Professional Documents
Culture Documents
Reference Guide
About Daikin:
SYSTEM SELECTION
Indoor Unit Range............................................................20
Indoor Unit Consideration................................................22
Controls............................................................................30
73º 69º
OFF 73º
6
INTRODUCTION
Inverter Driven Compressors allow for energy
savings using only the system capacity needed
to heat or cool the space.
7
Inverter Driven Compressors
The inverter driven compressor is the heart of Daikin’s VRV system to help
maximize energy savings. Daikin’s inverter technology is responsible for
delivering intelligent comfort, at a variable capacity, with efficiency, based
on demand.
Variable Capacity Output
Daikin’s inverter driven compressors will only provide the required amount
of refrigerant needed to meet the capacity demand. Daikin inverter
technology helps systems run at an energy-conserving level, despite
the climate conditions, by making slight adjustments to the compressor’s
speed. Daikin inverter systems will reach the desired temperature faster
and maintain a more constant temperature compared to traditional
Desired speed ON/OFF systems. It will
not frequently start and
stop the “old fashioned
way” just as a car is more
speed
8
First VRV with Dual Fuel Capabilities
9
Capacity Range & Operating Limits
Outdoor Unit (ODU) Range
Capacity MBH Max # Dimensions
Power Supply ODU Appearance
(Tons) IDU* (HxWxD)
24 (2) 4
36 (3) 6 39 x 37 x
12-5/8
48 (4) 8
1/208-
230/60Hz
52 15/16 x 35
60 (5) 9
7/16 x 12-5/8
40 100
Range for Operation
Range for Warm
Up Opearation
30 90
20 80
10 70
60
0
-4
50
-10
50 60 70 80 90
40
Indoor Temperature (ºFWB)
30
Warm Up/Pull Down Operation: 23
prolonged periods of not conditioning 20
the space, or setback periods, may result 50 60 70 80 90
in entering air conditions (EAC) at the Indoor Temperature (ºFWB)
indoor unit (IDU) in these “warm up” and
“pull down” ranges. Actual continuous
operation EAC’s should fall within the
“range for operation” temperatures.
10
Refrigerant Piping Limitations
C
B
Receiver
Equivalent Piping length: includes total actual pipe length plus the
equivalent straight piping length associated with each fitting or bend.
Note: lengths are based on liquid line length not gas and liquid
11
Capacity Range & Operating Limits
Refrigerant Piping Connections
Standard pipe sizes are recommended. However, there are applications
where larger sized refrigerant lines exist due to previously installed HVAC
systems. Replacement of existing refrigerant lines can pose challenges,
VRV LIFE™ systems can be configured to re-use these refrigerant lines.
See the table below for allowable connection sizes. See ODU installation
manual for field settings when using non-standard sizes.
Liquid Gas
Tons
To Other
VRV IDU (s)
3
/8 5
/8 ¾ 7
/8 11/8
2 • •® ¡
3 • • ¡® ¡
4 • • ¡ ¡® ¡
5 • • ¡ ¡® Main Liquid Line
12
Communication Wiring
Communication wiring should have the following characteristics.
»» 18 AWG (16 AWG is permitted if necessary)
»» 2 Strand
»» No Polarity
»» No Sheilding
F H
P1-P2
E G B
13
Capacity Range & Operating Limits
Allowable Configurations
Draw Through
Installation
14
Connection Ratio
Both indoor and outdoor units have a capacity index number and the
connection ratio is defined as the ratio of these two numbers.
Example:
Both indoor and outdoor units have a capacity index number and the
connection ratio is defined as the ratio of these two numbers.
»» 2 x FXMQ36PB connected to 1 RXSQ60T = 72 / 57 = 1.26
»» Therefore the Connection ratio = 126%
IDU Size 5 7 9 12 15 18 24 30 36 42 48 54 60
IDU
Capacity 5.8 7.5 9.5 12 15 18 24 30 36 42 48 54 60
Index
15
Nomenclature
VRV Indoor Units
FX M Q 24 P VJ U
Standard
Indoor Unit Category Compatibility Symbol
FX: VRV system indoor unit U: United States of America
Refrigerant Type
Q: R-410A
Standard
Indoor Unit Category Compatibility Symbol
FX: VRV Cased Coil U: United States of America
16
Nomenclature (cont.)
Outdoor Units
R X S Q 24 TA VJ U
Unit Category
R: Outdoor
Unit
Standard
Unit Type Compatibility Symbol
X: Heat Pump U: United States of America
Gas Furnace
D M 96 V C 060 3 B N A A
Brand
Daikin
Configuration
M: Upflow/Horizontal
D: Downflow/Horizontal
Minor
AFUE Revisions
97 – 97-98% AFUE A: Initial Release
B: 1st Release
96 – 96% AFUE
80 - 82% AFUE Major Revisions
A: Initial Release
B: 1st Release
Gas Valve
M: Modulating H: Convertible Two-Stage NOx
V: Two Stage S: Single Stage N: Natural Gas A: Low Nox
17
System
Selection
Indoor Unit Range
Sizes & Accessories Available of all IDU’s
TYPE MODEL BUILT-IN / OPTION
CXTQ
Must Be Paired
A-COIL
24 36 48 60
DM/DC
GAS FURNACES
40 60 80 100 120
FXTQ
MULTI POSITION AHU
9 12 18 24 30 36 42 48 54 60
FXFQ
ROUNDFLOW (3’ x 3’) CASSETTE
7 9 12 15 18 24 30 36 48
5 7 9 12 15 18
FXEQ 36
1 WAY FLOW CASSETTE
=OA Connection
FXUQ
4 WAY FLOW UNDER CEILING
18 24 30 36
FXHQ
=Pump Included
=Pump Options
12 24 36
FXAQ
WALL MOUNTED
= Filter Included
= Filter Options
7 9 12 18 24
FXLQ
FLOOR MOUNTED
7 9 12 18 24
20
TYPE MODEL BUILT-IN / ADD ON
FXNQ
CONCEALED FLOOR MOUNTED
7 9 12 18 24
SYSTEM SELECTION
FXSQ
MEDIUM STATIC
CEILING DUCTED
5 7 9 12 15 18 24 30 36 48 54
FXMQ-P
HIGH STATIC
CEILING DUCTED
7 9 12 15 18 24 30 36 48 54
Accessories
The best location to find a list of all available accessories (for every unit
type & size) is via WEBXpress: Click on the ‘options’ link located at the
bottom of the IDU ‘properties’ window, to reveal the following page:
Example
Options Page
21
Indoor Unit Considerations
Gas Furnace & VRV A-Coil Up-Flow
Drain Connection
Positive Liquid
Seal Required 3" Min
at Trap
22
»» CXTQ Insulation kit
–– To prevent drain pan “sweating”, a coil insulation kit (DPICX)
is recommended in applications where operating conditions
may exceed 80% RH.
0.45
0.40
CXTQ Wet
Pressure Drop (in W.C.)
0.15
CXTQ60 Dry
0.10
0.05
0
400 600 800 1000 1200 1400 1600 1800 2000
Air Flow (SCFM)
23
Indoor Unit Considerations
Multi-Position Air Handling Unit (FXTQ)
Up-Flow
»» No field modifications are mandatory
»» To maintain maximum efficiency remove the
horizontal drip shield, side drain pan, and drain
pan extension
Down-Flow
»» Additional downflow kit (DFK) required
»» Rotate cabinet/blower assembly 180º
and remove and flip A-coil
»» Drain pan extension must be
removed, horizontal drip shield and
side drain pan may also
Removable Drain Pains / Drip Shield
Horizontal Left
»» Factory standard configuration
»» No field modifications necessary
Horizontal-Right
»» Rotate cabinet/blower
assembly 180º and remove
and flip A-coil
»» Drain pan extension must
be removed
24
CONCEALED UNITS offer the opportunity to hide away the equipment
when there is no ceiling void but the homeowner does not wish to use
exposed units or else has similar equipment existing and sees the benefit
of retro fitting with minimum disruption and expense.
Considerations:
»» Is there an existing centralized forced air system?
»» Does the homeowner prefer not to see the units?
»» Is heating the primary requirement?
24 ~ 36 221/16"
CXTQ NA
48 ~ 60 301/16"
09 ~ 36 45"
25
Indoor Unit Considerations
Multi-Position Air Handling Unit (FXTQ)
Considerations:
»» Is there a ceiling void space?
»» What is the height of the void space?
»» How far are the ceiling joists spaced?
12 ft
FXZQ All 1113/16"
(per outlet)
07 ~ 30 911/16"
14 ft
FXFQ
(per outlet)
36 ~ 48 11 /16"
5
14 ft
18 ~ 24 71316"
(per outlet)
FXUQ
16 ft
30 ~ 36 71316"
(per outlet)
FXEQ 07 ~ 24 111/16" 15 ft
26
DUCTED units offer the ultimate in flexibility of design, air distribution
and integration of ventilation
Considerations:
»» Is there a ceiling void space?
»» What is the height of the void space?
»» What level of ESP is likely to be required?
»» What level of control is required?
07 ~ 30 0.04" 0.12"
FXDQ 117/8"
07 ~ 30 0.06" 0.17"
05 ~ 12 0.20" 0.60"
FXSQ 911/16"
15 ~ 54 0.40" 0.60"
07 ~ 30 0.20" 0.40"
FXMQ-P 36 ~ 48 11 /16"
13 0.40" 0.80"
07 ~ 30 0.40" 0.56"
27
Indoor Unit Considerations
Multi-Position Air Handling Unit (FXTQ)
EXPOSED units often offer the home owner the most economical
installed cost solution on a VRV LIFE™ system. These types of units are
ideal for applications that do not have a ceiling void available or the attic
does not allow for a viable duct run. Exposed units are common in historic
homes or applications where minimal reconstructive work is desired.
Considerations:
»» How big is the space?
»» Where can the unit be located?
»» Is piping/condensate run clear?
»» Is the home owner accepting of exposed units?
28
Indoor Unit Considerations
Gas Furnace & A-Coil Compatibility Matrix
DM80VC0803CNA ¡
DM80VC
(2-stage – DM80VC0805CNA ¡ ¡
80% AFUE)
DM80VC0805DNA ¡
DM80VC1005CNA ¡ ¡
DM96VC0403BNA ¡ ¡
Upflow Furnace
DM96VC0603BNA ¡ ¡
DM96VC DM96VC0803BNA ¡ ¡
(2-stage –
96% AFUE) DM96VC0804CNA ¡
DM96VC1005CNA ¡ ¡
DM96VC1205DNA ¡
DM97MC0603BNA ¡ ¡
DM97MC0803BNA ¡ ¡
DM97MC
(Modulating – DM97MC0804CNA ¡
97% AFUE)
DM97MC1005CNA ¡ ¡
DM97MC1205DNA ¡
DC80VC DC80VC0805CXA ¡ ¡
(2-stage –
80% AFUE) DC80VC1005CXA ¡ ¡
DC96VC0403BNA ¡ ¡
Downflow Furnace
DC96VC0603BNA ¡ ¡
DC96VC
(2-stage – DC96VC0804CNA ¡
96% AFUE)
DC96VC1005CNA ¡ ¡
DC96VC1205DNA ¡
DC97MC0603BNA ¡ ¡
DC97MC DC97MC0803BNA ¡ ¡
(Modulating –
97% AFUE) DC97MC0804CNA ¡
DC97MC1005CNA ¡ ¡
29
Controls
BRC1E73 Navigation Controller
BRC1E72MF
BRC1E72RF
BRC1E72MF2
BRC1E72RF2
30
Advanced Control Function
Operation
»» 7 day Schedule Fan
Mode
Room
Speed Temp Current
Up to 5 actions per day (7 days, Date/Time
5+1+1,5+2, everyday), Off timer
(from 30 mins to 3 hours)
Set point
»» Temperature Limiting Backlit
Display
Configurable upper & lower limit
restriction for the occupied cool
and heat setpoints On/Off
31
Controls
Wireless Controller
32
Design &
Application
Residential Single Story
Single Zone Ducted
Living Closet
Laundry
Closet
Kitchen
Bath
Closet
Bedroom
Garage
Dining
CXTQ24
Sample System
Repurposed
Main Line Set
3/8 x 5/8
DM97MC0603B BRC1E73
RXSQ24
34
Two Zones & Tempered Garage
Living Closet
Laundry
Closet
Kitchen
Bath
Closet
Bedroom
Garage
Similar to the previous single zone example this layout reuses the
existing ductwork while also providing enhanced comfort control in a
key zone, the master bedroom. Additionally a wall mounted ductless unit
has been included in the garage for comfortable working conditions for
homeowners who may use the garage as a working space.
1/4 x 1/2
3/8 x 5/8
BRC1E73 BRC1E73
3/8 x 5/8
BHL-02A DM97MC0803B
RXSQ48 BRC1E73
35
Residential Single Story
Four Zones Mixed
Living Closet
Laundry
Closet
Kitchen
Bath
Bedroom
Closet
Garage
Dining
In some applications the VRV LIFE™ system can also be used as a 100%
heat pump system without the need for auxiliary heat. This single floor
example shows a four zone system using a mix of ductless (concealed floor
mounted units) and
d u c te d ( c o n c e a l e d
KHRP26A22T9
KHRP26A22T9 ducted units) for a
modern and efficient
3/8 x 5/8
1/4 x 1/2
RXSQ48
cooling a home.
Sample System FXNQ07 (Bed)
BRC1E73
1/4 x 1/2
BRC1E73
1/4 x 1/2
BRC1E73
36
Two Zones Ducted
Bath Kitchen
Laundry
Living
Media Dining
Garage
VRV A-Coil.
3/8 x 5/8
3/8 x 5/8
3/8 x 5/8
KHRP26A22T9 BRC1E73
DM96VC0603B
RXSQ48
CXTQ24
(Second Floor)
BRC1E73
DM96VC0403B
37
Residential Two Story
Three Zones & Conditioned Garage
Bath Kitchen
Laundry
Living
Media Dining
Garage
Bedroom Bedroom
In this example a centralized
forced air system has been
retrofitted with a Daikin gas Bedroom
furnace and VRV A-coil for
the first floor. The second
floor is utilizing concealed
ducted units for a distributed Bath
CXTQ36
KHRP26A22T9 3/8 x 5/8
KHRP26A22T9 3/8 x 5/8
1/4 x 1/2 FXAQ09 (Garage)
3/8 x 5/8
3/8 x 5/8
KHRP26A22T9
RXSQ60 BHL-02A
Sample System
1/4 x 1/2
BRC1E73
BRC1E73
38
Five Zones Mixed
Bath Kitchen
Laundry
Living
Media Dining
Garage
Bedroom Bedroom
In this example the first
floor’s existing central
forced air system has been Bedroom
retrofitted with a Daikin G/F
& A-Coil and paired with
a ductless solution for the
second floor. Bath
CL CL
KHRP26A22T9 KHRP26M22H9
3/8 x 5/8
BHL-02A
1/4 x 1/2
3/8 x 5/8
Sample System
1/4 x 1/2
1/4 x 1/2
BRC1E73
DM97MC0603B
39
Installation Considerations
Obstacle on the suction side only Obstacle on the discharge side only
ore ore
rm rm
0)o )o
(10 500
4 20(
Inch (mm)
40
Obstacle on the suction, left, Obstacle on the discharge, left,
and right side and right side
)
500
20( less
o r
40(1000)
or more
4(1
00
0)
or re
mo mo 6(
or
or m150)
re
4(1
000 0 00)
4(1 ore )
) or 50
mo
re 6(
or m150) 6(1 more
ore or
Inch (mm)
)
500
20( less
or
40(1000)
or more
ore
re orm
mo 0)
) or (10
0
500 40
inch(mm) 20(
Inch (mm)
41
Installation Considerations
the following:
»» Elevate the foundation Air Adjustment Grille
as high as possible (P/N KPW5E112) Headwind
42
Receiver Tank Kit Installation
A receiver (liquid refrigerant tank) is required in applications where the RXSQ
is connected to both a gas furnace and other VRV IDUs.
The receiver kit (BHL-02A) ships from the factory in a sheet metal
enclosures. The refrigerant tank is independent of refrigerant flow direction.
Either one of the 3/8” connections can be connected to the liquid connection
on the ODU.
Adhere to the following installation guidelines:
»» Install the tank in the nearest
and most convenient location
to the ODU near the liquid
service valve. The tank can
be oriented to the front, rear,
or side of the ODU.
»» Refer to the ODU installation 7.91”
43
Installation Considerations
Side View
Front
24”
Horizontal Installation
24”
Front
Side View
44
Slim Ducted Ceiling Concealed (FXDQ)
Control
Front View Box Side View 9½”
13/16" 100"
12"* 12"
Floor Surface
Side View
Top View 25”
12”
99”
Refrigerant
Connections
18”
Service Space
Floor Surface
28”
6” 6”
¾”
Top View
Front Side
40”
45
Installation Considerations
3-5/8”
1¼”
≤ 4¾”
Obstruction
99”
Floor Surface
100”
High Ceiling
Installations
46
Heat Pump Changeover
There are four ways to provide heat/cool changeover on a VRV LIFE™ system.
Master
Controller
Return Air
Sensor
MANUAL
CHANGEOVER AUTO CHANGEOVER
via Master via Master Unit
Controller
Master
Unit
Master Unit
The simplest way to address heat/cool changeover automatically is to
nominate a master unit. When the unit’s return air sensor measures outside
the temperature set point limitation, the unit switches itself and all other
units on the system to the different mode.
Master Controller
Similar to the previous option except mode selection is made manually by
a designated master controller. Again, all other units on the system will
switch mode in unison.
Note: A common pitfall is to elect an area that is not in constant use or
has no easy access to all occupants (bedroom). In both applications above,
if the unit isn’t running then mode change is not possible without
manual intervention.
47
Heat Pump Changeover
AUTO CHANGEOVER
Ambient
Sensor via Master Unit
MANUAL
CHANGEOVER
Summer/Winter Switch
A Daikin supplied switch is attached to “ABC” terminals on the outdoor
unit to allow manual change over from a central location. This is common in
applications that usually require year round cooling.
3rd Party Ambient Sensor
This option was developed to provide an automatic version of summer/
winter switch previously described. A remote ambient sensor will dictate
when mode change occurs. Although possible, it is an option rarely seen
on residential applications.
Summary: With ALL changeover options, when a system mode is changed,
the indoor units on the system are not forced into heating or cooling. If there
is no demand in the room for the mode that has been selected, the unit(s)
will run in fan only mode.
48
Auxiliary Heat
VRV LIFE™ systems (RXSQ) can provide heat pump heating with
ambient temperatures as low as -4º F. However, it may be necessary to
incorporate an auxiliary heat source to avoid oversizing the ODU to meet
a low design day temperature or for heating in temperatures below -4º F.
The switchover point from VRV heating to auxiliary heating is typically
based on a balance point considering several factors such as climate,
load, available capacity, fuel/system cost, and environmental impact.
Balance ty
Point apaci
DU C
Avail
able O
over from entirely VRV heating to
Alternative Heat
Covered by VRV
Outdoor Temperature
Coldest Day
An electrical coil downstream
of the Year of an indoor unit is considered
a supplemental heat source.
Heating Load
Balance
Point DU C
apaci
ty
The electrical coil works in
ble O
SH Avail
a
conjunction with the VRV system
Spare VRV Capacity
to provide heating beyond the
Hea
ting
Req
uirem
balance point.
ent
Covered by VRV
Outdoor Temperature
49
Auxiliary Heat
60 15º F
RXSQ60
RXSQ48
50 20º F
25º F RXSQ36
40
30
20
10
-10 0 10 20 30 40 50 60 70 80
Ambient Temperature (ºF)
50
Auxiliary Heat
Note: The FXTQ IDU has the option of integrated auxiliary electric heat up to
25 kW without the need of the KRPIC 74/75.
51
Refrigerant Piping Design
REFNETs
REFNET joints and headers are a factory designed option for the branching
within the refrigerant piping network. These fittings are engineered to allow
for uniform refrigerant flow and distribution, and smooth oil return.
REFNET Joint
A REFNET joint splits a gas or refrigerant
line into two lines. These joints account for
approximately 1.5 feet of equivalent pipe Towards
Condensing
length. It is allowable to install these joints
Unit
in either a vertical or ±30º from horizontal. In
noise sensitive applications it is recommended Vertical
the clearances around a REFNET joint
displayed below are maintained.
+30º
20”min. 40”min.
-30º
Horizontal
20”min.
52
Recommended support intervals for 12-20” 12-20”
REFNET Header
REFNET headers are available in 4-port and 8-port configurations and
account for approximately 3.3 feet of equivalent pipe length. Headers must
be installed horizontally level and are typically installed suspended from the
ceiling (spacing below).
Ceiling Support
12-20” 12-20”
Gas headers and liquid headers differ in that the branch piping extends
from the bottom of the main header pipe for the liquid line while the gas line
header extends horizontally from the header.
Pedestal
53
Refrigerant Piping Design
Bath
Kitchen Bedroom
Bedroom
Living
Bedroom
Laundry
Bath
Common CL CL
Space
Dining
Bath
Kitchen Bedroom
Bedroom
Living
Bedroom
Laundry
Bath
Common CL CL
Space
Dining
54
Power Wiring
Below is a general power wiring diagram. Refer to the installation manual for
further details.
Power Supply
Single Phase
60 Hz 208/230V
L1 L2
Outdoor Unit
Switch
L2 L1
FUSE
Power Supply
Single Phase
Power Supply
60 Hz 208/230V
Single Phase
L1 L 2
60 Hz 115V
L1 L2
Single
Phase
24V
Transfermer from
kit mounted in gas
L1 L2 L1 L2
Switch Switch furnace
FUSE FUSE
L1 L1 L1
L2 L2 L2
(CXTQ )
Indoor Units
55
General
Equipment
Specifications
Capacities
Outdoor and Indoor Unit Capacities
58
Indoor Unit Capacities
Rated
Model Number Nominal (Tons)
Heating (MBH) Cooling (MBH)
FXZQ
FXZQ07MVJU9 0.6 8,700 7,500
FXZQ09MVJU9 0.75 11,100 9,500
FXZQ12MVJU9 1 14,000 12,000
FXZQ15MVJU9 1.25 17,500 15,000
FXZQ18MVJU9 1.5 21,000 18,000
FXUQ
FXUQ18PVJU 1.5 20,000 18,000
FXUQ24PVJU 2 27,000 24,000
FXUQ30PVJU 2.5 34,000 30,000
FXUQ36PVJU 3 40,000 36,000
FXEQ
FXEQ07PVJU 0.6 8,500 7,500
FXEQ09PVJU 0.75 10,500 9,500
FXEQ12PVJU 1 13,500 12,000
FXEQ15PVJU 1.25 17,000 15,000
FXEQ18PVJU 1.5 20,000 18,000
FXEQ24PVJU 2 27,000 24,000
FXDQ
FXDQ07MVJU 0.6 8,500 7,500
FXDQ09MVJU 0.75 10,500 9,500
FXDQ12MVJU 1 13,500 12,000
FXDQ18MVJU 1.5 20,000 18,000
FXDQ24MVJU 2 27,000 24,000
FXMQ
FXMQ07PBVJU 0.6 8,500 7,500
FXMQ09PBVJU 0.75 10,500 9,500
FXMQ12PBVJU 1 13,500 12,000
FXMQ15PBVJU 1.25 17,000 15,000
GENERAL EQUIPMENT
59
Capacities
Outdoor and Indoor Unit Capacities
60
Pipe Sizes
61
Electrical
Electrical Requirements
Outdoor Units
Model Number MCA (A) MOCP (A)
RXSQ24TAVJU 16.5 25
RXSQ36TAVJU 16.5 35
RXSQ48TAVJU 29.1 35
RXSQ60TAVJU 29.1 35
Indoor Units
Model Number MCA (A) MOCP (A)
FXTQ
FXTQ09TAVJU 4.9 15
FXTQ12TAVJU 4.9 15
FXTQ18TAVJU 4.9 15
FXTQ24TAVJU 4.9 15
FXTQ30TAVJU 4.9 15
FXTQ36TAVJU 4.9 15
FXTQ42TAVJU 6.5 15
FXTQ48TAVJU 6.5 15
FXTQ54TAVJU 8.6 15
FXTQ60TAVJU 8.6 15
FXNQ
FXNQ07MVJU 0.3 15
FXNQ09MVJU 0.3 15
FXNQ12MVJU 0.5 15
FXNQ18MVJU 0.6 15
FXNQ24MVJU 0.6 15
FXFQ-T
FXFQ07TVJU 0.3 15
FXFQ09TVJU 0.3 15
FXFQ12TVJU 0.3 15
FXFQ15TVJU 0.4 15
FXFQ18TVJU 0.6 15
FXFQ24TVJU 0.7 15
FXFQ30TVJU 1.3 15
FXFQ36TVJU 1.5 15
FXFQ48TVJU 1.8 15
FXZQ
FXZQ07MVJU9 0.8 15
FXZQ07MVJU9 0.8 15
62
Indoor Units
Model Number MCA (A) MOCP (A)
FXZQ07MVJU9 0.8 15
FXZQ07MVJU9 0.8 15
FXZQ07MVJU9 0.9 15
FXUQ
FXUQ18PVJU 0.6 15
FXUQ24PVJU 0.6 15
FXUQ30PVJU 1.4 15
FXUQ36PVJU 1.4 15
FXEQ
FXEQ07PVJU 0.3 15
FXEQ09PVJU 0.4 15
FXEQ12PVJU 0.4 15
FXEQ15PVJU 0.5 15
FXEQ18PVJU 0.5 15
FXEQ24PVJU 0.7 15
FXDQ
FXDQ07MVJU 0.9 15
FXDQ09MVJU 0.9 15
FXDQ12MVJU 0.9 15
FXDQ18MVJU 1.3 15
FXDQ24MVJU 1.4 15
FXMQ
FXMQ07PBVJU 0.6 15
FXMQ09PBVJU 0.6 15
FXMQ12PBVJU 1.4 15
FXMQ15PBVJU 1.5 15
FXMQ18PBVJU 1.6 15
FXMQ24PBVJU 1.8 15
FXMQ30PBVJU 2.8 15
FXMQ36PBVJU 2.9 15
FXMQ48PBVJU 3.4 15
FXMQ54PBVJU 3.4 15
FXAQ
FXAQ07PVJU 0.4 15
FXAQ09PVJU 0.4 15
FXAQ12PVJU 0.4 15
FXAQ18PVJU 0.5 15
FXAQ24PVJU 0.5 15
63
Electrical
Electrical Requirements
Indoor Units
Model Number MCA (A) MOCP (A)
FXHQ
FXHQ12M 0.8 15
FXHQ24M 1 15
FXHQ36M 1.4 15
FXLQ
FXLQ07MVJU 0.3 15
FXLQ09MVJU 0.3 15
FXLQ12MVJU 0.5 15
FXLQ18MVJU 0.6 15
FXLQ24MVJU 0.6 15
CXTQ
CXTQ24TASBLU - -
CXTQ36TASBLU - -
CXTQ48TASBLU - -
CXTQ60TASBLU - -
Gas Furnace
Model Number MCA (A) MOCP (A)
DM80VC
DM80VC0604B 12.1 15
DM80VC0805C 12.1 15
DM80VC1005C 12.1 15
DM96VC
DM96VC0403BNA 7.8 15
DM96VC0603BNA 7.8 15
DM96VC0803BNA 7.8 15
DM96VC0804CNA 10.6 15
DM96VC1005CNA 14.4 20
DM96VC1205DNA 14.4 20
DM97MC
DM97MC0603BNA 8.8 15
DM97MC0803BNA 8.8 15
DM97MC0804CNA 11.6 15
DM97MC1005CNA 15.4 20
DM97MC1205DNA 15.4 20
64
Electrical Requirements
DC80VC
DC80VC0805CXA 10.6 15
DC80VC1005CXA 10.6 15
DC96VC
DC96VC0403BNA 7.8 15
DC96VC0603BNA 7.8 15
DC96VC0804CNA 10.6 15
DC96VC1005CNA 14.4 20
DC96VC1205DNA 14.4 20
DC97MC
DC97MC0603BNA 8.8 15
DC97MC0803BNA 8.8 15
DC97MC0804CNA 11.6 15
DC97MC1005CNA 15.4 20
65
Tips & Considerations
66
Where to find official information
Handbook
Submittal
Eng. Data
Bulletin
Design
Product Detail
Option
Guide
Sales
SVM
IOM
Features Summary ◆ ◆ ◆
Summary Table ◆ ◆ ◆ ◆
Specification
Electrical ◆ ◆ ◆ ◆
Dimension ◆ ◆ ◆
Drawings Piping ◆ ◆ ◆
Wiring ◆ ◆
Capacity
Correction
◆ ◆
Performance Piping ◆ ◆
Airflow / ESP ◆ ◆
Sound Level ◆ ◆
Piping ◆ ◆
Wiring ◆ ◆
Installation Fundamentals ◆ ◆
How to use ◆
Operation
Controls ◆ ◆ ◆ ◆
Specification ◆ ◆ ◆
Accessories
Installation ◆ ◆
Characteristics Functions ◆ ◆
Test Operation ◆ ◆
Set-up, Troubleshooting ◆
Commissioning
& Service Flow Charts ◆
Replace Procedure ◆
67
Notes
68
Notes
69
Notes
70
www.daikincity.com
For more information:
Sales and Technical Support: 1-855-DAIKIN1
www.daikincomfort.com or daikinac.com
Additional Information
Before purchasing this appliance, read important information about its estimated
annual energy consumption, yearly operating cost, or energy efficiency rating that
is available from your retailer.
2018
PM-DKLIFE 09-18