IN THE ABSENCE OF CAPACITIVE VOLTAGE TRANSFORMER SWITCH OFF LOAD CONTROL(TO AVOID OVER SPEED) CLOSE GB BEFORE START OF ROLLING
BYPASS REVERSE POWER PROTECTION
SYN.THRO BUS COUPLER ROLL THE TURBINE MATCH m/c SPEED WITH GRID SPEED IN CONSULTATION WITH SY. STAFF RAISE Nref AFTER SYNCHRONISATION TO GET BLOCK LOAD MATCH LOAD SET WITH ACTUAL LOAD SYN.THRO BUS COUPLER LOAD CONTROL CAN BE SWITCHED ON. LOAD LOOP SELECTED IN EHC RAISE LOAD AS USUAL NORMALISE REV.POWER PROTECTION