You are on page 1of 4

Outgoing VCB

Test Module
Name: OMICRON QuickCMC Version: 3.00
Test Start: 12-Oct-2019 21:56:09 Test End: 12-Oct-2019 22:03:47
User Name: Manager:
Company:

Test Results

Title: 50/51 Step-1 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 7,500 A 0,00 ° 50,000 Hz
I L2 7,500 A -120,00 ° 50,000 Hz
I L3 7,500 A 120,00 ° 50,000 Hz

Generator Settings
I L1 7,500A 0,00° +90°
I L2 7,500A -120,00° I L3
I L3 7,500A 120,00°

I L1
180° 0°

I L2
8,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
2,914s n/a n/a

Title: 50/51 Step-1 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 10,00 A 0,00 ° 50,000 Hz
I L2 10,00 A -120,00 ° 50,000 Hz
I L3 10,00 A 120,00 ° 50,000 Hz

Generator Settings
I L1 10,000A 0,00° +90°
I L2 10,000A -120,00° I L3
I L3 10,000A 120,00°

I L1
180° 0°

I L2
10,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
1,697s n/a n/a
Title: 50/51 Step-2 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 30,00 A 0,00 ° 50,000 Hz
I L2 30,00 A -120,00 ° 50,000 Hz
I L3 30,00 A 120,00 ° 50,000 Hz

Generator Settings
I L1 30,000A 0,00° +90°
I L2 30,000A -120,00°
I L3 30,000A 120,00° I L3

I L1
180° 0°

I L2

40,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,059s n/a n/a

Title: 50/51 Step-2 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 40,00 A 0,00 ° 50,000 Hz
I L2 40,00 A -120,00 ° 50,000 Hz
I L3 40,00 A 120,00 ° 50,000 Hz

Generator Settings
I L1 40,000A 0,00° +90°
I L2 40,000A -120,00° I L3
I L3 40,000A 120,00°

I L1
180° 0°

I L2
40,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,049s n/a n/a

Title: 50N/51N Step-1 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1,500 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz
Generator Settings
I L1 1,500A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

2,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
2,885s n/a n/a

Title: 50N/51N Step-1 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 2,000 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz

Generator Settings
I L1 2,000A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

2,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
1,701s n/a n/a

Title: 50N/51N Step-2 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 6,000 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz

Generator Settings
I L1 6,000A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

8,0 A -90°
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,066s n/a n/a

Title: 50N/51N Step-2 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 8,000 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz

Generator Settings
I L1 8,000A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

8,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,059s n/a n/a

Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100,00% passed
Test passed