I S O 9 0 0 1:2008
ISO14001:2004
Advanced Power Supplier
Digital Series UPS D6K(S) -3D20KS parallel redundancy adopts double conversion true on-line structure,
which can avoid the loading strike from abnormal power and can ensure the output stabilization and
Miniaturization
On-Line maintenance
LOAD LOAD
If you have the optional maintenance switch, just
need to transfer the UPS to repair mode, you can
repair the UPS on- line safely, when UPS is providing
the uninterrupted electric power to the loads; With
N+1 parallel redundancy function, even if the utility
is interrupted when the UPS is under the repair, your
valuable devices still can get the high quality power
supply.
Sketch of parallel redundant
Parallel Redundant N+X Max: 60KVA
Complete Function
DC Startup function let you still use UPS when main fails. Timing startup and shutdown, remote monitor functions
realize unmanned purpose. Strong charging capability is convenient to extend the backup time. Intelligent
charging management mode prolongs the batter y life to save expense. Automatic restart function can start UPS
automatically after batter y discharged fully. Complete function design brings more convenience for your work.
Frequency 50/60Hz±10%
Voltage 220/230±1%VAC
Same with input (utility mode)
Output Frequency
50/60Hz±0.5 ( battery mode )
( 192VDC )
Dimension 515x250x616 515x240x460 515x250x616 515x240x460 515x250x616
(D x W x H)(mm)
570x260x717(240VDC)
192VDC
56 18.5 61 20 27 35 35.5
Net Weight(Kg)
240VDC
90 35 93 38 39 55 55
Remark: 1. 'S' means long backup model. Meet International EMC standards
2. Customizable output PF=0.9.
Altitude( m ) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Coefficient of reduction 100% 95% 91% 86% 82% 78% 74% 70% 67%
If UPS is used in elevation above 1000m, it is necessar y to use the declining rating output, the drop coefficient is above the table.
※The above parameters can be adjusted and changed, please prevail in kind.