 option) Excitation system 12 wires (option) SHUNT AREP
Protection IP 23 AVR type R120 (*) R180 (*)
Altitude ≤ 1000 m Voltage regulation (**) ±1%
Overspeed 2250 R.P.M. Total Harmonic Distortion THD (***) in no-load <2%
Air flow 50 Hz (m3/s) 0.25 Total Harmonic Distortion THD (***) in linear load <5%
Air flow 60 Hz (m3/s) 0.30 Waveform: NEMA = TIF (***) < 50
AREP Short-circuit current = 2.7 In : 5 second Waveform: I.E.C. = FHT (***) < 2%
(*) SHUNT: R220 - AREP: R438, R450 if ULc/us (**) Steady state (***) Total harmonic distortion between phases, no-load or on-load (non-distorting)
86.8
85.0 85.0
0 20 40 60 80 100 0 20 40 60 80 100 120 140 160
100.0
TAL 044 B 100.0
TAL 044 H
100.0
TAL 044 C 100.0
TAL 044 J
88.4
85.0 85.0
0 20 40 60 80 100 120 0 20 40 60 80 100 120 140 160 180
100.0
TAL 044 D 100.0
TAL 044 K
85.0 85.0
0 20 40 60 80 100 120 0 20 40 60 80 100 120 140 160 180 200
A B C D E H J K A B C D E H J K
30%
30% 30%
25%
25% 25%
20%
20% 20%
Voltage drop
Voltage drop
15%
15% 15%
10%
10% 10%
5%
5% 5%
0%
0% 0%
0 50 100 150 200 250 300 350 0 50 100 150 200 250 300 350
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP) - kVA at P.F. = 0.8
A B C D E H J K A B C D E H J K
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 50 100 150 200 250 300 350 0 50 100 150 200 250 300 350
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP) - kVA at P.F. = 0.8
A B C D E H J K A B C D E H J K
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 50 100 150 200 250 300 350 0 50 100 150 200 250 300 350
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
100.0
TAL 044 B 100.0
TAL 044 H
94.9 94.8
95.0 95.0 94.3 94.7
93.4 93.5
92.4 93.4
91.2 92.9 93.0
92.4 92.1
90.0 91.0 90.0
90.6 90.6 90.2 90.3
88.0
86.8
85.0 85.0
0 20 40 60 80 100 120 0 20 40 60 80 100 120 140 160 180 200
100.0
TAL 044 C 100.0
TAL 044 J
87.3
85.0 85.0
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140 160 180 200 220
100.0
TAL 044 D 100.0
TAL 044 K
88.1
85.0 85.0
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160 180 200 220 240
A B C D E H J K A B C D E H J K
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 50 100 150 200 250 300 350 400 450 0 50 100 150 200 250 300 350 400 450
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP) - kVA at P.F. = 0.8
A B C D E H J K A B C D E H J K
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 50 100 150 200 250 300 350 400 450 0 50 100 150 200 250 300 350 400 450
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP) - kVA at P.F. = 0.8
A B C D E H J K A B C D E H J K
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 50 100 150 200 250 300 350 400 450 0 50 100 150 200 250 300 350 400 450
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
10000
TAL 044 A
1000
10 AREP
1
1 10 100 1000
Time (ms)
10000
TAL 044 B
1000
10 AREP
1
1 10 100 1000
Time (ms)
10000
1000
TAL 044 C SHUNT
In In
Symmetrical -------- 100
Asymmetrical - - -
Current (A)
10 AREP
1
1 10 100 1000
Time (ms)
10000
SHUNT
Symmetrical -------- 100
In In
Asymmetrical - - -
Current (A)
10 AREP
1
1 10 100 1000
Time (ms)
10000
TAL 044 E
1000
SHUNT
Symmetrical --------
In In
Asymmetrical - - - 100
Current (A)
10 AREP
1
1 10 100 1000
Time (ms)
10000
TAL 044 H
1000
SHUNT
Symmetrical -------- In In
Asymmetrical - - - 100
Current (A)
10 AREP
1
1 10 100 1000
Time (ms)
10000
1000
10 AREP
1
1 10 100 1000
Time (ms)
10000
Asymmetrical - - - 100
Current (A)
10
AREP
1
1 10 100 1000
Time (ms)
General characteristics
Insulation class H Excitation system SHUNT
Winding pitch 2/3 AVR type R121
Number of wires 4 Voltage regulation (*) ±1%
Protection IP 23 Total Harmonic Distortion THD (**) in no-load ....: < 3.5 %
Altitude ≤ 1000 m Total Harmonic Distortion THD (**) in linear load: <5%
Overspeed 2250 R.P.M. Waveform: NEMA = TIF (**) < 100
Air flow (m3/s) 50 Hz: 0.25 - 60 Hz: 0.30 Waveform: I.E.C. = FHT (**) <2%
(*) Steady state (**) Total harmonic distortion between phases, no-load or on-load (non-distorting)
TAL 044 E - - - - - -
TAL 044 K - - - - - -
TAL 044 J - - - - - -
XBG Ø S holes
equid. on Ø M
266.5
Ø N - 0.127
- 0.050
Ø BX - 0.150
15°
600
+0
ØP
Ø444
+1
H -3
Access to
diodes X Ø Y holes
equid. on Ø U
Air inlet 6
150
Air outlet A1
137.2 20 50 50 184 474
6.5 C 25
Xr
Torsional data
Ø 40
Ø 72
Ø 75
Ø 40
Ø 70
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flex plate Flex plate S.A.E. 10 Flex plate S.A.E. 11 1/2
Type Xr Lr M J Xr Lr M J
TAL 044 A 344.7 704 107.2 0.770 332.1 704 106.8 0.769
TAL 044 B 344.7 704 107.2 0.770 332.1 704 106.8 0.769
TAL 044 C 355.2 704 121 0.894 342.4 704 120.6 0.893
TAL 044 D 355.2 704 121 0.894 342.4 704 120.6 0.893
TAL 044 D1 376.1 704 139.1 1.051 363.2 704 138.7 1.050
TAL 044 E 400.2 774 153.7 1.167 387.2 774 153.3 1.166
TAL 044 H 400.2 774 153.7 1.167 387.2 774 153.3 1.166
TAL 044 J 411.0 774 165.5 1.274 398.0 774 165.1 1.273
TAL 044 K 431.0 814 180.6 1.409 417.9 814 180.2 1.408
NOTE : Dimensions are for information only and may be subject to modifications. The torsional analysis of the transmission is imperative. All values are available
upon request.
Linkedin.com/company/Leroy-Somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
© Nidec 2017. The information contained in this brochure is for guidance only and does not form part of
any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development
and reserve the right to change the specification of their products without notice.
Moteurs Leroy-Somer SAS. Siège : Bd Marcellin Leroy, CS 10015, 16915 Angoulême Cedex 9, France.
Capital social : 65 800 512 €, RCS Angoulême 338 567 258.
5224 en - 2017.11 / l