C.L COVER HINGED
650 250, TO Ci. FRAME
GL. WIRE MESH 4 GL
100 PVC i a
CONDUIT |
EMBEDED seme TP EARTH FILLING
oot 600 af
375 375
° AFTER FIXING SURFACE
8 SHOULD COVERED WITH
3| BITUMIN OR GREASE
ae 25 50 75
etl | fers
“ifr | th th, tt, | A fh, ot,
16MM} * 3 TD fru of
AP a 75x10 \
AHomocenous [|X I] ea SLSTRP
ALTERNATE LAYER \ : 10 80LTs
loF COKE/ CHARCOAL, |: ‘ AND NUTS 50x6 GL STRIP
SALTAND SAND [s+ Pol.
ee DETALA
Cil. PIPE 100 1.0,
13 THICK
NOTE:-
1, ORIGINALLY DRAWING IS PREPARED FROM THE RECOMENDATION
DRAWING GIVEN IN IS-3043 1987,
2, ITS WORKING SPACE IS REVISED FROM 400 TO 650MM AS PER CBIP
MANUAL ON EARTHING SYSTEM # 302.
3. __ IN CASE OF LOW RESISTIVITY (<50 OHM MTR) TREATED ELECTRODE
MAY NOT BE REQUIRED, SIMPLE PIPE OF SAME DIMENSIONS MAY BE
PROVIDED
Cl PIPE SHOULD BE MANUFACTURED AS PER IS 1536: 2001
5, COVER WITH BRICK MASONARY MAY ALSO BE PROVIDED TO THIS ie
ELECTRODE.
GUJARAT ENERGY TRANSMISSION CORPN.LTD.
‘SP VIDVUT BHAVAN, RACE COURSE,
“Typical Arrangement of Pipe Eating