You are on page 1of 10

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 51, NO.

3, MAY/JUNE 2015 2691

Transferred Potential—A Hidden


Killer of Many Linemen
K. Suresh, Member, IEEE, and S. Paranthaman, Member, IEEE

Abstract—The causes of electrical accidents which occur during at the source end, which is intended to safeguard the worker,
maintenance of power lines are sometimes not traceable. Unfortu- causes uncontrollable transferred potential at the worksite.
nately, a grounding practice which has been widely adopted in the This paper discusses modifications required in the personal
utility industry in India, U.K., and some other countries uninten-
tionally causes so many fatal accidents every year. The conclusion protective grounding practices to prevent accidents caused by
was arrived after analyzing some fatal accidents. This practice of the transferred potential.
protective grounding is still continued by many distribution com-
panies without realizing the hazards involved. For de-energized
line maintenance, grounding the line at source end is commonly II. P ROTECTIVE G ROUNDING C URRENTLY P RACTICED
practiced for the purpose of personal protection. This paper ex-
plains how this safety practice turns into hazard by transferring Normally, maintenance works are carried out on a distribu-
the substation ground grid potential to the worksite and why this tion line only after providing personal protective grounding
transferred potential cannot be controlled by any means in three- either at the worksite alone or both at the source end and at
wire overhead distribution systems which run with no separated the worksite. The advantages of each method are discussed as
ground wire. This paper suggests the solution to avoid the trans- follows.
ferred potential and to describe it in IEEE Std. 1048—Guide for
Protective Grounding of Power Lines, IEEE Std. 80-2000—Guide
for Safety in AC Substation Grounding, British Std. 7430— A. Protective Grounding at the Worksite Alone
Code of Practice for Earthing, and Indian Std. 3043—Code of
Practice for Earthing to bring an end to the accidents caused by Work on a de-energized overhead line can be considered safe
this safety practice. only if, in the event of any voltage being accidentally imposed
Index Terms—Electrostatic induction, equipotential bonding, on the line, the body current caused by the voltage should be
ground potential rise (GPR), let-go current, magnetic induction, well within the human let-go magnitude.
metal-to-metal voltage, personal protective grounding, transferred Attempts to control the voltages by temporarily grounding
potential.
the line at the worksite fail because the grounding does not
bring down the line-Earth resistance sufficiently to divert haz-
I. I NTRODUCTION
ardous voltages. However, it does aid in causing the source
which energizes the line to trip [1]. Hence, grounding at the
T HE discussion in this paper is confined only to three-phase
three-wire (3ph, 3w) neutral solidly grounded systems
with overhead radial distribution lines run with no dedicated
worksite alone cannot be considered as an effective safety
measure to control the voltages. In addition to grounding at
neutral or ground conductor. This kind of distribution system is the worksite, an equipotential zone should be established to
widely adopted in many countries including India. overcome the effects of the hazardous voltages.
For de-energized line maintenance, a common practice in
India and some other countries is to ground the line both at
B. Benefits of Grounding at Source End, in Addition to
the source end and at the worksite. This practice is being
Grounding at the Worksite, and Its Limitations
followed in transmission as well as distribution networks. The
distribution lines (11, 22, and 33 kV) are normally 3ph 3wire Providing protective grounding on the distribution lines at
with no separate neutral or ground wire. In actuality, during the source end in addition to the worksite grounding is being
maintenance, the practice of grounding the distribution line practiced in many distribution companies. Although it has some
advantages, it has a strong limitation for those advantages as
listed in the following.
Manuscript received March 22, 2014; revised July 29, 2014; accepted August
4, 2014. Date of publication November 25, 2014; date of current version 1) Re-energization: If the voltage source which has been
May 15, 2015. Paper 2014-ESafC-0098.R1, presented at the 2014 IEEE IAS disconnected to carry out a maintenance work is mistak-
Electrical Safety Workshop, San Diego, CA, USA, February 4–7, and approved
for publication in the IEEE T RANSACTIONS ON I NDUSTRY A PPLICATIONS
enly reconnected, all of the phase voltages of the source
by the Electrical Safety Committee of the IEEE Industry Applications Society. get shorted with the neutral, through the metallic path
K. Suresh is with Special Maintenance, TANGEDCO, Chennai-600 002, offered by the grounding connection made at the source
India (e-mail: sureshmrt@yahoo.com).
S. Paranthaman is with the Dr. M.G.R. Educational and Research Institute end. Hence, the inadvertent voltage appearing on the line
University, Chennai-600 095, India, and also with Environment Management due to reconnection of the source can be controlled within
Cell, TANGEDCO, Chennai-600 002, India (e-mail: vsparanth@yahoo.co.in). a safe limit.
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. 2) Energization from a different source: If any accidental
Digital Object Identifier 10.1109/TIA.2014.2375386 extension of supply from another source occurs, the
0093-9994 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
2692 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 51, NO. 3, MAY/JUNE 2015

grounding made at the source end will offer a path of


minimum possible impedance to the grounded neutral of
the source which energizes the line, thereby diverting the
voltage effectively.
3) Controlling the effects of electrostatic induction: The
grounding connection made at the source end effectively
shorts the capacitance formed between the de-energized
line and the Earth, thereby diverting the voltage which
may develop on the line with respect to ground due to
electrostatic induction.
4) Limitations: The previously stated reasons justify the
practice of grounding the line additionally at the source
end. However, this practice minimizes the hazards and
ensures safety only if the ground potential of the sub-
station always remains at zero. A ground fault can raise
the ground potential at any time, and hence, this practice
only maximizes the hazards to the line worker. This
accounts for the lack of a good safety record with the
accepted maintenance practice in three-wire systems with
no grounding wire.

III. GPR IN D ISTRIBUTION S UBSTATIONS Fig. 1. Transfer of substation ground potential during ground fault in a 3w
system.
In solidly grounded systems, the substation ground grid
potential is always at neutral potential of the power transformer. substation is Ig × Rg . Similarly, the GPR at the faulty pole is
The neutral potential remains at Earth potential only during Ig × RP , where RP is the grounding resistance of the pole.
normal conditions. Whenever a current passes through the The effects of GPR are step potential and touch potential.
resistance offered by the substation ground grid, the potential of Since the substations are designed to overcome these effects,
the neutral and hence the ground grid rises with respect to the the GPR at the substation is not considered as serious in
remote Earth. This rise in voltage will reflect on the enclosure comparison to the GPR at fault location. However, the effect
of all of the equipment, metallic structures, which are connected of the substation GPR is also dangerous whenever the ground
to the substation ground grid, and also reflect on the soil in and grid potential of the substation is permitted to transfer outside
around the substation. the substation area. Fig. 1 illustrates how the raised ground grid
Fig. 1 illustrates a single line-to-ground fault on a distribution potential gets transferred outside the substation area through a
line of a substation (fault is shown as a closed switch). The grounded conductor (GC).
power transformer in the distribution substation is delta/wye
connected, and the wye point is solidly grounded. The fault is
developed on the low-voltage (LV) side due to direct contact IV. ACCIDENT D URING A D E -E NERGIZED W ORK
of the line conductor with the supporting metallic pole outside A maintenance work was being carried out on an overhead
the substation area at a remote location (the impedance formed distribution line by two linemen after de-energizing, isolating,
between the line and metallic pole is neglected). Since there is and grounding the line at the substation end. The line has no
no neutral or ground wire, the entire fault current is driven into neutral or ground conductor. Additional grounding was pro-
the Earth at the fault location through the grounding resistance vided at the worksite using temporary ground rods but without
of the metallic pole (RP ). The current then spreads in the establishing equipotential bonding at the worksite. During the
Earth and finally reaches the power transformer neutral through work, the workers suddenly experienced severe shock. One of
the substation ground grid. Along the path of the current, the them was electrocuted, and the other sustained severe injuries.
area offered by the soil is confined at the fault location (entry Generally, if the cause of such an accident is not revealed
into the Earth) and at the substation (exit from the Earth). The by usual methods of analysis, it is determined to be an accident
fault current encounters a significant resistance at both of these caused by an induced potential from an adjacent live line. How-
locations and results in ground potential rise (GPR) both at ever, the effect of electrostatic or electromagnetic induction is
the substation and at the fault location. Other than at these significant only in parallel feeders, and the effects are not nor-
locations, the Earth offers an enormous area to the fault current; mally significant in lower voltage (less than or equal to 33 kV)
therefore, the resistance is negligible, and hence, the ground distribution feeders which are normally run in single circuit.
potential remains at zero.
The GPR of a substation is the product of the substation
A. Preliminary Analysis
ground grid resistance (Rg ) and the portion of the ground fault
current which returns to the power transformer neutral through On examining the substation and the worksite after the
the substation ground grid (Ig ). Therefore, the GPR at the accident, the personal protective grounding was found to be
SURESH AND PARANTHAMAN: TRANSFERRED POTENTIAL—A HIDDEN KILLER OF MANY LINEMEN 2693

Fig. 2. Accident—transfer of ground grid potential to worksite.

undisturbed. No incorrect operations had been carried out. The work was carried out on the line (see Fig. 2) after
There was no live line crossing or passing adjacent to the line grounding the line (feeder-A) at the substation end. During
under maintenance. Therefore, possibility of any physical con- the work, a ground fault occurred in another line (feeder-B).
tact or induction from any adjacent line was ruled out. However, It raised the ground potential of the substation. The ground-
during the time of the accident, another feeder breaker in the ing connection made on the de-energized line at the source
same substation which fed the line being worked on tripped due end for personal protection effectively transferred the raised
to a ground fault. substation ground grid potential to the worksite through the
The coincidence of this fault event and the accident was not de-energized line. Since there was only temporary grounding
considered relevant in the preliminary analysis. and no equipotential bonding connection provided at the work-
On further analysis, the cause of the accident and the rele- site, the supporting pole remained at remote ground potential.
vance of the substation feeder ground fault trip were revealed. Therefore, the entire transferred voltage appeared across the
What follows is a detailed analysis of the causes of the accident. worker’s body. The body current and its duration, caused by this
transferred voltage exceeded the tolerable limit and resulted in
a fatality. Some of similar accidents, which had been “closed”
B. Accident in Detail
without finding the real cause, were also analyzed. From the
The power transformer in the distribution substation has records, it was noted that, during the time of these accidents,
10-MVA capacity, 110 kV/11 kV ratio, and delta/wye con- one of the other feeder breakers of the respective substation had
nected with solidly grounded neutral. All of the outgoing feeder tripped due to ground faults as well. The protective grounds
lines were overhead lines with no dedicated neutral or ground on the isolated line also remained undisturbed both at the
conductor. A ground wire of a 110-kV incoming feeder was substation and at the worksite in all of the cases. A record of es-
kept isolated from the substation ground grid. tablishing equipotential bonding was found in none of the cases.
2694 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 51, NO. 3, MAY/JUNE 2015

V. D ISTRIBUTION OF G ROUND FAULT C URRENT Since Igw = 0 and the supply is fed by a single source
through the delta/star-connected power transformer, Ig = IF .
The GPR of a substation depends upon both ground grid
Therefore,
resistance and ground grid current. For a distribution substation,
normally, the ground grid resistance is high, and the ground grid
GPR = IF × Rg . (1)
current which is a portion of the ground fault current is also
high, relative to the transmission substation. Let us see why it
Since the entire quantity of the fault current accounts for the
is so by comparing the grid currents of these substations, for a
GPR, the GPR and its effects are normally very high in distri-
ground fault external to the substations, in detail.
bution substations in comparison to a transmission substation.
1) A transmission line normally interconnects many sources. The following sections explain in detail how the transferred
For a ground fault on a transmission line, multiple sources ground potential causes a hazard in a distribution system having
feed the fault, and hence, the current which returns to an no ground conductor during a de-energized line maintenance.
individual source is only a small portion of the total fault
current.
However, the distribution feeders (nongrid feeders) are VI. E FFECT OF G ROUNDING AT S UBSTATIONS
normally fed by a single source. Hence, the entire fault
current has to return to that particular source. Grounding a de-energized line at the substation end to carry
2) The transmission towers are steel structures, and the lines out a maintenance work outside the substation does not raise
always run with ground wires whose ends are normally any problem if the ground grid potential of the substation re-
connected to the source neutrals. For a ground fault out- mains within the tolerable limit of the line worker. Controlling
side the substation, only a small portion of the fault cur- the ground grid potential within this limit during the work is
rent returns to the source neutral through the ground grid, practically impossible because it requires isolation of the entire
and the remaining portion returns through the ground substation from all sources of supply. We shall discuss the
wires of both the faulty line and other transmission lines, hazards of the transferred potential caused by the grounding
which offer metallic paths to the source neutral. practice in detail.
However, the distribution feeders normally run with-
out any neutral or ground conductors. Also, the ground A. Transferred Potential Versus Step and Touch Potentials
wire of the incoming transmission line of a distribution
substation is usually isolated from the substation ground During a ground fault, a rise in potential possibly on the order
grid to avoid transfer of the substation ground potential of thousands of volts for a fraction of a second is permitted on
to nearby tower bases. Therefore, for a ground fault on a the metallic enclosure of the substation equipment with respect
distribution line outside the substation, the entire portion to remote Earth. This raised ground potential causes potential
of the fault current is fed into the Earth at the fault gradient in and around the substation and results in step and
location, and the entire portion has to return only through touch potentials. The design of the substations should control
the substation ground grid to the source neutral. the step and touch potentials and its effects within a tolerable
3) Autotransformers in a transmission substation are nor- limit at the substation area. However, the substation design does
mally wye connected, and the neutral point is solidly not ensure safety from the raised ground potential which may
grounded. For a ground fault on the LV side in any one get transferred outside the substation area by other means. This
of the transmission lines outside the substation area, the is also not practically possible.
autotransformer LV contributes some fault current, and To control the effect of step and touch potentials, a layer
the HV side draws an equivalent current from its source. of high-resistivity material, such as gravel, is often spread
The substation ground grid offers a common path for on the Earth’s surface above the ground grid to increase the
both the LV and HV currents. Since both currents are contact resistance between the soil and the feet of persons in
almost opposite to each other, the net ground grid current the substation [4]. The increased resistance supports to keep the
(difference between the LV and HV grid currents) is still body current caused by the step and touch potential within the
lesser than the LV grid current. tolerable limit.
The power transformer in the distribution substations However, unlike step and touch potentials at a substation, the
is normally delta/wye connected. For the ground fault effect of the transferred ground potential cannot be controlled
on the LV side, the entire fault current returns to LV by design features of the substation because of the following.
neutral through the ground grid, but the current drawn 1) The magnitude of the transferred potential on the line
by the delta-connected HV from its source (equivalent to conductor with respect to the supporting pole which is
LV fault current) circulates through the line conductors at remote ground potential can be as much as the GPR.
and not through the ground grid. Hence, the ground fault 2) The transferred potential is not always a touch voltage;
current, which is entirely fed by the LV side, is the net it becomes a metal-to-metal touch voltage if the support-
ground grid current. ing pole is a metallic one. For the metal-to-metal touch
In Fig. 1, the nonavailability of the ground wire is shown as voltage, the current through the worker’s body has to be
an open circuit between points A and B, and hence, Igw is equal limited by the resistance of the worker’s body (on the
to zero. order of 1000 Ω) alone.
SURESH AND PARANTHAMAN: TRANSFERRED POTENTIAL—A HIDDEN KILLER OF MANY LINEMEN 2695

B. Transferred Potential Versus Direct Extension of Supply


Grounding a de-energized line at the source end is considered
as an essential safety measure to overcome the effects of acci-
dental reconnection of supply from the source end. However, it
transfers the ground grid potential to the worksite. To ascertain
the relative risk associated with the accidentally reconnected
supply and the transferred potential, let us compare these effects
in detail.
1) Effects of accidentally reconnected 3ph voltage: Let us
consider that a line, which is de-energized and grounded
at the worksite and not grounded at substation, is ener-
gized with a three-phase supply from the substation end
mistakenly.
For the accidental voltage at the substation, the inter- Fig. 3. Accident—equivalent circuit.
connection made for grounding the three line conduc-
tors at the worksite forms a wye-connected load. The between the line and the Earth to effectively divert the
interconnected portion acts as a neutral, and the line transferred voltage.
conductors themselves act as the load impedance. The
At the substation end, distribution feeders are normally
worksite grounding establishes connection between this
provided with isolating switches on both sides of the circuit
neutral point and Earth. Since the value of the resistance
breaker. The line can be completely isolated from the supply
offered by the worksite grounding is significant, it does
by opening these two line switches in addition to opening
not play any major role in controlling the neutral voltage
the circuit breaker. The isolated line requires three separate
at the worksite. The neutral voltage at the worksite will
operations for re-energization. Therefore, the probability for
be zero if all of the phase voltages which are mistakenly
an unintentional or negligent reconnection of the line with
extended at the source end and impedances offered by
the source is very low and can be eliminated totally by rea-
the line conductors are balanced. Only any unbalance
sonable procedures. However, the probability for GPR in the
(caused by the difference in switching times of individual
distribution substations due to a ground fault in any of the
phases or unbalance in supply voltage or unbalance in
distribution lines while carrying out de-energized line work in
impedance, etc.) will result in the development of some
another feeder of the same substation is very high. Grounding
voltage at the neutral point and, therefore, on the line
the lines at the substation presents a greater hazard than if the
conductors at the worksite.
lines are not grounded at the substation, although this seems
Since high short-circuit currents are stimulated by the
counterintuitive. The other dangerous effects of grounding the
worksite grounding, the protective relay quickly operates
de-energized line at the source end are detailed in the following
and trips the breaker, through which the voltage got
discussion.
extended accidentally.
Hence, both the magnitude and duration of the voltage
which is mistakenly extended to the worksite can be con- C. Can Worksite Grounding Control the Transferred
trolled within safe limit by grounding with equipotential Potential?
bonding at the worksite alone.
2) Effects of the transferred ground potential: Grounding Let us analyze the role of protective grounding in controlling
the line at the substation end in addition to the worksite the transferred potential.
bridges the two locations and transfers the substation The transferred potential at a worksite on a line, which is
ground grid potential to the worksite by direct conduction grounded both at the substation and worksite, due to a ground
through the metallic path offered by the three paralleled fault in another distribution line of the substation is illustrated
line conductors (see Fig. 3). in Fig. 2. The equivalent circuits are also shown in Figs. 3 and 4,
The severity and probability of the hazard caused by where
the transferred potential are high in comparison to the VS phase voltage of the power transformer;
direct extension of voltage caused by inappropriate three- ZS impedance of the source;
phase energization of the line. The details are as follows. ZF fault impedance;
1) In distribution substations, the ground grid resistance ZC combined impedance of the source and fault;
is normally high, and the ground fault on the distri- ZL net impedance offered by the three paralleled line con-
bution lines occurs frequently. Hence, the magnitude ductors between the substation and at worksite;
of the ground potential which gets transferred to the RW resistance of the grounding made at the worksite;
worksite and its frequency of occurrence are also high. Rg resistance of the substation ground grid;
2) As the transferred ground potential appears on the line RB resistance of the worker’s body;
only with respect to the mass of Earth, grounding the Ig fault current through the ground grid from the surround-
line at the worksite cannot offer a low-impedance path ing Earth.
2696 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 51, NO. 3, MAY/JUNE 2015

Fig. 5. Thevenin voltage.

Fig. 4. Simplified equivalent circuit.

Let us calculate the maximum transferred voltage while


carrying out the line work. To find out the maximum transferred
voltage, the worksite is considered to be out of the GPR zone.
1) Without protective grounding at the worksite: The ground
potential transferred to the worksite without protective
grounding at the worksite is illustrated in Fig. 1.
Fig. 6. Thevenin impedance.
From (1),

GPR = IF · Rg .

Therefore, Transferred Potential = IF · Rg = GPR.


Since there is no protective grounding at the worksite
(the line is open circuited at the worksite), the maximum
transferred ground potential will be as much as the GPR
of the substation.
2) With protective grounding at the worksite: Figs. 2–4 illus- Fig. 7. Thevenin equivalent circuit.
trate the effect of introducing the worksite grounding in
controlling the transferred potential, therefore controlling b) Thevenin voltage: The Thevenin voltage between
the body current (Ib ). points A and B can be calculated by simplifying the
a) Net impedance of the line conductors(ZL ): The line circuit (see Fig. 5). Since ZL is very small, it is
impedance (ZL ) is neglected for the calculation of the omitted in the circuit:
transferred potential due to the following reasons.
For line maintenance far away from the substation, Ig + IW = IF .
apart from opening the line switch at the substation,
another switch, if available nearby the worksite toward Since RW  Rg, IW  Ig. Hence, IW can be neglected.
the substation, is also opened. Therefore, the substa- Therefore, Ig = IF .
tion ground potential does not get transferred to the Now, the Thevenin voltage Vth ≈ IF ×Rg = GPR.
worksite. c) Thevenin impedance: Between points A and B, the
If the worksite is not far away from the substa- Thevenin impedance (ZTH ) is the parallel combina-
tion, no other line switch can be found other than tion of RW , Rg , and ZC (see Fig. 6), whose net value
the one at the substation itself. Hence, only for the is very less (less than the least among the three).
line maintenance which is carried out within a few d) Thevenin equivalent circuit: In the Thevenin equiv-
kilometer distance from the substation, isolation and alent circuit (see Fig. 7), since ZTH  RB , almost
grounding at the substation are practiced, in addition the entire ground potential of the substation gets
to grounding at the worksite. The interconnections transferred without any drop and applies across the
made for grounding the line conductors at the substa- worker’s body (RB ).
tion end and at the worksite offer three parallel paths Hence, the protective grounding at the worksite does
between these locations. Hence, the net impedance not ensure protection against the transferred potential.
(ZL ) of the short portion of the three paralleled line 3) Numerical example: Let us verify this with a numerical
conductors is significantly smaller in comparison to example (see Fig. 8).
the impedance offered by the protective grounding Let
(RW ) at the worksite (see Fig. 4), and hence, ZL is 1) the substation ground grid resistance Rg = 1 Ω;
neglected in the calculations. 2) the worksite grounding resistance RW = 10 Ω;
SURESH AND PARANTHAMAN: TRANSFERRED POTENTIAL—A HIDDEN KILLER OF MANY LINEMEN 2697

fault persists. Hence, the probability of transferred potential


when carrying out de-energized work on a distribution line
which is grounded at the source end is increased.
Since the transferred potential normally disappears within
a fraction of a second, the important question is whether
the ground potential transferred to the worksite is capable of
causing electrocution. The answer is yes. The tolerable limit of
electric shock depends on the body current and its duration.
Consider a de-energized line work carried out on a metallic
pole. Under this condition, the transferred potential at the
worksite is a metal-to-metal touch voltage. The body resistance
(1000 Ω) is the main resistance in the circuit.
Fig. 8. Fault current with numeric values. During a ground fault, a transferred potential on the order
of 1000 V is common. Assuming these values of voltage and
3) the worker’s body’s resistance RB = 1000 Ω;
resistance,
4) ground fault current IF = 1101 A.
a) Without worksite grounding: Since there is no work-
Current through the body, I = 1000 V/1000 Ω = 1 A.
site grounding and ZL is neglected, Rg and RB are
parallel For a current of I through the body, the maximum tolerable
GPR = IF · (Rg ll RB )le duration t can be calculated by using Dalziel’s formula

= 1101 × 0.999 = 1100 V. I = 116/ t(I in mA and t in s). (2)
Under this condition, the entire ground potential Let us apply the value of 1000 mA in this relation
(1100 V) transfers and applies across the worker

1000 = 116/ t which gives t = 13.4 ms.
Body current = 1100 V/1000 Ω = 1.1 A.
For the transferred voltage not to be lethal, the protective
b) With worksite grounding: Under this condition, the gear should clear the fault within this small duration. However,
same fault current (IF = 1101 A) is assumed. This normally, it takes more than 250 ms, so a fatal accident is
fault current is split among the parallel resistances 1, probable.
10, and 1000 Ω along the return path to the source Now, let us calculate the tolerable body current for this fault
neutral. clearing time of 0.25 s
Combined value of resistances (RC ) = 0.908 Ω

I = 116/ 0.25 = 232 mA.
GPR = IF .RC = 1101 × 0.908 = 1000 V.
For this value of tolerable body current, let us calculate
Here, the protective grounding at the worksite diverts
the tolerable transferred voltage. Since the body resistance
a portion of the fault current (100 A) and lowers the
is 1000 Ω, the maximum tolerable transferred potential for
voltage at the worksite but not sufficiently. The voltage
250-ms duration is 232 mA × 1 kΩ = 232 V.
on the line is still 1000 V, even after introducing the
Therefore, a transferred potential of above 232 V (e.g., 240 V)
worksite grounding
is sufficient to cause electrocution within the fault clearing time
Body current (Ib ) = 1000 V/1000 Ω = 1 A. of 250 ms.
IEEE Guide 80-2000 states: “In the 9–25 mA range, currents
The body current is still 1 A. After introducing the may be painful and can make it difficult or impossible to release
worksite grounding, it is reduced only by 100 mA. energized objects grasped by the hand” [4].
Since the potential transferred to the worksite does Therefore, a transferred potential of 25 V (25 mA × 1 kΩ) is
not appear between the line conductors and appears on sufficient to induce a person to lose control while working on a
all of these line conductors with respect to the Earth, it line supported by a metallic pole and can cause fatal accidents
is impossible to offer sufficiently low impedance path due to mechanical injuries if the worker is not fall protected.
by providing temporary grounding at the worksite to Then, how is it possible to keep the GPR less than the 25 V in
divert the transferred voltage. the design of a substation?

D. Can This Transferred Potential Cause Electrocution? E. Effect of Grounding on Magnetically Induced Voltage
Ground faults on distribution lines are frequent. Some of the The grounding made on a line at the source end for personal
ground faults are temporary and persist only for a brief period. protection can effectively suppress the electrostatically induced
Therefore, after a fault, before proceeding for line patrol, the voltages. However, on the other hand, it offers a ground Refer-
line is normally test charged, which again leads to GPR if the ence: to the electromagnetically induced voltages.
2698 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 51, NO. 3, MAY/JUNE 2015

Let us consider a radial line, which is isolated from supply In a 3w system having no ground conductor, the impedance
at a substation and runs parallel to another live line. The offered by the worksite grounding is very high in comparison
isolated line will have some voltage between its ends due to to the line impedance from the substation to the worksite, and
the magnetic field induction. For any fault on the live line, the hence, the potential transferred is not controllable by adopting
induced voltage, which depends upon the current in the adjacent any methods at the worksite.
live line, will be very high. The need for removing protective grounding at the source
If the isolated line is grounded at the substation end for line end to isolate the worksite from the transferred potential while
maintenance outside the substation, a difference in potential carrying out de-energized cable work is detailed in [6].
which exists on the line conductor at the worksite with respect The distribution of power using only three line conductors
to the substation end will now get transferred and appear on the (without ground wire) is a common practice in many countries.
line conductor at the worksite with respect to the local ground. Surprisingly, this problem that is unique to the widely used
This transferred voltage cannot be sufficiently diverted by pro- 3w distribution system discussed in this paper has not been
viding safety grounding on the line additionally at the worksite. highlighted in any safety codes. The authors believe that this
In IEEE 1048 [2], the effects of the induced voltage at the specific distribution system and the associated hazard caused
worksite arising due to the provision of protective grounding by the transferred potential need to be specifically addressed in
on the line at the source end are detailed. relevant industry standards. Addressing this situation in relevant
Hence, to safeguard the worker from the effects of elec- standards can prevent accidents and fatalities that are occurring
tromagnetically induced voltage during the de-energized line now. It is the hope of the authors that this paper initiates this
work, grounding shall not be provided at the source end. On the discussion and results in the standards addressing this hazard
other hand, the voltage, if any, due to electrostatic induction being modified so lives can be saved in the future.
as well as the electromagnetic induction can be effectively
controlled by establishing the equipotential zone in addition to VIII. C ONCLUSION
the grounding at the worksite.
The practice of grounding an isolated distribution line at the
source end effectively suppresses the voltages arising out of
VII. S AFETY P ROCEDURE I NCREASES THE H AZARDS
accidental extension such as physical contact with another live
Applying of Hierarchy of Hazard Control Measures provided line. On the other hand, this practice transfers the substation
in American National Standard Institute (ANSI) Z10 for Arc ground potential to the worksite during GPR. The first one
flash hazard is detailed by Valdes in his paper [3]. Similarly, it is a rare event, and its effects can further be minimized. The
can be applied for the transferred potential hazards also. second one of transferring substation ground potential is severe
ANSI Z10 identifies a ranking for specific types of hazard because GPR is a daily event in a distribution substation, and
mitigation methods. At the top of the list is “elimination of the transferred voltage can be as high as the GPR. Hence,
the hazard.” A total elimination of the activity, equipment, grounding at the source end, which has been considered as
environment, system, or situation that creates the hazard could an essential and obviously appropriate safety practice, has an
fall in this category. Since line conductors which are isolated unintended consequence that is a greater hazard than the hazard
from the supply and grounded at the substation become live it seeks to prevent.
for every GPR, handling these GCs should be treated as a live Many distribution companies have framed a rule of practice
work, and for elimination of the hazard, the work should not be to provide protective grounding on the line at the source end
carried out on the line with protective grounding at the source before carrying out a de-energized line work. Hence, this paper
end. However, presently, work on the line which is grounded at proposes the following.
the substation is treated as a de-energized line work, and hence, 1) The practice of providing protective grounding at the
the work is normally carried out without wearing insulating source end during de-energized line work shall be dis-
devices such as boots and gloves. Here, the entire safety against carded to prevent the transferred potential. The protective
shock rests only on how effectively the equipotential zone can grounding at the worksite alone should be practiced along
be established at worksite. with equipotential bonding connection as per IEEE stan-
IEEE Guide 80-2000 [4] states the following. dard 1048 [2].
1) “People often assume that any grounded object can be 2) To avoid accidents, the dangerous effects of the trans-
safely touched. A low substation ground resistance is not, ferred potential caused by the provision of protective
in itself, a guarantee of safety.” grounding at the source end shall be described in IEEE
2) “It is impractical, and often impossible, to design a Std. 1048—Guide for Protective Grounding of Power
ground grid to control the touch voltage caused by ex- lines, IEEE Std. 80-2000—Guide for Safety in AC Sub-
ternal transferred voltages.” station Grounding, British Std. 7430—Code of Practice
Handling the line conductors which are grounded at the for Earthing, Indian Std. 3043—Code of Practice for
source end is equivalent to touching the ground grid from the Earthing, etc.
remote Earth. Establishing an equipotential zone at the worksite is indeed
Again, it is clearly stated in [5], as “the amount of rise in a very good safety measure. It can help in overcoming the
potential on the line at the worksite is a function of the relative effect of accidental voltages including the transferred potential.
conductor and Earth impedances.” However, it cannot prevent the transferred potential. It is not
SURESH AND PARANTHAMAN: TRANSFERRED POTENTIAL—A HIDDEN KILLER OF MANY LINEMEN 2699

possible to establish an equipotential zone if the worker is K. Suresh (M’13) received the Associate Member
handling the line conductors when supporting his body over a title (B.E. degree equivalent) from The Institution of
Engineers (India), Calcutta, India, in 1993.
wooden or concrete pole or when standing on the ground. From 2003 to 2015, he was an Assistant Engineer
The three-wire distribution network running with no neutral with Meter and Relay Tests, TANGEDCO, Chennai,
or ground wire becomes live during every GPR if grounding India, where he is currently an Assistant Executive
Engineer with Special Maintenance. He is a Certified
the de-energized line at the source end is practiced. Hence, for Energy Auditor and is currently conducting research
elimination of the hazard which is ranked at the top of the list on “Hazards in the Present Protective Grounding
for hazard mitigation identified by ANSI Z10, the practice of Practices” and making efforts to incorporate the
safety aspects in relevant standards. The research
grounding the line at the source end needs to be discarded. gains importance because, within a year, over five fatal accidents were caused
by the grounding practice in a small region (within 50-km radius) of a
distribution company, and the hazardous practice is still continued by many
ACKNOWLEDGMENT countries, including India.
The authors would like to thank Er. K. Apparswamy,
CE/GTS/Chennai (Retd.) for sharing his experience in this
area to improve the paper. The authors are also thankful to
Engineers K. Mounagurusamy, P. Tamilmani, V. G. Manoharan,
M. Palaniyandi, G. Kuruchi, M. Manivelu, P. Bagavathiraj,
S. Nirmalatha, K. Natarajan, G. Velumani, C. Wilson,
J. Prabaharan, A. Krishnavel, M. Ramesh, and M. Venkatesan
for their contributions in carrying out the research.

R EFERENCES
[1] R. E. Mueller and E. F. Richards, “Temporary protective grounding of S. Paranthaman (M’13) is currently working to-
distribution circuits,” in Proc. 21st Annu. North-Amer. Power Symp., 1989, ward the M.Tech. degree in energy engineering (part
pp. 270–280. time) at the Dr. M.G.R. Educational and Research
[2] Guide for Protective Grounding of Power Lines, IEEE Std 1048-2003, Institute University, Chennai, India.
pp. 14, 25. From 1995 to 2010, he was an Assistant Engineer
[3] M. E. Valdes, “Adapting failure mode and effects analysis (FMEA) to select and an Assistant Executive Engineer with the North
hazard mitigation measures,” in Conf. Rec. 59th IEEE IAS Annu. Meeting Chennai Thermal Power Station, TANGEDCO,
PCIC, 2014, pp. 1–10. Chennai, India, where he is currently an Assistant
[4] Guide for Safety in AC Substation Grounding, IEEE Std 80-2000, pp. 8, 11, Executive Engineer with the Environment Manage-
and 26. ment Cell. As a Certified Energy Manager, he is
[5] N. Nichols and D. D. Shipp, “Designing to avoid hazardous transferred currently working to explore new ways of harnessing
Earth potentials,” IEEE Trans. Ind. Appl., vol. IA-18, no. 4, pp. 340–347, green energy at low cost suitable to India.
Jul. 1982. Mr. Paranthaman is an Associate Member of The Institution of Engineers
[6] “Worker protection while working de-energized underground distribution (India). He passed the Section A&B examination of IEI in electrical engineering
systems,” IEEE ESMOL Subcommittee 15.07 Paper. in 1993.
Copyright of IEEE Transactions on Industry Applications is the property of IEEE and its
content may not be copied or emailed to multiple sites or posted to a listserv without the
copyright holder's express written permission. However, users may print, download, or email
articles for individual use.

You might also like