You are on page 1of 69

Contents

A. Purpose/Scope ...................................................................................................................................... 3
B. Earth electrode rods: ............................................................................................................................ 4
C. Earth round conductor electrode: ...................................................................................................... 10
D. Earth rod with round conductor electrodes combination earthing network: .................................... 11
E. Interconnection of MV and LV Earths ................................................................................................. 12
F. Calculation of Touch and Step Potentials ........................................................................................... 14
G. Allowable touch and step potentials .................................................................................................. 15
H. Current Density at Surface of Earth Electrode .................................................................................... 16
I. Appendices : ........................................................................................................................................ 19

Page 2 of 19
A. Purpose/Scope

The purpose of this report to obtain the MV&LV earthing calculation study
for load centre A of KAIA project according to BS Code books

(BS 7430:1998), (BS 7354:1990) and the design report.

All the formulas and tables are copied from BS 7430:1998 and

BS 7354:1990

This study is to be used to aid in specifying the following:

• Earth electrode rod length.


• Number of earth electrode rods per each loop.
• Length of Earth round conductor electrode.
• Resistance of MV earthing network.
• Resistance of LV earthing network.
• Combined earth resistance interconnection of the MV and LV
networks.
• Touch and Step Potentials.
• Current Density at Surface of Earth Electrode.

Page 3 of 19
B. Earth electrode rods:

The resistance to earth of a rod or pipe electrode R, in ohms, is given by


the following equation:

Load Centre A - Structural floor level is 7m above MSL with the design
water table level at 4m above MSL, this level is based on recommendations
of HUTA and is subject to final confirmation by them.

So the effective length of the electrode rod through the wet soil (10 ohm.m
resistivity) will be [(3*2.4)-(7-4)] =4.2 m, where the total length of electrode
rod 3*2.4 = 7.2 m.

L = Effective Length of the electrode exist in the wet soil = 4.2 m

d =Diameter of the earthing rod = 0.02 m

Page 4 of 19
ρ = wet Soil resistivity (according to the design report) = 10 ohm.m

Then, R = 2.486 ohm for one earthing rod.

Page 5 of 19
Page 6 of 19
Page 7 of 19
Page 8 of 19
The total number of electrodes around the rectangle = 24 rods each of the
length of 9.6 m.

So, n = 7 and s = 41 m

R = earthing resistivity for one earthing rod = 2.486 ohm

ρ = wet Soil resistivity = 10 ohm.m

s = distance between adjacent rods = 41 m

λ = factor given in Table 3 = 7.03

Then, The combined resistance of all earth rod electrodes in parallel


Rn =0.394 ohm.

Page 9 of 19
C. Earth round conductor electrode:

For the round conductor electrode the resistance R, in ohms is given by the
following equation:

ρ = wet Soil resistivity = 200 ohm.m

L = length of the conductor = 1500 m

h = depth of electrode =2m

W = diameter of 240 mm2 bare copper conductor = 0.02 m

P = coefficient given in Table 5 for Two lengths at 90° electrode


arrangement =4

Q = coefficient given in Table 5 for Two lengths at 90° electrode


arrangement = 0.9

Then, the resistance R for the round conductor electrode = 0.206 ohm.

Page 10 of 19
D. Earth rod with round conductor electrodes
combination earthing network:

The equivalent resistance of the earthing network RLV for LV system

RLV = 0.1353ohm

The equivalent resistance of the earthing network RMV for MV system

RMV = 0.1353 ohm

According to the design report to ensure the ground potential rise meets
the requirement the resistance of the earth at the load center must be: -

This condition will be achieved as R = 0.1353 ohm less than 0.143 ohm

Page 11 of 19
E. Interconnection of MV and LV Earths
The MV and LV earth electrodes shall be interconnected within the ground
via a disconnectable test link.

So the combined earth resistance interconnection of the MV and LV


systems can be determined from the following equation:

Then,

RT = 0.067 ohm

Page 12 of 19
Page 13 of 19
F. Calculation of Touch and Step Potentials

ρ - [Ωm] Ground resistivity = 200

V - [V] Ground potential rise = 201

L - [m] Earth round electrode length = 1500

h - [m] Depth of earth conductor = 2

d - [m] Diameter of buried conductor = 0.02

D - [m] spacing between parallel conductors = 41

ki= (0.15n+0.7) = 1.75, where n = 7

Then, r = 171.13, where grid area equal to 92000

R = 0.4255 ohm

Then,

VT = 93.6 V and VS = 10.48 V

Page 14 of 19
G. Allowable touch and step potentials
BS7354 defines the following equations for calculating the allowable touch
and step potentials: -

Where:

Body resistance = 1,000Ω

Footwear resistance = 4,000Ω

Contact resistance = 3𝜌 Ω

It is taken from curve c2, Figure 5 of PD 6519-1:1988. At 1 second this


can be taken as 50mA.so Allowable Touch and Step Voltages as
following table:

Alternatively, Figure 3(a) in BS7354 graphs allowable touch and step


potentials as a function of the duration of the fault. Taking the maximum
time of 1 second and the minimum resistivity value gives VT < 240V and
VS < 720V.

Page 15 of 19
H. Current Density at Surface of Earth Electrode

Section 15 of BS7430 gives the following equation for the allowable


current density at the surface of an electrode:

Where ρ=200 ohm.m in the electrode level and t= 1 sec.

Then,

J= 537 A/m2

Tabulating the above equation against the soil resistivity data from 3.6 to
12m within Table 1 gives the following:

Page 16 of 19
Considering a 16mm diameter earth electrode, its surface area is given
by:

𝑆𝐴=𝑙.𝜋 𝑑

Where:

SA - [m2] The surface area

l - [m] The electrode length

d - [m] The electrode diameter

and the earth fault current is 3000A, the minimum electrode length can
be calculated using the following formula:

𝑙≥ 3000/ .𝜋 𝑑

Where:

J - [A/m2] The maximum current density of the earth electrode

d - [m] The electrode diameter

3000 [A] - Earth fault current

Page 17 of 19
Page 18 of 19
I. Appendices :
1- ATK005-422-C100-FD-X-RPT-0000: Design Report Load Centres
A, B, C and AC.
2- Appendix G. Earthing Calculations.
3- 422-C240-FD-E-RPT-00010-B: MV ELECTRICAL EARTHING
GENERAL REQUIREMENTS.

Page 19 of 19
100% Design Report Load Centres A, B, C and AC

14. Earthing
The earthing design for each Load Centre will generally follow the guiding principles as defined in
Atkins Report 422-C240-FD-E-RPT-0004 which sets out the design basis for the Medium Voltage
and Low Voltage earthing systems. The earthing system is being designed in accordance with the
British Standard Code of Practice for Earthing BS 7430:1998 and also Section 7 Earthing of BS
7354:1990 and in particular the guidance given in this document regarding the management of
Step and Touch Potentials.

14.1. Earth Electrode Design


The general ground conditions across the KAIA site are indicated to be a mix of sands, gravels and
clays which in a dry state would generally exhibit relatively high values of electrical resistivity.
However the ground water table is also at a generally high level and the ground water is indicated
to be of a saline nature which, from an earth electrode design basis, provides good conditions for
achieving an earth electrode of low ohmic value without need to install an extensive earth electrode
network. The depth of the water table does vary across the site with water tables at the Load
Centre locations being as follows:

Load Centre A - Structural floor level is 7m above MSL with the design water table level at 4m
above MSL

Load Centre B - Structural floor level is 8.3m above MSL with the design water table level at 4.3m
above MSL

Load Centre C - Structural floor level is 26.5m above MSL with the design water table level at
20.75m above MSL

Load Centre AC - Structural floor level is 25.75m above MSL with the design water table level at
22m above MSL

Note: The design water table level is based on a long-term uncontrolled design of groundwater
level = existing groundwater level plus 2m. These levels are based on recommendations of HUTA
and are subject to final confirmation by them.

In order to take advantage of the ground water requires a relatively deep electrode system to be
installed and would need to be in some form of deep bored or driven electrode such as earth rods.
In such instances advantage can be taken of other deep structures such as re-inforced concrete
foundations or deep bored piles.

In respect of the Load Centres the foundation design of the majority of the buildings are
constructed from raft type foundations the depths of with are such that they will not necessarily sit
below the ground water table. Originally an architectural screen was proposed to be installed
around a number of the Load Centre buildings, the height of which necessitated the need for deep
bored piles to form the support for the foundation beam upon which the screen would sit. The piles
will generally be in accordance with the parameters as given below and depending on the footprint
of the particular Load Centre which would require in excess of 100 piles to be installed per Load
Centre.

Table 21 - Foundation pile details


Parameter Value

Atkins Tracker Number: ATK005-422-C100-FD-X-RPT-00001 69


100% Design Report Load Centres A, B, C and AC

Depth of pile (approximate) Typically 12.5 metres - occasional piles up to 17m

Pile diameter 800 mm

Size of reinforcement H25’S

Length of reinforcement Full length of pile

No. of reinforcing 11 bars arranged in a ring


bars/formation

Spacing between piles 2m to 4m

The architectural screen is no longer part of the scope for the Load Centres however, it is
proposed to retain a number of the pile foundation in the design to form the primary MV and LV
earth electrodes.

Using an assumed worst case for Load Centre C where the ground water is typically just under 6
metres below the finished ground level would mean that for a 12.5 metre long pile the effective
length of pile within the water table would be 6.5 metres. Using the formulae from BS 7430:1998
and assumed resistivities of wet soil and concrete of 10 ohm metres and 30 ohm metres
respectively would give a typical effective resistance to earth for each pile of approximately 1.8Ω.

In accordance with Atkins report 422-C240-FD-E-RPT-0004 the maximum resistance of the earth
electrode shall be 0.143Ω in order to limit the maximum Ground Potential Rise to 430 volts. Thus
this value of earth electrode resistance could be achieved by connecting a minimum of 14 piles in
parallel to achieve the maximum required earth electrode resistance for both the MV and LV earth
electrodes. It shall be noted that the piles selected to be connected to the earth electrode system
shall be at least 13 metres apart (twice the effective length of the piled foundation) to ensure that
the maximum effectiveness of each pile is achieved and is not diminished by interaction with
adjacent piles.

It is therefore proposed that a minimum number of 16 piles per electrode will be used to form the
earth electrode using piles at each change of direction in the foundation. In other words 16 piles
will be used to form the MV earth electrode and a further 16 shall be used to form the LV electrode.

In addition a horizontal earth electrode will be installed buried typically at a depth of 2 metres below
finished ground level which will be used to interconnect each of the piles forming the earth
electrode and in addition will be laid around the perimeter of each of the primary buildings and
structures within the Load Centre. The horizontal earth electrode will be formed from either copper
strip or bare stranded copper conductor having a minimum cross sectional area of 120mm2. It is
envisaged that a minimum length of 1,500 metres of interconnecting conductor laid directly in the
ground will be required per Load Centre. Since this will typically be laid at a position in the ground
which is above the water table and assuming reasonably dry conditions at this level it is envisaged
the soil resistivity ‘seen’ by the horizontal electrode will be in the order of 200 ohm metres. Based
on the formulae in BS 7430:1998 this length of conductor and assumed soil resistivity would have
a typical effective resistance to earth of 0.8 ohms which can further contribute to an overall
lowering of the earth electrode resistance.

Calculation sheets for the above are available in Appendix G.

The calculation for Ground Potential Rise is shown in Appendix G. The configuration of earth
electrode as defined above gives a Ground Potential Rise of 215.6V.

Atkins Tracker Number: ATK005-422-C100-FD-X-RPT-00001 70


100% Design Report Load Centres A, B, C and AC

Maximum Allowable Touch and Step potentials have been determined from Figure 3 (a) of BS
7354:1990 as set out below:

Table 22 - Load Centre Touch and Step Potentials


Touch and Step Potentials Allowable Value

(V)

Touch Potential 240

Step Potential 750

The above figures were determined using the most conservative values possible. It is clear that as
the Ground Potential Rise is less than the maximum allowable value for Touch potential – hence it
is unnecessary to calculate the Touch and Step potentials as clearly it is not possible for them to
exceed the limits shown in Table 22.

14.2. Perimeter Fence


Perimeter fences formed of conductive materials have to be earthed in order to protect personnel
both within the site and outside of the site of being exposed to potentially injurious voltage and
current during system faults on the electrical network. The fence can either be connected to the
main earth electrode within the site or independently earthed. Where a fence is tied to the main
earth electrode it can in some instances be required to install an additional equipotential
counterpoise conductor on the outside of the fence throughout the whole length of the fence. This
is to ensure that under system fault conditions where the ground potential within the site becomes
higher than the general body of earth that personnel outside of the site that come into contact with
the fence are at the same ground potential as the ground within the site.

The alternative approach is to independently earth the fence and in such instances it has to be
ensured that the main earth electrode is a minimum distance from the fence (typically a minimum
of 3.0 metres). Since for the Load Centres the earth electrode will in the majority of the area be
quite significant distances from the fence and the touch and step potentials are well below the
acceptable limits it is proposed that the fence shall be independently earthed. This will be
achieved by employing earth rods of typical depths of 5.66metres (12 feet) driven into the ground
at each change of direction in the fence and also at maximum intervals of 100 metres in straight
sections of fences. Where the fence is not continuous such as at gate positions earth rods shall
also be located at either side of the break in continuity and an interconnecting conductor shall be
installed to connect the two earth rods together and maintain electrical continuity of the fence.

14.3. MV and LV Earthing and Distribution Networks


The proposed system design is to provide separate earth electrodes for the MV and LV earths.
These electrodes are to be interconnected at two points. As described above the electrodes shall
be formed by interconnecting a series of foundation piles using buried copper conductor. There will
then be two distribution systems around the Load Centre site (one for MV and one for LV earth)
which will allow each facility to be connected to the earth electrode as required.

Atkins Tracker Number: ATK005-422-C100-FD-X-RPT-00001 71


100% Design Report Load Centres A, B, C and AC

Separate MV and LV equipment earth bars will be installed in all equipment and plant rooms to
which all equipment earths, equipment metal work and all other extraneous and exposed
metalwork will be connected. These connections will be at sufficient intervals to ensure adequate
equipotential bonding of all exposed metalwork is achieved. This will be facilitated by the
installation of earthing distribution networks formed of bare copper strip affixed to walls at a
suitable levels and locations that will afford connections to be made from the various items of
equipment and plant and extraneous metalwork. These networks will be arranged such that the
equipment connections, etc to the earthing distribution system do not form obstructions, trip
hazards or any other impediment to the movement of people and equipment.

14.4. Bonding of Reinforcement


The majority of the Load Centre buildings and facilities will be constructed using reinforced
concrete containing a significant amount of re-inforcement steel. Whilst it is accepted that the vast
majority of the steel is covered in concrete and will not generally be accessible to personnel due to
the fact that some of the foundation system will form part of the earth electrode there is every
possibility that under system fault conditions the re-inforcement could experience a rise in
potential.

It is therefore proposed that connections shall be made to the re-inforcement steel at a number of
locations throughout all the various process plant buildings and facilities. It is proposed these
connections will be made at column positions and will use proprietary system that is exothermically
welded to the re-inforcement steel and is brought out to the face of the concrete as shown in the
detail below:

Atkins Tracker Number: ATK005-422-C100-FD-X-RPT-00001 72


100% Design Report Load Centres A, B, C and AC

Figure 3 - Re-inforcement steel earthing connection

Connections will then be made from these re-inforcement connection points to the earthing system
distribution network.

14.5. Tunnel Earthing


Where tunnels exit from the Load Centres to other facilities such as the Passenger Terminal
Building, SEC supply substations etc. the earthing distribution network within the Load Centres will
be extended out to the tunnel interface point and will be connected to the earthing distribution
system within the tunnel. This will be done in this manner to ensure that all systems such as cable
tray work, supporting steel structures, tunnel re-inforcement steel are all connected to a common
earthing system and operating at the same earth potential.

Atkins Tracker Number: ATK005-422-C100-FD-X-RPT-00001 73


100% Design Report Load Centres A, B, C and AC

Appendix G. Earthing Calculations

Atkins Tracker Number: ATK005-422-C100-FD-X-RPT-00001 88


Calculation Sheet

Calculation of Earth Electrode Resistance


Horizontal Electrode
in accordance with BS 7430 : 1998

Relevant extracts from BS 7430:1998

Input Data
General
Soil resistivity 200 ohm metres
Concrete resistivity 30 ohm metres
Electrode Arrangement Coefficient
P Q
Horizontal Electrode Strip Round
Length of conductor 250 metres Single 2 -1.0 -1.3
Depth of earth electrode 2 metres Two lengths @ 90° 4 0.5 0.9
Width/diameter of earthing conductor 0.0175 metres Three lengths @ 120° 6 1.8 2.2
Electrode Arrangement Single Four lengths @ 90° 8 3.6 4.1
Electrode Type Round Factor F
Coefficient P 2 No. of lengths F
Coefficient Q - 1.3 2 0.611
No. of lengths in parallel 2 3 0.443
Spacing between electrodes 80 metres 4 0.362
Factor F 0.611

Output Data Notes


Resistance of one electrode 1.76 ohms NB; Foundations need to be spaced at least two times the depth of the electrode to
Resistance of multiple electrodes 1.07 ohms ensure the effectiveness of each electrode is not diminished by interaction between
adjacent electrodes
Date 15/11/2012
Prepared by C Prentice
Job No. 5101762
Project Title KAIA
Project Ref C100/
Calculation Sheet

Calculation of Earth Electrode Resistance


Reinforced Concrete Foundations
in accordance with BS 7430 : 1998

Relevant extracts from BS 7430:1998

Input Data
General
Soil resistivity 10 ohm metres
Concrete resistivity 30 ohm metres

Structural Steelwork GMD Look Up


Diameter of reinforcing rod 0.012 metres No. of Rods GMD
Effective length of reinforcing rod 6.5 metres 2 0.0346
Thickness of concrete between rods 0.15 metres 3 0.0621
Distance between rods 0.2 metres 4 0.1079
GMD of rod cluster 0.2306 metres 6 0.1687
Number of rods 8 round 8 round 0.2306
Number of foundations 16 8 square 0.2082

Output Notes
Structural Steelwork NB; Foundations need to be spaced at least two times the depth of the electrode to
ensure the effectiveness of each electrode is not diminished by interaction between
Resistance of one foundation 1.23 ohms adjacent electrodes
Resistance of multiple foundations 0.08 ohms

Date 15/11/2012
Prepared by C Prentice
Job No. 5101762
Project Title KAIA
Project Ref C100/
Calculation Sheet

Calculation of Touch and Step Potentials

in accordance with BS 7354 : 1990

W/out crushed rock - BS7354:1990 Figure 3


Clearance Allowable Touch Potential (V) Allowable Step Potential (V)
t secs 100Ωm 500Ωm 1000Ωm 100Ωm 500Ωm 1000Ωm
0.1 2,400 2,900 3,400 7,300 9,200 11,000
0.2 1,700 2,100 2,400 5,100 6,500 8,100
0.3 1,250 1,500 1,800 3,800 4,700 6,000
0.4 880 1,050 1,250 2,700 3,300 4,200
0.5 600 700 810 1,800 2,250 2,900
0.6 410 500 590 1,250 1,600 2,000
0.7 330 390 470 1,000 1,300 1,600
0.8 280 340 410 870 1,100 1,400
0.9 260 315 380 790 1,000 1,250
1 240 300 340 750 950 1,200

Input Data
General Fault Clearance Time (s) 1
Soil resistivity ρ 200 ohm metres
Concrete resistivity ρ 30 ohm metres
Earth fault current I 3000 amps Allowable touch and Step
Resistance of grid to earth R 0.07 ohms Touch Voltage Vt 240 volts
Grid potential rise V 215.6 volts Step Voltage Vs 750 volts
Total length of buried conductor L 1500 metres
Diameter of buried conductor d 0.0175 metres
Depth of burial of grid h 2 metres
Spacing between parallel conductors D 150 metres
Notes
Output Allowable touch/step voltages for soil resistivity of 100Ωm has been conservatively used.
Touch Voltage Vt N/A volts
Step Voltage Vs 32.7 volts
Date 15/11/2012
Prepared by C Prentice
Job No. 5101762
Project Title KAIA
Project Ref C100/
Contact name: Phillip Norman
Address: P O Box 5668, Manama, Kingdom of Bahrain
Email: phillip.norman@atkinsglobal.com
Telephone: +973 1751 0400 / +973 3996 1420

© Atkins Ltd except where stated otherwise.

The Atkins logo, ‘Carbon Critical Design’ and the strap line
‘Plan Design Enable’ are trademarks of Atkins Ltd.
Saudi Binladin Group
Final Design Report
MV Electrical
Earthing General Requirements

SBG/DAH Report No

ATK002-422-C240-FD-E-RPT-00010 1
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Notice
This document and its contents have been prepared and are intended solely for Saudi Binladin Group’s
information and use in relation to King Abdulaziz International Airport.

[CONSULTANT] assumes no responsibility to any other party in respect of or arising out of or in connection
with this document and/or its contents.

Document History

JOB NUMBER:
TRACKER NUMBER:
Package 422
ATK002-422-C240-FD-E-RPT-00010

Revision Status Originated Checked Reviewed Authorised Date


100% submission for
A Mike Hales Ingar Loftus - Mike Hales 10-05-12
DAH review
100% submission for
B Mike Hales Ingar Loftus - Mike Hales 10-10-12
DAH review

ATK002-422-C240-FD-E-RPT-00010 2
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Table of Contents

Chapter pages

1. Abbreviations and References 5


1.1. Abbreviations 5
1.2. References 5
1.3. Client References 5
1.4. Atkins References 6

2. Introduction 6

3. Scope of Work 7
3.1. Deliverables 7

4. Design Input Information 8


4.1. SEC 110/13.8kV Substations 8
4.2. Load Centres 8
4.3. MV / LV Transformers 8
4.4. MV/MV Transformers 8
4.5. LV Network 9
4.6. Ground Conditions 9

5. Earthing Design 10
5.1. Earth Connections from SEC Substations to Load Centres 10
5.2. Facilities with 13.8kV Connections 10
5.3. 13.8kV Cable Connections 11
5.4. Standards 12
5.5. Lightning Protection 12
5.6. Equipotential Bonding 12
5.7. Surge Arrestors 12

6. Earth Grid Designs 13


6.1. Earth Resistivity Model 13
6.2. MV Earth Current 13
6.3. Load Centre Earth Grid Requirements 14
6.4. Facility Earth Grid Requirements 14
6.5. Current density at the surface of an earth electrode 15
6.6. Single Earth Rod Resistances 16
6.7. Multiple Earth Rod Resistances 16
6.8. Concrete Encased Earth Electrodes 16
6.9. Conductor Size 17
6.10. Touch and Step Potentials 17
6.11. Concrete Rebar Earth Connection 17

7. Summary 19

ATK002-422-C240-FD-E-RPT-00010 3
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Tables

Table 1 - Soil Resistivity Model ....................................................................................................................... 13


Table 2 - Earth rod resistances as a function of depth .................................................................................... 16
Table 3 - Earth Electrode Allowable Current Density ...................................................................................... 22
Table 4 - Minimum electrode length ................................................................................................................ 23
Table 5 - Detailed earth rod resistances as a function of depth ...................................................................... 24
Table 6 - Resistive values of 12m earth rods in group arrangements ............................................................. 25
Table 7 - Resistive values of 20m earth rods in group arrangements ............................................................. 26
Table 8 - Concrete Encased Earth Electrodes ................................................................................................ 28
Table 9 - Conductor Size Calculations ............................................................................................................ 29
Table 10 - Allowable Touch and Step Voltages .............................................................................................. 31
Table 11 - Site Resistivity Measurements ....................................................................................................... 36
Table 12 - Summarised Resistivity Measurements ......................................................................................... 37

Figures

Figure 1 - Simplified Block Diagram for facility earth potential rise ................................................................. 15
Figure 2 - Earth connections to rebar in concrete ........................................................................................... 18
Figure 3 - Electrical Network Diagram for Facility Earth Model ....................................................................... 20

Appendix

A. Proposed Earth Electrode Designs 20


A.1. Earth Potential Rise at Facility Substations 20
A.2. Current Density at Surface of Earth Electrode 22
A.3. Single Earth Rod Resistances 24
A.4. Resistance of Groups of Earth Rods 25
A.5. Resistance of Concrete Encased Earth Electrodes 27
A.6. Conductor Sizing 29
A.7. Calculation of Touch and Step Potentials 30
A.8. Allowable touch and step potentials 31
A.9. Concrete Rebar Connections 32
A.10. Hot Zone 33

B. Site Measurements of Electrical Resistivity 34

C. Generic Earthing Schematic 38

D. CRS Responses 39

ATK002-422-C240-FD-E-RPT-00010 4
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

1. Abbreviations and References


The following abbreviations and references are used throughout this document.

1.1. Abbreviations
[1] HV High Voltage, above 13.8kV;
[2] KAIA King Abdulaziz International Airport;
[3] LV Low Voltage, 0.4kV and below;
[4] MV Medium Voltage, between 0.4kV and 13.8kV;
[5] NEC National Electrical Code;
[6] NER Neutral Earthing Resistor;
[7] RFI Request for Information;
[8] SEC Saudi Electricity Company;
[9] Zsc Short circuit impedance;
[10] TT Earth is independent of earth from power source
[11] TNS Earth and Neutral conductors are separate from power source

1.2. References
All system design, installation and commissioning works must comply with the manufacturer’s
requirements, the requirements of authorities having jurisdiction and in accordance with the following
reference standards and relevant publications from the following internationally recognised organisations:

[1] NFPA: National Fire Protection Association.


[2] ANSI: American National Standards Institute.
[3] IEEE: Institute of Electrical and Electronics Engineers.
[4] BS7430 - Code of practice for Earthing
[5] BS7354 - Design of High Voltage Substations, Section 7
[6] PD 6519-1:1988 - Guide to Effects of Current on Human Beings and Livestock Part 1:
General Aspects
[7] IEEE80 - Guide for Safety in AC Substation Grounding
[8] ASTM: American Society for Testing and Materials.
[9] ISO: Standard by the International Standard Organization.
[10] ICAA: International Civil Airports Association
[11] IBC 2006 - International Building Code 2006; Standards relating to Electrical Installations
and Equipment as issued by the IBC 2006
[12] The local power authority regulations (for the MV cable connections to SEC substations).
[13] The Saudi Arabian Distribution Code Issue 01 Revision 00 dated November 2008
[14] Saudi Building Code Electrical Requirements SBC 401

1.3. Client References


[1] SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
[2] SECTION 264113 - LIGHTNING PROTECTION FOR STRUCTURES

ATK002-422-C240-FD-E-RPT-00010 5
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

1.4. Atkins References


[1] MV Cable Report reference ATK002-422-C240-FD-E-RPT-00008-A

2. Introduction
The King Abdulaziz International Airport (KAIA) is expanding its runway and passenger capability. To
facilitate this expansion, a new Air Traffic Control tower, a new Passenger Terminal, Transport Facilities
and supporting buildings and shall be constructed. The new airport shall initially support up to 30 million
passengers per year, growing to 45 million in the first few years to an eventual capacity of 80 million
passengers per year.

This document describes the Generic Earthing for the General MV and LV Systems to be installed in the
King Abdulaziz International Airport to support the distribution of Electrical Power and provide a safe
environment for operators, passengers and equipment. The specific Earthing design will be completed by
the appropriate sections, this document providing an overall co-ordinated design basis. The Generic
Earthing for the General MV and LV System comprises earth busbars, earth rods, cable and terminations
to connect all metallic components of the System to an appropriate earth.

This document does not cover the requirements for earthing of telecommunication systems nor systems
requiring special earthing requirements. This design will be coordinated with the designs for the earthing
requirements for the telecommunications systems to ensure compatibility.

ATK002-422-C240-FD-E-RPT-00010 6
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

3. Scope of Work
The scope of work shall include, but not be limited to:

1) Provision of all generic earthing design necessary for the General MV and LV Systems. All
necessary components shall meet the requirements of 2008 NFPA-70 Article 250;

2) All design services, drawing and specifications, equipment, materials, labour and services, not
specifically mentioned or shown, which may be necessary to complete the generic design and
installation of the Earthing for General MV and LV Systems;

3) Comply with the Contract Exhibits D1 and D2 revised in August 2011;

4) Generally comply with Exhibit “D” Section 260526 - Earthing and Bonding for Electrical Systems

3.1. Deliverables
The following are the deliverables for this package:

3.1.1. 70% Submission

1) Draft Design Report - Ref: ATK002-422-C240-DF-E-0004

2) Draft generic earthing requirements for buildings.

3.1.2. 100% Submission

1) Final Design Report

2) Final generic earthing requirements for buildings.

3) Earthing calculations.

ATK002-422-C240-FD-E-RPT-00010 7
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

4. Design Input Information


4.1. SEC 110/13.8kV Substations
The SEC transformers are proposed as: -

• Primary voltage: 110kV


• Secondary voltage: 13.8kV
• Transformer capacity: 67MVA
• Earthing on HV side: Solidly earthed
• Earthing on MV side: via an NER (Neutral Earthing Resistor) of 5.3 Ohms limiting phase
earth fault current to 1500A
• Switchboard short circuit rating: 40kA for 3 sec on the 13.8kV supply
• Star / Delta / Star
• 60Hz
SEC will not permit their earth to be connected to the KAIA earth system.

4.2. Load Centres


The Load Centres distribute the power from the SEC substations and have no direct affect on the
earthing arrangement except for the generator connections. The generators are connected to the 13.8kV
network via 1:1 isolating transformers. When the generators are operating, the SEC network is
disconnected as is the SEC earthing arrangement. To ensure the network remains earthed the generator
busbars have a switchable earthing arrangement to mimic the SEC earthing and this is achieved by a
NER of 5.3 Ohms limiting phase earth fault current to 1500A.

4.3. MV / LV Transformers
The MV / LV transformers are proposed as: -

• Primary Voltage: 13.8kV


• Secondary Voltage: 400V
• Transformer capacity: Various standard sizes up to 2000kVA
• Earthing on MV side: Not applicable
• Earthing on LV side: Direct earth connection
• Delta / Star

4.4. MV/MV Transformers


The MV / MV transformers are proposed as: -

• Primary Voltage: 13.8kV


• Secondary Voltage: 4.16kV
• Transformer capacity: Various sizes
• Earthing on MV side: Not applicable

ATK002-422-C240-FD-E-RPT-00010 8
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

• Earthing on LV side: via an NER (Neutral Earthing Resistor) limiting the short circuit current
to 100A
• Delta / Star
The value of the NER can be calculated by considering the phase to neutral voltage, the required earth
current and then applying Ohm’s Law. This gives:

V = I.R

R = 4160 / ( 100 . √ 3 ) = 24Ω

4.5. LV Network
The LV network is specified as 400/230V, 60Hz, 3 phase, 4 wire, solidly earthed.

4.6. Ground Conditions


The KAIA is situated 20 km north of the Jeddah City centre, between the ring road and the Madinah
road. The KAIA measures around 105 square kilometres. The western boundary of the site is around
4 km from the Red Sea whereas the eastern boundary touches the mountainous region of the
Arabian Shield. The surface soil at the site comprises silty / clayey / gravely sand and sandy silt.
Some loose sandy conditions were observed along the southern periphery of the Airport fence.
The water table across the site varies between 24 metres below sea level at some locations and only
3 metres at others, therefore the calculated homogonous resistivity level across the site would vary
depending on the height of the water table.

4.6.1. Site Subsurface Conditions


The sub-soil conditions at the site area have been formed in the recent and very recent geological
past without any noteworthy geological digenesis surcharge or other densification or solidification
effects. According to the investigations for the proposed site, extremely variable coral and alluvial
deposits can prevail in such cases, with abraded or completely decomposed coralline detritus
materials with medium dense to very dense sandy/silty to clayey marine soils of medium to good
bearing capacity. The coralline soil layers were encountered at shallow depths.
The coral soils are overlain by recent deposits. These top soils are partly sandy, though in most
cases silty. The soil underlying coral is alluvium comprising Wadi deposits i.e., clayey, silty sand with
gravel.

ATK002-422-C240-FD-E-RPT-00010 9
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

5. Earthing Design
The Earthing Design shall be compliant with BS7430 - Code of practice for Earthing. The design shall ensure
the safe operation of the electrical network during normal and abnormal conditions and protection personnel
and equipment. The safe operation is demonstrated by calculations.

5.1. Earth Connections from SEC Substations to Load Centres


st
SEC have confirmed verbally, at meeting on 21 June, they will not permit their earth within the
110/13.8kV substations to be connected to the earth within the KAIA installation. Thus the earth
connection between these points is considered to be ‘TT’.

5.2. Facilities with 13.8kV Connections


All facilities with 13.8kV connections are to have a similar arrangement, which is a 13.8kV supply
and dual 13.8/0.4kV transformers providing LV supplies. Hence these are considered to be common
designs. This will apply to Load Centres, Passenger Terminal Building, Mosque and many other
locations.
The primary requirement is to establish a MV earth and a LV earth. These are to be installed as
electrically separate. To comply with the requirements of BS7430 and to enable the MV and LV
earths to be interconnected, the maximum combined earth resistance allowed is 1Ω, therefore t he
target value of the earthing will be: -
• MV Earth < 1Ω
• LV Earth < 1Ω
However, the maximum allowable earth value for both is 5Ω; this value is only to be used where
achieving the target value is considered to be impractical and additional calculations would be
required to ensure the system is safe.
See also Section 6.4, where the value of the earth resistance is calculated to maintain the ground
potential rise to below 430V. This section takes precedence over the target values.
For any earthing arrangement for the distribution network, it is important to consider that this should
not clash with any additional earthing requirements for telecommunications and lightning protection.

5.2.1. MV Earth
The MV earth will be achieved by a group of earth rods installed external to the building, the number
of rods depending on the ground conditions but not less than 2. These rods will be interconnected. A
minimum of 4m separation will be maintained between this rod group and any LV earthing.
At any location where the MV earth does not maintain the 4m separation from the LV earth, the MV
earth will be insulated to maintain the electrical isolation between the two systems.
The MV Main Earth Bar will be connected to MV Main Earth Bars in adjacent substations.

5.2.2. LV Earth
The LV earth will be achieved by a buried copper conductor surrounding the building to achieve a LV
Earth Loop. Duplicate stranded copper conductor cables will connect the LV Earth Loop back to the
LV Main Earth Bar. The LV Earth Loop will be supplemented with earth rods to achieve the required
LV Earth Resistance. The number of earth rods will be dependent on the ground conditions but the
minimum will be two earth rods.
Where practical, the LV Main Earth Bar will be connected to LV Main Earth Bars in adjacent
substations.

ATK002-422-C240-FD-E-RPT-00010 10
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

5.2.3. Clean Earth


The clean earth will be established via a separate group of earth rods located a minimum of 1800mm
from all other earth rod groups. The clean earth shall not be connected to any other earth system.
The minimum value of the earth rod group shall be 1Ω.
Clean earths shall typically be provided for data systems, telephony, other communication systems
and UPS.

5.2.4. Interconnection of MV and LV Earths


Within the substation, the MV Main Earth Bar and LV Main Earth Bar shall be electrically
independent. The MV and LV earth electrodes shall be interconnected within the ground via a
disconnectable test link.
Interconnection of MV and LV earths is discussed in Section 19.2 of BS7430. To permit the
interconnection of the MV and LV earth, the standard requires the combined resistance of the earth
electrode to be less than 1Ω and the rise of earth potential not to exceed 430V.
To ensure this arrangement is safe, the ground potential rise will be calculated as per Section 16 of
BS7430 and confirmed as lower than the acceptable touch and step voltages within the same
standard.

5.2.5. 13.8/0.4kV Transformer LV Star Point Earthing


The 13.8/0.4kV Transformer LV star point will be directly connected to the LV Main Earth Bar to
provide a TNS earthing solution for the 400V network.

5.2.6. 13.8/0.4kV Transformer Foundations


The 13.8/0.4kV transformer foundations shall include a perimeter earthing conductor loop, earth rods
as required, and shall be connected to the MV earth. Where transformers are mounted internal to
buildings, this will be achieved by suitable connections to the reinforcement bars within the concrete,
see Section 6.11.

5.2.7. MV/LV Substations


The equipment within the MV/LV substations is to be supplied as an integrated solution,
incorporating MV switchgear, MV/LV transformer, LV switchgear and busduct providing a single
metallic connection in terms of earthing.
The MV switchgear, MV/LV transformer and by implication the LV enclosure require connecting to
the MV Earth.
It has been agreed via an RFI that the MV and LV earth systems can be connected. For this to be
completed whilst maintaining system of the personnel and equipment, the specific requirements
within BS7430 must be met. These are discussed in Section 5.2.4.
The outgoing LV circuits require connecting to the LV Earth mat.
To ensure safety, all exposed metal within the MV/LV substations shall be connected to the MV Main
Earth Bar. This will include but not be limited to: ventilation ductwork, pipe work and structural steel.
To provide an equipotential zone within the substation the concrete reinforcement bars within the
substation shall also be connected to the MV Main Earth Bar.

5.3. 13.8kV Cable Connections


The 13.8kV cables include a non-magnetic bare copper drain wire screen. The revised specifications
2 2
changed the screen on the MV cables to 47mm per conductor that is equivalent to 141mm per
three phase trefoil group. The MV Cable Design considers the requirements for the earthing of the
MV cable screen.
The MV Cable Design concludes this screen is adequate to control the sheath voltage and therefore
separate earth conductors are not required for control of the screen voltage.

ATK002-422-C240-FD-E-RPT-00010 11
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

However, as per Section 2.6.3.2 of Specification ‘Aprons, Taxiways, Roads, Tunnels, Bridges, Load
Centres and Infrastructure, Transportation Centre and Supporting Facilities’ Exhibit “D” Part D1
requires a separate earth conductor installed in a separate duct: -
‘Medium Voltage: 13.8 kV and 4.16 kV, 60 Hz 3 phases, 3 wires, and ground (Ground
conductor is to be installed in a separate duct).’
2
Therefore for each 13.8kV cable connection a separate 120mm bare stranded copper conductor will
be installed. Where the cables are ducted, this conductor will be installed in a separate duct. The
function of this conductor is to duplicate the interconnection provided by the MV cable screens and
provide an interconnected MV earth network.
2
The MV Cable screens to the earth bar within the MV switchboards. The 120mm earth conductors
associated with the MV Cables will be connected to the MV Main Earth Bar.
As per Section 5.1, there is no earth connection between the SEC substations and the Load Centres.
Therefore a separate earth conductors shall be installed and the screens of the MV cables earthed
at the SEC substations via this separate conductor. A carefully coordinated design will be required to
ensure the MV cable screens are earthed without interconnection the KAIA and SEC earth systems.
Similarly, the MV cable support structures will require careful design to ensure they do not provide
an earth path between the KAIA and SEC substations.

5.4. Standards
When calculating the earth electrode resistance BS7430 considers the earth rods. It does not
consider the contribution from the buried electrode connecting the earth rods. Also, BS7430 does not
provide a means of calculating the touch and step potentials.
Given the length of conductor required for the load centre BS7430 would under-estimate the overall
electrode resistance.
Section 7 of BS7354 ‘Design of high-voltage open-terminal stations’ provides the equations
necessary to address these aspects. Therefore Section 7 of BS7354 will be used in the following
calculations.
Informative note: BS EN 50522 ‘Earthing of power installations exceeding 1kV AC’ is due for release
soon and will combine the earthing requirements from BS7430 and BS7354 into one document.

5.5. Lightning Protection


The lightning protection scheme shall comply with Specification 264113 and IEC/BS EN 62305. This
shall be achieved by locating earth pits to minimise the length of lightning conductors. The lightning
earth pits shall have a maximum resistance of 10Ω and shall be interconnected to other earth
systems.

5.6. Equipotential Bonding


Equipotential bonding shall be installed in compliance with BS7671. The protective conductor cross-
2
sectional area shall not be less than 4mm .

5.7. Surge Arrestors


Surge Arrestors shall be connected the to earth grid using the minimum standard conductor size to
provide a power frequency earth path.
Supplementary earthing shall be used between the surge arrestor and the earth grid to provide high
frequency earthing. This shall utilise stranded conductors with no sharp changes of direction
connected via as shorter path as practical to the earth grid. Where possible these high frequency
earth connections will be made to dedicated earth rods.

ATK002-422-C240-FD-E-RPT-00010 12
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

6. Earth Grid Designs


6.1. Earth Resistivity Model
Earth resistivity measurements have been taken on site at Load Centre A, Load Centre B and Load
Centre C. The measurements taken are detailed in Table 11 - Site Resistivity Measurements within
Appendix B.
The measurements were taken using the Wenner Array measurement system. This 4 probe
measurement technique allows the electrical resistivity at increasing soil depth to be investigated by
increasing the spacing of the test probes. The probe spacing effectively gives the depth at which the
measurement is being taken. Therefore a resistivity model against soil depth can be built up by
increasing the probe spacing. Table 12 - Summarised Resistivity Measurements shows the
measurements summarised against soil depth.
Using Table 12 the following soil model against varying earth electrode depth can be determined:

Soil
Soil Depth / Probe Maximum
Resistivity
Spacing Resistivity
Model
(m) (Ω.m)
(Ω.m)

0.75 870 290

1.1 560 240

1.6 420 220

2.4 245 210

3.6 140 120

5.4 85 34

8.1 25 22

12 6 6

20 4 4

Table 1 - Soil Resistivity Model

The above table has been determined by considering the maximum measured values and the
second maximum measured value. The second maximum measured value is used for the soil
resistivity model for soil depths between 0.75 and 8.1m as the maximum value is a single value
which is unrepresentative of the bulk of measurements taken. We consider this to be a worst case
model and would expect the actual reading achieved on site to be no worse than the details
identified.
As per Specification 260526 clause 2.2 we seek the Engineer’s agreement to the soil model shown
in Table 1.

6.2. MV Earth Current


The MV earth fault current with two SEC transformers in parallel is 3000A. Specification 260526
clause 2.4 (C) 3 states a diversity of 0.8 is to be used in mesh systems. The interconnection
between the load centres and the facilities does provide a degree of mesh design, however it is not
considered this meets the requirements of the clause and therefore a diversity of 1.0 is used.

ATK002-422-C240-FD-E-RPT-00010 13
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

6.3. Load Centre Earth Grid Requirements


The design of the earth grid is to comply with the requirements of BS7430. Further there is a
requirement for the MV and LV earths to be interconnected. Section 19.2 of BS 7430 requires the
ground potential rise to be less than 430V and the combined earth resistance to be 1Ω or less for
interconnection of the MV and LV earths.
The maximum earth current is when two SEC transformers are connected in parallel. As per Section
4.1 each transformer will contribute 1500A giving a maximum earth current of 3000A. Thus to ensure
the ground potential rise meets the requirement the resistance of the earth at the load centre must
be: -
𝑉 430
𝑅 ≤ ≤ ≤ 0.143Ω
𝐼𝑒 3000

The Load Centre earth grid will achieve this value without considering the contribution from the
outgoing circuits and their associated earthing.
Also, in order to meet the requirements of Specification 260526 clause 2.4 (D) 6, the above rating
shall be achieved with the rod group with the lowest calculated resistance disconnected.
Both of the above points will mean the Load Centre earth resistance will, under normal conditions,
be less than 0.143Ω as required by BS7430 and therefore the MV and LV earths can be
interconnected.

6.4. Facility Earth Grid Requirements


The maximum earth fault at each facility is as per Section 6.2 that is 3000A. This fault current will
flow into the local earth electrodes and back to the Load Centre via the earth conductors installed
with the MV cables and the screens of the MV cables.
As per the Load Centre design, the design of the facility earth grid is to comply with the requirements
of BS7430 and there is the requirement for the MV and LV earths to be interconnected. Section 19.2
of BS 7430 requires the ground potential rise to be less than 430V and the combined earth
resistance to be 1Ω or less for interconnection of the MV and LV earths.
The facility has its own earth grid providing a local earth resistance. It is also connected to the Load
Centre by a minimum of 2 MV cables each having associated screens and earth conductors. These
2
act in series with the earth grid resistance at the Load Centre. The MV cable screens are 47mm per
2 2
single phase core and therefore 141mm per trefoil group. The earth conductors are 120mm .
Thus a model is required to determine the relative flow of earth current under fault conditions. The
model used is:

ATK002-422-C240-FD-E-RPT-00010 14
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Simplified Block Diagram 3000A

IF
IR
Load Centre Facility VL

RL IL
RR

Key
120mm2 Cu Earth Conductor
47mm2 x 3 Cu MV Cable Screen
IF - Earth fault current
IR - Proportion of IF flowing to remote earth network
IL - Proportion of IF flowing to local earth network
VL - Voltage rise at local earth network
RL - Resistance of local earth network
RR - Resistance of remote earth network
RC - Resistance of earth conductors
RS - Resistance of MV cable screen

Figure 1 - Simplified Block Diagram for facility earth potential rise

The voltage rise at the facility substation is calculated in Appendix A.1. This shows the maximum
acceptable total earth resistance at the facility substation is 0.28Ω.
Referring to Section 5.2 the target resistance for MV and LV earths is 1Ω. These target for MV and
LV earths must be reduced to 0.56Ω, the combination in parallel achieving the required earth
impedance.
The simplified block diagram in Figure 1 only considers 2 MV sets of MV cable screens and 2
associated earth conductors. In most installations the minimum will be 4 of each. Also, the simplified
block diagram does not consider additional substations along the feeder providing additional earthing.
These considerations indicate that the earth resistance stated is conservative.

6.5. Current density at the surface of an earth electrode


In general, soils have a negative temperature coefficient of resistance so that sustained current
loading results in an initial decrease in electrode resistance and a consequent rise in the earth fault
current for a given applied voltage. However, as soil moisture is driven away from the soil-electrode
interface, the resistance increases and will ultimately become infinite if the temperature rise is
sufficient. For short-duration loading this occurs in the region of 100 °C and results in complete
failure of the electrode.
Section 15 of BS7430 gives the relevant equation to confirm the suitable sizing of the earth electrode.
Calculations are completed in Appendix A.2 for a 16mm diameter earth rod and at the various

ATK002-422-C240-FD-E-RPT-00010 15
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

resistivity values shown in Table 1, showing the minimum summated earth rod length required for
the various resistivities under fault conditions.

6.6. Single Earth Rod Resistances


Using the resistivity values in Table 1 the resistance of different depth earth rods can be calculated.
Given the layered resistivity model as per Table 1, each earth rod is calculated as a series of smaller
earth rods all connected in parallel. This takes advantage of the majority of the earth rod length.
Earth rod resistances are calculated in Appendix A.3 and summarised: -

Rod Length Rod


(m) Resistance
(Ω)

3.6 150.3

5.4 61.6

8.1 10.4

12 3.759

20 0.707

25 0.390

Table 2 - Earth rod resistances as a function of depth

Earth rods 9m in length or less are considered shallow and driven. Earth rods greater than 9m in
length are considered deep.
To achieve the resistances required in Sections 6.3 and 6.4 and the surface current densities given
in Section 6.5 and Appendix A.2, it is clear that the lower resistivities provided by longer / deeper
earth rods will be required. As a practical observation, it is recommended that the minimum earth rod
length considered is in excess of 12m.
The earth rod resistances calculated above should be achieved across the whole KAIA site due to
the resistivity data used. The design could be optimised by taking electrical resistivity measurements
at individual facilities. In the majority of locations this will provide lower resistivity values and will
allow the design to be optimised.

6.7. Multiple Earth Rod Resistances


Using the single earth rod resistances in Section 6.6, the values of groups of earth rods can be
calculated. Combinations of earth rods are considered in Appendix A.4. The lengths of earth rods
selected are aligned to earth rod lengths in Table 2 and considered for 12m and 20m lengths.
Results are provided in Table 6 and Table 7 of Appendix A.4.

6.8. Concrete Encased Earth Electrodes


Alternative designs to the earth rod can be considered. One such alternative design is to consider
concrete encased earth electrodes. The resistance of such arrangements is very much dependent of
the design. Some typical calculations are provided in Appendix A.9. The results shown in Table 8
that concrete encased earth electrode can provide significant contribution to the earth grid.

ATK002-422-C240-FD-E-RPT-00010 16
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

6.9. Conductor Size


The earth conductor size is checked in Appendix A.6. To comply with the requirements of 260526
2
the MV earth conductor is selected to have a minimum cross section of 120mm .
2
The temperature rise for a 120mm conductor under MV fault current is also calculated in Appendix
A.6 and is shown to be small such that it is practical for the earth conductor to be installed adjacent
to the MV cables without the need for additional precautions.

6.10. Touch and Step Potentials


Formulae to calculate the touch and step potentials are included in Appendix A.7. These must be
used once the earth grid design for the facility has been finalised.
The effect of a voltage applied to the body varies significantly from person to person. On a balance
of probabilities, the time dependent body current used to establish the tolerable voltage is the curve
c2 of Figure 5 of PD 6519-1:1988. Body resistance also varies but most standards use a value of
1,000Ω. The contact resistance at the surface of the ground also adds resistance which limits the
body current and a value of 3 times the ground resistivity per foot is taken. There is growing
international acceptance that footwear resistance should be taken into account and this now is UK
practice. Footwear resistance is taken as 4,000Ω per foot.
The allowable Touch and Step potentials are calculated in Appendix A.8 using the above information.
The calculated values of touch and step potential must be less than the allowable touch and step
potentials as indicated in Table 10 of Appendix A.8.

6.10.1. Hot Zone


The ground potential rise is limited by design to be less than 430V. Therefore the hot zone as
designed in BS7354 is within the earth electrode. Therefore calculations as per Appendix A.10 are
not necessary.

6.10.2. High Resistivity Surface Layer


The use of high resistivity surface layer can be useful for reducing the touch and step potentials. The
KAIA includes significant quantities of MV equipment installed indoors on concrete floors. These
areas could not implement high resistivity surface layers.

6.11. Concrete Rebar Earth Connection


Specification 260526 states the following requirements within Section 2.7 (D): -
“When the reinforcing in concrete is used as a part of the earthing system the fittings used to
provide a connection point at the surface of the concrete shall be exothermically welded to a
reinforcing bar. This fitting shall be provided with a bolted connection for an earthing
conductor. The main bars in the reinforcing shall be welded together at intervals to ensure
electrical continuity throughout the reinforcing.”
Summarising the requirement gives: -
• Connection shall be exothermically welded to the rebar.
• The fitting shall provide a bolted connection for an earth conductor.
• The main bars in the reinforcement shall be welded together at intervals to ensure electrical
continuity.
The effects of fault current flowing in the rebar must not be detrimental to the rebar and / or the
concrete and therefore the temperature rise during fault conditions must be limited. Appendix A.9
o
calculates the minimum cross sectional area required to limit the temperature rise to 55 C as
2 2
174mm ; as 16mm diameter rebar has an approximate cross sectional area of 200mm this is
considered safe. The design further reduces the effect of heating on the rebar by requiring the main
rebar either side of the connection to be welded together, thus distributing any fault current. This is
shown diagrammatically as: -

ATK002-422-C240-FD-E-RPT-00010 17
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Figure 2 - Earth connections to rebar in concrete

Note: Whilst the calculations in Appendix A.9 consider the MV fault current, the connection to the
rebar is not intended to form part of the earth fault current path. This connection is intended to
ensure equipotential voltages during fault conditions to protect personnel and equipment.

ATK002-422-C240-FD-E-RPT-00010 18
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

7. Summary
This report shows how the requirements for the earthing as part of the KAIA installation can be met.
The report and calculations are based on the British Standard BS7430 as required by the revision to
Contract Exhibits D1 and D2. British Standard BS7354 has been used for equations to calculate the
touch and step potentials, as these calculations are not included within BS7430.

ATK002-422-C240-FD-E-RPT-00010 19
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A. Proposed Earth Electrode Designs

A.1. Earth Potential Rise at Facility Substations


The Simplified Block Diagram showing in Figure 1 can be represented as an electrical network diagram as
below:

Electrical Network Diagram 3000A

RC IR IF

RS
Key
RF RC 120mm2 Cu Earth Conductor
VL 47mm2 x 3 Cu MV Cable Screen
RS IF - Earth fault current
IR - Proportion of IF flowing to remote earth network
IL - Proportion of IF flowing to local earth network
VL - Voltage rise at local earth network
RR IR RL IL RL - Resistance of local earth network
RR - Resistance of remote earth network
RC - Resistance of earth conductors
RS - Resistance of MV cable screen
RF - Total feeder resistance

Figure 3 - Electrical Network Diagram for Facility Earth Model

Solving this network:

The resistance of the earth conductors and MV cable screens can be calculated by the following equation: -

𝑙
𝑅= 𝜌
𝐴
Where:

R - [Ω] Total resistance

𝜌 - [Ωm] Resistivity of material

l - [m] Length of conductor

A - [m2] Cross sectional area of conductor

For copper, 𝜌 = 1.68 x 10-8 at 20oC


2
With the maximum feeder length taken to be 5km long and the MV screens 141 (74 x 3)mm cross
sectional area, their resistance can be calculated to be 0.596Ω. Using the same feeder, the earth
conductor resistance can be calculated to be 0.7Ω.

ATK002-422-C240-FD-E-RPT-00010 20
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

The combined resistance of the MV cable screens and the associated earth conductors can be
calculated as:

0.596 0.7
.
𝑅𝐹 = 2 2 = 0.16Ω
0.596 0.7
+
2 2

Using the model in Figure 3, the following equations can be determined using Ohms Law: -

𝑉𝐿 = 𝐼𝐿 . 𝑅𝐿

𝑉𝐿 = (𝐼𝐹 − 𝐼𝐿 ) (𝑅𝐹 + 𝑅𝑅 )

Solving gives:

𝐼𝐹 (𝑅𝐹 + 𝑅𝑅 )
𝐼𝐿 =
𝑅𝐿 + 𝑅𝐹 + 𝑅𝑅

𝑅𝐿 . 𝐼𝐹 (𝑅𝐹 + 𝑅𝑅 )
𝑉𝐿 =
𝑅𝐿 + 𝑅𝐹 + 𝑅𝑅

Where:

IF - Earth fault current

IR - Proportion of IF flowing to remote earth network

IL - Proportion of IF flowing to local earth network

VL - Voltage rise at local earth network

RL - Resistance of local earth network

RR - Resistance of remote earth network

RF - Total feeder resistance

Rearranging:

𝑉𝐿 (𝑅𝐹 + 𝑅𝑅 )
𝑅𝐿 =
(𝐼𝐹 (𝑅𝐹 + 𝑅𝑅 ) − 𝑉𝐿 )

VL must be less than 430V to satisfy BS7430, IF is 3000A, RF is 0.16Ω and RR is 0.143Ω as per Section 6.3.
Solving the equation shows RL is required to be less than 0.28Ω to maintain the VL below the 430V limit.

ATK002-422-C240-FD-E-RPT-00010 21
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.2. Current Density at Surface of Earth Electrode


Section 15 of BS7430 gives the following equation for the allowable current density at the surface of
an electrode:

57.7
J = 103 �
𝜌𝑡

Where:
2
J - [A/m ] The maximum current density of the earth electrode

𝜌 - [Ωm] The ground resistivity

t - [sec] the duration of the fault

Tabulating the above equation against the soil resistivity data from 3.6 to 12m within Table 1 gives
the following:

Allowable
Soil Resistivity Time
Current Density
(Ω.m) (sec)
(A/m2)

120 1 693

34 1 1303

22 1 1619

6 1 3101

4 1 3798

Table 3 - Earth Electrode Allowable Current Density

Considering a 16mm diameter earth electrode, its surface area is given by:

𝑆𝐴 = 𝑙. 𝜋 𝑑

Where:

SA - [m2] The surface area

l - [m] The electrode length

d - [m] The electrode diameter

and the earth fault current is 3000A, the minimum electrode length can be calculated using the
following formula:

3000
𝑙≥
𝐽 .𝜋 𝑑

Where:
2
J - [A/m ] The maximum current density of the earth electrode

ATK002-422-C240-FD-E-RPT-00010 22
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

d - [m] The electrode diameter

3000 [A] - Earth fault current

Minimum
Allowable
Soil Resistivity Electrode
Current Density
(Ω.m) 2 Length
(A/m )
(m)

120 693 86

34 1303 46

22 1619 37

6 3101 19

4 3798 16

Table 4 - Minimum electrode length

ATK002-422-C240-FD-E-RPT-00010 23
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.3. Single Earth Rod Resistances

Based on the resistivity values in Table 1 the resistance of earth rods of various depths can be calculated
using Section 10.2 of BS7430: -

ρ 8L
R= 2πL
�ln � d � − 1� Section 10.2

Where:
ρ - [Ωm] Ground resistivity
L - [m] Length of rod
d - [m] Diameter of rod = 16mm

Given the resistivity model is layered, each section of earth rod is calculated and then the total rod resistance
is calculated by considering the sections in parallel (sections of earth rod with resistance greater than 100Ω
are not included in the total rod resistance):

Rod Length Section Section Rod


(m) Length Resistance Resistance
(m) (Ω) (Ω)

1.6 0.5 345.4 Not Calculated

2.4 0.8 218.5 Not Calculated

3.6 1.2 150.3 Not Calculated

5.4 1.8 61.6 61.6

8.1 2.7 12.4 10.4

12 3.9 5.904 3.759

20 8 0.871 0.707

25 5 0.869 0.390

Table 5 - Detailed earth rod resistances as a function of depth

Earth rods 9m in length or less are considered shallow and driven. Earth rods greater than 9m in length are
considered deep.

ATK002-422-C240-FD-E-RPT-00010 24
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.4. Resistance of Groups of Earth Rods


Section 10.2 of BS7430 allows the resistance of a group of earth rods connected in a straight line to be
calculated using the equations: -
1+ 𝜆𝛼
𝑅𝑛 = 𝑅 � � - Section 10.2
𝑛

Where:
R - [Ω] Resistance of single rod, as Appendix A.3
ρ
α=
2πRs
s - [m] Distance between rods
𝜆 - Is stated in BS7430 in Tables 2 and 3 for the various configurations
n - number of earth rods
Giving: -

12m Rods

Equilateral
Item Hollow square Straight Line Units
Triangle

n 3 2 3 4 5

R 3.8 3.8 3.8 3.8 3.8 Ω

s 24 24 24 24 24 m

𝜌 22 22 22 22 22 Ωm

𝛼 0.038 0.038 0.038 0.038 0.038

𝜆 1.66 2.71 4.51 2.15 2.54

Number of
Electrodes 3 4 8 4 5

Total Length of
Electrode* 11.7 15.6 31.2 15.6 19.5 m

Rn 1.35 1.05 0.56 1.03 0.83 Ω

Table 6 - Resistive values of 12m earth rods in group arrangements

* - adjusted based on resistivity and maximum current density

ATK002-422-C240-FD-E-RPT-00010 25
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

20m Electrodes

Equilateral
Item Hollow square Straight Line Units
Triangle

n 3 2 3 3 4

R 3.8 3.8 3.8 3.8 3.8 Ω

s 40 40 40 40 40 m

𝜌 6 6 6 6 6 Ωm

𝛼 0.006 0.006 0.006 0.006 0.006

𝜆 1.66 2.71 4.51 2.15 2.54

Number of
Electrodes 3 4 8 3 4

Total Length of
Electrode* 24 32 64 24 32 m

Rn 1.28 0.97 0.49 1.28 0.97 Ω

Table 7 - Resistive values of 20m earth rods in group arrangements

* - adjusted based on resistivity and maximum current density

ATK002-422-C240-FD-E-RPT-00010 26
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.5. Resistance of Concrete Encased Earth Electrodes


Section 12.2 of BS7430 considers using structural steelwork encased in concrete. The resistance of a single
arrangement is given by: -

1 𝛿 2𝐿
𝑅= �(𝜌𝑐 − 𝜌) 𝑙𝑜𝑔𝑒 �1 + � + 𝜌 𝑙𝑜𝑔𝑒 � ��
2𝜋𝐿 𝑧 𝑧

Where:

𝜌 - [Ωm] Soil resistivity

ρc - [Ωm] Concrete resistivity

L - [m] Length below ground

δ - [m] Thickness of concrete between rods and soil

z - [m] Value from Table 9 of BS7430

Considering the following arrangement:

a s

Gives:
8
𝑧 = �52 . 𝑎 . 𝑠 7
Where:

a - [m] Radius of reinforcement bar

s - [m] Distance between adjacent rods

Using the following values:

ρc = 30Ωm

δ = 0.15m

a = 0.006m

s = 0.2m

and the values of resistivity given in Table 1, allows the following values to be calculated:

ATK002-422-C240-FD-E-RPT-00010 27
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Item Case 1 Case 2 Case 3 Units

𝜌 22 6 4 Ωm

L 12 8 5 m

R 1.44 0.77 0.93 Ω

Table 8 - Concrete Encased Earth Electrodes

ATK002-422-C240-FD-E-RPT-00010 28
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.6. Conductor Sizing


The required conductor size can be calculated using Section 14 of BS7430: -

𝐼 √𝑡
𝑆= Section 14
𝑘

Where:
2
S - [mm ] Conductor cross sectional area
I - [A] Fault current
t - [sec] Fault current duration
k - Constant from Table 10 of BS7430

The fault current is rated at earth fault current for the MV installation and LV installation. The fault duration is
o
as per 260526 Section 2.5 (G), which also specifies the maximum final temperature of 160 C enabling k to
be looked up in Table 10 of BS7430. These give: -

Item MV LV Units / Comments

I 3,000 40,000 A

t 1.0 0.4 Seconds


o
k 138 138 Limit final temperature to 160 C
2
S 22 183 mm

Table 9 - Conductor Size Calculations

2
Specification 260526 Section 2.5 (G) states the minimum earth conductor to be 120mm and hence this size
is selected for the MV network.

Using further equations in Section 14 of BS7430: -


𝑇2 + 𝛽
𝑘 = 𝐾 �log 𝑒 � �
𝑇1 + 𝛽

Where:
k - [A/mm2] Current density
o
𝑇1 - [ C] Initial temperature
o
𝑇2 - [ C] Final temperature
K and 𝛽 are material specific constants (for copper 226 and 254 respectively)
2
Using the above equations it is possible to calculated the final temperature of a 120mm conductor with a
o o
3000A fault for 1 second and an initial temperature of 40 C. This gives a final temperature of 43.6 C .

ATK002-422-C240-FD-E-RPT-00010 29
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.7. Calculation of Touch and Step Potentials


BS7354 defines the following equations to calculate the touch and step potentials: -

𝜌𝑉 1 1 1− 0.5𝑛−2
𝑉𝑇 =
𝜋𝑅𝐿
�ln ��ℎ⁄𝑑 � + �2ℎ + 𝐷+ℎ
+
𝐷
�� 𝑘𝑖 - Equation [17]

𝜌𝑉 1 1 1− 0.5𝑛−2
𝑉𝑠 = � + + � 𝑘𝑖 - Equation [20]
𝜋𝑅𝐿 2ℎ 𝐷+ℎ 𝐷

Where:

VT - [V] Touch Voltage

Vs - [V] Step Voltage

ρ - [Ωm] Ground resistivity

V - [V] Ground potential rise

R - [Ω] Earth electrode resistance

L - [m] Earth electrode length

h - [m] Depth of earth conductor

d - [m] Diameter of buried conductor

D - [m] spacing between parallel conductors

n - Number of parallel conductors / cables / lines

k i = (0.15n + 0.7)

ATK002-422-C240-FD-E-RPT-00010 30
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.8. Allowable touch and step potentials


BS7354 defines the following equations for calculating the allowable touch and step potentials: -

(𝐹𝑜𝑜𝑡𝑤𝑒𝑎𝑟 + 𝐶𝑜𝑛𝑡𝑎𝑐𝑡 𝑅𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒)


𝑉𝑇 = 𝐼𝑡 �𝐵𝑜𝑑𝑦 𝑅𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 + �
2
𝑉𝑆 = 𝐼𝑡 {𝐵𝑜𝑑𝑦 𝑅𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 + 2(𝐹𝑜𝑜𝑡𝑤𝑒𝑎𝑟 + 𝐶𝑜𝑛𝑡𝑎𝑐𝑡 𝑅𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒) }

Where:

Body resistance = 1,000Ω

Footwear resistance = 4,000Ω

Contact resistance = 3𝜌 Ω

It is taken from curve c2, Figure 5 of PD 6519-1:1988. At 1 second this can be taken as
50mA.

Resistivity Allowable Allowable


Touch Step
(Ωm) Voltage Voltage
(V) (V)

500 188 600

200 165 510

100 158 480

50 154 465

Table 10 - Allowable Touch and Step Voltages

Alternatively, Figure 3(a) in BS7354 graphs allowable touch and step potentials as a function of the duration
of the fault. Taking the maximum time of 1 second and the minimum resistivity value gives VT < 240V and VS
< 720V.

ATK002-422-C240-FD-E-RPT-00010 31
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.9. Concrete Rebar Connections


o
BS7430 includes data and calculations to consider temperature rises commencing at 150 C. The likely effect
of this temperature on rebar within concrete is considered to be detrimental to the concrete. Therefore
IEEE80 Equation 10-13 is considered to be more appropriate as it allows lower temperatures to be
considered: -

If
Amm² = [Equ 10-13]
TCAP x 10−4 K +T
�� � .ln� o m �
tc .αr .ρr K o + Ta

Where:

If = 3 kA This is the MV earth fault level

Tm = 55 ºC All other values from Table 10-1 of IEEE80

Ta = 40 ºC

αr = 0.0016

ρr = 15.9 µΩ.cm

t c = 1 sec.

TCAP = 3.28

K o = 605

Amm² = 174 mm²

o
This calculation shows that to limit the temperature rise of the rebar to 55 C will require a cross sectional
area of 174mm² or greater. 16mm diameter rebar has a cross sectional area of approximately 200mm² and
therefore will meet this requirement.

ATK002-422-C240-FD-E-RPT-00010 32
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

A.10. Hot Zone


The hot zone can be calculated using equation 23 in BS7354. This enables the extent of voltage contours
outside of the earth grid to be determined. The equation is given by: -

1
𝑥 = 𝑟 �� � − 1�
𝜋𝑉𝑥
𝑎𝑟𝑐 sin
2𝑉

Where

x - [m] is the distance from the edge of the grid to the extent of the hot zone

r - [m] is the equivalent circular plate radius

Vx - [V] is the hot zone voltage

V - [V] is the ground potential rise

Within the UK the value of Vx it usually taken as either 430V or 690V. As both the load centres and the
package substations are designed to maintain the ground potential rise below 430V the hot zone is
maintained within the earth electrode and the calculation of the zone is unnecessary.

ATK002-422-C240-FD-E-RPT-00010 33
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

B. Site Measurements of Electrical Resistivity

The following tabulates the electrical resistivity measurements taken on site:

Anode Probe Resistance Constant Apparent


Load
Test No Depth Spacing Reading K" Resistivity
Centre
(cm) (m) (Ω) (2.π.a) (Ω.m)
A 1 15 0.3 2.960 1.885 5.579
A 1 15 0.5 0.440 3.142 1.382
A 1 15 0.75 0.420 4.712 1.979
A 1 15 1.1 0.400 6.912 2.765
A 1 15 1.6 0.380 10.05 3.820
A 1 15 2.4 0.370 15.08 5.579
A 1 15 3.6 0.240 22.62 5.429
A 1 15 5.4 0.190 33.93 6.447
A 1 15 8.1 0.080 50.89 4.072
A 1 15 12 0.010 75.40 0.754
A 1A 15 0.3 4.880 1.885 9.199
A 1A 15 0.5 4.570 3.142 14.36
A 1A 15 0.75 0.180 4.712 0.848
A 1A 15 1.1 0.290 6.912 2.004
A 1A 15 1.6 0.280 10.05 2.815
A 1A 15 2.4 0.250 15.08 3.770
A 1A 15 3.6 0.160 22.62 3.619
A 1A 15 5.4 0.080 33.93 2.714
A 1A 15 8.1 0.010 50.89 0.509
A 2 15 0.3 0.560 1.885 1.056
A 2 15 0.5 0.510 3.142 1.602
A 2 15 0.75 0.370 4.712 1.744
A 2 15 1.1 0.270 6.912 1.866
A 2 15 1.6 0.400 10.05 4.021
A 2 15 2.4 0.070 15.08 1.056
A 2 15 3.6 0.050 22.62 1.131
A 2 15 5.4 0.020 33.93 0.679
A 2 15 8.1 0.000 50.89
A 2A 15 0.3 0.540 1.885 1.018
A 2A 15 0.5 0.390 3.142 1.225
A 2A 15 0.75 0.270 4.712 1.272
A 2A 15 1.1 0.200 6.912 1.382
A 2A 15 1.6 0.130 10.05 1.307
A 2A 15 2.4 0.070 15.08 1.056
A 2A 15 3.6 0.040 22.62 0.905
A 2A 15 5.4 0.010 33.93 0.339
A 3 15 0.3 4.670 1.885 8.803
A 3 15 0.5 3.180 3.142 9.990
A 3 15 0.75 3.030 4.712 14.279
A 3 15 1.1 1.670 6.912 11.542
A 3 15 1.6 0.640 10.053 6.434
A 3 15 2.4 0.090 15.080 1.357
A 3 15 3.6 0.050 22.619 1.131
A 3 15 5.4 0.010 33.929 0.339

ATK002-422-C240-FD-E-RPT-00010 34
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Anode Probe Resistance Constant Apparent


Load
Test No Depth Spacing Reading K" Resistivity
Centre
(cm) (m) (Ω) (2.π.a) (Ω.m)
A 3 15 8.1 0.000 50.894
A 3 15 12 0.000 75.398
A 3A 15 0.3 5.260 1.885 9.915
A 3A 15 0.5 3.250 3.142 10.210
A 3A 15 0.75 3.180 4.712 14.985
A 3A 15 1.1 2.150 6.912 14.860
A 3A 15 1.6 1.050 10.053 10.556
A 3A 15 2.4 0.620 15.080 9.349
A 3A 15 3.6 0.190 22.619 4.298
A 3A 15 5.4 0.080 33.929 2.714
A 3A 15 8.1 0.010 50.894 0.509
A 3A 15 12 0.000 75.398
B 1 15 0.3 2.930 1.885 5.523
B 1 15 0.5 1.740 3.142 5.466
B 1 15 0.75 0.950 4.712 4.477
B 1 15 1.1 0.400 6.912 2.765
B 1 15 1.6 0.250 10.053 2.513
B 1 15 2.4 0.110 15.080 1.659
B 1 15 3.6 0.050 22.619 1.131
B 1 15 5.4 0.040 33.929 1.357
B 1 15 8.1 0.030 50.894 1.527
B 1 15 12 0.000 75.398
B 1A 15 0.3 3.790 1.885 7.144
B 1A 15 0.5 1.760 3.142 5.529
B 1A 15 0.75 0.850 4.712 4.006
B 1A 15 1.1 0.540 6.912 3.732
B 1A 15 1.6 0.260 10.053 2.614
B 1A 15 2.4 0.160 15.080 2.413
B 1A 15 3.6 0.090 22.619 2.036
B 1A 15 5.4 0.020 33.929 0.679
B 1A 15 8.1 0.010 50.894 0.509
B 1B 15 0.3 2.730 1.885 5.146
B 1B 15 0.5 1.400 3.142 4.398
B 1B 15 0.75 0.750 4.712 3.534
B 1B 15 1.1 0.470 6.912 3.248
B 1B 15 1.6 0.290 10.053 2.915
B 1B 15 2.4 0.130 15.080 1.960
B 1B 15 3.6 0.080 22.619 1.810
B 1B 15 5.4 0.080 33.929 2.714
B 1B 15 8.1 0.000 50.894
B 2 15 0.3 16.980 1.885 32.007
B 2 15 0.5 8.770 3.142 27.552
B 2 15 0.75 1.680 4.712 7.917
B 2 15 1.1 0.510 6.912 3.525
B 2 15 1.6 0.350 10.053 3.519
B 2 15 2.4 0.210 15.080 3.167
B 2 15 3.6 0.200 22.619 4.524
B 2 15 5.4 0.140 33.929 4.750
B 2 15 8.1 0.010 50.894 0.509
B 2 15 12 0.000 75.398

ATK002-422-C240-FD-E-RPT-00010 35
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Anode Probe Resistance Constant Apparent


Load
Test No Depth Spacing Reading K" Resistivity
Centre
(cm) (m) (Ω) (2.π.a) (Ω.m)
B 2 15 20 0.000 125.664
B 2 15 30 0.000 188.496
B 2B 15 0.3 2.510 1.885 4.731
B 2B 15 0.5 1.220 3.142 3.833
B 2B 15 0.75 1.200 4.712 5.655
B 2B 15 1.1 0.610 6.912 4.216
B 2B 15 1.6 0.500 10.053 5.027
B 2B 15 2.4 0.460 15.080 6.937
B 2B 15 3.6 0.130 22.619 2.941
B 2B 15 5.4 0.120 33.929 4.072
B 2B 15 8.1 0.010 50.894 0.509
B 2B 15 12 0.000 75.398
C 1A 15 0.3 347.000 1.885 654.080
C 1A 15 0.5 265.000 3.142 832.522
C 1A 15 0.75 184.100 4.712 867.551
C 1A 15 1.1 80.100 6.912 553.611
C 1A 15 1.6 41.000 10.053 412.177
C 1A 15 2.4 16.000 15.080 241.274
C 1A 15 3.6 5.280 22.619 119.431
C 1A 15 5.4 1.000 33.929 33.929
C 1A 15 8.1 0.480 50.894 24.429
C 1A 300 12 0.050 75.398 3.770
C 1A 300 20 0.030 125.664 3.770
C 1A 300 30 0.020 188.496 3.770
C 1A 300 50 0.010 314.159 3.142
C 1 15 0.3 270.000 1.885 508.938
C 1 15 0.5 116.000 3.142 364.425
C 1 15 0.75 60.100 4.712 283.215
C 1 15 1.1 33.600 6.912 232.227
C 1 15 1.6 21.300 10.053 214.131
C 1 15 2.4 13.790 15.080 207.948
C 1 15 3.6 6.000 22.619 135.717
C 1 15 5.4 2.450 33.929 83.127
C 1 15 8.1 0.420 50.894 21.375
C 1 300 12 0.080 75.398 6.032
C 1 300 20 0.010 125.664 1.257
C 2 15 0.3 5.170 1.885 9.745
C 2 15 0.5 4.070 3.142 12.786
C 2 15 0.75 4.640 4.712 21.865
C 2 15 1.1 3.550 6.912 24.536
C 2 15 1.6 2.200 10.053 22.117
C 2 15 3.6 2.120 22.619 47.953
C 2 15 5.4 0.760 33.929 25.786
C 2 15 8.1 0.080 50.894 4.072
C 2 300 12 0.010 75.398 0.754
C 2 300 20 0.010 125.664 1.257
Table 11 - Site Resistivity Measurements

The apparent resistivity column is left blank where the resistance reading is 0.

ATK002-422-C240-FD-E-RPT-00010 36
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

The basic measurements taken on site can be summarised as below:

Probe Maximum Minimum Average


Spacing Resistivity Resistivity Resistivity Count
(m) (Ω.m) (Ω.m) (Ω.m)
0.3 654.1 1.018 90.21 14
0.5 832.5 1.225 92.52 14
0.75 867.6 0.848 88.09 14
1.1 553.6 1.382 61.59 14
1.6 412.2 1.307 49.57 14
2.4 241.3 1.056 37.50 13
3.6 135.7 0.905 23.72 14
5.4 83.13 0.339 12.12 14
8.1 24.43 0.509 5.802 10
12 6.032 0.754 2.827 4
20 3.770 1.257 2.094 3
30 3.770 3.770 3.770 1
50 3.142 3.142 3.142 1
Table 12 - Summarised Resistivity Measurements

ATK002-422-C240-FD-E-RPT-00010 37
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

C. Generic Earthing Schematic

ATK002-422-C240-FD-E-RPT-00010 38
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

D. CRS Responses

Electrical comments on report ref. no. 422-C240-DF-E-RPT-00004-A ……Action code 3


1. General: the following shall be indicated:
a. The overall grounding system network scheme.
b. ICT network scheme.
c. Grounding system for lightning protection system network scheme.
d. Measure the specific earth resistance of the soil for related areas / load centers.
Contractors Response: A schematic diagram will be added to the report to provide an
indication of the overall earthing network.
Philosophy and basic proposals for ICT earthing will be included.
Lightning protection is outside of the scope of this report.
The measurements of electrical resistivity are being taken on site for the load centres.
This information will be used to update the report.
2. Clause 4.4: Indicate the rating of NGR to limit the S.C current to 100A and indicate the
calculation note validating the 100A S.C current.
Contractors Response: The earthing report is not intended to design and / or size
neutral earthing resistors. This information will not be included within the report.
3. Clauses 6.1 & 7: The exact ground resistivity must be measured; considering 3 values
is not acceptable.
Contractors Response: As above, the measurements of electrical resistivity are being
taken on site for the load centres. This information will be used to update the report.
4. Clause 6.6.3: Provide reference for the calculation note where the overall earth
electrode resistance is 0.12 ohm and ground potential rise of 360V were calculated.
Contractors Response: The calculations are provided in Appendix A.5 as indicated in
the first paragraph. The wording will be amended to clarify and Appendix A.5 updated
to clarify the 360V calculation.
5. Clause 5.2.1: It is indicated that MV earth will be insulated to maintain the electrical
isolation between the MV & LV system while in figure 4 both system are interconnected,
Contractor is to justify.
Contractors Response: The specification requires the ability to test earth electrodes.
To facilitate this insulation is maintained between the MV and LV earths. Please provide
an instruction if the testing is no longer a requirement.
6. Clause A1: Clarify how average ground resistivity is calculated for each earth rod.
Contractors Response: The average resistivity is calculated using a weighted average
which considers depth and soil resistivity at the depth. This model is very conservative.
Resistivity measurements on site will supersede this model.
7. Clause A2: This item is to calculate the surface current density not to determine the
minimum length of earth rod. Also, the actual current density shall be calculated as well
by dividing the fault current by the grid surface area.
Contractors Response: Agreed. The equation calculates the maximum current density
given a specific electrical resistivity. This result is shown is table 4.
Table 4 then calculates the minimum earth rod length to dissipate the fault current. An
additional equation will be included to shown this calculation.
8. Clause A5: Justify calculating earth electrode resistance using BS7354 while the
resistance of earth electrode and resistance of groups of electrodes were calculated in
accordance to BS7430 in item A3 and A9 respectively.
Contractors Response: BS7430 provides equations to calculate the resistance of
individual earth rod arrangements. It does not provide equations to calculate the
effective resistance of an earth network comprising earth rods and conductors in an
interconnected network. BS7354 provides the equations necessary to calculate the
effective resistance of an earth network.
This is recognised by the standards organisation who are working on BS EN 50522
which will be a harmonised earthing standard incorporating BS7430 and section 7 of
BS7354.

ATK002-422-C240-FD-E-RPT-00010 39
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

9. Clause A8:
a. Provide the criteria on which the MV screen C.S.A is considered to be 285 mm2.
b. Indicate the reference standard where the ground potential rise formula is derived.
Contractors Response:
a. The screen of the MV cable has been changed based on a previous DAH comment.
The screen size is 47mm2 per core or 141mm2 per trefoil. The report will be
updated.
b. The ground potential rise is calculated by applying Ohm's Law to Figure 3.
10. Clause A10: Soil resistivity is 140 Ω -m while it has never been measured nor in
accordance with the values used throughout the report, Contractor is to clarify.
Contractors Response: The resistivity will be updated based on the response to item
6 inspect of this report.
Also the calculations will be expanded to include alternative values of z (this defines the
quantity and arrangement of rebars within the concrete) which will align with the
structural design for the piles which will be installed on site.
11. Indicate the ratings / sizes or dimensions of the equipotential copper busbars within MV
and LV rooms as per the related short circuit calculations.
Contractors Response: This will be included in the updated report.
12. Indicate the surge arrestors earthing.
Contractors Response: This will be included in the updated report.
13. Using 21 meter deep driven earth electrodes for load center peripheral earthing system
needs to be revisited considering the existing soil conditions.
Contractors Response: Noted. The load centre earthing design will change based on
the measured earth resistivity and the availability of earth connections to the piles for
the visual screening.
14. 45kA ground-fault level shown on page 28 must be substantiated by explicit calculation.
Contractors Response: The LV fault level will be changed to 40kA to align with the
maximum switchgear ratings. Calculations are provided in Report ref. no. 422-C240-DF-
E-RPT-00001 demonstrating the fault level to be lower than 40kA.

ATK002-422-C240-FD-E-RPT-00010 40
MV ELECTRICAL EARTHING GENERAL REQUIREMENTS

Contact name
Address

Email:
Telephone:
Direct telephone:
Fax:

© Atkins Ltd except where stated otherwise.

The Atkins logo, ‘Carbon Critical Design’ and the strapline


‘Plan Design Enable’ are trademarks of Atkins Ltd.

ATK002-422-C240-FD-E-RPT-00010 41

You might also like