You are on page 1of 9

Switchgear

SF6 or vacuum?

Choosing the right MV circuit-breaker


Guenter Leonhardt, Mauro Marchi, Giandomenico Rivetti

More than three decades of experience in developing SF6 and vacuum circuit-breakers, accompanied
by increasingly close cooperation between the participating research centers, gives ABB a strong
advantage when it comes to deciding which technology is best for a given application. The
pioneering role played by the company uniquely qualifies it to pursue R&D on both fronts with the
goal of pushing performance levels to the limit. The sum of this research work, coupled with
unrivalled knowledge of the marketplace, puts ABB in a position to offer unbiased advice and
assistance to customers searching for the switchgear that best suits their needs.

A
pproximately 35 years ago, in the both technologies has continued be used when choosing one of these
mid 1960s, two new breaker unabated since then, and today it can two dominant technologies. Instead of
technologies, one using SF6 gas and the be said that, together, they have all an objective selection based on real-
other vacuum as its arc quenching but replaced the older types of switch- world characteristics, the choice is very
medium, were introduced to the market. gear. There is, however, not always much driven by the circuit-breaker
Research and development work on agreement on which criteria should manufacturer.

26 ABB Review 4/2000


100
SF6 and vacuum switchgear enjoy
varying market success in the different
80
parts of the world 1 ; whereas Europe
and most of the Middle East countries 60
[% ]
tend to favor SF6, China, Japan and the
USA definitely prefer vacuum. In other 40
regions, the two technologies are equally
popular. Bulk-oil and minimum-oil 20

technologies are still used in China,


0
Eastern Europe, India and Latin America,
a ) A)
A
ic EL pe ca na ia
but trends clearly indicate that these US er I o ri
Ch
i M As
AP ur Af EE
technologies will disappear very soon, to Am (C n
E
rt
h (I
in er ia
t
op
e t No d
La r as In
be replaced by SF6 and vacuum. Eu E s t& Others
&
rn al Ea SF 6
As 2 shows, ABB concentrates today te tr e
es n dl
almost entirely on the two dominant W Ce M
id Vacuum

technologies, and is equally present in the


market with both SF6 and vacuum. 1 Worldwide market for MV circuit-breakers by region (1998)

Experience with more than


300,000 MV circuit-breakers of both
100
designs installed worldwide, backed up
by over 30 years of intensive involvement 80 (SF 6 +vacuum) SF 6

in research [1], has convinced ABB that Others Vacuum

the two technologies are entirely 60

complementary, though in some cases


[ %]

40
their different designs can be seen as
alternatives. Based on this conviction that
20
SF6 and vacuum have equally important
roles to play, the company has continued 0
to force the development of both, and 1991 1992 1993 1994 1995 1996 1997 1998 1999

hence, as the world’s largest manufacturer


2 MV circuit-breakers manufactured by ABB
of MV circuit-breakers, occupies the
unique position of being able to provide
unprejudiced advice and assistance in the led to better service for customers. At the advantage to both user and manufacturer
selection of switchgear for any special same time, keen competition between the if the circuit-breakers were constructed so
application. company’s research laboratories has led as to be completely interchangeable, as
The decision by ABB to pursue both to top team performances, the exchange shown by 3 .
technologies with equal emphasis has of information between them having Proceeding in this way, all new
produced several important benefits. First extracted the maximum synergy from developments are equally advantageous
and foremost, a profound knowledge of parallel work. Finally, it was recognized at to both technologies. The most important
the behavior of the two technologies has an early stage that it would be of great developments to come out of this

ABB Review 4/2000 27


Switchgear

approach are the use of magnetic The specific advantages of SF6 gas in generation of designs produced the gas
actuators as the operating mechanism and electrical engineering applications have flow by utilizing the energy contained in
the integration of sensors in the switchgear been widely recognized since the early the arc. This ‘self-blast’ circuit-breaker
panels. With total interchangeability, 1930s, but it was only in the late 1950s design resulted in significantly less energy
users are faced with easier choices and that the first high-voltage SF6 insulated being required for its operation.
structural factors are no longer a major circuit-breakers were developed and The more than 30 years of ABB
consideration in their decisions. installed. SF6 medium-voltage circuit- experience and research associated with
breakers followed some years later. the puffer and self-blast circuit-breakers
Arc-interrupting characteristics The first generation of MV SF6 circuit- have now culminated in a new and very
breakers employed a dual-pressure gas efficient design. This so-called ‘auto-
SF6 circuit-breakers system. Second-generation designs puffer’ combines the advantages of both
Sulfur hexafluoride (SF6) is an artificial included the pressure differential previous designs. The auto-puffer circuit-
inert gas with excellent insulating necessary to create the gas flow, this breaker operates as a pure puffer device
properties and exceptional thermal and being provided by a mechanically driven when interrupting currents up to 30% of
chemical stability. These characteristics piston which compressed a small volume the maximum rated breaking capacity and
of the gas have led to its widespread use of gas. The piston was integrated in the as a self-blast interrupter at higher levels.
in both HV and MV switchgear, both of moving contact assembly. Such ‘puffer- The auto-puffer requires only a minimum
which exhibit very high performance type’ circuit-breakers required a relatively amount of energy from the operating
and reliability as a result. powerful mechanism [2]. The third mechanism, but offers the high

3 VM1 vacuum (left) and HM1 SF6 medium-voltage circuit-breakers with magnetic actuator

28 ABB Review 4/2000


performance levels of the self-blast type. 4 Cutaway view of the magnetic actuator
Reduced arc energy dissipation at both 1 Coils
low and high (short-circuit) currents 2 Permanent magnets
ensures a longer electrical life than either 3 Plunger
of the former designs. This performance
is obtained without jeopardizing the total
absence of chopping currents, which is a
key characteristic of the self-blast
technique. The design of the mechanism
has been optimized to generate only
enough pressure to ensure the safe
interruption of currents in the range in
which the puffer technique is operative.
Consequently, small inductive currents are
effectively interrupted with overvoltage 1

factors lower than 2.5 pu.

Vacuum circuit-breakers 2

As early as the beginning of the last


century, the interruption of current in a 3
vacuum was recognized as an ‘ideal’
switching technique. However, several
practical difficulties led to it being
ignored for almost three decades. One of
the fundamental problems was the
manufacture of a suitable insulating
enclosure, which had to be hermetically
sealed for life. This problem existed
through a number of decades until, in considerable problem. The contacts had showed that chromium possessed most
the early 1960s, a solution using glass to exhibit a high resistance to arc erosion of the required properties. Further
enclosures was developed. Curiously, the during both opening and closing research showed composite material of
fundamental technology of blown-glass operations, and any erosion had to be copper/chromium to be the most suitable
containers had been commonly available diffuse and even over the whole contact and best able to satisfy the basic
for centuries. A further step forward came surface. The contact material had to have requirements. Cu/Cr with a chromium
with the development of alumina (Al2O3) a low propensity to weld during closing content of between 20% and 60% is now
ceramics, a material which possesses a as well as when closed. Low current the standard material for contacts, and is
much higher resistance to cyclic chopping characteristics when used by all manufacturers of vacuum
temperature stresses. interrupting small currents was also circuit-breakers.
Finding a suitable material and form important, as was an adequate gettering The mechanism of charge carrier
for the circuit-breaker contacts was also a effect. The search for a suitable material formation gives a vacuum circuit-breaker

ABB Review 4/2000 29


Switchgear

the inherent ability to extinguish current This reduction in operating energy The change of status of the moving
arcs of small to medium values has led to the development of an entirely contacts is brought about by a change
automatically when the current passes new design of operating mechanism, in direction of the magnetic field
through zero. A satisfactory interruption the permanent magnet actuator. resulting from the energizing of the
of short-circuit currents, however, electromagnets, which are the control
requires additional design measures. Magnetic actuator elements of the actuator. Modulation of
The initial designs used a specially The operating mechanism of a circuit- the current supply to the electromagnets
shaped electrode to produce a radial breaker has the apparently ‘simple’ allows the energy developed by the
magnetic field in the arc contact area. function of moving the contacts from the system to be adjusted to the requirements
This magnetic field, reacting with the arc closed to the open position or vice versa of different types and ratings of circuit-
current, forced the arc root to move and, when the required position is breakers.
continually around the contact surface, reached, of ensuring that the contacts The resulting operating mechanism is
thus preventing local overheating and remain in that position until a definite considerably simpler in construction than
uneven wear. command to again change position is the conventional mechanical system. The
A further design improvement, aimed given. The operating mechanism is thus a drastic reduction in the number of parts
particularly at increasing the current typical bistable actuator. This function has inherently reduces the susceptibility to
interrupting capacity to extremely high been performed with a high degree of failure, and the level of maintenance
short-circuit currents, was the reliability and surety for many years by required by this operating mechanism is
development of the ‘axial’ magnetic field. mechanical spring and latch mechanisms. reduced to the very minimum. 4 shows
Again a specially designed electrode is However, the opportunities now offered the construction of such an actuator with
employed to generate an axial magnetic by developments in power electronics its fixed laminated iron core, permanent
field, which distributes the arc root have led to the search for a more flexible magnets, steel armature and closing and
homogeneously over the whole of the and more readily controllable operating opening coils. All auxiliary functions,
contact area. device. Of course, an essential prerequi- such as interlocking, signaling, tripping,
site of any new system was that it had closing, etc, are provided electronically;
Common trends in SF6 to guarantee at least as good or better self-diagnostic facilities are also included.
and vacuum circuit-breaker performance, in terms of reliability, safety An electrolytic capacitor provides the
development and durability, than the traditional spring- surge power required for the opening
ABB SF6 and vacuum circuit-breakers based mechanism. and closing coils.
have been used for many years in An appropriate solution has been
medium-voltage switchgear and service found in the ‘magnetic actuator’. Basic construction of the
experience has shown them to be A specially designed system combining switching devices
reliable, almost maintenance-free and electromagnets with permanent magnets The new vacuum and SF6 magnetically
safe under operating conditions. provides the operating energy for the actuated circuit-breakers are fully
Innovations in both technologies have movement of the contacts as well as the interchangeable with each other as well
continually improved their efficiency, essential bistable characteristic. The as with previous designs. This
reduced their overall dimensions vacuum and the SF6 interrupters are held interchangeability is of considerable
and, most importantly, reduced the in either their open or closed positions by importance to plant operators as it allows
amount of energy required to operate the force of a permanent magnet and this existing switchgear to be re-equipped at
them. without the need for any external energy. minimum cost.

30 ABB Review 4/2000


5 View of the VM1 vacuum (right) and HM1 SF6 medium-voltage circuit-breakers
showing the small number of components

technique involves the circuit-breaker


poles being independently operated,
with each pole opened or closed at the
best point in time relative to the current
and/or voltage conditions prevailing in
the relevant phase. Synchronous
switching minimizes the electrical and
mechanical stresses which arise on both
the supply and load sides of the circuit
being switched and in the circuit-breaker
itself when the current is interrupted.
With synchronous switching, the amount
of energy which has to be dissipated in
4 and 5 show clearly the very power-quality sensitive loads, mostly due the interruption chamber is minimized
small number of components used, a fact to the use of electronic equipment. The and any overvoltage resulting from the
that significantly reduces the potential for present solution, based on power switching operation is greatly reduced.
failure. electronics devices, is very efficient from All of these advantages result from the
Simplicity is also a feature of the em- the technical point of view but also very precise control of the circuit-breaker
bedded vacuum pole and the SF6 inter- expensive. Introduction of the magnetic operation made possible by the magnetic
rupter using the auto-puffer technique, actuator has made it possible to actuator. The control accuracy is so great
specially adapted for medium-voltage accelerate the operation of an MV circuit- that it is possible to synchronize the
applications 6 . breaker to the absolute minimum, that is completion of the moving contact travel
Thanks to the embedding technology to the pure arc extinction time. Using with the current zero-crossing in each
there is no need for special support struc- magnetically actuated medium-voltage phase. Furthermore, synchronous
tures for the interrupter or its terminals. circuit-breakers and appropriate basic switching minimizes, theoretically even
electronics, it has been possible to reduces to zero, the inrush current peaks
Rapid switching reduce power source transfer-switching and overvoltages that occur during the
An important property of the magnetic times to less than 40 ms. This elapsed energization of inductive or capacitive
actuator that has already been mentioned time is so short that it solves most of the loads. Given the type of load, these
is the versatility of its control functions. problems of sensitive loads and at a results are obtained by controlling the
Exploitation of this flexibility opens the cost which is very competitive compared closing of the contacts to correspond
door to new solutions to key problems with the power electronics based with either the current or voltage
in electrical distribution, problems which solutions [5]. maximum. The closing and opening
until today have been solvable, if at all, operations described are performed with
only at great expense. One of these Synchronous circuit-breaker a maximum tolerance of ± 0.5 ms and
issues is the rapid transfer-switching The availability of these new circuit- ± l ms, respectively. These figures are a
between energy sources in the event of a breakers with their magnetic actuator true measure of the value of the
fault in one system. This problem has mechanisms has another important technological breakthrough achieved by
been dramatically emphasized in the last advantage: they provide the basis for the combination of digital electronics
few years by an exponential increase in synchronous switching. This switching with the magnetic actuator.

ABB Review 4/2000 31


Switchgear

6 Section through the embedded vacuum pole (left) and the auto-puffer SF6 pole

These developments will result in


improved reliability for the entire
electrical system, greater safety for the
personnel, and cost reductions due to the
minimization of electrical stress and wear
on the electrical equipment [6].

Integration with sensors


and electronics
The hardware and software presently
available for use with the magnetically
actuated circuit-breakers allow a further
step forward in the direction of complete
functional integration. With the appropriate
software and the necessary current and
voltage sensors, the direct integration of
the protection functions in the circuit-
breaker control system is now possible.
This makes the circuit-breaker a fully
automated device for protection and
switching functions and achieves the
goal of maximum reliability – the result
of minimization of the component inter-
faces. This total integration of the core
functions in switchgear has already been breakers as given in the IEC 60056 The standard prescribes two
shown to be the correct path to follow in standard [3]. This states that: alternative test cycles for the verification
medium-voltage secondary distribution ‘A circuit breaker class B (in the IEC of electrical endurance performance of a
applications, just as it is already the draft document, in the future it will be circuit-breaker. The test cycle in
current state of the art in the field of low E2) is a circuit breaker designed so as not accordance with List 1 is the preferred
voltage equipment. to require maintenance of the interrupting one; the test cycle of List 2 may be
parts during the expected operating life of applied as a valid alternative for circuit-
Technical performance the circuit-breaker, and only minimal breakers for use in solidly grounded
maintenance of its other parts.’ Based on systems. The severity level of these two
Electrical and mechanical service experience, the IEC standard test cycles is regarded as identical.
endurance establishes the number of operations that
Both SF6 and vacuum circuit-breakers a circuit-breaker shall be capable of Reliability of dielectric
can be considered maintenance-free. performing under the severe service media
High-quality SF6 circuit-breakers as well conditions associated with an overhead Modern SF6 and vacuum circuit-breakers
as high-quality vacuum circuit-breakers line connected network and including are sealed for life; diagnostic systems for
fulfil the requirements for class B circuit- auto-reclosing duty. the purpose of measuring the gas

32 ABB Review 4/2000


pressure or the vacuum level are considered to be a likely cause of global the total. When considering vacuum
therefore unnecessary. warming, SF6 among them, need to be circuit-breakers, it is evident that because
reduced. It was therefore necessary to of the quantity of copper and the number
Switching overvoltages analyze the greenhouse gas (ie, SF6 and of insulating components, as well as the
Any switching overvoltages generated by CO2) emissions occurring as a main circuit resistance, the results are
circuit-breakers using either technology consequence of the manufacturing very close to those for the SF6 circuit-
are contained within such limits as not to process and the power losses in service. breaker.
present any danger to connected The Life Cycle Assessment (LCA) that was Considering the global warming effect
equipment or installations. subsequently carried out for vacuum and alone, it can be concluded that the impact
Due to their inherently soft interruption SF6 circuit-breakers leads to the following is determined essentially by the main
characteristics SF6 circuit-breakers offer conclusions, which are substantially the circuit power losses. However, these
this level of performance without the same for both types of equipment. losses are in turn fully negligible when
need of any additional devices. The impact of the manufacturing and compared with those caused by the
Vacuum circuit-breakers using modern the service phases are to be considered cables, connections and all the other
contact materials also exhibit low chopping separately. Consideration of the SF6 apparatus which make up the electrical
currents; however, in exceptional cases, circuit-breaker shows that the distribution system.
and depending on the characteristics of environmental impact during the entire
the individual installation, a detailed study manufacturing phase is more than Specific switching applications
of the system parameters may be 100 times greater than the environmental
necessary in order to determine if specific impact of the unit throughout a 30-year Overhead lines and cables
voltage limiting devices are required. total life cycle due to the fact that When applied to the onerous duty of
medium-voltage SF6 breakers are sealed switching and protecting overhead line
Environmental impact for life [4]. The production of the copper distribution networks, in which the fault
The operation of either circuit-breaker and insulating components of the circuit- currents are distributed over the whole
type presents no health hazard to breaker is the predominant contributor to current range, both technologies provide
personnel. In the unlikely event of a the environmental impact throughout the adequate margins over and above the
major malfunction, overpressure valves manufacturing phase. maximum required by the relevant
built into the SF6 circuit-breakers would As regards the environmental impact standards and in normal service practice.
respond, while vacuum circuit-breakers during service, based on an assumed
would be subject to no more than 30-year service life and an average load Transformers
implosion phenomena. Experience has current of 20% of the rated current it can Modern vacuum circuit-breakers as well
also shown that any emission products be calculated that the service phase has as SF6 circuit-breakers are suitable for
from either type of circuit-breaker do not an environmental heating effect of more switching the magnetizing currents of
constitute a toxic hazard. The component than 7 to 8 times that caused during the unloaded transformers with overvoltages
materials of both types of apparatus can manufacturing phase. This is due to the lower than 3.0 pu. In special cases, for
be readily recycled at the end of their resistance losses in the circuit-breaker. instance when vacuum circuit-breakers
service lives. The Kyoto Protocol to the The analysis shows that the environmental are used for switching dry-type
United Nations Framework Convention impact of the SF6 gas itself, relative to the transformers in industrial installations,
on Climate Change (10th December 1997) impact of the complete apparatus over its the use of surge arresters is to be
has established that emissions of six gases complete life cycle, is only about 0.1% of recommended.

ABB Review 4/2000 33


Switchgear

Motors Vacuum circuit-breakers are particularly requirements are the decision-drivers


When choosing circuit-breakers for suited to these service conditions. that favor one or the other technology.
motor-switching duty, attention should Typical of such special applications is
be paid to the problems of overvoltages Shunt reactors the switching of dry-type transformers,
during operation. The target limit for SF6 circuit-breakers are suitable for small-size motors, capacitors, arc
overvoltages of less than 2.5 pu is switching with overvoltages generally furnaces, shunt reactors and railway
obtainable with both technologies.Where lower than 2.5 pu. Where vacuum circuit- traction systems. The need for ‘frequent
vacuum circuit-breakers are used for breakers are employed, it may be neces- switching’ or ‘soft switching’ can be an
switching small motors (starting currents sary under certain circumstances to take additional element influencing the
less than 600 A), measures may be additional measures to limit overvoltages. choice. In such cases, a comprehensive
necessary to limit overvoltages due to study of the planned installation may be
multiple re-ignitions; however, the Railway traction needed to find the best answer. ABB has
probability of this phenomenon arising is In principle, both interrupting technologies the know-how and experience necessary
low. are well suited for this duty; however, in to provide unbiased advice and
the case of low-frequency applications assistance to users in choosing the
Capacitor banks (eg, 16.67 Hz), vacuum circuit-breakers circuit-breaker most suitable for any
Both technologies are suitable for are to be recommended. particular application.
restrike-free switching of capacitor
banks. When capacitors must be Matching the circuit-breaker Authors
switched back-to-back, reactors may be to the task Guenter Leonhardt
necessary to limit the inrush currents. Thirty years of experience in developing, ABB Calor Emag
The synchronous control of circuit- Oberhausenerstraße, 33
manufacturing and marketing both SF6
40472 Ratingen, Germany
breakers is an effective solution to this and vacuum medium-voltage circuit- guenter.leonhardt@de.abb.com
problem. SF6 is specifically recom- breakers worldwide has yielded up
Mauro Marchi
mended for applications with rated ample evidence that neither of the two
ABB Trasmissione e Distribuzione
voltages higher than 27 kV. technologies is generally better than the Via Friuli 4, 24044 Dalmine (BG), Italy
other, and especially that they are mauro.marchi@it.abb.com

Arc furnaces complementary from the application Giandomenico Rivetti


Arc furnace switching is often point of view. Economical factors, user ABB Power Distribution
characterized by frequent operation at preferences, national ‘traditions’, Via Friuli 4, 24044 Dalmine (BG), Italy
giandomenico.rivetti@it.abb.com
high current values and short intervals. competence and special switching

References
[l] D. Braun, W. Heilmann, A. Plessl: Application criteria for SF6 and vacuum circuit-breakers. ABB Review 4/89, 25–33.
[2] A. Plessl, L. Niemeyer, F. Perdoncin: Research for medium-voltage SF6 circuit-breakers. ABB Review 2/89, 3–10.
[3] IEC 60056 – High-voltage alternating-current circuit-breakers, Amendment 3, 1996-09.
[4] R. Borlotti, A. Giacomucci: A simplified LCA of SF6 medium-voltage circuit-breaker. 7th SETAC Symposium, Brussels, 1999.
[5] R. Tinggren, Y. Hu, L. Tang, H. Mathews, R. Tyner: Power factor controller – an integrated power quality device. 1999 IEEE Transmission and
Distribution Conference, New Orleans.
[6] C. Cereda, C. Gemme, C, Reuber: Synchronous medium-voltage circuit-breaker: ABB solution based on magnetic drive and electronic control.
15th International Conference and Exhibition on Electrical Power Distribution Engineering, CIRED, Nice, 1999.

34 ABB Review 4/2000

You might also like