‘TABLE 1 - SUGGESTED INITIAL FREQUENCY OF INSPECTION AND
‘TESTING OF EQUIPMENT
| [type of Typeof [User Chass I Class II Note 4
| Premises Equipment Checks
Notel —|Note2_ Formal Combined |Formal | Combined
Visual Inspection | Visual__ Inspection
Inspection and Testing |Inspection and Testing
Note} _|Note 5 Note 3__|Note 5
[oa 2 3 | aed 6 | 7
1 Construction s None Imonth | 3months | Imonth | 3 months
sites IT None | Imonth | 3months | Imonth | 3 months
HOV yo Me weekly | tmonth | 3months | 1month | 3 months
equipment }) Pe weekly | fmonth | 3months | 1 month 3 months
He weekly | Imonth 3months | 1 month 3 months
2 Industrial s weekly | None | 12months None 12. months
including Ir weekly | None 12months | None 12 months
commercial M ——beforeuse month | 12months 3 months 12 months
kitchens | P before use month 6 months 3 months 6 months
H_ before use _Imonth _ 6months 3 months 6 months
3 Equipment s Note6* monthly 12 months | 3 months | 12 months
sused by the IT Note6* monthly | 12 months 3 months | 12 months
public M Note 6? | weekly months | 1 month | 12 months
P Note6’ | weekly months | 1month | 12 months
Note 6* weekly 6 months I month | 12 months
4 Schools s weekly None 12 months 12 months 48 months
Ir weekly? None 12 months 12 months | 48 months
M weekly? months 12 months 4 months | 48 months
P weekly? 4 months 12 months 4 months | 48 months
H__beforeuse” 4 months | 12months 4 months 48 months
5 Hots s None 24months | 48months 24 months None
IT None 24months | 48 months 24 months | None
| M weekly | 2months | 24months 24 months | None
P weekly I2months 24months 24 months _ None
a __H__| before use __6months | 12 months 6 months | None _
6 Offices and s None 24 months 48 months 24 months | None
shops IT None 24months | 48months 24 months | None
M weekly I2months | 24months 24 months | None
P weekly I2months | 24 months | 24months | None
a H____beforeuse__6months | 12months | 6months | __None_
() Stationary equipment
IT Information technology equipment
M Movable equipment
P-—_Portable equipment
H Hand-held equipment
2) User checks are not recorded unless 2 faules found,
(8) The formal visual inspection may form part ofthe combined inspection and tests when they
coincide, and must be recorded see 7.2b,
(4) If class of equipment is nor knowa, it must be tested as Class I.
(5) The results of combined inspections and tests are recorded see 7.2c.
(8) Forsome equipment such as children’s rides a daily check may be necessary
oO By supervisor/teacher/member of staff
TOV earthed centre tapped supply. 230V portable or hand-held equipment must be supplied via
230 mA red. and the intervals between inspections and tests reduced.
‘The information on suggested initial frequencies given above is more detailed and specific than HSE
Guidance, but is not considered inconsistent with it