1MRK506267 WEN C en REL670 Setting Example 1 PDF
1MRK506267 WEN C en REL670 Setting Example 1 PDF
Line to :
Setting summary for REL670
Station C Voltage: 400 kV
CT ratio 2000 / 1 A
Parameter Description
CVT ratio 400 / 0.110 kV
General settings
Station
Maximum load Name: 1448 A ==>
on line: 159 ohm/ph = 88 ohm/ph" Export
Frequency A ==> 159 ohm/ph = 88 ohm/ph" Import
Station No:
Maximum loadObjectexport
Name:gives angles between sources: 22 deg
Name REL670 REL670
Object No:
SUBSTATION Station A Station A
1. Terminal identification
information contained therein. Reproduction, use
We reserve all rights in this document and in the
Unit Name:
SUBSTATION-Address 1 1
or disclosure to third parties without express
StationName:
BAYUnit No: Station A 400 OHL1 400 OHL1
authority is strictly forbidden. ©ABB PTSX
StationNumber:
BAY-ADDRESS 1 1 1
ObjectName:
DEVICE-ADDRESS 400 OHL1 1 1
Voltage
Object Number: 1 System voltage
VNOM 110 110
UnitName: Length Line length
VVPRIM-LL REL670 400 400000
UnitNumber: X1
INOM 1 Line Positive Sequence1 Reactance 1
Relay serial No
R1
IMAX A1234 Line Positive Sequence2.5 Resistance 2.5
FrequencyIPRIM
X0 50 Hz Line Zero Sequence 2000 Reactance 2000
Aux voltage
FNOM 110.000 V 50Resistance 50
R0 Line Zero Sequence
BEGIN
2. Setting of
Xm0 DISTANCE
fault locator values (LFL)
Line mutual reactance
LINE
Line length LENGTH km
unit: 100 100
Rm0 Line mutual resistance
Length LINE ANGLE 100.0 km 87.34 87.34
X1SA
CTSTARPOINT Source A reactance
X1 j30.00 ohm LINE LINE
R1SA Source
Zone 1 A resistance
R1 1.40 ohm
X0 X1SB
TripTime j90.00 Source
ohm B reactance 0.00(remote source)
0.00 0
R0 R1SB Zone 2
Source B resistance (remote source)
16.00 ohm 0
X1SA TripTime
VTprim/VTsec j19.80 Voltage
ohm 0.30 Voltage 0.30
Transformer 0.3
R1SA j0.90 Zone 3
ohm 0.3
CTPrim/sec Current Transformer Primary Current
X1SB TripTime 0.60 0.60 0.6
CT Earth j32.80 Direction
ohm of CT earthing
R1SB Zone
j5.10 ohm 4 0.6
XM0 TripTime j50.000 ohm 0.90 0.90 0.9
RM0 Phase Selection
j9.000Zone
ohm 5 0.9
TripTime
X1 Ph l ti 1.50
R ti 1.50
h 1.5
1.5
CTStarPoint = Out Indicates the earthing towards object (Out) or towards busbar (In).
Setting of the analogue preprocessing function blocks SMAI (General settings/Power system)
Set ref for DFT filter adjustment: DFTReferencen = InternalRef set voltage L1 as ref
Set the measured minimum value: MinValFreqMeasn = 10%
Set the connection type Connectionn = Ph-N
Set negation of the function block Negationn = Off
Set the base voltage UBasen = 400.00 kV
For first function block in each task time (1,13,25) also
SYNCH output reference DFTRefExtOut = InternalRef set voltage L1 as ref
General settings for Distance protection zones (Note! Set under Direction)
Set the Base values for the Distance protection zones in primary Ampere resp kV.
Ibase = 2000 A
Ubase= = 400.0 kV
Setting of minimum sensitivity for Distance zones. Note! Ref for zones settings
IMinOp = 20% *Ibase
Set the Directional angle Distance protection zones
ArgDir = 15 deg
Set the Negartive restraint angle for Distance protection zone
ArgNegRes = 115 deg
Project
Project
Project
Project
Project
Project
Phase selector phase fault reach is set to 144.0% of the total line value
Positive sequence reactance as set for the reach of phase selectors in reactive direction
X1 = 43.20 ohm
The secondary setting will thus be
X1" = 23.8 ohm
earth fault reach zero sequence component is set to 144.0% of the total line zero sequence value
Zero sequence reactance as set for the reach of phase selectors in reactive direction at phase-to-earth faults
X0 = 129.60 ohm
The secondary setting will thus be
X0" = 71.3 ohm
Reach of the phase selector in resistive direction at ph-to-ph faults (Note! In ohms per loop)
RFFwPP = 118.80 ohm RFRvPP = 118.80 ohm
The secondary setting will thus be
RFFwPP" = 65.3 ohm RFRvPP" = 65.3 ohm
Set the Base current for the Phase selection function in primary Ampere.
IBase = 2000 A
Setting of Neutral release current (shall be set below minimum neutral current expected at earth faults)
INReleasePE = 20% *Ibase
Setting of phase-phase blocking current
element for other phases at a earth fault
IBlockPP = 40% *Ibase
Set the load limitation reach to <Zload*0,8 giving Zload Note! In Ohm/phase
RLdFw' = 119.6 ohm Note: Set in Ohms/phase
The secondary setting will thus be Compare with min load impedance on sh 1
RLdFw = 65.79 ohm When Power Swing blocking is used this
Set the load limitation in the reverse (import) direction shall be allowed outside this setting.
RLdRv' = 119.6 ohm
The secondary setting will thus be
RLdRv = 65.79 ohm
Set the angle of the load limitation line
ARGLd = 20 deg
Project
Project
tPP3 = On
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
tPE3 = On
Setting of Zone timers:
tPP3 = 0.60 s
tPE3 = 0.60 s
Project
,,
or disclosure to third parties without express
29.7,0,87.33
authority is strictly forbidden. ©ABB PTSX
10
30.62,19.8,180
-9.23,19.8,-65
5
Zone3Fw Forward On On
0,0,-15
X" ohm/ph
0 49.5,-13.26,90
,,
,,
-5
,,
49.5,0,87.33
-10 51.04,33,180
-15.39,33,-65
Zone4Fw
-15 Off Off
0,0,-15
0,0,90
-20
,,
,,
-25 ,,
0,0,87.33
-30 0,0,180
0,0,-65
Z 5F R O O
-35
-40
-45
-70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60
Note: x Indicates the line impedance
R" ohm/ph
O : Phase Selection
Note! o Angle will be 90 deg at 3ph faults
Project
55
50
45
40
35
30
information contained therein. Reproduction, use
We reserve all rights in this document and in the
25
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
20
15
X" ohm/loop
10
-5
-35
-150 -100 -50 0 50 100 150 200
Project
Set th on delay
OnDelayTime1 = 0.000 s OnDelayTime2 = 0.000 s OnDelayTime2 = 0.000 s
Set the off delay
OffDelayTime1 = 0.000 s OffDelayTime2 = 0.000 s OffDelayTime2 = 0.000 s
Project
Setting of the current reversal logic for distance protection(used in overreaching schemes) (ZCAL) (REV)
Activation of the current reversal logic
CurrRev = Off
Setting of the pick-up timer
tPickUpRev = 0.020 s
Setting of the delay timer
tDelayRev = 0.100 s
Setting of the Weak End Infeed (WEI) logic (used in overreaching schemes)
Activation of the current reversal logic
WEI = Off
Setting of the U< voltage
UPP< = 70% *UBase
UPN< = 70% *UBase
Setting of the delay timer
information contained therein. Reproduction, use
tPickUpWEI = 0.100 s
We reserve all rights in this document and in the
Setting of the Base voltage level on which the WEI voltage is based
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
UBase = 400.0 kV
Set the analogue channels in the Disturbance recorder used for Fault locator calculations.
Current ch for IL1 1 Voltage ch for UL1 7
Current ch for IL2 2 Voltage ch for UL1 8
Current ch for IL3 3 Voltage ch for UL1 9
Current channel for IN 4
Current ch for INP 5
Project
Project
t1Min = 0.30 s
or disclosure to third parties without express
ResetTypeCrv1 = Instantaneous
Set the Reset time delay for definite time delayed function
tReset1 = 0.02 s
Set the release of Harmonic restraint blocking for the stage
HarmRestrain1 = On
Setting of parameters for second stage
Setting of the operating direction for the stage or switch it off
DirMode2 = Off
Setting of the operating characteristic
Characteristic2 = IEC NI
Setting of the operating current level in primary values
IN2>' = 600 A
IN2> = 30% *Ibase
Set the current multiplier for IN2 valid at activation of input ENMULT
IN2Mult = 2.00
Set the definite time delay, when definite time characteristic has been selected
t2 = 0.30 s
Set the back-up trip time delay multiplier for inverse characteristic
k2 = 0.20
Set the Minimum operating time for inverse characteristic
t2Min = 0.30 s
Select the reset curve type for the inverse delay
ResetTypeCrv2 = Instantaneous
Set the Reset time delay for definite time delayed function
tReset2 = 0.02 s
Set the release of Harmonic restraint blocking for the stage
HarmRestrain2 = On
Project
DirMode4 = Off
Setting of the operating characteristic
Characteristic4 = IEC NI
Setting of the operating current level in primary values
IN4> = 6000 A
IN4> = 300% *Ibase
Set the current multiplier for IN4 valid at activation of input ENMULT
IN4Mult = 2.00
Set the definite time delay, when definite time characteristic has been selected
t4 = 0.30 s
Set the back-up trip time delay multiplier for inverse characteristic
k4 = 0.20
Set the Minimum operating time for inverse characteristic
t4Min = 0.30 s
Select the reset curve type for the inverse delay
ResetTypeCrv4 = Instantaneous
Set the Reset time delay for definite time delayed function
tReset4 = 0.02 s
Set the release of Harmonic restraint blocking for the stage
HarmRestrain4 = On
Set of Direction, Harmonic blocking and SOTF functionality
Setting of the minimum neutral point polarizing voltage level for the directional funtion
UPolMin = 1.00 %*Ubase
Set the relay characteristic angle, i.e. the angle between the neutral point voltage and current
AngleRCA = 65 deg Normal zero sequence source angle at direct earthing
Setting of the operating current level for the directional release. Note! Sensitivity at RCA
IN>DirCmp = 10% *Ibase Note! Used for POR
Project
Set the time after closing or position change during which the SOTF function is active
or disclosure to third parties without express
t4U = 1.00 s
authority is strictly forbidden. ©ABB PTSX
Project
I_2nd/I_fund = 20% of I
or disclosure to third parties without express
Current level above which the 2nd harmonic blocking is inhibited (to avoid problem with CT saturation)
authority is strictly forbidden. ©ABB PTSX
BlkLev2nd = 1000.0%
Enable the current restraint for overcurrent functions
EnRestrCurr = Off
Select the restraint current parameter
RestCurrInput = PosSeq
Give the current restraint coefficient (slope)
RestCurrCoeff = 0.00
Setting of parameters for GF Overcurrent 1 function OC1 for functions GF1 to GF3
The function is used for Phase selection at high resistive earth faults in combination with EF4 function and EFC
Activation of the OC1 function
Operation_OC1 = On
Setting of the operating direction for the stage
DirMode_OC1 = Forward
Setting of the operating priciple for the direction function
DirPrinc_OC1 = IcosFandU
Setting of the operating characteristic
CurveType_OC1 = Def
Setting of the operating current level in primary values
OC1> = 200 A set to detect 300 ohm fault resistance
StartCurr_OC1 = 10% *Ibase
Set the definite time delay, when definite time characteristic has been selected
tDefOC1 = 0.00 s
Set the back-up trip time delay multiplier for inverse characteristic
k_OC1 = 0.30
Set the Minimum operating time for inverse characteristic
t1Min_OC1 = 0.30 s
Select the reset curve type for the inverse delay
ResetCrvType_OC1 = Instantaneous
Project
DirPrinc_OC2 = IcosFandU
We reserve all rights in this document and in the
CurveType_OC2 = IEC NI
Setting of the operating current level in primary values
OC2> = 150 A
StartCurr_OC2 = 8% *Ibase
Set the definite time delay, when definite time characteristic has been selected
tDef_OC2 = 0.30 s
Set the back-up trip time delay multiplier for inverse characteristic
k_OC2 = 0.20
Set the Minimum operating time for inverse characteristic
t1Min_OC2 = 0.30 s
Select the reset curve type for the inverse delay
ResetCrvType_OC2 = Instantaneous
Set the Reset time delay for definite time delayed function
tResetDef_OC2 = 0.02 s
Set the release of Harmonic restraint blocking for the stage
HarmRestr_OC2 = On
Set the Voltage Control mode for OC1 function
VoltCntrMode_OC2 = Off
Set the Voltage Dependent mode for OC1 function
VoltDepMode_OC2 = Slope
Set the Voltage Dependent factor for OC1 when function is voltage dependent function
VoltFactor_OC2 = 1.00
Set the Voltage Low limit
ULowLimjt_OC2 = 50.0
Set the VoltageHigh limit
UHighLimit_OC2 = 100.0
Action for directional OC1 at voltage lower than set level above
ActLowVolt2_VM = Memory
Project
Project
Operation_OV2 = Off
authority is strictly forbidden. ©ABB PTSX
Project
Set the Reset time delay for IDMT time delayed function
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
tResetIDMT_UV1 = 0.00 s
Project
t2 3Ph = 60.00 s
authority is strictly forbidden. ©ABB PTSX
Project
Project
t2 3Ph = 60.00 s
authority is strictly forbidden. ©ABB PTSX
Project
Project
Set the operating level for the Bus high voltage at Line energizing
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
Project
FreqDiffMax = 0.220 Hz
or disclosure to third parties without express
Set the operating level for the Bus high voltage at Line synchronism check
authority is strictly forbidden. ©ABB PTSX
Project
Set the operating level for the Bus high voltage at Line energizing
or disclosure to third parties without express
Setting of the operating voltage level for the low line voltage level at line energizing
ULowLineEnerg = 40% *UBase
Set the operating level for the Line high voltage at Bus energizing
UHighLineEnerg = 80% *UBase
Setting of the operating voltage level for the low Bus voltage level at Bus energizing
ULowBusEnerg = 40% *UBase
Setting of the energizing check directions to be activated.
AutoEnergi = DLLB
Set the time delay for the Auto Energizing
tAutoEnerg = 0.10 s
Setting of the manual Dead line/bus and Dead/Dead switching conditions to be allowed
ManEnerg = Both
ManEnergDLDB = Off
Set the time delay for the Manual Energizing
tManEnerg = 0.10 s
Set general settings for the Synchronism check function
Setting of the operating mode for the synchonism check (paralleling) function
OperationSync = On
Setting of the allowed voltage difference for Manual and Auto synchronism check
UDiff = 10%
Set the operating level for the Bus high voltage at Line synchronism check
UHighBusSync = 80% *UBase
Set the operating level for the Line high voltage at Line synchronism check
UHighLineSync = 80% *UBase
Project
FreqDiffMax = 0.220 Hz
or disclosure to third parties without express
Set the operating level for the Bus high voltage at Line synchronism check
authority is strictly forbidden. ©ABB PTSX
Project
ResetTypeCrv1 = Instantaneous
authority is strictly forbidden. ©ABB PTSX
Project
ResetTypeCrv1 = Instantaneous
authority is strictly forbidden. ©ABB PTSX
Project
Operation = On
or disclosure to third parties without express
Project
t3 = 0.030 s
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
Project
Project
Setting of Current Phasors values CMMXU Note! Measures the line values!
Set under General settings/Monitoring:
Operation = On
Set for phase L1 current Set for phase L2 current
Set the reporting type IL1RepType = Deadband IL2RepType = Deadband
Set deaband in % resp sec IL1 db = 1% IL2 db = 1%
Set the deadband at zero IL1 Zero db 0.2% IL2 Zero db 0.2%
Set the supervision limits for high and low alarm and the hystereses for the limits in A
IL1 HHlimit = 3600 IL2 HHlimit = 3600
IL1 Hlimit = 3200 IL2 Hlimit = 3200
information contained therein. Reproduction, use
Project
Project
SeqTypeLED10 = LatchedAck-S-F
or disclosure to third parties without express
authority is strictly forbidden. ©ABB PTSX
SeqTypeLED11 = LatchedAck-S-F
SeqTypeLED12 = LatchedAck-S-F
SeqTypeLED13 = LatchedAck-S-F
SeqTypeLED14 = LatchedAck-S-F
SeqTypeLED15 = LatchedAck-S-F
Project
Project
67 BUS CB AR PREP 3P BUS CB AR Prep 3Ph Trip Off Off Trig on 1 Show
or disclosure to third parties without express
69 BUS CB POLE DISC Bus CB Pole Discordance Off Off Trig on 1 Show
70 BUS CB PD TRIP Bus CB Pole Discordance Trip Off Off Trig on 1 Show
71 TIE CB AR ATTEMPT Tie CB AR Attempt Off Off Trig on 1 Show
72 TIE CB AR IN PROGR Tie CB AR In Progress Off Off Trig on 1 Show
73 TIE CB AR PREP 3P Tie CB AR Prep 3Ph Trip Off Off Trig on 1 Show
74 TIE CB AR INHIBIT Tie CB AR Inhibit Off Off Trig on 1 Show
75 TIE CB POLE DISC Tie CB Pole Discordance Off Off Trig on 1 Show
76 TIE CB PD TRIP Tie CB Pole Discordance Trip On Off Trig on 1 Show
77 Not Used Off Off Trig on 1 Hide
78 Not Used Off Off Trig on 1 Hide
79 BUS CB BUTRIP Bus CB Circuit Breaker failure On On Trig on 1 Show
80 TIE CB BUTRIP Tie CB Circuit Breaker failure On On Trig on 1 Show
81 BUS CB CLOSED Busbar Circuit Breaker Closed Off Off Trig on 1 Show
82 BUS CB OPEN Busbar Circuit Breaker Open Off Off Trig on 1 Show
83 BUS CBREADY Busbar Circuit Breaker Ready Off Off Trig on 1 Show
84 TIE CB CLOSED Tie Circuit Breaker Closed Off Off Trig on 1 Show
85 TIE CB OPEN Tie Circuit Breaker Open Off Off Trig on 1 Show
86 TIE CBREADY Tie Circuit Breaker Ready Off Off Trig on 1 Show
87 LINE 1 DS CLOSED Line 1 DSClosed Off Off Trig on 1 Show
88 LINE 1 DS OPEN Line 1 DS Open Off Off Trig on 1 Show
89 LINE 2 DS CLOSED Line 2 DS Closed Off Off Trig on 1 Show
90 LINE 2 DS OPEN Line 2 DS Open Off Off Trig on 1 Show
91 TEST ACTIVE Test Active Off Off Trig on 1 Show
92 ACTIVE SETTING GR1 Active setting Group 1 Off Off Trig on 1 Show
93 ACTIVE SETTING GR2 Active setting Group 2 Off Off Trig on 1 Show
94 Not Used Off Off Trig on 1 Hide
95 Not Used Off Off Trig on 1 Hide
96 Not Used Off Off Trig on 1 Hide
Project