Professional Documents
Culture Documents
1-1
1.1 About This Chapter ................................................................................ 1-1
1.2 Maintenance Personnel Qualifications ................................................... 1-1
1.3 Major Instruments and Meters ................................................................ 1-2
1.4 Troubleshooting Procedure .................................................................... 1-2
1.4.1 Collecting Fault Information ........................................................... 1-3
1.4.2 Locating and Clearing Faults ......................................................... 1-4
1.4.3 Verifying Troubleshooting Result ................................................... 1-4
1.5 Methods for Locating Faults ................................................................... 1-4
1.5.1 Analyzing Original Information ....................................................... 1-4
1.5.2 Analyzing Alarm Information .......................................................... 1-5
1.5.3 Analyzing Indicator States ............................................................. 1-5
1.5.4 Analyzing Interface Signaling Tracing Message ............................ 1-5
1.5.5 Analyzing Faults with Apparatus and Meters ................................. 1-5
1.5.6 Analyzing Faults Through Comparison and Interchange ............... 1-6
1.5.7 Analyzing Faults with Performance Measurement and
Statistics .................................................................................................. 1-6
1.6 Contacting Huawei Technical Support ................................................... 1-6
1.6.1 Technical Support System ............................................................. 1-6
1.6.2 Contact Approaches to Technical Support .................................... 1-6
1.6.3 Service Flow for Customer Complaints.......................................... 1-7
1.6.4 Preparations before Seeking Technical Support ........................... 1-7
Chapter 2 Locating and Handling Cell Faults ............................................... 2-1
2.1 About This Chapter ................................................................................ 2-1
2.2 Fundamental Knowledge........................................................................ 2-1
2.3 Logical Cell Cannot Be Set Up ............................................................... 2-1
2.4 The 120-ohm E1 Cable is Abnormal ...................................................... 2-3
2.5 Cell Cannot Be Set up and Multi-Frame Out-of-Sync Alarm Is
Reported at RNC .......................................................................................... 2-5
2.6 Only One Cell Can Be Set up After Modification of Cell Radius ............ 2-6
2.7 RNC Deletes Cell after Receiving Cell and Common Transport
Channel Setup Response Message from NodeB ......................................... 2-6
2.8 RNC Sends a CELL SETUP REQUEST Message and NodeB
Responds with a CELL SETUP FAIL Message Directly ............................... 2-8
Chapter 3 Locating and Handling Service Faults ......................................... 3-1
3.1 About This Chapter ................................................................................ 3-1
3.2 UE Sends RRC CONN REQ and RNC Responds with RRC CONN
REJ............................................................................................................... 3-1
3.3 Calls Are Dropped Due to Soft Handover Failure .................................. 3-2
3.4 Only Hard Handover Succeeds during High-Speed Services ................ 3-2
3.5 Multiple 384 kbps Data Services Fail to Be Activated ............................ 3-3
Chapter 4 Locating and Handling O&M Faults ............................................. 4-1
4.1 About This Chapter ................................................................................ 4-1
4.2 Downloading Software Lasts Too Long or Fails ..................................... 4-1
4.3 Starting Built-in FTP Server Fails ........................................................... 4-2
4.4 Logging in to NodeB in Near End Fails after NodeB Is Restarted
upon Completion of Downloading Data Configuration File........................... 4-3
4.5 Signals in a Cell Are Weak ..................................................................... 4-4
4.6 Copying Files through Telnet Fails ......................................................... 4-5
Appendix A Flow Chart ................................................................................... A-1
A.1 Overview ................................................................................................ A-1
A.2 Cell Setup .............................................................................................. A-2
A.3 Location Updating .................................................................................. A-4
A.4 Call Initiation .......................................................................................... A-6
A.5 Call Termination ..................................................................................... A-9
A.6 PDP Activation & Deactivation ............................................................... A-12
Index .................................................................................................................
HUAWEI
WCDMA NodeB
Maintenance Manual - Troubleshooting
V100R003
WCDMA NodeB
Maintenance Manual
Volume Troubleshooting
BOM 31033277
Huawei Technologies Co., Ltd. provides customers with comprehensive technical support
and service. Please feel free to contact our local office or company headquarters.
Website: http://www.huawei.com
Email: support@huawei.com
Copyright © 2004 Huawei Technologies Co., Ltd.
Trademarks
All other trademarks mentioned in this manual are the property of their respective
holders.
Notice
The information in this manual is subject to change without notice. Every effort has
been made in the preparation of this manual to ensure accuracy of the contents, but
all statements, information, and recommendations in this manual do not constitute
the warranty of any kind, express or implied.
Summary of Updates
This section provides the update history of this manual and introduces the contents of
subsequent updates.
Update History
This manual is updated for a major product version to maintain consistency with system
hardware or software versions and to incorporate customer suggestions.
Updates of Contents
Updates between manual versions are cumulative. Therefore, the latest manual
version contains all updates made to previous versions.
1) Adding index.
4) Optimizing the procedure of handling each type of faults and presenting specific
command to be used.
About This Manual
Release Notes
Organization
This manual includes four chapters, one appendix and one index:
Chapter 2 Cell Faults: presents major troubleshooting methods for cell faults.
Chapter 3 Service Faults: presents major troubleshooting methods for service faults.
Intended Audience
Conventions
I. General conventions
Convention Description
Arial Normal paragraphs are in Arial.
Arial Narrow Warnings, cautions, notes and tips are in Arial Narrow.
Convention Description
Bold Headings, Command, Command Description are in boldface.
Terminal Display
Terminal Display is in Courier New; message input by the user via the
terminal is in boldface.
II. Symbols
Eye-catching symbols are also used in the manual to highlight the points worthy of
special attention during the operation. They are defined as follows:
Table of Contents
i
Maintenance Manual – Troubleshooting
WCDMA NodeB Table of Contents
3.4 Only Hard Handover Succeeds during High-Speed Services ........................................... 3-2
3.5 Multiple 384 kbps Data Services Fail to Be Activated ....................................................... 3-3
ii
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
Note:
This manual only focuses on general troubleshooting procedure and methods of alarms. For details about
fault alarms and corresponding handling suggestion, refer to the online help of the alarm management
system.
I. Technical Expertise
1-1
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
To locate a fault effectively, you have to be certificated and be familiar with operations
associated with NodeB. It is advised that some serious faults be handled by the
personnel trained by Huawei.
In addition, you havev to keep in mind the following:
z Which operations lead to partial or entire service failure.
z Which operations cause damage to the equipment.
z Which operations can be taken as emergency measures or backup measures.
1-2
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
Start
Collect fault
information
End
1-3
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
Note:
Make analysis and judgment of a fault based on not only fault symptoms, but also various original
information collected, for example, system running log.
After clearing a fault, verify that you have correctly cleared the fault through the
troubleshooting methods suggested. This step is mandatory.
1-4
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
Alarm information refers to that output by the alarm control module in the NodeB. You
can collect alarm information through the following approaches::
z Alarm tone
z LED indicator
z Alarm management system
Alarm information reported by alarm managenent system of LMT includes:
z Alarm meaning
z Possible causes
z Handling suggestions
The above information covers various aspects such as hardware, softeware, RF,
transport, and so on. It provides a significant basis for troubleshooting.
On each board in NodeB, there are running status indicators and alarm indicators.
They directly reflect working states of boards, circuits, links and nodes.
Analyzing indicator states is a procedure to locate a possible cause range for a fault in
the initial troubleshooting stage. Because indicator state analysis cannot provide all
possible informaition, it usually works with alarm informaitn analysis.
Interface signaling tracing plays an important role in locating service failures during call
connection or signaling coordination between NodeB and RNC. Generally, you can find
out the cause for a call failure directly from the tracing results.
You can trace Iub interface signaling by the standard interface tracing function of
NodeB O&M system. You can also carry out interface signaling tracing through devices
of a third party, such as NetHawk.
It is a common method to locate a fault with apparatus and meters. Since measurement
data obtained by using apparatus and meters reflects the essence of a fault visually,
apparatus and meters are widely used in power test, signaling tracing, waveform
analysis, bit error rate (BER) detection, and so on.
1-5
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
You can compare the working status of a faulty part with that of a normal one to find out
causes. This method applies to the faults in a limited scope.
If you cannot locate a fault after replacing the possibly faulty parts, interchange the
possibly faulty parts (for example, boards or optical fibers) with the ones in normal
operation. After that, observe the running states of both to locate the fault. This method
applies to rather complex occasions.
You can analyze some key performances and resources, such as CPU/DSP occupancy,
and E1 BER, by using the performance measurement and statistics function provided
by O&M system. Judge whether the system is in normal operation by comparing the
measurement results with the corresponding values of normal operation.
Note:
Contact approaches to Huawei local offices are available in the technical support website
http://support.huawei.com.
1-6
Maintenance Manual – Troubleshooting Chapter 1
WCDMA NodeB General Troubleshooting Procedure and Methods
Huawei has developed a service flow for customer complaints. The following describes
Huawei service flow for you to ask for technical support efficiently.
You can feed back problems of Huawei products by telephone, fax, regular mail, email,
and so on. You can also feed back your problems to engineers in Huawei local offices
who will record the problems in Huawei Problem Management System and take care of
the problem handling process.
Before turning to Huawei technical support system for troubleshooting, make the
following preparations to handle the trouble more efficiently.
Make preparations for debugging before turning to Huawei technical support system for
troubleshooting help.
1-7
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
1) Symptom 1
z The logical cell cannot be set up.
z Use DSP CELL to query the local cell resources on the NodeB O&M system and
find that the local cell resources are available.
2-1
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
z Use DSP CP to query the states of both NCP and CCP on the NodeB O&M system
and find that the states of both NCP and CCP are normal.
z Use ADT RES to request the RNC for resource audit on NodeB O&M system. The
RNC does not send resource audit command, but continuously sends the NBAP
RESET REQ message to the NodeB.
z Start Iub interface tracing on the NodeB O&M system and the tracing message
shown in Figure 2-1 is displayed.
2) Symptom 2
z The logical cell cannot be set up.
z Use DSP CELL to query the local cell resources on the NodeB O&M system and
find that the local cell resources are available.
z Use DSP CP to query the states of both NCP and CCP on the NodeB O&M system
and find that the states of both NCP and CCP are normal.
z The RNC sends only a resource audit command but no CELL SETUP REQUEST
message.
II. Troubleshooting
2-2
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
3) Compare the configuration for NCP and CCP in NodeB with that in the RNC. And
will find there is any inconsistency
4) Use RMV CP to remove the NCP and CCP on NodeB O&M system
5) Use ADD CP to add NCP and CCP on NodeB O&M system. modify them as
consistent with that in the RNC.
z For the second case:
1) Check whether the maximum downlink power in the audit message from the
NodeB is smaller than that configured in the RNC. For example, if the maximum
downlink power from the NodeB is 398 (unit: 0.1 dBm) and the value configured in
the RNC is 400 (unit: 0.1 dBm), the logical cell cannot be set up.
2) On the O&M system , use MOD CELL to modify the maximum transmit power of cell
in the RNC to that no more than the reported value in NodeB.
3) If the logical cell can be set up successfully in this case, it indicates the fault has
been cleared. Otherwise, follow the next step to clear the fault.
4) On the NodeB O&M system, use DSP CELL to check whether the local cell ID is
consistent with that negotiated with the RNC.
5) If not, use RMV LOCELL to delete the cell on the NodeB O&M system..
6) On the NodeB O&M system, use ADD LOCELL to add a new local cell with the
local cell ID is the same as that negotiated with the RNC.
III. Verification
After the measures above, if the cell setup between the RNC and the NodeB succeeds,
including cell setup, common transport channel setup and system message updating, it
means you have cleared the fault.
A 120-Ω E1 cable connects the NodeB to the RNC properly, and the data configuration
is correct. However, the state of the E1 cable state is abnormal when queried with DSP
E1T1.
II. Troubleshooting
Generally, the fault is caused by incorrect setting of DIP switches on the NDTI and E1
lightning protection board. Therefore, clear the fault by correcting settings of DIP
switches. Figure 2-2 shows the DIP switches on the NDTI.
The grounding status of the Rx end of E1 cables are set on the two E1 lightning
protection boards on the top of the NodeB cabinet, as illustrated in Figure 2-3.
z J4: used to set the grounding status of the Tx end of E1/T1 cables
z J5: used to set the grounding status of the Rx end of E1/T1 cables
2-3
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
S7 S4
J2
S8 S3 board indicators
S9 S6 J9
S10 S5
J21 J22
S11
J3
Note:
For description of DIP switches on the NDTI, refer to board information in online help of NodeB O&M
system.
2-4
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
III. Verification
Use DSP E1T1WORKMODE to query E1 work mode on the NodeB O&M system. If the
line matching impedance of the query result is 120Ω, it means the fault has been
cleared.
Use DSP E1T1 to check whether the state of E1 cable is normal on the NodeB O&M
system. If yes, it means that the fault has been cleared.
II. Troubleshooting
The most possible cause for this fault is that E1 working mode in the NodeB is not
consistent with that in the RNC. Clear the fault in the steps described in the following:
1) Use DSP E1T1WORKMODE to query E1 work mode on the NodeB O&M system.
2) Use DSP E1T1 to query E1 work mode on the RNC O&M system.
3) Compare the two work modes.
4) On the NodeB O&M system, use SET E1T1WORKMODE to modify the E1 work
mode to be consistent with that in RNC.
III. Verification
After the E1 working mode of the NodeB is consistent with that of the RNC, check
whether the multi-frame out-of-synchronization alarm in the RNC is automatically
cleared and whether the cell can be successfully set up.
2-5
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
Before the modification of cell radius, both the two cells, cell 0 and cell 2, can be set up
normally. After their radius is modified from 256*78 m to 1536*78 m, cell 2 fails to be set
up.
On the NodeB O&M system, use DSP CELL to query the state of the local cell and find
that it is unavailable due to lack of baseband resources.
II. Troubleshooting
The fault must be caused by lack of access resources. A set of access resources
includes an access ASIC and an access DSP. When the cell radius is smaller than or
equal to 384*78 m, a set of access resources can support three cells. When the cell
radius is greater than 384*78 m, it can support only one cell.
Clear the fault as follows:
1) Check the number of NULPs.
2) If there is only one NULP and a cell whose radius is greater than 384*78 m is
required, Use ADD BRD to add one NULP on the NodeB O&M system, and insert
one NULP in NodeB cabinet.
3) Otherwise, on the NodeB O&M system, use MOD LOCELL to modify the radius
of both cells as smaller than or equal to 384*78 m.
III. Verification
After the procedure above, both cells can be successfully set up.
The RNC sends a CELL SETUP REQUEST message to the NodeB, and the NodeB
reports a CELL SETUP RESPONSE message to the RNC. After that, RNC sends two
COMMON TRANSPORT CHANNEL SETUP REQUEST messages. Upon receipt of
two COMMON TRANSPORT CHANNEL SETUP RESPONSE messages from the
NodeB, the RNC then sends a CELL DELETION REQUEST message instead of a
SYSTEM INFORMATION UPDATE REQUEST message to the NodeB.
There is no alarm at the NodeB or the RNC.
2-6
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
II. Troubleshooting
The fault lies on Iub interface user plane. In this case, perform the following steps to
check whether the user plane data configuration and hardware connection of the
NodeB is consistent with those at the RNC.
Clear the fault as follows:
1) Use LST AAL2PATH to query data configuration of AAL2 path on the NodeB O&M
system.
2) Use LST AAL2PATH to query data configuration of AAL2 path on the RNC O&M
system.
3) Check whether the data configuration of the AAL2 path in the NodeB is consistent
with that in the RNC.
z The data configuration is consistent. Go to step 7).
z The data configuration is not consistent. Go to step 4).
4) If there is any inconsistency, use RMV AAL2PATH to delete the AAL2 path on the
NodeB O&M system.
5) On the NodeB O&M system, use ADD AAL2PATH to add an AAL2 path, and
modify data configuration as consistent with that in the RNC.
6) Check whether the fault is cleared. Refer to “III. Verification”.
z The fault is cleared. The fault handling ends.
z The fault is not cleared. Go to step 7).
7) Check that the E1/T1 or STM1 ports configured with AAL2 path between the
NodeB and the RNC are connected correctly.
8) Re-connect them if they are not connected correctly.
9) Check whether the fault is cleared. Refer to “III. Verification”.
z The fault is cleared. The fault handling ends.
z The fault is not cleared. Go to step 10).
10) On the NodeB O&M system, query the ATM address of ALCAP configured in the
NodeB though LST AAL2NODE.
11) On the RNC O&M system, query the corresponding data of RNC through LST
AAL2RT.
12) Check whether the ATM address of ALCAP configured in NodeB is consistent with
that in RNC.
13) If not consistent, use RMV AAL2NODE to delete ALACP on the NodeB O&M
system.
14) Use ADD AAL2NODE to add ALCAP on the NodeB O&M system. The
configuration data at NodeB is consistent with that at RNC.
III. Verification
After the procedure above, if Cell Setup procedure succeeds, including cell setup,
common transport channel setup and system message updating, it means the fault has
been cleared.
2-7
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 2 Locating and Handling Cell Faults
II. Troubleshooting
III. Verification
After the procedure above, the logical cell can be set up normally. The local cell and
logical cell are both available.
2-8
Maintenance Manual – Troubleshooting Chapter 3 Locating and Handling Service
WCDMA NodeB Faults
3.2 UE Sends RRC CONN REQ and RNC Responds with RRC
CONN REJ
I. Fault Symptoms
On the Uu interface, the UE sends a RRC CONN REQ message, but RNC responds
with a RRC CONN REJ message. In addition, on the Iub interface, the RNC sends a RL
SETUP REQ message and the NodeB responds with a RL SETUP RSP message.
However, the RNC does not send an AAL2 ESTABLISH REQUEST message.
II. Troubleshooting
This fault is caused by the inconsistent setting of CCP parameters between the RNC
and the NodeB.
Clear the fault as follows:
1) Use LST CP to query the CCP port configuration of the NodeB on the NodeB O&M
system.
2) Use LST SAALINK to query the CCP parameter configuration of the RNC on the
RNC O&M system.
3) Check that the setting of CCP parameters (including CCP port No., VPI, VCI, UNI
port No., IMA group No.) in the NodeB is consistent with that in the RNC.
4) If they are inconsistent, use RMV CP to remove the CCP.
5) Use ADD CP to a new CCP and make the new CCP consistent with that in the
RNC on the NodeB O&M system.
III. Verification
Power off the UE and then power it on again to verify whether the fault has been
cleared. Observe the Uu interface messages from the RNC. If the RNC responds with a
3-1
Maintenance Manual – Troubleshooting Chapter 3 Locating and Handling Service
WCDMA NodeB Faults
RRC CONN SETUP message instead of RRC CONN REJ message, it indicates RRC
connection has been set up successfully and the fault has been cleared.
Calls are dropped in the course of soft handover. Soft handover fails.
II. Troubleshooting
Start single user tracing on the RNC O&M system and you may find the following two
cases:
Case 1: There are new links added for this user in the course of soft handover, but
there is no RL LINK RESTORE message on the Iub interface. Clear the fault as follows:
1) Query cell configuration parameter on the NodeB O&M system by using LST
LOCELLCFG.
2) Check whether cell inner handover radius is close or equal to cell radius.
3) Modify the cell inner handover radius to 2*78 m by using MOD LOCELL if it is too
large.
Case 2: There are no links newly added for this user in the course of soft handover.
Clear the fault as follows:
1) Query the configuration parameters of the neighboring cell on the RNC O&M
system by using LST INTRAFREQCELL.
2) Configure a neighboring cell correctly by using MOD INTRAFREQCELL if there
are no neighboring cells.
3) If cell neighboring relationship in the RNC is correct, compare the configuration
parameters of both cells on the RNC O&M system by using LST CELL.
4) Check whether the downlink primary scrambling codes of both cells are the same.
5) If yes, modify either of them by using MOD CELLSETUP to make them different.
III. Verification
After the procedure above, no calls are dropped and soft handover is successful.
Only hard handover, instead of soft handover, succeeds during 384 kbps services.
II. Troubleshooting
This fault occurs because the decision threshold of RNC handover rate is too low.
Clear the fault as follows:
3-2
Maintenance Manual – Troubleshooting Chapter 3 Locating and Handling Service
WCDMA NodeB Faults
1) Check that the “BEBitRateThd” is D384 on the RNC O&M system by using LST
HOCOMM.
2) Modify “BEBitRateThd” to D384 on the RNC O&M system by using SET
HOCOMM.
III. Verification
After value modification of “BEBitRateThd”, 384 kbps service is available after soft
handover. Soft handover of 384 kbps service is successful.
Not multiple high-speed (384 kbps) services but low-speed (64 kbps) services can be
activated successfully.
II. Troubleshooting
This fault occurs especially when there are not enough transport bandwidth resources.
Clear the fault as follows:
1) Start standard interface tracing on the NodeB O&M system, as shown in Figure
3-1.
Observe the Iub interface messages and you will find that the NodeB responds with an
AAL2 RELEASE CONFIRM message, after RNC delivers an AAL2 ESTABLISH
REQUEST message, as shown in Figure 3-1. Note that under normal cases, the
NodeB should respond with an AAL2 ESTABLISH CONFIRM message, as shown in
Figure 3-2.
3-3
Maintenance Manual – Troubleshooting Chapter 3 Locating and Handling Service
WCDMA NodeB Faults
2) Double click the AAL2 RELEASE CONFIRM to see the message contents, as
shown in Figure 3-3. The cause of the fault is displayed as lack of transport
bandwidth resource on the user plane.
III. Verification
After the procedure above, multiple 384 kbps services can be activated successfully.
3-4
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 4 Locating and Handling O&M Faults
Note:
This manual does not introduce such basic operations and maintenance as RF channel calibration, clock
source setting and NodeB version upgrading.
During software upgrading, it takes several hours to download the software package, or
the software package fails to be downloaded.
II. Troubleshooting
Generally, this fault occurs because of poor network quality. Clear the fault as follows:
1) Click [Start/Run].
2) Enter “ping XX.XX.XX.XX” where “XX.XX.XX.XX” refers to the IP address of the
NMPT or NodeB IPoA and observe the returned result.
z If it takes long for the system to return ping result, it indicates the network path is
too long or the IPoA bandwidth is too narrow.
z If timeout occurs continually, it indicates the network is in poor connection and
some packets may have been lost.
3) In near end maintenance mode, connect the LMT with the NMPT directly with a
crossover cable to clear the interference of poor network quality.
4) For maintenance over IPoA through RNC, check on the RNC O&M system
whether the IPoA bandwidth is too narrow by using LST IPOAPVC and LST
ATMTRF. Generally, the transport rate depends on the transmit end. For IPoA of
4-1
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 4 Locating and Handling O&M Faults
64 kbps configuration, the downloading procedure may last two hours. Increase
the IPoA bandwidth to speed up software downloading progress based on the
actual situation.
III. Verification
After the above procedure, you can speed up and succeed in downloading the
software.
During the start of the NodeB O&M system, a dialog box is displayed, prompting failure
to start the built-in FTP Server.
II. Troubleshooting
The cause of this fault is that an FTP Server has already been running in this computer.
Clear the fault as follows:
1) Click [Start/Run].
2) Enter “ftp://XX.XX.XX.XX” where “ftp://XX.XX.XX.XX” refers to the IP address of
the local computer.
z If the computer has started the FTP Server, a message will be displayed,
prompting the user to enter user name and password, or the FTP Service interface
will be displayed directly.
z If the local computer has no FTP Server, an error message will be displayed, as
shown in Figure 4-1.
3) Check whether there are other commercial FTP Servers started by observing the
task bar on the local computer.
4) Stop them if any.
5) If the operating system on the local computer is windows 2000, check whether it
has started the FTP Server by clicking [Start/Settings/Control Panel].
4-2
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 4 Locating and Handling O&M Faults
6) Select [Management Tool/Service] to check whether the system has started the
FTP Server.
7) Stop the FTP Server if yes.
III. Verification
Stop other FTP services and restart the LMT, the built-in FTP Server can be started
normally.
In near end maintenance mode, you can log in to the NodeB normally through the LMT
before downloading data configuration file. However, after the NodeB is restarted upon
the completion of downloading data configuration file, you cannot log in to the NodeB
through the LMT.
In this case, board indicators are normal.
However, you can still log in to the NodeB over IPoA
II. Troubleshooting
The fault may be caused by incorrect setting of IP address of near end maintenance
channel.
During the configuration of data configuration file, if you have forgotten the IP address
setting of the near end maintenance channel, the default IP address 17.21.2.15 will be
taken in the data configuration file.
Clear the fault as follows:
Method 1
z Log in to the NodeB over IPoA link through the O&M system.
z Configure the IP address for the near end maintenance channel by using SET IP.
z Use LST IP to check whether the IP address is successfully configured.
Method 2
z Log in to NodeB over IPoA link through the LMT.
z Open the data configuration file on the configuration management system to
modify attributes of the NodeB.
z Modify the local IP address as the value demanded.
z Download the data configuration file again.
z Restart the NodeB.
4-3
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 4 Locating and Handling O&M Faults
III. Verification
After the procedure above, you can log in to the NodeB in the near end normally.
II. Troubleshooting
4-4
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 4 Locating and Handling O&M Faults
III. Verification
After the procedure above, the fault is cleared if the test device can detect signals of
normal intensity.
Either at the near end or at the far end, you fail in copying files from the computer to the
NodeB or from the NodeB to the computer through Telnet.
II. Troubleshooting
If you can log in to NodeB through Telnet, it indicates that the network is working
normally. Failure in copying files is mostly likely caused by improper operations or
incorrect settings.
Clear the fault as follows:
1) Respectively set the user name, password, and default path to “aa”, “123”, and
“C:\” for the FTP Server.
2) Run version on the Telnet, and you will get the following printout information:
-> version
VxWorks (for Motorola MPC8260 ADS) version 5.4.
Kernel: WIND version 2.5.
4-5
Maintenance Manual – Troubleshooting
WCDMA NodeB Chapter 4 Locating and Handling O&M Faults
When you copy files from the computer to the NodeB, you shall use the following
command:
5) if the “OMC ‘default’ FTP Server IP” in step 2) is different from that of the FTP
Server, run copy to copy the files as follows:
z Create a network device, and then run netDevCreate "device name:","FTP
Server IP address",1
z Run copy to copy files.
For example, you use the following command to copy files from the NodeB to the
computer:
When you copy files from the computer to the NodeB, you shall use the following
command:
III. Verification
After the above operations, you can copy files either from the NodeB to the computer or
from the computer to the NodeB.
4-6
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
A.1 Overview
This chapter presents several major flow charts, including cell setup, location updating,
call initiation, call termination and PDP activation/deactivation. Any failure occurring to
any step between UE and UTRAN may cause trouble in the corresponding procedure.
A-1
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
N odeB C R N C
N C P : R e s o u r c e s t a t e in d ic a t io n
N C P : A u d it R e q u e s t
N C P : A u d it R e s p o n s e
R e s o u rc e c h e c k
-
N C P : C e ll S e tu p R e q u e s t
N C P : C e ll S e t u p R e s p o n s e
N C P : C o m m o n tra n s p o rt
c h a n n e l S e tu p R e q u e s t
N C P : C o m m o n tra n s p o rt
c h a n n e l S e tu p R e s p o n s e
A L C A P : Q A A L 2 E s t a b lis h R e q u e s t
A L C A P : Q A A L 2 E s t a b lis h C o n f ir m
N C P : C o m m o n tra n s p o rt
c h a n n e l S e tu p R e q u e s t
N C P : C o m m o n tra n s p o rt
c h a n n e l S e tu p R e s p o n s e
A L C A P : Q A A L 2 E s t a b lis h R e q u e s t
A L C A P : Q A A L 2 E s t a b lis h C o n f ir m
A L C A P : Q A A L 2 E s t a b lis h R e q u e s t
A L C A P : Q A A L 2 E s t a b lis h C o n f ir m
A L C A P : Q A A L 2 E s t a b lis h R e q u e s t
A L C A P : Q A A L 2 E s t a b lis h C o n f ir m
F A C H F P : D L S y n c h r o n iz a t io n
c o n tro l fra m e
F A C H F P : U L S y n c h r o n iz a tio n
c o n tro l fra m e
F A C H F P : D L S y n c h r o n iz a t io n
c o n tro l fra m e
F A C H F P : U L S y n c h r o n iz a t io n
c o n tro l fra m e
P C H F P : D L S y n c h r o n iz a t io n
o n tro l fra m e
P C H F P : U L S y n c h r o n iz a tio n
c o n tro l fra m e
P C H F P : D L N ode
S y n c h r o n iz a t io n c o n t r o l f r a m e
P C H F P : U L N ode
S y n c h r o n iz a t io n c o n t r o l f r a m e
As shown in Figure A-1, RNC initiates an Audit Request, and NodeB acknowledges it
with an Audit Response. RNC sends a Cell Setup Request upon receipt of the Audit
Response. After the cell setup procedure finishes, the procedure to setup common
channels, common measurement and system message updating starts. The success
A-2
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
of system message updating indicates completion of cell setup. In this case, UE can
stay and make calls in this cell. Location for cell faults must refer to cell state, Iub
interface tracing messages, fault information of NodeB alarm management system.
A-3
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
N ode B Serving
UE
Serving RN S RNC CN
Start R X
Q .A A L2 Establis h Request Q .A A L2
Establis h C o nfirm
Q .A A L 2 Q .A A L2
Start T X
C C C H : RRC C onnectio n Setup
R RC R RC
D C C H : R RC C o nnecti o n Setup C o mple te
R RC R RC
D C C H : R RC C o nnecti o nSetup C om plete ack
R LC R LC
DCCH : Inital D irect T rans fer
R RC R RC
Initial U E M essa ge
RA N A P (Locatio n U pdate Request) RA N A P
RA N A P Iu Re lease C o mplete
RA N A P
DCCH : R RC C o nnectio n Re lease
R RC R RC
Radio Li nk D eletio n
N BA P N BA P
Q .A A L 2 Re lease Request Q .A A L2
Release C o mple te
Q .A A L 2 Q .A A L 2
A-4
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
As shown in Figure A-2, the location updating procedure involves RACH random
access, radio link setup, transport channel synchronization, radio link deletion and
DCCH/CCCH data transport.
A-5
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
Node B Serving
UE
Serving RNS RNC CN
Start RX
Establish Confirm
Q.AAL2 Q.AAL2
Uplink Synchronisation
DCH-FP DCH-FP
Start TX
Initial UE Message
RANAP RANAP
(CM Service Request)
Establish Confirm
Q.AAL2 Q.AAL2
Radio Link Reconfiguration
NBAP NBAP
Prepare
A-6
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
No d e B
S erv ing R NS S erv ing
UE CN
R NC
Q .A A L2 Establish Request Q .A A L2
Establish C onfirm
Q .A A L2 Q .A A L2
Ap p ly n e w tra ns p o rt fo rm at s et
R A N AP RA B A ssignment Response
R A N AP
(Establishment )
D irect T ransfer
RA N A P RA N A P
(A lerting)
RRC D C C H : D ow nlink D irect T ransfer
RRC
D irect T ransfer RA N A P
RA N A P (C onnect)
RRC D C C H : D ow nlink D irect T ransfer RRC
Iu Release C ommand
RA N A P RA N A P
Q .A A L2 Release Request Q .A A L2
Release C omplete
Q .A A L2 Q .A A L2
D C C H : RRC C onnection Release
Q .A A L2 Release Request Q .A A L2
Release C omplete
Q .A A L2 Q .A A L2
Iu Release C omplete RA N A P
RA N A P
A-7
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
As shown in Figure A-3 and Figure A-4, call initiation is a procedure of RRC connection
setup and RAB assignment. RRC connection setup is a procedure to establish 3.4K
radio link and perform high-level signaling interworking on this link. RAB assignment is
a procedure to reconfigure the radio link for the corresponding service to meet the
requirements for transport service.
Note:
RAB represents radio access bearing. It is a term of high-level protocol and corresponds to service type
and transport layer FP respectively. RAB may contain multiple RBs, which corresponds to DCHs of the
transport layer respectively.
A-8
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
Node B Serving
UE
Serving RNS RNC CN
Paging
RANAP RANAP
Paging
Start RX
Radio Link Setup Response
NBAP NBAP
Establish Confirm
Q.AAL2 Q.AAL2
Downlink Synchronisation
DCH-FP DCH-FP
Uplink Synchronisation
DCH-FP DCH-FP
Start TX
CCCH : RRC Connection Setup
RRC RRC
RRC
RRC DCCH : Downlink Direct Transfer RRC
A-9
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
Node B
S erv in g
UE S erv in g R N S CN
R NC
E stablish C o nfirm
Q .A AL 2 Q .A AL 2
A p p ly new tra ns p o rt fo rm at s et
R A B A ssig nm e nt R es po nse
R AN AP R AN AP
(E stablish m e nt )
D C C H : U plin k D irect Tra nsf er
RRC RRC
D irect Tra nsf er
R A N AP R AN AP
(Alerti ng)
D C C H : U plin k D irect Tra nsfer
RRC RRC
D irect Tra nsf er R AN AP
R A N AP (C o nn ect)
D irect Tr an sfer R A N AP
R A N AP
(C o nnect Ac k no w led ge)
D C C H : D o w nlin k D irect Tra nsf er RRC
RRC
A-10
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
As shown in Figure A-5 and Figure A-6, the call termination procedure is similar to call
initiation procedure except that there is a paging procedure ahead in the call initiation
procedure.
Paging procedure: Once UE registers in a network system, it will be arranged in a
paging group. If an UE in a paging group is being paged, NodeB will send the
corresponding periodic Paging Indication (PI) over the PICH channel. Upon detection
of PI, UE wakes up from the dormant state and check whether there are any paging
messages in the next PCH frame. UE initiates random access if any, or backs to the
dormant state to go on monitoring PICH if otherwise.
A-11
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
Start RX
Establish Confirm
Q.AAL2 Q.AAL2
Downlink Synchronisation
DCH-FP DCH-FP
Uplink Synchronisation
DCH-FP DCH-FP
Start TX
CCCH : RRC Connection Setup
RRC RRC
Radio Link Restore Indication
NBAP NBAP
Establish Confirm
Q.AAL2 Q.AAL2
Radio Link Reconfiguration
NBAP NBAP
Prepare
A
Figure A-7 PDP activation and deactivation (1)
A-12
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
Node B
Serving RNS Serving
UE CN
RNC
激活成功
PDP activation successful
DCCH:
Uplink Direct Transfer(0a46)
RRC RRC
Direct Transfer
RANAP
RANAP (Dea. PDP Request)
RAB Assignment Request RANAP
RANAP
A-13
Maintenance Manual – Troubleshooting
WCDMA NodeB Appendix A Flow Chart
As shown in Figure A-7 and Figure A-8, PDP activation procedure is similar to call
initiation procedure except that the bearing service is different. The connection setup in
the call initiation procedure bears AMR voice and that in PDP setup bears data service.
PDP deactivation procedure is similar to the UE initiated call termination procedure.
A-14
Maintenance Manual – Troubleshooting
WCDMA NodeB Index
Index
F P
fault, clearing, 1-4 PDP activation & deactivation, A-12
fault, collecting information, 1-3
fault, locating, 1-4 R
flow char, A-1 RNC deletes cell, 2-6
RRC connect is rejected, 3-1
G
general methods, 1-1 S
service faults, 3-1
I signals in a cell are weak, 4-4
instruments and meters, 1-2 starting built-in FTP server fails, 4-2
L T
location updating, A-4 troubleshooting procedure, 1-2
i-1