Professional Documents
Culture Documents
Additions and Corrections: 2006 Refrigeration
Additions and Corrections: 2006 Refrigeration
p. 45.7, References. Add the following source: p. 35.13, Table 6. For fuel oil, household usage values should be
153.8 GJ (for “yes”) and 97.0 GJ (for “no”).
ASHRAE. 2002. Reducing the release of halogenated refrigerants from
refrigerating and air-conditioning equipment and systems. ANSI/ p. 41.21, 1st col, 10th line. In the numbered list, first item, the chiller
ASHRAE Standard 147-2002. should be 19.3 MW.
p. 41.22, Example 3. The reference to Table 6 should be to Table 5.
2007 HVAC Applications
p. 41.25, Eq. (26). The second term on the left side of the equation
Contributors List. Wayne Lawton of X-nth should be listed as con- should be Q· blr ,i .
tributor for Chapters 29 and 30.
p. 41.30, Eq. (33). Change D to Δ.
p. 13.30, Example 2, step 4. Replace the equation and bulleted item
with the following: p. 47.26, Eq. (26). The final number subtracted should be 11, not 0.5.
–3 3 L w2 ⁄ 10
C occ = 10 ( 116 mg/m ) ( 22.5 – ( 0.773Q – 2.09P – 0.109X ) p. 47.37, Eq. (29). The final term should be 10 .
– 0.346Z + 0.0159QZ + 0.236PX + 0.0407PZ p. 47.38, Vibration Criteria, 1st paragraph. ANSI Standard 3.29
3 is the former designation; update this to ANSI Standard S2.71-1983
+ 0.00190XZ – 0.00499PXZ = 1.13 mg/m
(R2006).
• Iterate between steps 5 and 4. With 5 ach, Cocc = 1.13 mg/m3. This is
greater than the desired limit of 0.94 mg/m3. If the fan flow rate p. 47.39, Fig. 37. The corrected figure is shown on p. A.2, left.
is increased to provide 10.5 ach, Cocc decreases to 0.94 mg/m3. This
meets the design criterion. p. 47.39, Table 46. In the next to the last row, change 0.0054 to
0.0064 mm/s.
Ch. 14, Laboratories. Revisions were inadvertently omitted from
the 2007 volume; please go to http://www.ashrae.org/publications/ p. 47.40, Table 48, Packaged AH, AC, H and V Units. In the Shaft
page/158 to download the revised chapter. Power kW and Other column, change all ≤ to ≥ (i.e., should be ≥11,
p. 16.13, Table 3. In the column headings, the first ceiling height ≥1 kPa SP).
should be 12.2 m. p. 49.5, Table 1. In the leftmost column, change “1/2” to “13” and
p. 17.2, Fig. 1B. The title should read “Allowable Data Center Class “3/4” (in two places) to “19.”
1, Class 2, and NEBS Operating Conditions.” p. 49.21, Eq. (19). The equation should read F = 1000 N P Vf / T.
p. 17.16, References. Please update the following two URLs:
p. 49.26, Example 11. In the first equation, “DTlm” should be
For LBNL 2003, “ΔTlm.”
http://hightech.lbl.gov/dc-benchmarking-results.html.
For NIOSH 1986, p. 49.24, Figs. 25 and 26. Figure 26’s caption should refer to Figure
http://www.cdc.gov/niosh/86-113.html. 25, not Figure 22.
p. 21.13, Table 3. Class AA control should be defined as “Precision p. 52.7, Figs. 8 and 9. Reverse the order: the current Figure 8 should
control, no seasonal rh adjustment, very limited seasonal temperature be Figure 9, and the current Figure 9 should be Figure 8.
adjustment possible.”
p. 52.10, Example 7, 3rd paragraph. The equation for Abo should
p. 31.14, 1st col., 5th line. The outside air requirement for cafeterias be 560(0.17 × 10–3) = 0.095 m2. Consequently, Δpsbt (third line from
and fast food should be based on 100 persons per 100 m2. bottom of example) should be 82.6 Pa.
A.1
Copyright © 2009, ASHRAE
A.2 2006–2008 ASHRAE Handbook Additions and Corrections (SI)
p. 54.18, Example 3. For calculations using Eqs. (2) and (3), SDS
should be 0.623, not 0.85. The result using Eq. (2) should be p. 21.1, Fig. 1. Please replace the figure with the one shown above.
16 447 N, and the result using Eq. (3) should be 3084 N.
p. 22.1, Fig. 1. Please replace the figure with the one provided on
p. 54.19, Example 4. For calculations using Eqs. (2) and (3), SDS p. A.3, 1st column..
should be 0.623, not 0.85. The result using Eq. (2) should be 3289 N,
and the result using Eq. (3) should be 617 N. p. 23.4, Fig. 7. Replace the figure with the one provided on p. A.3,
2nd column.
2008 HVAC Systems and Equipment p. 23.10, Dry Air-Conditioning Systems, 4th paragraph. After
the second sentence, please add, “Dehumidified ventilation air that
p. 6.4, 1st col. After Eq. (9b), the multiplier for large spaces should positively pressurizes the building may help counter moist air infil-
be (4.91/De)0.25. tration.”
p. 10.7, Fig. 9. The title should read “Trapping Temperature-Regulated p. 30.10, 2nd col. Midway down the column, change “31.00 MJ/m3”
Coils.” Also, the bottom of the figure was cut off; please see the entire to “31.21 MJ/m3.”
figure, presented above right.
p. 31.7, 2nd col., 4th line. Change “sue” to “use.”
p. 12.20, 2nd col., after Eq. (18). The reference to Equation (21)
should be to Equation (18). p. 43.6, Eq. (3). Change “Dp” to “Δp.”
p. 12.24, Effect on Piping Pressure Loss. The reference to Equa- p. 49.3, 1st col., 3rd line. The Energy Policy and Conservation Act
tion (235) should be to Equation (18). of 2005 should be Public Law 109-58.
2006–2008 ASHRAE Handbook Additions and Corrections (SI) A.3
Fig. 1 Typical Water Circuit Arrangement Fig. 2 Typical Rotary Dehumidification Wheel